- myRoom XC BACnet (system and area devices)
Hospitality lighting and HVAC control system (BACnet IP) · BACnet points list
Lutron myRoom XC BACnet (system and area devices) BACnet points list
Updated 4 November 2026
The myRoom XC processor speaks BACnet IP. A system device carries the master load-shed object, and each guestroom area is a virtual device with lighting state, scene, occupancy, guest presence, lighting power and the Palladiom thermostat's HVAC zone objects (temperature, humidity, mode, fan, setpoint and drift).
This page lists 22 BACnet objects for the Lutron myRoom XC BACnet (system and area devices) — 16 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Lutron’s own free documentation, linked below.
- Manufacturer
- Lutron
- Model
- myRoom XC BACnet (system and area devices)
- Equipment
- Hospitality lighting and HVAC control system (BACnet IP)
- Equipment type
- Other equipment
- BACnet objects
- 22 (16 writable)
- Transport
- BACnet IP
- Firmware
- Not stated
- Also known as
- Lutron myRoom XC BACnet, myRoom XC processor, 3691271, Lutron Palladiom thermostat BACnet, Lutron guestroom BACnet XC
Reference only, provided as-is: verify against Lutron’s current documentation and the live device before use. Not official Lutron information. Terms of use.
BMS integration notes: Lutron myRoom XC BACnet (system and area devices)
Each guestroom area is a virtual BACnet device behind the myRoom XC processor. Read guest presence (MV 20) and occupancy (MV 8), command the thermostat mode (MV 7106), setpoint (AV 7114) and fan mode (MV 7108), and select lighting scenes (MV 4). If no FCU controller or VRF interface is wired to the Palladiom thermostat, the BMS must write the zone temperature, humidity and fan state.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| MV 7106 | {HVACZoneName} Operating Mode | Thermostat mode: 1 Off, 4 Auto | Write |
| MV 7108 | {HVACZoneName} Fan Mode | Fan mode: Auto, High, Medium, Low | Write |
| MV 4 | Lighting Scene | Lighting preset; 1 = Off scene | Write |
| AV 7114 | {HVACZoneName} Single Setpoint Celsius | Zone setpoint, °C | Write |
| AV 7100 | {HVACZoneName} Temperature Celsius | Zone temperature; BMS writes it if no FCU link | Write |
| MV 7107 | {HVACZoneName} Operating State | Heating/cooling stage reported for the zone | Write |
| MV 20 | Guest Presence Detection State | 1 Unoccupied, 2 Occupied, 256 Unknown | Read |
| AV 8000 | Measured Temperature Reading (Celsius) | Thermostat sensor temperature, °C | Read |
| AV 18 | Total Lighting Power | Present lighting power, W | Read |
Enable & remote start
BACnet integration is a licensed feature set up in Lutron Designer; there is no BMS enable point.
Sensors & values from the BMS
If no FCU controller or VRV/VRF interface is connected directly to the Palladiom thermostat, the HVAC system must write zone temperature (AV 7100/7103), humidity (AV 7120) and fan state (MV 7109) for display on the thermostat. Otherwise Lutron writes them and they are read-only to the BMS.
Network setup
- BACnet IP; area devices are virtual devices routed behind the processor's physical device.
- The processor can register as a foreign device with a BBMD.
- Lutron's BACnet report from Designer shows which processor is the main one (it carries BV 2).
Watch out for
- Lighting Scene reads Unknown when the room is not in a defined preset.
- Celsius and Fahrenheit objects exist side by side; map one set only.
- Writing BV 2 sheds lighting load in every area of the system.
Lutron myRoom XC BACnet (system and area devices) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| BV | 2 | Master Load Shed Enabled | Load shed for all areas (main processor only) | Write | 0=Disabled, 1=Enabled | |
| BV | 3 | Lighting State | On if any lighting zone in the area is on | Write | 0=Off, 1=On | |
| MVmin | 4 | Lighting Scene | Lighting preset; 1 = Off scene | Write | 1=Off scene; other states = scenes named in Lutron Designer ({SceneName}) | |
| MV | 8 | Occupancy State | Occupancy from the area's sensors | Read | 1=Unoccupied, 2=Occupied, 3=Inactive (unused), 4=Unknown | |
| AVmin | 18 | Total Lighting Power | Present lighting power in the area | W | Read | |
| AV | 19 | Maximum Lighting Power | Connected lighting load of the area | W | Read | |
| MVmin | 20 | Guest Presence Detection State | Guest presence of the room | Read | 1=Unoccupied, 2=Occupied, 256=Unknown | |
| AVmin | 7100 | {HVACZoneName} Temperature Celsius | Zone display temperature | °C | Write | |
| AV | 7103 | {HVACZoneName} Temperature Fahrenheit | Zone display temperature | °F | Write | |
| MVmin | 7106 | {HVACZoneName} Operating Mode | Thermostat operating mode | Write | 1=Off, 4=Auto, 256=Unknown | |
| MVmin | 7107 | {HVACZoneName} Operating State | Reported HVAC stage | Write | 1=None, Heat Last; 2=Heating; 6=None, Cool Last; 7=Cooling; 9=Off; 256=Unknown | |
| MVmin | 7108 | {HVACZoneName} Fan Mode | Commanded fan mode | Write | 1=Auto, 4=No Fan, 5=High, 6=Medium, 7=Low, 256=Unknown | |
| MV | 7109 | {HVACZoneName} Fan State | Reported fan speed | Write | 1=Unknown, 2=Off, 3=High/On, 4=Medium, 5=Low, 256=Unknown | |
| AVmin | 7114 | {HVACZoneName} Single Setpoint Celsius | Zone setpoint, 0-100 | °C | Write | |
| AV | 7115 | {HVACZoneName} Single Setpoint Fahrenheit | Zone setpoint, 32-212 | °F | Write | |
| AV | 7116 | {HVACZoneName} Negative (Heating) Drift Celsius | Allowed drift below setpoint, 0-8 | °C | Write | |
| AV | 7117 | {HVACZoneName} Positive (Cooling) Drift Celsius | Allowed drift above setpoint, 0-8 | °C | Write | |
| AV | 7118 | {HVACZoneName} Negative (Heating) Drift Fahrenheit | Allowed drift below setpoint, 0-15 | °F | Write | |
| AV | 7119 | {HVACZoneName} Positive (Cooling) Drift Fahrenheit | Allowed drift above setpoint, 0-15 | °F | Write | |
| AV | 7120 | {HVACZoneName} Relative Humidity | Zone relative humidity | % | Write | |
| AVmin | 8000 | Measured Temperature Reading (Celsius) | Palladiom thermostat sensor, 0.5 °C steps | °C | Read | |
| AV | 8001 | Measured Temperature Reading (Fahrenheit) | Palladiom thermostat sensor, 1 °F steps | °F | Read |
No points match these filters.
Object ID lookup: Lutron myRoom XC point IDs by name
BV2Master Load Shed EnabledBV3Lighting StateMV4Lighting SceneMV8Occupancy StateAV18Total Lighting PowerAV19Maximum Lighting PowerMV20Guest Presence Detection StateAV7100{HVACZoneName} Temperature CelsiusAV7103{HVACZoneName} Temperature FahrenheitMV7106{HVACZoneName} Operating ModeMV7107{HVACZoneName} Operating StateMV7108{HVACZoneName} Fan ModeMV7109{HVACZoneName} Fan StateAV7114{HVACZoneName} Single Setpoint CelsiusAV7115{HVACZoneName} Single Setpoint FahrenheitAV7116{HVACZoneName} Negative (Heating) Drift CelsiusAV7117{HVACZoneName} Positive (Cooling) Drift CelsiusAV7118{HVACZoneName} Negative (Heating) Drift FahrenheitAV7119{HVACZoneName} Positive (Cooling) Drift FahrenheitAV7120{HVACZoneName} Relative HumidityAV8000Measured Temperature Reading (Celsius)AV8001Measured Temperature Reading (Fahrenheit)
Integration notes
- BV 2 Master Load Shed Enabled sits on the system device of the main processor only; all other objects are on each area virtual device.
- Names in braces ({HVACZoneName}, {SceneName}) take the names set in Lutron Designer.
- Unknown (256) is a transitional state after a power cycle.
- HVAC temperature, humidity and fan state are written by Lutron when an FCU controller or VRV/VRF interface is wired to the Palladiom thermostat; otherwise the HVAC system must write them over BACnet.
- Occupancy State (MV 8) is the sensor status; Guest Presence Detection State (MV 20) is the room's guest presence.
- Source: Lutron PIC statement 3691271c (09.15.25).
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the myRoom XC BACnet (system and area devices) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Lutron myRoom XC BACnet (system and area devices)
How many BACnet points does the Lutron myRoom XC BACnet (system and area devices) have?
This list has 22 BACnet objects: 13 analog values, 2 binary values, 7 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Lutron myRoom XC BACnet (system and area devices) BACnet points are writable?
16 of the 22 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Lutron myRoom XC BACnet (system and area devices) BACnet documentation?
The source is BACnet PIC Statement for myRoom XC (3691271c), revision 2025-09-15, published free by Lutron at https://assets.lutron.com/a/documents/3691271.pdf.
What are the minimum BACnet points to integrate the Lutron myRoom XC BACnet (system and area devices)?
Start with MV 7106 {HVACZoneName} Operating Mode (Thermostat mode: 1 Off, 4 Auto); MV 7108 {HVACZoneName} Fan Mode (Fan mode: Auto, High, Medium, Low); MV 4 Lighting Scene (Lighting preset; 1 = Off scene); AV 7114 {HVACZoneName} Single Setpoint Celsius (Zone setpoint, °C); AV 7100 {HVACZoneName} Temperature Celsius (Zone temperature; BMS writes it if no FCU link); MV 7107 {HVACZoneName} Operating State (Heating/cooling stage reported for the zone); MV 20 Guest Presence Detection State (1 Unoccupied, 2 Occupied, 256 Unknown); AV 8000 Measured Temperature Reading (Celsius) (Thermostat sensor temperature, °C); AV 18 Total Lighting Power (Present lighting power, W).
How do I enable BMS control of the Lutron myRoom XC BACnet (system and area devices)?
BACnet integration is a licensed feature set up in Lutron Designer; there is no BMS enable point.
Can the BMS supply sensor values to the Lutron myRoom XC BACnet (system and area devices)?
If no FCU controller or VRV/VRF interface is connected directly to the Palladiom thermostat, the HVAC system must write zone temperature (AV 7100/7103), humidity (AV 7120) and fan state (MV 7109) for display on the thermostat. Otherwise Lutron writes them and they are read-only to the BMS.
How do I check these points on the real myRoom XC BACnet (system and area devices)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Lutron BACnet points lists
- Hospitality lighting and HVAC control system (BACnet IP area device)
Lutron myRoom BACnet Area Virtual Device (myRoom 3.3)
Lutron myRoom hospitality guestroom control systems (software 3.3) with BACnet integration; each guestroom area is its own virtual BACnet device.
Also known as: Lutron myRoom BACnet, myRoom guestroom BACnet, myRoom area device, 3691087, Lutron hotel guestroom control BACnet - Lighting control system (BACnet IP area device)
Lutron Quantum BACnet Area Virtual Device
Lutron Quantum lighting control systems with the BACnet license; each programmed area appears as its own virtual BACnet device.
Also known as: Lutron Quantum BACnet, Quantum area device, Quantum BACnet integration, QSW-BAC-PP-A, 369696, Lutron lighting BACnet points, Quantum Lighting Hub BACnet - Lighting control system (BACnet IP subsystem device)
Lutron Quantum BACnet Subsystem Device (Quantum 3.1)
Lutron Quantum lighting control systems (Quantum 3.1) with BACnet; one physical subsystem device per subsystem, typically one per floor.
Also known as: Lutron Quantum subsystem BACnet, Quantum main device BACnet, Quantum timeclock BACnet, 369997, Quantum BACnet integration subsystem - Lighting control system (BACnet IP)
Lutron Vive BACnet (hub and area devices)
Lutron Vive wireless lighting control systems with BACnet IP on the Vive hub (Vive 1.07); one hub device plus one virtual device per area.
Also known as: Lutron Vive, Vive hub, Vive BACnet Integration, 369996, Vive 1.07
Source: BACnet PIC Statement for myRoom XC · 3691271c · rev. 2025-09-15. Object names, instances and units are reproduced as published; descriptions are our own.