- myRoom BACnet Area Virtual Device (myRoom 3.3)
Hospitality lighting and HVAC control system (BACnet IP area device) · BACnet points list
Lutron myRoom BACnet Area Virtual Device (myRoom 3.3) BACnet points list
Updated 4 November 2026
A myRoom processor speaks BACnet IP and routes to one virtual device per guestroom area. Each area device has fixed objects for light level, lighting state, scene, occupancy, power and failure counters, plus HVAC zone objects (temperature, mode, fan, setpoint, drift) and one object per lighting zone, shade group, 3-wire motor zone, temperature sensor and keypad.
This page lists 30 BACnet objects for the Lutron myRoom BACnet Area Virtual Device (myRoom 3.3) — 23 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Lutron’s own free documentation, linked below.
- Manufacturer
- Lutron
- Model
- myRoom BACnet Area Virtual Device (myRoom 3.3)
- Equipment
- Hospitality lighting and HVAC control system (BACnet IP area device)
- Equipment type
- Other equipment
- BACnet objects
- 30 (23 writable)
- Transport
- BACnet IP
- Firmware
- myRoom 3.3
- Default device instance
- Base + System + 1 (Base default 1760000)
- Also known as
- Lutron myRoom BACnet, myRoom guestroom BACnet, myRoom area device, 3691087, Lutron hotel guestroom control BACnet
Reference only, provided as-is: verify against Lutron’s current documentation and the live device before use. Not official Lutron information. Terms of use.
BMS integration notes: Lutron myRoom BACnet Area Virtual Device (myRoom 3.3)
The BACnet base and system numbers are set in the myRoom configuration software; each guestroom then shows up as a virtual device behind the myRoom processor. Read occupancy (MV 8) and lighting power, command scenes (MV 4) or level (AV 2), and use the HVAC zone objects for mode, setpoint and fan. If the room's HVAC unit is on BACnet, the BMS must write temperature, operating state and fan state to the 71xx objects.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| MV 4 | Lighting Scene | Scene select; 1 = Off scene | Write |
| MV 7106 | {HVACZoneName} Operating Mode | HVAC mode: 1 Off/Protect, 4 Auto | Write |
| MV 7108 | {HVACZoneName} Fan Mode | Fan mode: Auto, High, Medium, Low | Write |
| AV 2 | Lighting Level | Area light level command, 0-100 % | Write |
| AV 7114 | {HVACZoneName} Single Setpoint Celsius | Zone setpoint, °C | Write |
| AV 7100 | {HVACZoneName} Temperature Celsius | Zone temperature; BMS writes it if HVAC is on BACnet | Write |
| MV 7107 | {HVACZoneName} Operating State | HVAC stage; BMS writes it if HVAC is on BACnet | Write |
| MV 8 | Occupancy State | 1 Unoccupied, 2 Occupied, 4 Unknown | Read |
| AV 18 | Total Lighting Power | Present lighting power, W | Read |
| MV 7111 | {HVACZoneName} HVAC Fault Status | 2 = generic HVAC fault | Write |
Enable & remote start
BACnet integration is a licensed feature set up in the myRoom configuration software; there is no BMS enable point.
Sensors & values from the BMS
When the HVAC unit is connected over BACnet rather than the thermostat's Modbus link, the zone temperature (AV 7100/7103), operating state (MV 7107) and fan state (MV 7109) must be written by the HVAC side so the thermostat can display them and energy reports work.
Network setup
- BACnet IP. The myRoom processor is a router: area virtual devices sit on a virtual network behind the main device.
- Area device ID = Base + System + 1; Base default 1760000, System 0-127, both set in the myRoom software.
- The processor can register as a foreign device with a BBMD.
Watch out for
- Lighting Level reports the brightest fixture in the area when fixtures differ; RF zones are not included.
- Lutron says objects not described in the PIC may appear in a BACnet browser and should not be used.
- Celsius and Fahrenheit objects exist side by side; map one set only.
Lutron myRoom BACnet Area Virtual Device (myRoom 3.3) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AVmin | 2 | Lighting Level | Highest light level in the area, 0-100 | % | Write | |
| BV | 3 | Lighting State | On if any light in the area is on | Write | 0=Off, 1=On | |
| MVmin | 4 | Lighting Scene | Active scene; 1 = Off scene | Write | 1=Off scene; other states = scenes named in the myRoom project ({SceneName}) | |
| MVmin | 8 | Occupancy State | Occupancy from the room's sensors | Read | 1=Unoccupied, 2=Occupied, 4=Unknown | |
| AV | 15 | Number of Lamp Failures | Digital ballasts/drivers reporting lamp failure | Read | ||
| AV | 16 | Number of Devices Not Responding | Programmed devices not responding | Read | ||
| AVmin | 18 | Total Lighting Power | Present lighting power in the area | W | Read | |
| AV | 19 | Maximum Lighting Power | Connected lighting load of the area | W | Read | |
| AV | 23 | Number of Wireless Input Device Failures | Wireless inputs not communicating | Read | ||
| AV | 1000 | {ZoneName} Level | Zone light level; one object per zone, instances 1000-1099 | % | Write | |
| AV | 2000 | {ShadeGroupName} Level | Shade group level, 100 = open; instances 2000-2999 | % | Write | |
| MV | 3000 | {ShadeGroupName} Preset | Shade group preset; instances 3000-3999 | Write | 1=Open, 2-30=user presets, 31=Closed, 32-33=not used, 34=Undefined | |
| MV | 5000 | {3-WireMotorZoneName} | 3-wire motor output state; instances 5000-5099 | Write | 1=Stop, 2=Open, 3=Close | |
| AVmin | 7100 | {HVACZoneName} Temperature Celsius | HVAC zone display temperature | °C | Write | |
| AV | 7103 | {HVACZoneName} Temperature Fahrenheit | HVAC zone display temperature | °F | Write | |
| MVmin | 7106 | {HVACZoneName} Operating Mode | Commanded HVAC mode | Write | 1=Off/Protect, 4=Auto, 256=Unknown | |
| MVmin | 7107 | {HVACZoneName} Operating State | Reported HVAC stage | Write | 1=None, Heat Last; 2=Heat 1; 3=Heat 1+2; 4=Heat 1+2+3; 5=Heat 3; 6=None, Cool Last; 7=Cool 1; 8=Cool 1+2; 9=Off; 10=Emergency Heat; 11=Dry; 256=Unknown | |
| MVmin | 7108 | {HVACZoneName} Fan Mode | Commanded fan mode | Write | 1=Auto, 4=No Fan, 5=High, 6=Medium, 7=Low, 256=Unknown | |
| MV | 7109 | {HVACZoneName} Fan State | Reported fan speed | Write | 1=Unknown, 2=Off, 3=High/On, 4=Medium, 5=Low, 256=Unknown | |
| MVmin | 7111 | {HVACZoneName} HVAC Fault Status | HVAC fault indication | Write | 1=Unknown, 2=Generic Fault(s), 3=No Fault | |
| AV | 7113 | {HVACZoneName} HVAC Power | Calculated HVAC zone power | W | Read | |
| AVmin | 7114 | {HVACZoneName} Single Setpoint Celsius | Zone setpoint, 0-100 | °C | Write | |
| AV | 7115 | {HVACZoneName} Single Setpoint Fahrenheit | Zone setpoint, 32-212 | °F | Write | |
| AV | 7116 | {HVACZoneName} Negative Drift Celsius | Allowed drift below setpoint, 0-8 | °C | Write | |
| AV | 7117 | {HVACZoneName} Positive Drift Celsius | Allowed drift above setpoint, 0-8 | °C | Write | |
| AV | 7118 | {HVACZoneName} Negative Drift Fahrenheit | Allowed drift below setpoint, 0-15 | °F | Write | |
| AV | 7119 | {HVACZoneName} Positive Drift Fahrenheit | Allowed drift above setpoint, 0-15 | °F | Write | |
| AV | 7300 | {TemperatureSensorName} Temperature Celsius | Optional FCU supply air sensor; instances 7300-7399 | °C | Write | |
| AV | 7400 | {TemperatureSensorName} Temperature Fahrenheit | Optional FCU supply air sensor; instances 7400-7499 | °F | Write | |
| BV | 8000 | {KeypadName} State | Enables or disables a keypad; instances 8000-8999 | Write | 0=Disabled, 1=Enabled |
No points match these filters.
Object ID lookup: Lutron myRoom BACnet Area Virtual Device point IDs by name
AV2Lighting LevelBV3Lighting StateMV4Lighting SceneMV8Occupancy StateAV15Number of Lamp FailuresAV16Number of Devices Not RespondingAV18Total Lighting PowerAV19Maximum Lighting PowerAV23Number of Wireless Input Device FailuresAV1000{ZoneName} LevelAV2000{ShadeGroupName} LevelMV3000{ShadeGroupName} PresetMV5000{3-WireMotorZoneName}AV7100{HVACZoneName} Temperature CelsiusAV7103{HVACZoneName} Temperature FahrenheitMV7106{HVACZoneName} Operating ModeMV7107{HVACZoneName} Operating StateMV7108{HVACZoneName} Fan ModeMV7109{HVACZoneName} Fan StateMV7111{HVACZoneName} HVAC Fault StatusAV7113{HVACZoneName} HVAC PowerAV7114{HVACZoneName} Single Setpoint CelsiusAV7115{HVACZoneName} Single Setpoint FahrenheitAV7116{HVACZoneName} Negative Drift CelsiusAV7117{HVACZoneName} Positive Drift CelsiusAV7118{HVACZoneName} Negative Drift FahrenheitAV7119{HVACZoneName} Positive Drift FahrenheitAV7300{TemperatureSensorName} Temperature CelsiusAV7400{TemperatureSensorName} Temperature FahrenheitBV8000{KeypadName} State
Integration notes
- Names in braces ({ZoneName}, {HVACZoneName}, {ShadeGroupName}, {KeypadName}...) take the names set in the myRoom project.
- Only the first instance of each repeating range is listed: zone levels 1000-1099, shade levels 2000-2999, shade presets 3000-3999, 3-wire motors 5000-5099, supply air sensors 7300-7399 (C) and 7400-7499 (F), keypads 8000-8999.
- HVAC temperature, operating state and fan state are read-only when the HVAC unit is on the thermostat's Modbus link, and must be written by the BMS when the HVAC unit is connected over BACnet.
- Occupancy State reflects the room's sensors; Lutron reports guest presence (GPD) through a state variable on the myRoom main device.
- Source: Lutron PIC statement 3691087c (09.20.24).
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the myRoom BACnet Area Virtual Device (myRoom 3.3) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Lutron myRoom BACnet Area Virtual Device (myRoom 3.3)
How many BACnet points does the Lutron myRoom BACnet Area Virtual Device (myRoom 3.3) have?
This list has 30 BACnet objects: 19 analog values, 2 binary values, 9 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Lutron myRoom BACnet Area Virtual Device (myRoom 3.3) BACnet points are writable?
23 of the 30 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Lutron myRoom BACnet Area Virtual Device (myRoom 3.3) BACnet documentation?
The source is BACnet PIC Statement for myRoom Virtual Devices Using Version 3.3 (3691087c), revision 2024-09-20, published free by Lutron at https://assets.lutron.com/a/documents/3691087.pdf.
What are the minimum BACnet points to integrate the Lutron myRoom BACnet Area Virtual Device (myRoom 3.3)?
Start with MV 4 Lighting Scene (Scene select; 1 = Off scene); MV 7106 {HVACZoneName} Operating Mode (HVAC mode: 1 Off/Protect, 4 Auto); MV 7108 {HVACZoneName} Fan Mode (Fan mode: Auto, High, Medium, Low); AV 2 Lighting Level (Area light level command, 0-100 %); AV 7114 {HVACZoneName} Single Setpoint Celsius (Zone setpoint, °C); AV 7100 {HVACZoneName} Temperature Celsius (Zone temperature; BMS writes it if HVAC is on BACnet); MV 7107 {HVACZoneName} Operating State (HVAC stage; BMS writes it if HVAC is on BACnet); MV 8 Occupancy State (1 Unoccupied, 2 Occupied, 4 Unknown); AV 18 Total Lighting Power (Present lighting power, W); MV 7111 {HVACZoneName} HVAC Fault Status (2 = generic HVAC fault).
How do I enable BMS control of the Lutron myRoom BACnet Area Virtual Device (myRoom 3.3)?
BACnet integration is a licensed feature set up in the myRoom configuration software; there is no BMS enable point.
Can the BMS supply sensor values to the Lutron myRoom BACnet Area Virtual Device (myRoom 3.3)?
When the HVAC unit is connected over BACnet rather than the thermostat's Modbus link, the zone temperature (AV 7100/7103), operating state (MV 7107) and fan state (MV 7109) must be written by the HVAC side so the thermostat can display them and energy reports work.
How do I check these points on the real myRoom BACnet Area Virtual Device (myRoom 3.3)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Lutron BACnet points lists
- Hospitality lighting and HVAC control system (BACnet IP)
Lutron myRoom XC BACnet (system and area devices)
Lutron myRoom XC hospitality guestroom systems with BACnet integration (Lutron Designer projects); one system device plus one virtual device per area.
Also known as: Lutron myRoom XC BACnet, myRoom XC processor, 3691271, Lutron Palladiom thermostat BACnet, Lutron guestroom BACnet XC - Lighting control system (BACnet IP area device)
Lutron Quantum BACnet Area Virtual Device
Lutron Quantum lighting control systems with the BACnet license; each programmed area appears as its own virtual BACnet device.
Also known as: Lutron Quantum BACnet, Quantum area device, Quantum BACnet integration, QSW-BAC-PP-A, 369696, Lutron lighting BACnet points, Quantum Lighting Hub BACnet - Lighting control system (BACnet IP subsystem device)
Lutron Quantum BACnet Subsystem Device (Quantum 3.1)
Lutron Quantum lighting control systems (Quantum 3.1) with BACnet; one physical subsystem device per subsystem, typically one per floor.
Also known as: Lutron Quantum subsystem BACnet, Quantum main device BACnet, Quantum timeclock BACnet, 369997, Quantum BACnet integration subsystem - Lighting control system (BACnet IP)
Lutron Vive BACnet (hub and area devices)
Lutron Vive wireless lighting control systems with BACnet IP on the Vive hub (Vive 1.07); one hub device plus one virtual device per area.
Also known as: Lutron Vive, Vive hub, Vive BACnet Integration, 369996, Vive 1.07
Source: BACnet PIC Statement for myRoom Virtual Devices Using Version 3.3 · 3691087c · rev. 2024-09-20. Object names, instances and units are reproduced as published; descriptions are our own.