Air handling unit controller · BACnet points list
Komfovent C8 controller BACnet points list
Updated 4 November 2026
The Komfovent C8 controller exposes its settings and readings over BACnet IP on its RJ-45 Ethernet port (no MS/TP). The list has 136 objects: temperatures and setpoints as AVs, on/off, enables and alarms as BVs, modes and settings as multistate values, and flows, timers, readings and run-hour counters as positive integer values. Two date values hold the holiday period, and a time value gives the next scheduled mode change.
This page lists 136 BACnet objects for the Komfovent C8 controller — 78 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Komfovent’s own free documentation, linked below.
- Manufacturer
- Komfovent
- Model
- C8 controller
- Equipment
- Air handling unit controller
- Equipment type
- Rooftop units, AHUs & DOAS
- BACnet objects
- 136 (78 writable)
- Transport
- BACnet IP
- Firmware
- Not stated
- Default device instance
- 60
- Also known as
- Komfovent C8, BACnet-C8
Reference only, provided as-is: verify against Komfovent’s current documentation and the live device before use. Not official Komfovent information. Terms of use.
BMS integration notes: Komfovent C8 controller
Switch the unit with BV 0 CONTROL: ON/OFF status and select the mode with MV 1 CONTROL: current mode (only away, normal, intensive and boost can be written). Each mode has its own temperature setpoint AV and supply/extract flow PIVs. Read the INFO temperatures and flows, the ALARMS BVs and the active alarm count; writing 39366 to that count resets alarms.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 0 | CONTROL: ON/OFF status | On/off command (1 = on) | Write |
| MV 1 | CONTROL: current mode | Mode command; writable values 2-5 (away to boost) | Write |
| AV 1 | NORMAL: setpoint | Temperature setpoint for NORMAL mode | Write |
| AV 11 | INFO: supply temperature | Supply air temperature | Read |
| AV 12 | INFO: extract temperature | Extract air temperature | Read |
| AV 13 | INFO: outdoor temperature | Outdoor air temperature | Read |
| PIV 26 | INFO: current supply flow | Supply fan flow, % | Read |
| PIV 24 | ALARMS: active alarms count | Active alarms (0-10); write 39366 to reset | Write |
Enable & remote start
BV 0 CONTROL: ON/OFF status turns the unit on (1) or off (0). BV 2 CONTROL: AUTO mode hands mode selection to the schedule or air quality control (MV 0 shows which).
Network setup
- Factory network settings: DHCP off, IP 192.168.0.60, mask 255.255.255.0, gateway 192.168.0.1, BACnet ID 60.
- Change them in the controller web server (Connectivity) or on the control panel (Advanced settings > Connectivity).
- Komfovent recommends a polling interval of at least 1 second.
Watch out for
- MV 1 CONTROL: current mode accepts only values 2-5 (away, normal, intensive, boost) as writes.
- Writing 39366 to the ALARMS: active alarms count PIV resets alarms.
- CONNECTIVITY IP address and mask PIVs are writable; a wrong write can drop the controller off the network.
- The RESET SETTINGS multistate value restores factory settings for the chosen group; keep it out of normal BMS writes.
Komfovent C8 controller BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AV | 0 | AWAY: setpoint | Range 5.0 – 40.0 | °C | Write | |
| AVmin | 1 | NORMAL: setpoint | Range 5.0 – 40.0 | °C | Write | |
| AV | 2 | INTENSIVE: setpoint | Range 5.0 – 40.0 | °C | Write | |
| AV | 3 | BOOST: setpoint | Range 5.0 – 40.0 | °C | Write | |
| AV | 4 | KITCHEN: setpoint | Range 5.0 – 40.0 | °C | Write | |
| AV | 5 | FIREPLACE: setpoint | Range 5.0 – 40.0 | °C | Write | |
| AV | 6 | OVERRIDE: setpoint | Range 5.0 – 40.0 | °C | Write | |
| AV | 7 | HOLIDAYS: setpoint | Range 5.0 – 40.0 | °C | Write | |
| AV | 8 | ECO: minimum supply air temperature | Range 5.0 – 40.0 | °C | Write | |
| AV | 9 | ECO: maximum supply air temperature | Range 5.0 – 40.0 | °C | Write | |
| AV | 10 | AIR QUALITY: temperature setpoint | Range 5.0 – 40.0 | °C | Write | |
| AVmin | 11 | INFO: supply temperature | °C | Read | ||
| AVmin | 12 | INFO: extract temperature | °C | Read | ||
| AVmin | 13 | INFO: outdoor temperature | °C | Read | ||
| AV | 14 | INFO: water temperature | °C | Read | ||
| AV | 15 | INFO: panel 1 temperature | °C | Read | ||
| AV | 16 | INFO: panel 2 temperature | °C | Read | ||
| AV | 17 | INFO: current supply fan intensity | % | Read | ||
| AV | 18 | INFO: current extract fan intensity | % | Read | ||
| AV | 19 | INFO: heat exchanger | % | Read | ||
| AV | 20 | INFO: electric heater | % | Read | ||
| AV | 21 | INFO: analog output 0-10V | % | Read | ||
| AV | 22 | INFO: DX unit | % | Read | ||
| AV | 23 | THERMOSTAT 1: Temperature | Range 5.0 – 40.0 | °C | Write | |
| AV | 24 | THERMOSTAT 1: Hysterysis | Range 0.1 – 5.0 | °C | Write | |
| AV | 25 | THERMOSTAT 2: Temperature | Range 5.0 – 40.0 | °C | Write | |
| AV | 26 | THERMOSTAT 2: Hysterysis | Range 0.1 – 5.0 | °C | Write | |
| BVmin | 0 | CONTROL: ON/OFF status | Write | 0=off, 1=on | ||
| BV | 1 | CONTROL: ECO mode | Write | 0=off, 1=on | ||
| BV | 2 | CONTROL: AUTO mode | Write | 0=off, 1=on | ||
| BV | 3 | AWAY: heating | Write | 0=off, 1=on | ||
| BV | 4 | NORMAL: heating | Write | 0=off, 1=on | ||
| BV | 5 | INTENSIVE: heating | Write | 0=off, 1=on | ||
| BV | 6 | BOOST: heating | Write | 0=off, 1=on | ||
| BV | 7 | KITCHEN: heating | Write | 0=off, 1=on | ||
| BV | 8 | FIREPLACE: heating | Write | 0=off, 1=on | ||
| BV | 9 | OVERRIDE: heating | Write | 0=off, 1=on | ||
| BV | 10 | HOLIDAYS: heating | Write | 0=off, 1=on | ||
| BV | 11 | ECO: free heating/cooling | Write | 0=off, 1=on | ||
| BV | 12 | ECO: heating enable denied | Write | 0=off, 1=on | ||
| BV | 13 | ECO: cooling enable denied | Write | 0=off, 1=on | ||
| BV | 14 | ECO: non stop recuperation | Write | 0=off, 1=on | ||
| BV | 15 | AIR QUALITY: enabled | Write | 0=disabled, 1=enabled | ||
| BV | 16 | AIR QUALITY: heating | Write | 0=off, 1=on | ||
| BV | 17 | ALARMS: return water temperature low | Read | 0=no, 1=yes | ||
| BV | 18 | ALARMS: low supply air temperature | Read | 0=no, 1=yes | ||
| BV | 19 | ALARMS: high supply air temperature | Read | 0=no, 1=yes | ||
| BV | 20 | ALARMS: electric heater overheat | Read | 0=no, 1=yes | ||
| BV | 21 | ALARMS: heat exchanger failure | Read | 0=no, 1=yes | ||
| BV | 22 | ALARMS: heat exchanger icing | Read | 0=no, 1=yes | ||
| BV | 23 | ALARMS: internal fire alarm | Read | 0=no, 1=yes | ||
| BV | 24 | ALARMS: external fire alarm | Read | 0=no, 1=yes | ||
| BV | 25 | ALARMS: temperature sensor failure | Read | 0=no, 1=yes | ||
| BV | 26 | ALARMS: controller failure | Read | 0=no, 1=yes | ||
| BV | 27 | ALARMS: service mode | Read | 0=no, 1=yes | ||
| BV | 28 | ALARMS: clogged air filters | Read | 0=no, 1=yes | ||
| BV | 29 | ALARMS: heat exchanger low efficiency | Read | 0=no, 1=yes | ||
| BV | 30 | ALARMS: fire dampers communication error | Read | 0=no, 1=yes | ||
| BV | 31 | ALARMS: fire dampers failure | Read | 0=no, 1=yes | ||
| BV | 32 | INFO: heating | Read | 0=off, 1=on | ||
| BV | 33 | INFO: cooling | Read | 0=off, 1=on | ||
| BV | 34 | CLEAN FILTERS CALIBRATION | Write | 0=no, 1=yes | ||
| BV | 35 | THERMOSTAT 1: Enable | Write | 0=no, 1=yes | ||
| BV | 36 | THERMOSTAT 2: Enable | Write | 0=no, 1=yes | ||
| BV | 37 | ALARMS: communication error | Read | 0=no, 1=yes | ||
| BV | 38 | ALARMS: supply fan failure | Read | 0=no, 1=yes | ||
| BV | 39 | ALARMS: exhaust fan failure | Read | 0=no, 1=yes | ||
| Other | 0 | HOLIDAYS: from | BACnet Date Value object; 2017-01-01 – 2035-12-31 | Write | ||
| Other | 1 | HOLIDAYS: till | BACnet Date Value object; 2017-01-01 – 2035-12-31 | Write | ||
| MV | 0 | CONTROL: auto mode control | Read | 1=scheduling, 2=air quality | ||
| MVmin | 1 | CONTROL: current mode | Write | 1=standby, 2=away, 3=normal, 4=intensive, 5=boost, 6=kitchen, 7=fireplace, 8=override, 9=holiday, 10=auto, 11=off | ||
| MV | 2 | SCHEDULER: operation program | Write | 1=stay at home, 2=working week, 3=office, 4=custom | ||
| MV | 3 | SCHEDULER: next mode | Read | 1=standby, 2=away, 3=normal, 4=intensive, 5=boost | ||
| MV | 4 | SCHEDULER: next mode weekday | Read | 1=today, 2=mo, 3=tu, 4=we, 5=th, 6=fr, 7=sa, 8=su | ||
| MV | 5 | CONTROL: temperature control | Write | 1=supply, 2=extract, 3=room, 4=balance | ||
| MV | 6 | CONTROL SEQEUENCE: stage 1 | Write | 1=none, 2=external coil, 3=electric heater, 4=external DX unit | ||
| MV | 7 | CONTROL SEQEUENCE: stage 2 | Write | 1=none, 2=external coil, 3=electric heater, 4=external DX unit | ||
| MV | 8 | CONTROL SEQEUENCE: stage 3 | Write | 1=none, 2=external coil, 3=electric heater, 4=external DX unit | ||
| MV | 9 | SETTINGS: coil type | Write | 1=hot water, 2=cold water | ||
| MV | 10 | SETTINGS: language | Write | 1=en, 2=lt, 3=ru, 4=pl, 5=sk, 6=de, 7=fr, 8=hu, 9=it, 10=ee, 11=nl, 12=lv, 13=pt, 14=se, 15=fi, 16=hr, 17=sl, 18=cz, 19=dk | ||
| MV | 11 | OVERRIDE: mode | Write | 1=all time, 2=if on, 3=if off | ||
| MV | 12 | HOLIDAYS: microventilation | Write | 1=1 t. per day, 2=2 t. per day, 3=3 t. per day, 4=4 t. per day | ||
| MV | 13 | AIR QUALITY: sensor type B8 | Write | 1=none, 2=CO2, 3=VOC, 4=RH | ||
| MV | 14 | RESET SETTINGS | Write | 1=none, 2="away", 3="normal", 4="intensive", 5="boost", 6="holidays", 7="override", 8="kitchen", 9="fireplace", 10=air quality, 11=eco, 12=advanced | ||
| MV | 15 | THERMOSTAT 1: output | Write | 1=Heating, 2=Cooling | ||
| MV | 16 | THERMOSTAT 1: output type | Write | 1=NO, 2=NC | ||
| MV | 17 | THERMOSTAT 2: output | Write | 1=Heating, 2=Cooling | ||
| MV | 18 | THERMOSTAT 2: output type | Write | 1=NO, 2=NC | ||
| PIV | 0 | CONNECTIVITY: IP address | Range 0 – 4294967295 | Write | ||
| PIV | 1 | CONNECTIVITY: mask | Range 0 – 4294967295 | Write | ||
| PIV | 2 | AWAY: supply flow | Range 20 – 100 | % | Write | |
| PIV | 3 | AWAY: extract flow | Range 20 – 100 | % | Write | |
| PIV | 4 | NORMAL: supply flow | Range 20 – 100 | % | Write | |
| PIV | 5 | NORMAL: extract flow | Range 20 – 100 | % | Write | |
| PIV | 6 | INTENSIVE: supply flow | Range 20 – 100 | % | Write | |
| PIV | 7 | INTENSIVE: extract flow | Range 20 – 100 | % | Write | |
| PIV | 8 | BOOST: supply flow | Range 20 – 100 | % | Write | |
| PIV | 9 | BOOST: extract flow | Range 20 – 100 | % | Write | |
| PIV | 10 | KITCHEN: supply flow | Range 20 – 100 | % | Write | |
| PIV | 11 | KITCHEN: extract flow | Range 20 – 100 | % | Write | |
| PIV | 12 | FIREPLACE: supply flow | Range 20 – 100 | % | Write | |
| PIV | 13 | FIREPLACE: extract flow | Range 20 – 100 | % | Write | |
| PIV | 14 | OVERRIDE: supply flow | Range 20 – 100 | % | Write | |
| PIV | 15 | OVERRIDE: extract flow | Range 20 – 100 | % | Write | |
| PIV | 16 | KITCHEN: timer | Range 0 – 300 | min | Write | |
| PIV | 17 | FIREPLACE: timer | Range 0 – 300 | min | Write | |
| PIV | 18 | OVERRIDE: timer | Range 0 – 300 | min | Write | |
| PIV | 19 | AIR QUALITY: air quality setpoint | 0-2000 ppm or 0-100 % | ppm, % | Write | |
| PIV | 20 | AIR QUALITY: humidity setpoint | Range 0 – 100 | % | Write | |
| PIV | 21 | AIR QUALITY: minimum intensity | Range 0, 20 – 100 | % | Write | |
| PIV | 22 | AIR QUALITY: maximum intensity | Range 0, 20 – 100 | % | Write | |
| PIV | 23 | AIR QUALITY: check period | Range 1 – 24 | h | Write | |
| PIVmin | 24 | ALARMS: active alarms count | Range 0-10; write 39366 to reset alarms | Write | ||
| PIV | 25 | ALARMS: alarm history count | Range 0 – 50 | Read | ||
| PIVmin | 26 | INFO: current supply flow | % | Read | ||
| PIV | 27 | INFO: current extract flow | % | Read | ||
| PIV | 28 | INFO: filters impurity | % | Read | ||
| PIV | 29 | INFO: air dampers | % | Read | ||
| PIV | 30 | INFO: air quality/humidity sensor | ppm, % | Read | ||
| PIV | 31 | INFO: panel 1 humidity | % | Read | ||
| PIV | 32 | INFO: panel 2 humidity | % | Read | ||
| PIV | 33 | INFO: panel 1 air quality | ppm | Read | ||
| PIV | 34 | INFO: panel 2 air quality | ppm | Read | ||
| PIV | 35 | EFFICIENCY/STATUS: heater power | W | Read | ||
| PIV | 36 | OPERATION COUNTERS: supply air fan (day) | h | Read | ||
| PIV | 37 | OPERATION COUNTERS: supply air fan (month) | h | Read | ||
| PIV | 38 | OPERATION COUNTERS: supply air fan (total) | h | Read | ||
| PIV | 39 | OPERATION COUNTERS: exhaust air fan (day) | h | Read | ||
| PIV | 40 | OPERATION COUNTERS: exhaust air fan (month) | h | Read | ||
| PIV | 41 | OPERATION COUNTERS: exhaust air fan (total) | h | Read | ||
| PIV | 42 | OPERATION COUNTERS: electric heater (day) | h | Read | ||
| PIV | 43 | OPERATION COUNTERS: electric heater (month) | h | Read | ||
| PIV | 44 | OPERATION COUNTERS: electric heater (total) | h | Read | ||
| PIV | 45 | OPERATION COUNTERS: heat exchanger (day) | h | Read | ||
| PIV | 46 | OPERATION COUNTERS: heat exchanger (month) | h | Read | ||
| PIV | 47 | OPERATION COUNTERS: heat exchanger (total) | h | Read |
No points match these filters.
Object ID lookup: Komfovent C8 controller point IDs by name
AV0AWAY: setpointAV1NORMAL: setpointAV2INTENSIVE: setpointAV3BOOST: setpointAV4KITCHEN: setpointAV5FIREPLACE: setpointAV6OVERRIDE: setpointAV7HOLIDAYS: setpointAV8ECO: minimum supply air temperatureAV9ECO: maximum supply air temperatureAV10AIR QUALITY: temperature setpointAV11INFO: supply temperatureAV12INFO: extract temperatureAV13INFO: outdoor temperatureAV14INFO: water temperatureAV15INFO: panel 1 temperatureAV16INFO: panel 2 temperatureAV17INFO: current supply fan intensityAV18INFO: current extract fan intensityAV19INFO: heat exchangerAV20INFO: electric heaterAV21INFO: analog output 0-10VAV22INFO: DX unitAV23THERMOSTAT 1: TemperatureAV24THERMOSTAT 1: HysterysisAV25THERMOSTAT 2: TemperatureAV26THERMOSTAT 2: HysterysisBV0CONTROL: ON/OFF statusBV1CONTROL: ECO modeBV2CONTROL: AUTO modeBV3AWAY: heatingBV4NORMAL: heatingBV5INTENSIVE: heatingBV6BOOST: heatingBV7KITCHEN: heatingBV8FIREPLACE: heatingBV9OVERRIDE: heatingBV10HOLIDAYS: heatingBV11ECO: free heating/coolingBV12ECO: heating enable deniedBV13ECO: cooling enable deniedBV14ECO: non stop recuperationBV15AIR QUALITY: enabledBV16AIR QUALITY: heatingBV17ALARMS: return water temperature lowBV18ALARMS: low supply air temperatureBV19ALARMS: high supply air temperatureBV20ALARMS: electric heater overheatBV21ALARMS: heat exchanger failureBV22ALARMS: heat exchanger icingBV23ALARMS: internal fire alarmBV24ALARMS: external fire alarmBV25ALARMS: temperature sensor failureBV26ALARMS: controller failureBV27ALARMS: service modeBV28ALARMS: clogged air filtersBV29ALARMS: heat exchanger low efficiencyBV30ALARMS: fire dampers communication errorBV31ALARMS: fire dampers failureBV32INFO: heatingBV33INFO: coolingBV34CLEAN FILTERS CALIBRATIONBV35THERMOSTAT 1: EnableBV36THERMOSTAT 2: EnableBV37ALARMS: communication errorBV38ALARMS: supply fan failureBV39ALARMS: exhaust fan failureMV0CONTROL: auto mode controlMV1CONTROL: current modeMV2SCHEDULER: operation programMV3SCHEDULER: next modeMV4SCHEDULER: next mode weekdayMV5CONTROL: temperature controlMV6CONTROL SEQEUENCE: stage 1MV7CONTROL SEQEUENCE: stage 2MV8CONTROL SEQEUENCE: stage 3MV9SETTINGS: coil typeMV10SETTINGS: languageMV11OVERRIDE: modeMV12HOLIDAYS: microventilationMV13AIR QUALITY: sensor type B8MV14RESET SETTINGSMV15THERMOSTAT 1: outputMV16THERMOSTAT 1: output typeMV17THERMOSTAT 2: outputMV18THERMOSTAT 2: output typePIV0CONNECTIVITY: IP addressPIV1CONNECTIVITY: maskPIV2AWAY: supply flowPIV3AWAY: extract flowPIV4NORMAL: supply flowPIV5NORMAL: extract flowPIV6INTENSIVE: supply flowPIV7INTENSIVE: extract flowPIV8BOOST: supply flowPIV9BOOST: extract flowPIV10KITCHEN: supply flowPIV11KITCHEN: extract flowPIV12FIREPLACE: supply flowPIV13FIREPLACE: extract flowPIV14OVERRIDE: supply flowPIV15OVERRIDE: extract flowPIV16KITCHEN: timerPIV17FIREPLACE: timerPIV18OVERRIDE: timerPIV19AIR QUALITY: air quality setpointPIV20AIR QUALITY: humidity setpointPIV21AIR QUALITY: minimum intensityPIV22AIR QUALITY: maximum intensityPIV23AIR QUALITY: check periodPIV24ALARMS: active alarms countPIV25ALARMS: alarm history countPIV26INFO: current supply flowPIV27INFO: current extract flowPIV28INFO: filters impurityPIV29INFO: air dampersPIV30INFO: air quality/humidity sensorPIV31INFO: panel 1 humidityPIV32INFO: panel 2 humidityPIV33INFO: panel 1 air qualityPIV34INFO: panel 2 air qualityPIV35EFFICIENCY/STATUS: heater powerPIV36OPERATION COUNTERS: supply air fan (day)PIV37OPERATION COUNTERS: supply air fan (month)PIV38OPERATION COUNTERS: supply air fan (total)PIV39OPERATION COUNTERS: exhaust air fan (day)PIV40OPERATION COUNTERS: exhaust air fan (month)PIV41OPERATION COUNTERS: exhaust air fan (total)PIV42OPERATION COUNTERS: electric heater (day)PIV43OPERATION COUNTERS: electric heater (month)PIV44OPERATION COUNTERS: electric heater (total)PIV45OPERATION COUNTERS: heat exchanger (day)PIV46OPERATION COUNTERS: heat exchanger (month)PIV47OPERATION COUNTERS: heat exchanger (total)
Integration notes
- The two Date Value objects (HOLIDAYS: from / till, instances 0-1) are listed with type Other. The doc also has a Time Value object 0, SCHEDULER: next mode start time (read-only, 00:00-24:00), left out here because it would clash with Other 0.
- Mode-specific setpoints, flows and heating flags exist for each mode (away, normal, intensive, boost, kitchen, fireplace, override, holidays).
- Mode flows and the current flow readings are in % (20-100 %), not m3/h; the C8 list has no pressure readings or flow-unit setting.
- Unlike the C6, the C8 list has no general INFO: alarm BV; use the active alarm count or the ALARMS BVs.
- The C8 list adds fire damper alarms and fan / heater / heat exchanger run-hour counters.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the C8 controller and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Komfovent C8 controller
How many BACnet points does the Komfovent C8 controller have?
This list has 136 BACnet objects: 27 analog values, 40 binary values, 19 multi-state values, 48 positive integer values, 2 others. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Komfovent C8 controller BACnet points are writable?
78 of the 136 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Komfovent C8 controller BACnet documentation?
The source is BACnet Connection C8 - Installation and Service Manual (BACnet-C8_26-07), revision 2026-07, published free by Komfovent at https://www.komfovent.com/en/downloads/Bacnet_connection_C8_EN.pdf.
What are the minimum BACnet points to integrate the Komfovent C8 controller?
Start with BV 0 CONTROL: ON/OFF status (On/off command (1 = on)); MV 1 CONTROL: current mode (Mode command; writable values 2-5 (away to boost)); AV 1 NORMAL: setpoint (Temperature setpoint for NORMAL mode); AV 11 INFO: supply temperature (Supply air temperature); AV 12 INFO: extract temperature (Extract air temperature); AV 13 INFO: outdoor temperature (Outdoor air temperature); PIV 26 INFO: current supply flow (Supply fan flow, %); PIV 24 ALARMS: active alarms count (Active alarms (0-10); write 39366 to reset).
How do I enable BMS control of the Komfovent C8 controller?
BV 0 CONTROL: ON/OFF status turns the unit on (1) or off (0). BV 2 CONTROL: AUTO mode hands mode selection to the schedule or air quality control (MV 0 shows which).
How do I check these points on the real C8 controller?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Komfovent BACnet points lists
- Air handling unit controller
Komfovent C5 controller
Komfovent air handling units fitted with the C5 controller.
Also known as: Komfovent C5, C5.1, BACnet-C5 - Air handling unit controller
Komfovent C6 / C6M controller
Komfovent air handling units fitted with the C6 / C6M controller.
Also known as: Komfovent C6, Komfovent C6M, C6M, C6.1, BACnet-C6
Source: BACnet Connection C8 - Installation and Service Manual · BACnet-C8_26-07 · rev. 2026-07. Object names, instances and units are reproduced as published; descriptions are our own.