Lighting control system (BACnet IP area device) · BACnet points list
Lutron Quantum BACnet Area Virtual Device BACnet points list
Updated 28 October 2026
Quantum processors (Quantum Lighting Hubs) speak BACnet IP natively once a BACnet license is enabled. Each subsystem is a main BACnet device that routes to one virtual device per area (room). Every area device carries the same fixed objects for light level, scene, occupancy, daylighting, load shedding, Hyperion shades, power and device failures, plus one object per lighting zone, shade group, 3-wire motor zone and light sensor in that area.
This page lists 29 BACnet objects for the Lutron Quantum BACnet Area Virtual Device — 19 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Lutron’s own free documentation, linked below.
- Manufacturer
- Lutron
- Model
- Quantum BACnet Area Virtual Device
- Equipment
- Lighting control system (BACnet IP area device)
- Equipment type
- Other equipment
- BACnet objects
- 29 (19 writable)
- Transport
- BACnet IP
- Firmware
- Quantum 2.6 (BACnet integration software 2.0)
- Also known as
- Lutron Quantum BACnet, Quantum area device, Quantum BACnet integration, QSW-BAC-PP-A, 369696, Lutron lighting BACnet points, Quantum Lighting Hub BACnet
BMS integration notes: Lutron Quantum BACnet Area Virtual Device
A Lutron service engineer enables the BACnet license and sets device IDs and network numbers. Each area then shows up as a virtual device behind the processor. Command the area light level (AV 2) or scene (MV 4), read occupancy (MV 8) and power (AV 18), and watch the failure counters.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AV 2 | Lighting Level | Area light level command, 0-100 % | Write |
| MV 4 | Lighting Scene | Scene select; 1 = Off scene | Write |
| BV 3 | Lighting State | On if any light in the area is on | Write |
| MV 8 | Occupancy State | 1 Unocc, 2 Occ, 3 Inactive, 4 Unknown | Read |
| AV 18 | Total Power | Present lighting power, W | Read |
| AV 15 | Number of Lamp Failures | Count of failed lamps | Read |
| AV 16 | Number of Devices Not Responding | Count of offline lighting devices | Read |
Enable & remote start
BACnet is native to the Quantum processor but needs a BACnet software license per processor (QSW-BAC-PP-A covers 50 areas); a Lutron service representative enables it and sets the device IDs and network numbers. No separate BMS enable point exists.
Network setup
- BACnet IP (Annex J). The processor is a BACnet router: area virtual devices sit on a virtual network behind the subsystem device.
- Device ID = Base + System + 1; Base default 1760000, System 0-127. Agree device IDs and network numbers with the integrator first.
- Lutron advises at most 50 areas per subsystem; more areas means slower BACnet responses.
- The processor can register as a foreign device; give the BBMD address to the Lutron engineer if the BMS is on another subnet.
- Enable COV on the Lutron side before the BMS discovers the system.
Watch out for
- Lighting Level reports the brightest fixture in the area when fixtures differ.
- Lutron application notes say Schedule and Trend Log objects are not supported; trend and schedule from the BMS or the Quantum timeclock.
- Zone and shade object instances are assigned per area; read the object list of each area device.
Lutron Quantum BACnet Area Virtual Device BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AVmin | 2 | Lighting Level | Highest light level in the area, 0-100 | % | Write | |
| BVmin | 3 | Lighting State | On if any light in the area is on | Write | 0=Off, 1=On | |
| MVmin | 4 | Lighting Scene | Active lighting scene; 1 = Off scene | Write | 1=Off scene; 2..n = scenes named in the Quantum project ({SceneName}) | |
| BV | 5 | Daylighting Enabled | Lets daylight sensors limit the area's light level | Write | 0=Disabled, 1=Enabled | |
| AV | 6 | Daylighting Level | Daylight target cap, 0-100 | % | Write | |
| BV | 7 | Disable Occupancy | True stops occupancy sensors affecting the lights | Write | 0=False, 1=True | |
| MVmin | 8 | Occupancy State | Occupancy of the whole area | Read | 1=Unoccupied, 2=Occupied, 3=Inactive, 4=Unknown | |
| AV | 9 | Unoccupied Level | Light level/scene used when the area goes unoccupied (0-216) | Write | 0=Off, 1-100=level %, 101=Unaffected, 102=Daylighting, 200=Off scene, 201-216=Scene 1-16 | |
| AV | 10 | Occupied Level | Light level/scene used when the area goes occupied (0-216) | Write | 0=Off, 1-100=level %, 101=Unaffected, 102=Daylighting, 200=Off scene, 201-216=Scene 1-16 | |
| AV | 11 | Additional Occupied Timeout | Extra wait after sensors go unoccupied, 0-300 | min | Write | |
| BV | 12 | Loadshed Allowed | Area takes part in load shedding | Write | 0=No, 1=Yes | |
| AV | 13 | Loadshed Goal | Light reduction when loadshed is on, 0-90 % | Write | ||
| MV | 14 | Occupancy Mode | How occupancy sensors control the lights | Write | 1=Inactive, 2=Automatic ON and Automatic OFF, 3=Manual ON and Automatic OFF, 4=Not Applicable | |
| AVmin | 15 | Number of Lamp Failures | Digital ballasts/drivers reporting lamp failure | Read | ||
| AVmin | 16 | Number of Devices Not Responding | Programmed devices not responding | Read | ||
| BV | 17 | Hyperion Enabled | Sun-tracking shade control for the area | Write | 0=Disabled, 1=Enabled | |
| AVmin | 18 | Total Power | Present lighting power in the area | watts | Read | |
| AV | 19 | Maximum Power | Connected lighting load of the area | watts | Read | |
| BV | 20 | Roof-Mount Cloudy Day Sensor: Area Status | Cloudy-day override for Hyperion shades | Write | 0=Dark, 1=Sunny | |
| BV | 21 | Radio Window Sensor State | Radio window sensor override of Hyperion | Write | 0=Disabled, 1=Enabled | |
| BV | 22 | Light Level Discrepancy | Photo sensor reading disagrees with timeclock state | Read | 0=False, 1=True | |
| AV | 23 | Number of Wireless Input Device Failures | Wireless keypads/sensors not communicating | Read | ||
| AV | 25 | Number of Loads with Lamps Nearing End of Life | Loads past their programmed lamp-hours | Read | ||
| AV | 1000 | {ZoneName} Level | Zone light level; one object per zone, instances 1000-1999 | % | Write | |
| AV | 2000 | {ShadeGroupName} Level | Shade group level, 100 = open; instances 2000-2999 | % | Write | |
| MV | 3000 | {ShadeGroupName} Preset | Shade group preset; instances 3000-3999 | Write | 1=Open, 2-30=user presets, 31=Closed, 32-33=not used, 34=Undefined | |
| MV | 4000 | {ShadeGroupName} Radio Window Sensor Shade Group Status | Window sensor state per shade group; instances 4000-4999 | Read | 1=Unknown, 2=Sunny, 3=Dark | |
| MV | 5000 | {3-Wire Motor Zone Name} | 3-wire motor output state; instances 5000-5999 | Write | 1=Stop, 2=Open, 3=Close | |
| AV | 6000 | Light Sensor Value | Light sensor reading per sensor; instances 6000-6999 | fc | Read |
No points match these filters.
Integration notes
- Object names in braces ({ZoneName}, {ShadeGroupName}, {3-Wire Motor Zone Name}) take the names set in the Quantum project.
- Only the first instance of each repeating range is listed. The document gives each zone level object a unique instance from 1000 to 1999 and each shade group level a unique instance from 2000 to 2999; shade group presets use 3000-3999, shade group window sensor status 4000-4999, 3-wire motor zones 5000-5999 and light sensors 6000-6999.
- Instance 24 is not used in the document.
- Area device IDs are Base + System + 1, with Base set in the Quantum software (default 1760000) and System 0-127.
- Unoccupied Level and Occupied Level are numeric codes: 0 off, 1-100 percent, 101 unaffected, 102 daylighting, 200 off scene, 201-216 scenes 1-16.
- The document is Lutron 369696a (PIC statement for Quantum area virtual devices, Quantum 2.6).
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Quantum BACnet Area Virtual Device and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Lutron Quantum BACnet Area Virtual Device
How many BACnet points does the Lutron Quantum BACnet Area Virtual Device have?
This list has 29 BACnet objects: 15 analog values, 8 binary values, 6 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Lutron Quantum BACnet Area Virtual Device BACnet points are writable?
19 of the 29 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Lutron Quantum BACnet Area Virtual Device BACnet documentation?
The source is BACnet PIC Statement for Quantum Area Virtual Devices using Quantum Version 2.6 (369696a), revision 2013-08-12, published free by Lutron at https://assets.lutron.com/a/documents/369696.pdf.
What are the minimum BACnet points to integrate the Lutron Quantum BACnet Area Virtual Device?
Start with AV 2 Lighting Level (Area light level command, 0-100 %); MV 4 Lighting Scene (Scene select; 1 = Off scene); BV 3 Lighting State (On if any light in the area is on); MV 8 Occupancy State (1 Unocc, 2 Occ, 3 Inactive, 4 Unknown); AV 18 Total Power (Present lighting power, W); AV 15 Number of Lamp Failures (Count of failed lamps); AV 16 Number of Devices Not Responding (Count of offline lighting devices).
How do I enable BMS control of the Lutron Quantum BACnet Area Virtual Device?
BACnet is native to the Quantum processor but needs a BACnet software license per processor (QSW-BAC-PP-A covers 50 areas); a Lutron service representative enables it and sets the device IDs and network numbers. No separate BMS enable point exists.
How do I check these points on the real Quantum BACnet Area Virtual Device?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
Source: BACnet PIC Statement for Quantum Area Virtual Devices using Quantum Version 2.6 · 369696a · rev. 2013-08-12. Object names, instances and units are reproduced as published; descriptions are our own.