Lighting control system (BACnet IP subsystem device) · BACnet points list

Lutron Quantum BACnet Subsystem Device (Quantum 3.1) BACnet points list

Updated 4 November 2026

Short answer

Each Quantum subsystem is a physical BACnet IP device that routes to the area virtual devices (listed separately). The subsystem device holds the subsystem-wide objects: master load shed, master Hyperion shade control, the roof-mount cloudy-day sensor, and one set of objects per timeclock, timeclock event and state variable.

This page lists 9 BACnet objects for the Lutron Quantum BACnet Subsystem Device (Quantum 3.1) — 9 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Lutron’s own free documentation, linked below.

Manufacturer
Lutron
Model
Quantum BACnet Subsystem Device (Quantum 3.1)
Equipment
Lighting control system (BACnet IP subsystem device)
Equipment type
Other equipment
BACnet objects
9 (9 writable)
Transport
BACnet IP
Firmware
Quantum 3.1 (BACnet integration software 2.0)
Default device instance
Base + System + 1 (Base default 1760000)
Also known as
Lutron Quantum subsystem BACnet, Quantum main device BACnet, Quantum timeclock BACnet, 369997, Quantum BACnet integration subsystem
Source document
BACnet PIC Statement for Quantum Subsystem Physical Devices using Quantum Version 3.1 · 369997a · rev. 2016-05-24
Download CSV 9 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Lutron’s current documentation and the live device before use. Not official Lutron information. Terms of use.

BMS integration notes: Lutron Quantum BACnet Subsystem Device (Quantum 3.1)

Integration in brief

Use the subsystem device for building-wide actions: master load shed (BV 2), Hyperion shade control (BV 3) and timeclock enable/disable (MV 2000 range). Area lighting itself is read and commanded on the area virtual devices.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 2Master Loadshed EnabledTurns load shedding on for the subsystemWrite
MV 2000{TimeclockName} Enable CommandEnable or disable a timeclock scheduleWrite
BV 3Master Hyperion EnabledTurns automatic sun-tracking shades on/offWrite
BV 4Roof-Mount Cloudy Day Sensor: Subsystem StatusCloudy-day input: 0 Dark, 1 SunnyWrite

Enable & remote start

BACnet IP is built into the Quantum processor as a licensed software option; device IDs come from the Base and System numbers set in the Quantum configuration software. No separate BMS enable point exists.

Sensors & values from the BMS

A BMS sensor can stand in for the roof-mounted cloudy-day sensor by writing BV 4 (Dark overrides Hyperion shades to open).

Network setup

Watch out for

Lutron Quantum BACnet Subsystem Device (Quantum 3.1) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

9 of 9 shown
Type
AnalogBinaryMulti-state
Show
Lutron Quantum BACnet Subsystem Device (Quantum 3.1) BACnet Points List
DescriptionStates
BVmin2Master Loadshed EnabledLoad shed for all areas in the subsystemWrite0=Disabled, 1=Enabled
BVmin3Master Hyperion EnabledSun-tracking shade control for the subsystemWrite0=Disabled, 1=Enabled
BVmin4Roof-Mount Cloudy Day Sensor: Subsystem StatusCloudy-day override for Hyperion shadesWrite0=Dark, 1=Sunny
BV1000{TimeclockName} EnabledEnable/disable a timeclock; instances 1000-1999Write0=Disabled, 1=Enabled
MVmin2000{TimeclockName} Enable CommandTimeclock enable command; instances 2000-2999Write1=Disable Permanently, 2=Disable Until End of Day Without Catch Up, 3=Disable Until End of Day With Catch Up, 4=Enable Without Catch Up, 5=Enable With Catch Up, 6=Enable and Run Previous Event Only
MV4000{VariableName} Current Variable StateState variable value; instances 4000-4999Write1..n = {StateName} set in the Quantum software
BV5000{Timeclock Name} / {Timeclock Event} EnabledEnable/disable a timeclock event; instances 5000-5999Write0=Disabled, 1=Enabled
AV6000{Timeclock Name} / {Timeclock Event} HourEvent hour, 0-23; instances 6000-6999hWrite
AV7000{Timeclock Name} / {Timeclock Event} MinuteEvent minute, 0-59; instances 7000-7999minWrite
Object ID lookup: Lutron Quantum BACnet Subsystem Device point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Quantum BACnet Subsystem Device (Quantum 3.1) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Lutron Quantum BACnet Subsystem Device (Quantum 3.1)

How many BACnet points does the Lutron Quantum BACnet Subsystem Device (Quantum 3.1) have?

This list has 9 BACnet objects: 2 analog values, 5 binary values, 2 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Lutron Quantum BACnet Subsystem Device (Quantum 3.1) BACnet points are writable?

9 of the 9 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Lutron Quantum BACnet Subsystem Device (Quantum 3.1) BACnet documentation?

The source is BACnet PIC Statement for Quantum Subsystem Physical Devices using Quantum Version 3.1 (369997a), revision 2016-05-24, published free by Lutron at https://assets.lutron.com/a/documents/369997.pdf.

What are the minimum BACnet points to integrate the Lutron Quantum BACnet Subsystem Device (Quantum 3.1)?

Start with BV 2 Master Loadshed Enabled (Turns load shedding on for the subsystem); MV 2000 {TimeclockName} Enable Command (Enable or disable a timeclock schedule); BV 3 Master Hyperion Enabled (Turns automatic sun-tracking shades on/off); BV 4 Roof-Mount Cloudy Day Sensor: Subsystem Status (Cloudy-day input: 0 Dark, 1 Sunny).

How do I enable BMS control of the Lutron Quantum BACnet Subsystem Device (Quantum 3.1)?

BACnet IP is built into the Quantum processor as a licensed software option; device IDs come from the Base and System numbers set in the Quantum configuration software. No separate BMS enable point exists.

Can the BMS supply sensor values to the Lutron Quantum BACnet Subsystem Device (Quantum 3.1)?

A BMS sensor can stand in for the roof-mounted cloudy-day sensor by writing BV 4 (Dark overrides Hyperion shades to open).

How do I check these points on the real Quantum BACnet Subsystem Device (Quantum 3.1)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Lutron BACnet points lists

Source: BACnet PIC Statement for Quantum Subsystem Physical Devices using Quantum Version 3.1 · 369997a · rev. 2016-05-24. Object names, instances and units are reproduced as published; descriptions are our own.