Short answer

Quantum processors (Quantum Lighting Hubs) speak BACnet IP natively once a BACnet license is enabled. Each subsystem is a main BACnet device that routes to one virtual device per area (room). Every area device carries the same fixed objects for light level, scene, occupancy, daylighting, load shedding, Hyperion shades, power and device failures, plus one object per lighting zone, shade group, 3-wire motor zone and light sensor in that area.

This page lists 29 BACnet objects for the Lutron Quantum BACnet Area Virtual Device — 19 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Lutron’s own free documentation, linked below.

Manufacturer
Lutron
Model
Quantum BACnet Area Virtual Device
Equipment
Lighting control system (BACnet IP area device)
Equipment type
Other equipment
BACnet objects
29 (19 writable)
Transport
BACnet IP
Firmware
Quantum 2.6 (BACnet integration software 2.0)
Also known as
Lutron Quantum BACnet, Quantum area device, Quantum BACnet integration, QSW-BAC-PP-A, 369696, Lutron lighting BACnet points, Quantum Lighting Hub BACnet
Source document
BACnet PIC Statement for Quantum Area Virtual Devices using Quantum Version 2.6 · 369696a · rev. 2013-08-12
Download CSV 29 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Lutron Quantum BACnet Area Virtual Device

Integration in brief

A Lutron service engineer enables the BACnet license and sets device IDs and network numbers. Each area then shows up as a virtual device behind the processor. Command the area light level (AV 2) or scene (MV 4), read occupancy (MV 8) and power (AV 18), and watch the failure counters.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AV 2Lighting LevelArea light level command, 0-100 %Write
MV 4Lighting SceneScene select; 1 = Off sceneWrite
BV 3Lighting StateOn if any light in the area is onWrite
MV 8Occupancy State1 Unocc, 2 Occ, 3 Inactive, 4 UnknownRead
AV 18Total PowerPresent lighting power, WRead
AV 15Number of Lamp FailuresCount of failed lampsRead
AV 16Number of Devices Not RespondingCount of offline lighting devicesRead

Enable & remote start

BACnet is native to the Quantum processor but needs a BACnet software license per processor (QSW-BAC-PP-A covers 50 areas); a Lutron service representative enables it and sets the device IDs and network numbers. No separate BMS enable point exists.

Network setup

Watch out for

Lutron Quantum BACnet Area Virtual Device BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

29 of 29 shown
Type
AnalogBinaryMulti-state
Access
Show
Lutron Quantum BACnet Area Virtual Device BACnet Points List
DescriptionStates
AVmin2Lighting LevelHighest light level in the area, 0-100%Write
BVmin3Lighting StateOn if any light in the area is onWrite0=Off, 1=On
MVmin4Lighting SceneActive lighting scene; 1 = Off sceneWrite1=Off scene; 2..n = scenes named in the Quantum project ({SceneName})
BV5Daylighting EnabledLets daylight sensors limit the area's light levelWrite0=Disabled, 1=Enabled
AV6Daylighting LevelDaylight target cap, 0-100%Write
BV7Disable OccupancyTrue stops occupancy sensors affecting the lightsWrite0=False, 1=True
MVmin8Occupancy StateOccupancy of the whole areaRead1=Unoccupied, 2=Occupied, 3=Inactive, 4=Unknown
AV9Unoccupied LevelLight level/scene used when the area goes unoccupied (0-216)Write0=Off, 1-100=level %, 101=Unaffected, 102=Daylighting, 200=Off scene, 201-216=Scene 1-16
AV10Occupied LevelLight level/scene used when the area goes occupied (0-216)Write0=Off, 1-100=level %, 101=Unaffected, 102=Daylighting, 200=Off scene, 201-216=Scene 1-16
AV11Additional Occupied TimeoutExtra wait after sensors go unoccupied, 0-300minWrite
BV12Loadshed AllowedArea takes part in load sheddingWrite0=No, 1=Yes
AV13Loadshed GoalLight reduction when loadshed is on, 0-90 %Write
MV14Occupancy ModeHow occupancy sensors control the lightsWrite1=Inactive, 2=Automatic ON and Automatic OFF, 3=Manual ON and Automatic OFF, 4=Not Applicable
AVmin15Number of Lamp FailuresDigital ballasts/drivers reporting lamp failureRead
AVmin16Number of Devices Not RespondingProgrammed devices not respondingRead
BV17Hyperion EnabledSun-tracking shade control for the areaWrite0=Disabled, 1=Enabled
AVmin18Total PowerPresent lighting power in the areawattsRead
AV19Maximum PowerConnected lighting load of the areawattsRead
BV20Roof-Mount Cloudy Day Sensor: Area StatusCloudy-day override for Hyperion shadesWrite0=Dark, 1=Sunny
BV21Radio Window Sensor StateRadio window sensor override of HyperionWrite0=Disabled, 1=Enabled
BV22Light Level DiscrepancyPhoto sensor reading disagrees with timeclock stateRead0=False, 1=True
AV23Number of Wireless Input Device FailuresWireless keypads/sensors not communicatingRead
AV25Number of Loads with Lamps Nearing End of LifeLoads past their programmed lamp-hoursRead
AV1000{ZoneName} LevelZone light level; one object per zone, instances 1000-1999%Write
AV2000{ShadeGroupName} LevelShade group level, 100 = open; instances 2000-2999%Write
MV3000{ShadeGroupName} PresetShade group preset; instances 3000-3999Write1=Open, 2-30=user presets, 31=Closed, 32-33=not used, 34=Undefined
MV4000{ShadeGroupName} Radio Window Sensor Shade Group StatusWindow sensor state per shade group; instances 4000-4999Read1=Unknown, 2=Sunny, 3=Dark
MV5000{3-Wire Motor Zone Name}3-wire motor output state; instances 5000-5999Write1=Stop, 2=Open, 3=Close
AV6000Light Sensor ValueLight sensor reading per sensor; instances 6000-6999fcRead

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Quantum BACnet Area Virtual Device and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Lutron Quantum BACnet Area Virtual Device

How many BACnet points does the Lutron Quantum BACnet Area Virtual Device have?

This list has 29 BACnet objects: 15 analog values, 8 binary values, 6 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Lutron Quantum BACnet Area Virtual Device BACnet points are writable?

19 of the 29 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Lutron Quantum BACnet Area Virtual Device BACnet documentation?

The source is BACnet PIC Statement for Quantum Area Virtual Devices using Quantum Version 2.6 (369696a), revision 2013-08-12, published free by Lutron at https://assets.lutron.com/a/documents/369696.pdf.

What are the minimum BACnet points to integrate the Lutron Quantum BACnet Area Virtual Device?

Start with AV 2 Lighting Level (Area light level command, 0-100 %); MV 4 Lighting Scene (Scene select; 1 = Off scene); BV 3 Lighting State (On if any light in the area is on); MV 8 Occupancy State (1 Unocc, 2 Occ, 3 Inactive, 4 Unknown); AV 18 Total Power (Present lighting power, W); AV 15 Number of Lamp Failures (Count of failed lamps); AV 16 Number of Devices Not Responding (Count of offline lighting devices).

How do I enable BMS control of the Lutron Quantum BACnet Area Virtual Device?

BACnet is native to the Quantum processor but needs a BACnet software license per processor (QSW-BAC-PP-A covers 50 areas); a Lutron service representative enables it and sets the device IDs and network numbers. No separate BMS enable point exists.

How do I check these points on the real Quantum BACnet Area Virtual Device?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

Source: BACnet PIC Statement for Quantum Area Virtual Devices using Quantum Version 2.6 · 369696a · rev. 2013-08-12. Object names, instances and units are reproduced as published; descriptions are our own.