Lighting control system (BACnet IP) · BACnet points list

Lutron Vive BACnet (hub and area devices) BACnet points list

Updated 6 November 2026

Short answer

The Vive hub speaks BACnet IP and acts as a virtual router: each area (usually a room) is a virtual BACnet device behind it. The hub device carries the master load-shed BV. Each area device exposes light level and on/off, occupancy state and mode, occupied/unoccupied levels, load-shed settings and lighting power.

This page lists 12 BACnet objects for the Lutron Vive BACnet (hub and area devices) — 9 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Lutron’s own free documentation, linked below.

Manufacturer
Lutron
Model
Vive BACnet (hub and area devices)
Equipment
Lighting control system (BACnet IP)
Equipment type
Other equipment
BACnet objects
12 (9 writable)
Transport
BACnet IP
Firmware
Vive 1.07
Also known as
Lutron Vive, Vive hub, Vive BACnet Integration, 369996, Vive 1.07
Source document
BACnet PIC Statement for Vive · 369996d · rev. 2018-05-09
Download CSV 12 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Lutron’s current documentation and the live device before use. Not official Lutron information. Terms of use.

BMS integration notes: Lutron Vive BACnet (hub and area devices)

Integration in brief

Each room is a virtual device behind its Vive hub. Command lights with BV 3 (on/off) or AV 2 (level), read occupancy (MV 8) and lighting power, and use the hub's BV 2 for building-wide load shed with each area's BV 12/AV 13 settings.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 3Lighting StateArea lights on/off command and statusWrite
AV 2Lighting LevelArea light level, 0-100 %Write
MV 8Occupancy State1 Unoccupied, 2 Occupied, 4 UnknownRead
AV 18Total PowerPresent lighting power, WRead

Enable & remote start

BACnet IP is set up in the Vive hub configuration; there is no BMS enable point.

Network setup

Watch out for

Lutron Vive BACnet (hub and area devices) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

12 of 12 shown
Type
AnalogBinaryMulti-state
Access
Show
Lutron Vive BACnet (hub and area devices) BACnet Points List
DescriptionStates
BV2Master Load shed EnabledLoad shed for all areas of the hub (hub device only)Write0=Disabled, 1=Enabled
AVmin2Lighting LevelHighest light level in the area; writing sets all lights%Write
BVmin3Lighting StateOn if any light in the area is on; writableWrite0=Off, 1=On
BV7Disable OccupancyTrue = occupancy sensors ignored in the areaWrite0=False, 1=True
MVmin8Occupancy StateArea occupancy from its sensorsRead1=Unoccupied, 2=Occupied, 4=Unknown
AV9Unoccupied LevelDimmed level when the area goes unoccupied%Write
AV10Occupied LevelDimmed level when the area goes occupied%Write
BV12Load shed AllowedWhether this area takes part in load shedWrite0=No, 1=Yes
AV13Load shed GoalLight level reduction during load shed, 0-90%Write
MV14Occupancy ModeHow occupancy sensors control the lightsWrite2=Automatic ON, Automatic OFF; 3=Manual ON, Automatic OFF; 4=Not Applicable (read-only); 5=Mixed (read-only)
AVmin18Total PowerPresent lighting power in the areaWRead
AV19Maximum PowerConnected lighting load of the areaWRead
Object ID lookup: Lutron Vive point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Vive BACnet (hub and area devices) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Lutron Vive BACnet (hub and area devices)

How many BACnet points does the Lutron Vive BACnet (hub and area devices) have?

This list has 12 BACnet objects: 6 analog values, 4 binary values, 2 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Lutron Vive BACnet (hub and area devices) BACnet points are writable?

9 of the 12 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Lutron Vive BACnet (hub and area devices) BACnet documentation?

The source is BACnet PIC Statement for Vive (369996d), revision 2018-05-09, published free by Lutron at https://assets.lutron.com/a/documents/369996.pdf.

What are the minimum BACnet points to integrate the Lutron Vive BACnet (hub and area devices)?

Start with BV 3 Lighting State (Area lights on/off command and status); AV 2 Lighting Level (Area light level, 0-100 %); MV 8 Occupancy State (1 Unoccupied, 2 Occupied, 4 Unknown); AV 18 Total Power (Present lighting power, W).

How do I enable BMS control of the Lutron Vive BACnet (hub and area devices)?

BACnet IP is set up in the Vive hub configuration; there is no BMS enable point.

How do I check these points on the real Vive BACnet (hub and area devices)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Lutron BACnet points lists

Source: BACnet PIC Statement for Vive · 369996d · rev. 2018-05-09. Object names, instances and units are reproduced as published; descriptions are our own.