Air handling unit controller · BACnet points list

Komfovent C6 / C6M controller BACnet points list

Updated 4 November 2026

Short answer

The Komfovent C6 / C6M controller exposes its settings and readings over BACnet IP on its RJ-45 Ethernet port (no MS/TP). The list has 154 objects: temperatures and setpoints as AVs, on/off, enables and alarms as BVs, modes and settings as multistate values, and flows, timers and energy figures as positive integer values. Two date values hold the holiday period, and a time value gives the next scheduled mode change.

This page lists 154 BACnet objects for the Komfovent C6 / C6M controller — 83 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Komfovent’s own free documentation, linked below.

Manufacturer
Komfovent
Model
C6 / C6M controller
Equipment
Air handling unit controller
Equipment type
Rooftop units, AHUs & DOAS
BACnet objects
154 (83 writable)
Transport
BACnet IP
Firmware
Not stated
Default device instance
60
Also known as
Komfovent C6, Komfovent C6M, C6M, C6.1, BACnet-C6
Source document
BACnet Connection C6 / C6M - Installation and Service Manual · BACnet-C6_26-08 · rev. 2026-08
Download CSV 154 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Komfovent’s current documentation and the live device before use. Not official Komfovent information. Terms of use.

BMS integration notes: Komfovent C6 / C6M controller

Integration in brief

Switch the unit with BV 0 CONTROL: ON/OFF status and select the mode with MV 1 CONTROL: current mode (only away, normal, intensive and boost can be written). Each mode has its own temperature setpoint AV and supply/extract flow PIVs. Read the INFO temperatures and flows, the ALARMS BVs and the active alarm count; writing 39366 to that count resets alarms.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 0CONTROL: ON/OFF statusOn/off command (1 = on)Write
MV 1CONTROL: current modeMode command; writable values 2-5 (away to boost)Write
AV 1NORMAL: setpointTemperature setpoint for NORMAL modeWrite
AV 11INFO: supply temperatureSupply air temperatureRead
AV 12INFO: extract temperatureExtract air temperatureRead
AV 13INFO: outdoor temperatureOutdoor air temperatureRead
PIV 30INFO: current supply flowSupply air flow, m3/h or l/sRead
BV 32INFO: alarmAny active alarmRead
PIV 28ALARMS: active alarms countActive alarms (0-10); write 39366 to resetWrite

Enable & remote start

BV 0 CONTROL: ON/OFF status turns the unit on (1) or off (0). BV 2 CONTROL: AUTO mode hands mode selection to the schedule or air quality control (MV 0 shows which).

Network setup

Watch out for

Komfovent C6 / C6M controller BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

154 of 154 shown
Type
AnalogBinaryMulti-state
Access
Show
Komfovent C6 / C6M controller BACnet Points List
DescriptionStates
AV0AWAY: setpointRange 5.0 – 40.0°CWrite
AVmin1NORMAL: setpointRange 5.0 – 40.0°CWrite
AV2INTENSIVE: setpointRange 5.0 – 40.0°CWrite
AV3BOOST: setpointRange 5.0 – 40.0°CWrite
AV4KITCHEN: setpointRange 5.0 – 40.0°CWrite
AV5FIREPLACE: setpointRange 5.0 – 40.0°CWrite
AV6OVERRIDE: setpointRange 5.0 – 40.0°CWrite
AV7HOLIDAYS: setpointRange 5.0 – 40.0°CWrite
AV8ECO: minimum supply air temperatureRange 5.0 – 40.0°CWrite
AV9ECO: maximum supply air temperatureRange 5.0 – 40.0°CWrite
AV10AIR QUALITY: temperature setpointRange 5.0 – 40.0°CWrite
AVmin11INFO: supply temperature°CRead
AVmin12INFO: extract temperature°CRead
AVmin13INFO: outdoor temperature°CRead
AV14INFO: water temperature°CRead
AV15INFO: panel 1 temperature°CRead
AV16INFO: panel 2 temperature°CRead
AV17INFO: current supply fan intensivity%Read
AV18INFO: current extract fan intensivity%Read
AV19INFO: heat exchanger%Read
AV20INFO: electric heater%Read
AV21INFO: water heater%Read
AV22INFO: water cooler%Read
AV23INFO: DX unit%Read
AV24EFFICIENCY/STATUS: SPIW/(m3/h)Read
AV25EFFICIENCY/STATUS: SPI (day)W/(m3/h)Read
AV26THERMOSTAT 1: TemperatureRange 5.0 – 40.0°CWrite
AV27THERMOSTAT 1: HysteresisRange 0.1 – 5.0°CWrite
AV28THERMOSTAT 2: TemperatureRange 5.0 – 40.0°CWrite
AV29THERMOSTAT 2: HysteresisRange 0.1 – 5.0°CWrite
BVmin0CONTROL: ON/OFF statusWrite0=off, 1=on
BV1CONTROL: ECO modeWrite0=off, 1=on
BV2CONTROL: AUTO modeWrite0=off, 1=on
BV3AWAY: heatingWrite0=off, 1=on
BV4NORMAL: heatingWrite0=off, 1=on
BV5INTENSIVE: heatingWrite0=off, 1=on
BV6BOOST: heatingWrite0=off, 1=on
BV7KITCHEN: heatingWrite0=off, 1=on
BV8FIREPLACE: heatingWrite0=off, 1=on
BV9OVERRIDE: heatingWrite0=off, 1=on
BV10HOLIDAYS: heatingWrite0=off, 1=on
BV11ECO: free heating/coolingWrite0=off, 1=on
BV12ECO: heating enable deniedWrite0=off, 1=on
BV13ECO: cooling enable deniedWrite0=off, 1=on
BV14AIR QUALITY: enabledWrite0=disabled, 1=enabled
BV15AIR QUALITY: heatingWrite0=off, 1=on
BV16ALARMS: low supply air flowRead0=no, 1=yes
BV17ALARMS: low extract air flowRead0=no, 1=yes
BV18ALARMS: return water temperature lowRead0=no, 1=yes
BV19ALARMS: low supply air temperatureRead0=no, 1=yes
BV20ALARMS: high supply air temperatureRead0=no, 1=yes
BV21ALARMS: electric heater overheatRead0=no, 1=yes
BV22ALARMS: heat exchanger failureRead0=no, 1=yes
BV23ALARMS: heat exchanger icingRead0=no, 1=yes
BV24ALARMS: internal fire alarmRead0=no, 1=yes
BV25ALARMS: external fire alarmRead0=no, 1=yes
BV26ALARMS: temperature sensor failureRead0=no, 1=yes
BV27ALARMS: controller failureRead0=no, 1=yes
BV28ALARMS: service modeRead0=no, 1=yes
BV29ALARMS: clogged air filtersRead0=no, 1=yes
BV30ALARMS: heat exchanger low efficiencyRead0=no, 1=yes
BV31ALARMS: air flow sensor failureRead0=no, 1=yes
BVmin32INFO: alarmRead0=off, 1=on
BV33INFO: heatingRead0=off, 1=on
BV34INFO: coolingRead0=off, 1=on
BV35CLEAN FILTERS CALIBRATIONWrite0=no, 1=yes
BV36THERMOSTAT 1: EnableWrite0=no, 1=yes
BV37THERMOSTAT 2: EnableWrite0=no, 1=yes
BV38ALARMS: humidity sensor failureRead0=no, 1=yes
BV39ALARMS: communication errorRead0=no, 1=yes
BV40ALARMS: supply fan failureRead0=no, 1=yes
BV41ALARMS: exhaust fan failureRead0=no, 1=yes
Other0HOLIDAYS: fromBACnet Date Value object; 2017-01-01 – 2035-12-31Write
Other1HOLIDAYS: tillBACnet Date Value object; 2017-01-01 – 2035-12-31Write
MV0CONTROL: auto mode controlRead1=scheduling, 2=air quality
MVmin1CONTROL: current modeWrite1=standby, 2=away, 3=normal, 4=intensive, 5=boost, 6=kitchen, 7=fireplace, 8=override, 9=holiday, 10=auto, 11=off
MV2SCHEDULER: operation programWrite1=stay at home, 2=working week, 3=office, 4=custom
MV3SCHEDULER: next modeRead1=standby, 2=away, 3=normal, 4=intensive, 5=boost
MV4SCHEDULER: next mode weekdayRead1=today, 2=mo, 3=tu, 4=we, 5=th, 6=fr, 7=sa, 8=su
MV5CONTROL: temperature controlWrite1=supply, 2=extract, 3=room, 4=balance
MV6CONTROL: flow controlWrite1=CAV, 2=VAV, 3=DCV
MV7CONTROL SEQEUENCE: stage 1Write1=none, 2=external coil, 3=electric heater, 4=external DX unit
MV8CONTROL SEQEUENCE: stage 2Write1=none, 2=external coil, 3=electric heater, 4=external DX unit
MV9CONTROL SEQEUENCE: stage 3Write1=none, 2=external coil, 3=electric heater, 4=external DX unit
MV10SETTINGS: coil typeWrite1=hot water, 2=cold water
MV11SETTINGS: languageWrite1=en, 2=lt, 3=ru, 4=pl, 5=sk, 6=de, 7=fr, 8=hu, 9=it, 10=ee, 11=nl, 12=lv, 13=pt, 14=se, 15=fi, 16=hr
MV12SETTINGS: flow unitsWrite1=m3/h, 2=l/s
MV13OVERRIDE: modeWrite1=all time, 2=if on, 3=if off
MV14HOLIDAYS: microventilationWrite1=1 t. per day, 2=2 t. per day, 3=3 t. per day, 4=4 t. per day
MV15AIR QUALITY: sensor type B8Write1=none, 2=CO2, 3=VOC, 4=RH
MV16AIR QUALITY: sensor type B9Write1=none, 2=CO2, 3=VOC, 4=RH
MV17RESET SETTINGSWrite1=none, 2="away", 3="normal", 4="intensive", 5="boost", 6="holidays", 7="override", 8="kitchen", 9="fireplace", 10=air quality, 11=eco, 12=advanced
MV18ECO: heat recovery controlWrite1=Auto, 2=Constant, 3=Non stop
MV19THERMOSTAT 1: outputWrite1=Heating, 2=Cooling
MV20THERMOSTAT 1: output typeWrite1=NO, 2=NC
MV21THERMOSTAT 2: outputWrite1=Heating, 2=Cooling
MV22THERMOSTAT 2: output typeWrite1=NO, 2=NC
PIV0CONTROL: maximum supply flowm3/h, l/sRead
PIV1CONTROL: maximum extract flowm3/h, l/sRead
PIV2CONTROL: maximum supply pressureRange 0 – 1000PaWrite
PIV3CONTROL: maximum extract pressureRange 0 – 1000PaWrite
PIV4CONNECTIVITY: IP addressRange 0 – 4294967295Write
PIV5CONNECTIVITY: maskRange 0 – 4294967295Write
PIV6AWAY: supply flowRange 0.2×max – maxm3/h, l/s, PaWrite
PIV7AWAY: extract flowRange 0.2×max – maxm3/h, l/s, PaWrite
PIV8NORMAL: supply flowRange 0.2×max – maxm3/h, l/s, PaWrite
PIV9NORMAL: extract flowRange 0.2×max – maxm3/h, l/s, PaWrite
PIV10INTENSIVE: supply flowRange 0.2×max – maxm3/h, l/s, PaWrite
PIV11INTENSIVE: extract flowRange 0.2×max – maxm3/h, l/s, PaWrite
PIV12BOOST: supply flowRange 0.2×max – maxm3/h, l/s, PaWrite
PIV13BOOST: extract flowRange 0.2×max – maxm3/h, l/s, PaWrite
PIV14KITCHEN: supply flowRange 0.2×max – maxm3/h, l/sWrite
PIV15KITCHEN: extract flowRange 0.2×max – maxm3/h, l/sWrite
PIV16FIREPLACE: supply flowRange 0.2×max – maxm3/h, l/sWrite
PIV17FIREPLACE: extract flowRange 0.2×max – maxm3/h, l/sWrite
PIV18OVERRIDE: supply flowRange 0.2×max – maxm3/h, l/sWrite
PIV19OVERRIDE: extract flowRange 0.2×max – maxm3/h, l/sWrite
PIV20KITCHEN: timerRange 0 – 300minWrite
PIV21FIREPLACE: timerRange 0 – 300minWrite
PIV22OVERRIDE: timerRange 0 – 300minWrite
PIV23AIR QUALITY: air quality setpoint0-2000 ppm or 0-100 %ppm, %Write
PIV24AIR QUALITY: humidity setpointRange 0 – 100%Write
PIV25AIR QUALITY: minimum intensivityRange 0, 20 – 100%Write
PIV26AIR QUALITY: maximum intensivityRange 0, 20 – 100%Write
PIV27AIR QUALITY: check periodRange 1 – 24hWrite
PIVmin28ALARMS: active alarms countRange 0-10; write 39366 to reset alarmsWrite
PIV29ALARMS: alarm history countRange 0 – 50Read
PIVmin30INFO: current supply flowm3/h, l/sRead
PIV31INFO: current extract flowm3/h, l/sRead
PIV32INFO: filters impurity%Read
PIV33INFO: air dampers%Read
PIV34INFO: supply pressurePaRead
PIV35INFO: extract pressurePaRead
PIV36INFO: air quality/humidity sensor 1ppm, %Read
PIV37INFO: air quality/humidity sensor 2ppm, %Read
PIV38INFO: panel 1 humidity%Read
PIV39INFO: panel 2 humidity%Read
PIV40INFO: panel 1 air qualityppmRead
PIV41INFO: panel 2 air qualityppmRead
PIV42EFFICIENCY/STATUS: power consumptionWRead
PIV43EFFICIENCY/STATUS: heater powerWRead
PIV44EFFICIENCY/STATUS: heat exchanger recoveryWRead
PIV45EFFICIENCY/STATUS: heat exchanger efficiency%Read
PIV46EFFICIENCY/STATUS: energy saving%Read
PIV47EFFICIENCY/STATUS: recovered energy (day)WhRead
PIV48EFFICIENCY/STATUS: recovered energy (month)WhRead
PIV49EFFICIENCY/STATUS: recovered energy (total)WhRead
PIV50CONSUMPTION: AHU (day)WhRead
PIV51CONSUMPTION: AHU (month)WhRead
PIV52CONSUMPTION: AHU (total)WhRead
PIV53CONSUMPTION: add. air heater (day)WhRead
PIV54CONSUMPTION: add. air heater (month)WhRead
PIV55CONSUMPTION: add. air heater (total)WhRead
PIV56INFO: extract humidity%Read
Object ID lookup: Komfovent C6 / C6M controller point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the C6 / C6M controller and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Komfovent C6 / C6M controller

How many BACnet points does the Komfovent C6 / C6M controller have?

This list has 154 BACnet objects: 30 analog values, 42 binary values, 23 multi-state values, 57 positive integer values, 2 others. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Komfovent C6 / C6M controller BACnet points are writable?

83 of the 154 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Komfovent C6 / C6M controller BACnet documentation?

The source is BACnet Connection C6 / C6M - Installation and Service Manual (BACnet-C6_26-08), revision 2026-08, published free by Komfovent at https://komfovent.com/en/downloads/Bacnet_connection_C6_EN.pdf.

What are the minimum BACnet points to integrate the Komfovent C6 / C6M controller?

Start with BV 0 CONTROL: ON/OFF status (On/off command (1 = on)); MV 1 CONTROL: current mode (Mode command; writable values 2-5 (away to boost)); AV 1 NORMAL: setpoint (Temperature setpoint for NORMAL mode); AV 11 INFO: supply temperature (Supply air temperature); AV 12 INFO: extract temperature (Extract air temperature); AV 13 INFO: outdoor temperature (Outdoor air temperature); PIV 30 INFO: current supply flow (Supply air flow, m3/h or l/s); BV 32 INFO: alarm (Any active alarm); PIV 28 ALARMS: active alarms count (Active alarms (0-10); write 39366 to reset).

How do I enable BMS control of the Komfovent C6 / C6M controller?

BV 0 CONTROL: ON/OFF status turns the unit on (1) or off (0). BV 2 CONTROL: AUTO mode hands mode selection to the schedule or air quality control (MV 0 shows which).

How do I check these points on the real C6 / C6M controller?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Komfovent BACnet points lists

Source: BACnet Connection C6 / C6M - Installation and Service Manual · BACnet-C6_26-08 · rev. 2026-08. Object names, instances and units are reproduced as published; descriptions are our own.