Air handling unit controller · BACnet points list

Komfovent C5 controller BACnet points list

Updated 4 November 2026

Short answer

The Komfovent C5 is the built-in controller of Komfovent air handling units. It speaks BACnet IP on its RJ-45 Ethernet port (no MS/TP). The list has 237 objects: sensor readings as AIs, output signals as AOs, wired contacts as BIs, relay outputs as BOs, alarms as BVs, and all commands, setpoints and function settings as AVs. On/off, modes and enable flags are AVs with numeric codes, not binary or multistate objects.

This page lists 237 BACnet objects for the Komfovent C5 controller — 85 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Komfovent’s own free documentation, linked below.

Manufacturer
Komfovent
Model
C5 controller
Equipment
Air handling unit controller
Equipment type
Rooftop units, AHUs & DOAS
BACnet objects
237 (85 writable)
Transport
BACnet IP
Firmware
Not stated
Default device instance
1100
Also known as
Komfovent C5, C5.1, BACnet-C5
Source document
BACnet Connection C5 - Installation and Service Manual · BACnet-C5_25-07 · rev. 2025-07
Download CSV 237 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Komfovent’s current documentation and the live device before use. Not official Komfovent information. Terms of use.

BMS integration notes: Komfovent C5 controller

Integration in brief

Start and stop the unit with AV 0 Unit On/Off and pick the ventilation mode with AV 2 Mode selection (Comfort1/2, Economy1/2, Special, Program). Each mode has its own supply/extract flow and temperature setpoint AVs. Read AV 1 Current mode, the supply, extract and outdoor temperatures (AI 0-2), the alarm BVs and BO 22 Alarm DOUT; reset alarms by writing 1 to AV 58.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AV 0Unit On/OffUnit on/off command (1 = on)Write
AV 2Mode selectionVentilation mode command, 1-6Write
AV 5Comfort1 SetpointComfort1 supply temperature setpointWrite
AV 58Actual alarms resetWrite 1 to reset current alarmsWrite
AV 1Current modeActive mode (0 = off/standby)Read
AI 0Supply air temperatureSupply air temperatureRead
AI 1Extract air temperatureExtract air temperatureRead
AI 2Outdoor air temperatureOutdoor air temperatureRead
BO 22Alarm DOUTCommon alarm output (1 = alarm)Read

Enable & remote start

AV 0 Unit On/Off switches the unit (0 = off, 1 = on). AV 2 Mode selection picks the operating mode; 6 = Program hands control to the unit's own schedule.

Sensors & values from the BMS

AV 73 External room temperature sensor accepts a room temperature from the BMS; a value outside -50..+120 °C disables the override.

Network setup

Watch out for

Komfovent C5 controller BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

237 of 237 shown
Type
Access
Show
Komfovent C5 controller BACnet Points List
DescriptionStates
AImin0Supply air temperatureRange -50.0..+120.0°CRead
AImin1Extract air temperatureRange -50.0..+120.0°CRead
AImin2Outdoor air temperatureRange -50.0..+120.0°CRead
AI3Exhaust air temperatureRange -50.0..+120.0°CRead
AI4Water temperatureRange -50.0..+120.0°CRead
AI5Air qualityRange 0..100%Read
AI6Supply air humidityRange 0..100%RHRead
AI7Supply air flowRange 0..1000000m3/h, l/s, m3/s or Pa (per AV 72)Read
AI8Exhaust air flowRange 0..1000000m3/h, l/s, m3/s or Pa (per AV 72)Read
AI9Outdoor air filter pressureRange 0..5500PaRead
AI10Extract air filter pressureRange 0..5500PaRead
AI11Zone 1 supply air temperatureRange -50.0..+120.0°CRead
AI12Zone 1 water temperatureRange -30.0..+120.0°CRead
AI13Zone 2 supply air temperatureRange -50.0..+120.0°CRead
AI14Zone 2 water temperatureRange -30.0..+120.0°CRead
AI15Internal supply air temperatureRange -50.0..+120.0°CRead
AI16Zone 1 air qualityRange 0..100%Read
AI17Zone 1 heater temperatureRange 0..+120.0°CRead
AI18Zone 2 air qualityRange 0..100%Read
AI19Zone 2 heater temperatureRange 0..+120.0°CRead
AI20Supply temperature set-pointRange +5..+45°CRead
AI21Supply air absolute humidityRange 0..40.0g/m3 or g/kgRead
AI22Supply air pressureRange 0..5500PaRead
AI23Extract air pressureRange 0..5500PaRead
AO0Water heater levelRange 0..100%Read
AO1Water cooler levelRange 0..100%Read
AO2Humidifier levelRange 0..100%Read
AO3Heat exchanger levelRange 0..100%Read
AO4Recirculation levelRange 0..100%Read
AO5Supply fan levelRange 0..100%Read
AO6Exhaust fan levelRange 0..100%Read
AO7Outdoor air damper levelRange 0..100%Read
AO8Exhaust air damper levelRange 0..100%Read
AO9El. Heater levelRange 0..100%Read
AO10DX levelRange -100..+100%Read
AO11Heat pump levelRange -100..+100%Read
AO12Zone 1 level/heater levelRange -100..+100%Read
AO13Zone 2 level/heater levelRange -100..+100%Read
AO14Zone 1 cooler levelRange 0..100%Read
AO15Zone 2 cooler levelRange 0..100%Read
AO16Zone 1 temperature setpoint/errorSetpoint (+5..+40 °C) or error (0..100 %)°C or %Read
AO17Zone 2 temperature setpoint/errorSetpoint (+5..+40 °C) or error (0..100 %)°C or %Read
BI0OVRRead0=open, 1=closed
BI1External stopRead0=open, 1=closed
BI2Zone 1 electric heater TK100Read0=open, 1=closed
BI3Zone 1 electric heater TK60Read0=open, 1=closed
BI4Zone 1 electric heater TK70Read0=open, 1=closed
BI5Zone 1 low water temperatureRead0=open, 1=closed
BI6Zone 1 combined coilRead0=open, 1=closed
BI7Zone 1 external stopRead0=open, 1=closed
BI8Zone 2 electric heater TK100Read0=open, 1=closed
BI9Zone 2 electric heater TK60Read0=open, 1=closed
BI10Zone 2 electric heater TK70Read0=open, 1=closed
BI11Zone 2 low water temperatureRead0=open, 1=closed
BI12Zone 2 combined coilRead0=open, 1=closed
BI13Zone 2 external stopRead0=open, 1=closed
BI14Outdoor air filterRead0=open, 1=closed
BI15Extract air filterRead0=open, 1=closed
BI16C5 ControlRead0=open, 1=closed
BO0Water heating pumpRead0=stop, 1=run
BO1Water cooling pumpRead0=stop, 1=run
BO2Zone 1 stage 1Read0=stop, 1=run
BO3Zone 1 stage 2Read0=stop, 1=run
BO4Zone 1 stage 3Read0=stop, 1=run
BO5Zone 1 stage 4Read0=stop, 1=run
BO6Zone 1 heating water pumpRead0=stop, 1=run
BO7Zone 1 cooling water pumpRead0=stop, 1=run
BO8Zone 1 DX level unit reverseRead0=stop, 1=run
BO9Zone 1 DX modulated unit operationRead0=stop, 1=run
BO10Zone 1 DX modulated unit coolingRead0=stop, 1=run
BO11Zone 1 DX modulated unit heatingRead0=stop, 1=run
BO12Zone 2 stage 1Read0=stop, 1=run
BO13Zone 2 stage 2Read0=stop, 1=run
BO14Zone 2 stage 3Read0=stop, 1=run
BO15Zone 2 stage 4Read0=stop, 1=run
BO16Zone 2 heating water pumpRead0=stop, 1=run
BO17Zone 2 cooling water pumpRead0=stop, 1=run
BO18Zone 2 DX level unit reverseRead0=stop, 1=run
BO19Zone 2 DX modulated unit operationRead0=stop, 1=run
BO20Zone 2 DX modulated unit coolingRead0=stop, 1=run
BO21Zone 2 DX modulated unit heatingRead0=stop, 1=run
BOmin22Alarm DOUTRead0=no alarm, 1=alarm
BO23AQC activeRead0=stop, 1=run
BO24OCV activeRead0=stop, 1=run
BO25MTC activeRead0=stop, 1=run
BO26OVR activeRead0=stop, 1=run
BO27SNC activeRead0=stop, 1=run
BO28OOD activeRead0=stop, 1=run
BO29REC activeRead0=stop, 1=run
BO30HUM activeRead0=stop, 1=run
BO31Defrost activeRead0=stop, 1=run
BV0Low supply air flowRead
BV1Low extract air flowRead
BV2VAV calibration failRead
BV3Change outdoor air filterRead
BV4Change extract air filterRead
BV5Electric heater offRead
BV6High pressure on compressorRead
BV7Low pressure on compressorRead
BV8Service timeRead
BV9Service modeRead
BV10Supply air temp. sensor failureRead
BV11Extract air temp. sensor failureRead
BV12Outdoor air temp. sensor failureRead
BV13Exhaust air temp. sensor failureRead
BV14Water temp. sensor failureRead
BV15Return water temp lowRead
BV16Internal fire alarmRead
BV17External fire alarmRead
BV18External stopRead
BV19Heat exchanger failureRead
BV20Heat exchanger icingRead
BV21Low supply air temperatureRead
BV22High supply air temperatureRead
BV23Electric heater overheatRead
BV24Evaporator air temp. sensor failureRead
BV25Evaporator coil temp. sensor failureRead
BV26Compressor failureRead
BV27Supply fan drive failureRead
BV28Supply fan drive overloadRead
BV29Supply fan motor failureRead
BV30Supply fan motor overloadRead
BV31Exhaust drive failureRead
BV32Exhaust fan drive overloadRead
BV33Exhaust fan motor failureRead
BV34Exhaust fan motor overloadRead
BV35Rotor drive failureRead
BV36Rotor drive overloadRead
BV37Rotor motor failureRead
BV38Rotor motor overloadRead
BV39Communication errorRead
BV40Controller failureRead
BV41Compressor offRead
BV42Evaporator icingRead
BV43Zone 1 TK100 alarmRead
BV44Zone 1 TK70 alarmRead
BV45Zone 1 TK60 alarmRead
BV46Zone 1 low water temperatureRead
BV47Zone 1 external stopRead
BV48Zone 2 TK100 alarmRead
BV49Zone 2 TK70 alarmRead
BV50Zone 2 TK60 alarmRead
BV51Zone 2 low water temperatureRead
BV52Zone 2 external stopRead
BV53Low heat exchanger efficiencyRead
BV54Water pump / coil alarmRead
AVmin0Unit On/OffWrite0=Off, 1=On
AVmin1Current modeRead0=Off/Standby, 1=Comfort1, 2=Comfort2, 3=Economy1, 4=Economy2, 5=Special
AVmin2Mode selectionWrite1=Comfort1, 2=Comfort2, 3=Economy1, 4=Economy2, 5=Special, 6=Program
AV3Comfort1 Supply flowRange 0..200000m3/h, l/s, m3/s or Pa (per AV 72)Write
AV4Comfort1 Extract flowRange 0..200000m3/h, l/s, m3/s or Pa (per AV 72)Write
AVmin5Comfort1 SetpointRange +5..+40°CWrite
AV6Comfort2 Supply flowRange 0..200000m3/h, l/s, m3/s or Pa (per AV 72)Write
AV7Comfort2 Extract flowRange 0..200000m3/h, l/s, m3/s or Pa (per AV 72)Write
AV8Comfort2 SetpointRange +5..+40°CWrite
AV9Economy1 Supply flowRange 0..200000m3/h, l/s, m3/s or Pa (per AV 72)Write
AV10Economy1 Extract flowRange 0..200000m3/h, l/s, m3/s or Pa (per AV 72)Write
AV11Economy1 SetpointRange +5..+40°CWrite
AV12Economy2 Supply flowRange 0..200000m3/h, l/s, m3/s or Pa (per AV 72)Write
AV13Economy2 Extract flowRange 0..200000m3/h, l/s, m3/s or Pa (per AV 72)Write
AV14Economy2 SetpointRange +5..+40°CWrite
AV15Special Supply flowRange 0..200000m3/h, l/s, m3/s or Pa (per AV 72)Write
AV16Special Extract flowRange 0..200000m3/h, l/s, m3/s or Pa (per AV 72)Write
AV17Special SetpointRange +5..+40°CWrite
AV18Special mode HeatingWrite0=Disable, 1=Enable
AV19Special mode CoolingWrite0=Disable, 1=Enable
AV20Special mode RecirculationWrite0=Disable, 1=Enable
AV21Special mode HumidifyingWrite0=Disable, 1=Enable
AV22Special mode DehumidifyingWrite0=Disable, 1=Enable
AV23Flow control modeWrite0=CAV, 1=VAV, 2=DCV
AV24Temp. control modeWrite0=Supply, 1=Extract, 2=Room, 3=Balance
AV25AQC EnableWrite0=Disable, 1=Enable
AV26AQC Setpoint 1200-1800 ppm, 10-90 % or 5-45 °C by sensor typeppm, % or °C (by sensor type)Write
AV27AQC Mode 1Write1=Comfort1, 2=Comfort2, 3=Economy1, 4=Economy2, 5=Special
AV28AQC Setpoint 2200-1800 ppm, 10-90 % or 5-45 °C by sensor typeppm, % or °C (by sensor type)Write
AV29AQC Mode 2Write1=Comfort1, 2=Comfort2, 3=Economy1, 4=Economy2, 5=Special
AV30OCV EnableWrite0=Disable, 1=Enable
AV31OCV Winter compensation stopRange -40.0..+50.0°CWrite
AV32OCV Winter compensation startRange -40.0..+50.0°CWrite
AV33OCV Summer compensation startRange -40.0..+50.0°CWrite
AV34OCV Summer compensation stopRange -40.0..+50.0°CWrite
AV35MTC EnableWrite0=Disable, 1=Enable
AV36MTC SetpointRange -40.0..+50.0°CWrite
AV37OVR EnableWrite0=Disable, 1=Enable
AV38OVR TypeWrite0=Alltime, 1=If on, 2=If off
AV39OVR ModeWrite0=Standby, 1=Comfort1, 2=Comfort2, 3=Economy1, 4=Economy2, 5=Special, 6=Program
AV40SNC EnableWrite0=Disable, 1=Enable
AV41SNC Start temperatureRange 15.0..+50.0°CWrite
AV42SNC Stop temperatureRange 15.0..+50.0°CWrite
AV43OOD EnableWrite0=Disable, 1=Enable
AV44OOD Setpoint200-1800 ppm, 10-90 % or 5-45 °C by sensor typeppm, % or °C (by sensor type)Write
AV45REC EnableWrite0=Disable, 1=Enable
AV46REC Setpoint 1200-1800 ppm, 10-90 % or 5-45 °C by sensor typeppm, % or °C (by sensor type)Write
AV47REC Mode 1Write1=Comfort1, 2=Comfort2, 3=Economy1, 4=Economy2, 5=Special
AV48REC Setpoint 2200-1800 ppm, 10-90 % or 5-45 °C by sensor typeppm, % or °C (by sensor type)Write
AV49REC Mode 2Write1=Comfort1, 2=Comfort2, 3=Economy1, 4=Economy2, 5=Special
AV50REC Min. Fresh Air 1Range 0..100%Write
AV51REC Min. Fresh Air 2Range 0..100%Write
AV52REC Winter endRange -40.0..+50.0°CWrite
AV53REC Winter startRange -40.0..+50.0°CWrite
AV54REC Summer startRange -40.0..+50.0°CWrite
AV55REC Summer endRange -40.0..+50.0°CWrite
AV56REC Default recirculationRange 0..100%Write
AV57REC Activated recirculationRange 0..100%Write
AV77HUM EnableWrite0=Disable, 1=Enable
AV78HUM Setpoint 1Range 10..90%Write
AV79HUM Mode 1Write1=Comfort1, 2=Comfort2, 3=Economy1, 4=Economy2, 5=Special
AV80HUM Setpoint 2Range 10..90%Write
AV81HUM Mode 2Write1=Comfort1, 2=Comfort2, 3=Economy1, 4=Economy2
AV84CF heatexchanger calibrationWrite 1 to start heat exchanger calibrationWrite0=No calibration, 1=Calibrated, 2=Calibrating
AV85HUM modeWrite0=Supply, 1=Indoor+Supply, 2=Indoor
AV86HUM TypeWrite0=RH, 1=AH
AV87HUM UnitsWrite0=g/m3, 1=g/kg
AV88OCV Minimum airflowRange 20..100%Write
AV89Water heater: Enable/DisableWrite0=Disable, 1=Enable
AV90Water cooler: Enable/DisableWrite0=Disable, 1=Enable
AVmin58Actual alarms resetWrite 1 to reset current alarmsWrite1=Reset current alarm
AV59Air heater operationRange 0..2^32hoursWrite
AV60Supply fan operationRange 0..2^32hoursWrite
AV61Exhaust fan operationRange 0..2^32hoursWrite
AV62Heat exchanger thermal efficiencyRange 1-100; 255 = none%Read
AV63Heat exchanger recoveryRange 0..2^32wattRead
AV64Thermal energy savingRange 0..100%Read
AV65Supply SFPRange 0..655Read
AV66Exhaust SFPRange 0..655Read
AV67DayRange 1..31daysWrite
AV68MonthRange 1..12monthsWrite
AV69YearRange 2000..2250yearsWrite
AV70HoursRange 0..23hoursWrite
AV71MinutesRange 0..59minutesWrite
AV72Flow unitsWrite0=m3/h, 1=l/s, 2=m3/s, 3=Pa
AV73External room temperature sensorValue from BMS; outside range disables override°CWrite
AV74Zone 1 setpointRange -50.0..+40.0°CWrite
AV75Zone 2 setpointRange -50.0..+40.0°CWrite
AV76Digital input IN4 overrideWrite-1=disabled, 0=heating, 1=cooling, 2=error
AV82Daylight saving timeWrite0=Disable, 1=Enable
AV83BACnet Broadcast Management DeviceWrite0=Disable, 1=Enable
Object ID lookup: Komfovent C5 controller point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the C5 controller and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Komfovent C5 controller

How many BACnet points does the Komfovent C5 controller have?

This list has 237 BACnet objects: 24 analog inputs, 18 analog outputs, 91 analog values, 17 binary inputs, 32 binary outputs, 55 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Komfovent C5 controller BACnet points are writable?

85 of the 237 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Komfovent C5 controller BACnet documentation?

The source is BACnet Connection C5 - Installation and Service Manual (BACnet-C5_25-07), revision 2025-07, published free by Komfovent at https://komfovent.com/en/downloads/Bacnet_connection_C5_EN.pdf.

What are the minimum BACnet points to integrate the Komfovent C5 controller?

Start with AV 0 Unit On/Off (Unit on/off command (1 = on)); AV 2 Mode selection (Ventilation mode command, 1-6); AV 5 Comfort1 Setpoint (Comfort1 supply temperature setpoint); AV 58 Actual alarms reset (Write 1 to reset current alarms); AV 1 Current mode (Active mode (0 = off/standby)); AI 0 Supply air temperature (Supply air temperature); AI 1 Extract air temperature (Extract air temperature); AI 2 Outdoor air temperature (Outdoor air temperature); BO 22 Alarm DOUT (Common alarm output (1 = alarm)).

How do I enable BMS control of the Komfovent C5 controller?

AV 0 Unit On/Off switches the unit (0 = off, 1 = on). AV 2 Mode selection picks the operating mode; 6 = Program hands control to the unit's own schedule.

Can the BMS supply sensor values to the Komfovent C5 controller?

AV 73 External room temperature sensor accepts a room temperature from the BMS; a value outside -50..+120 °C disables the override.

How do I check these points on the real C5 controller?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Komfovent BACnet points lists

Source: BACnet Connection C5 - Installation and Service Manual · BACnet-C5_25-07 · rev. 2025-07. Object names, instances and units are reproduced as published; descriptions are our own.