Air handling unit controller · BACnet points list
Komfovent C5 controller BACnet points list
Updated 4 November 2026
The Komfovent C5 is the built-in controller of Komfovent air handling units. It speaks BACnet IP on its RJ-45 Ethernet port (no MS/TP). The list has 237 objects: sensor readings as AIs, output signals as AOs, wired contacts as BIs, relay outputs as BOs, alarms as BVs, and all commands, setpoints and function settings as AVs. On/off, modes and enable flags are AVs with numeric codes, not binary or multistate objects.
This page lists 237 BACnet objects for the Komfovent C5 controller — 85 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Komfovent’s own free documentation, linked below.
- Manufacturer
- Komfovent
- Model
- C5 controller
- Equipment
- Air handling unit controller
- Equipment type
- Rooftop units, AHUs & DOAS
- BACnet objects
- 237 (85 writable)
- Transport
- BACnet IP
- Firmware
- Not stated
- Default device instance
- 1100
- Also known as
- Komfovent C5, C5.1, BACnet-C5
Reference only, provided as-is: verify against Komfovent’s current documentation and the live device before use. Not official Komfovent information. Terms of use.
BMS integration notes: Komfovent C5 controller
Start and stop the unit with AV 0 Unit On/Off and pick the ventilation mode with AV 2 Mode selection (Comfort1/2, Economy1/2, Special, Program). Each mode has its own supply/extract flow and temperature setpoint AVs. Read AV 1 Current mode, the supply, extract and outdoor temperatures (AI 0-2), the alarm BVs and BO 22 Alarm DOUT; reset alarms by writing 1 to AV 58.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AV 0 | Unit On/Off | Unit on/off command (1 = on) | Write |
| AV 2 | Mode selection | Ventilation mode command, 1-6 | Write |
| AV 5 | Comfort1 Setpoint | Comfort1 supply temperature setpoint | Write |
| AV 58 | Actual alarms reset | Write 1 to reset current alarms | Write |
| AV 1 | Current mode | Active mode (0 = off/standby) | Read |
| AI 0 | Supply air temperature | Supply air temperature | Read |
| AI 1 | Extract air temperature | Extract air temperature | Read |
| AI 2 | Outdoor air temperature | Outdoor air temperature | Read |
| BO 22 | Alarm DOUT | Common alarm output (1 = alarm) | Read |
Enable & remote start
AV 0 Unit On/Off switches the unit (0 = off, 1 = on). AV 2 Mode selection picks the operating mode; 6 = Program hands control to the unit's own schedule.
Sensors & values from the BMS
AV 73 External room temperature sensor accepts a room temperature from the BMS; a value outside -50..+120 °C disables the override.
Network setup
- Factory network settings: IP 192.168.0.50, mask 255.255.0.0, BACnet port 47808, BACnet ID 1100.
- Change them in the controller web server (Settings > Connectivity) or on the C5.1 panel (Settings > Air handling unit > Connectivity).
- Komfovent recommends a polling interval of at least 1 second.
- AV 83 enables BBMD (BACnet Broadcast Management Device) on the controller.
Watch out for
- Commands and enable flags are AVs holding 0/1 or mode codes, not BVs or MVs.
- Flow setpoint units follow AV 72; check it before writing flows.
- AV 59-61 run-hour counters and AV 67-71 clock values are writable; don't write them cyclically.
- AV 84 starts a heat exchanger calibration when 1 is written.
Komfovent C5 controller BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AImin | 0 | Supply air temperature | Range -50.0..+120.0 | °C | Read | |
| AImin | 1 | Extract air temperature | Range -50.0..+120.0 | °C | Read | |
| AImin | 2 | Outdoor air temperature | Range -50.0..+120.0 | °C | Read | |
| AI | 3 | Exhaust air temperature | Range -50.0..+120.0 | °C | Read | |
| AI | 4 | Water temperature | Range -50.0..+120.0 | °C | Read | |
| AI | 5 | Air quality | Range 0..100 | % | Read | |
| AI | 6 | Supply air humidity | Range 0..100 | %RH | Read | |
| AI | 7 | Supply air flow | Range 0..1000000 | m3/h, l/s, m3/s or Pa (per AV 72) | Read | |
| AI | 8 | Exhaust air flow | Range 0..1000000 | m3/h, l/s, m3/s or Pa (per AV 72) | Read | |
| AI | 9 | Outdoor air filter pressure | Range 0..5500 | Pa | Read | |
| AI | 10 | Extract air filter pressure | Range 0..5500 | Pa | Read | |
| AI | 11 | Zone 1 supply air temperature | Range -50.0..+120.0 | °C | Read | |
| AI | 12 | Zone 1 water temperature | Range -30.0..+120.0 | °C | Read | |
| AI | 13 | Zone 2 supply air temperature | Range -50.0..+120.0 | °C | Read | |
| AI | 14 | Zone 2 water temperature | Range -30.0..+120.0 | °C | Read | |
| AI | 15 | Internal supply air temperature | Range -50.0..+120.0 | °C | Read | |
| AI | 16 | Zone 1 air quality | Range 0..100 | % | Read | |
| AI | 17 | Zone 1 heater temperature | Range 0..+120.0 | °C | Read | |
| AI | 18 | Zone 2 air quality | Range 0..100 | % | Read | |
| AI | 19 | Zone 2 heater temperature | Range 0..+120.0 | °C | Read | |
| AI | 20 | Supply temperature set-point | Range +5..+45 | °C | Read | |
| AI | 21 | Supply air absolute humidity | Range 0..40.0 | g/m3 or g/kg | Read | |
| AI | 22 | Supply air pressure | Range 0..5500 | Pa | Read | |
| AI | 23 | Extract air pressure | Range 0..5500 | Pa | Read | |
| AO | 0 | Water heater level | Range 0..100 | % | Read | |
| AO | 1 | Water cooler level | Range 0..100 | % | Read | |
| AO | 2 | Humidifier level | Range 0..100 | % | Read | |
| AO | 3 | Heat exchanger level | Range 0..100 | % | Read | |
| AO | 4 | Recirculation level | Range 0..100 | % | Read | |
| AO | 5 | Supply fan level | Range 0..100 | % | Read | |
| AO | 6 | Exhaust fan level | Range 0..100 | % | Read | |
| AO | 7 | Outdoor air damper level | Range 0..100 | % | Read | |
| AO | 8 | Exhaust air damper level | Range 0..100 | % | Read | |
| AO | 9 | El. Heater level | Range 0..100 | % | Read | |
| AO | 10 | DX level | Range -100..+100 | % | Read | |
| AO | 11 | Heat pump level | Range -100..+100 | % | Read | |
| AO | 12 | Zone 1 level/heater level | Range -100..+100 | % | Read | |
| AO | 13 | Zone 2 level/heater level | Range -100..+100 | % | Read | |
| AO | 14 | Zone 1 cooler level | Range 0..100 | % | Read | |
| AO | 15 | Zone 2 cooler level | Range 0..100 | % | Read | |
| AO | 16 | Zone 1 temperature setpoint/error | Setpoint (+5..+40 °C) or error (0..100 %) | °C or % | Read | |
| AO | 17 | Zone 2 temperature setpoint/error | Setpoint (+5..+40 °C) or error (0..100 %) | °C or % | Read | |
| BI | 0 | OVR | Read | 0=open, 1=closed | ||
| BI | 1 | External stop | Read | 0=open, 1=closed | ||
| BI | 2 | Zone 1 electric heater TK100 | Read | 0=open, 1=closed | ||
| BI | 3 | Zone 1 electric heater TK60 | Read | 0=open, 1=closed | ||
| BI | 4 | Zone 1 electric heater TK70 | Read | 0=open, 1=closed | ||
| BI | 5 | Zone 1 low water temperature | Read | 0=open, 1=closed | ||
| BI | 6 | Zone 1 combined coil | Read | 0=open, 1=closed | ||
| BI | 7 | Zone 1 external stop | Read | 0=open, 1=closed | ||
| BI | 8 | Zone 2 electric heater TK100 | Read | 0=open, 1=closed | ||
| BI | 9 | Zone 2 electric heater TK60 | Read | 0=open, 1=closed | ||
| BI | 10 | Zone 2 electric heater TK70 | Read | 0=open, 1=closed | ||
| BI | 11 | Zone 2 low water temperature | Read | 0=open, 1=closed | ||
| BI | 12 | Zone 2 combined coil | Read | 0=open, 1=closed | ||
| BI | 13 | Zone 2 external stop | Read | 0=open, 1=closed | ||
| BI | 14 | Outdoor air filter | Read | 0=open, 1=closed | ||
| BI | 15 | Extract air filter | Read | 0=open, 1=closed | ||
| BI | 16 | C5 Control | Read | 0=open, 1=closed | ||
| BO | 0 | Water heating pump | Read | 0=stop, 1=run | ||
| BO | 1 | Water cooling pump | Read | 0=stop, 1=run | ||
| BO | 2 | Zone 1 stage 1 | Read | 0=stop, 1=run | ||
| BO | 3 | Zone 1 stage 2 | Read | 0=stop, 1=run | ||
| BO | 4 | Zone 1 stage 3 | Read | 0=stop, 1=run | ||
| BO | 5 | Zone 1 stage 4 | Read | 0=stop, 1=run | ||
| BO | 6 | Zone 1 heating water pump | Read | 0=stop, 1=run | ||
| BO | 7 | Zone 1 cooling water pump | Read | 0=stop, 1=run | ||
| BO | 8 | Zone 1 DX level unit reverse | Read | 0=stop, 1=run | ||
| BO | 9 | Zone 1 DX modulated unit operation | Read | 0=stop, 1=run | ||
| BO | 10 | Zone 1 DX modulated unit cooling | Read | 0=stop, 1=run | ||
| BO | 11 | Zone 1 DX modulated unit heating | Read | 0=stop, 1=run | ||
| BO | 12 | Zone 2 stage 1 | Read | 0=stop, 1=run | ||
| BO | 13 | Zone 2 stage 2 | Read | 0=stop, 1=run | ||
| BO | 14 | Zone 2 stage 3 | Read | 0=stop, 1=run | ||
| BO | 15 | Zone 2 stage 4 | Read | 0=stop, 1=run | ||
| BO | 16 | Zone 2 heating water pump | Read | 0=stop, 1=run | ||
| BO | 17 | Zone 2 cooling water pump | Read | 0=stop, 1=run | ||
| BO | 18 | Zone 2 DX level unit reverse | Read | 0=stop, 1=run | ||
| BO | 19 | Zone 2 DX modulated unit operation | Read | 0=stop, 1=run | ||
| BO | 20 | Zone 2 DX modulated unit cooling | Read | 0=stop, 1=run | ||
| BO | 21 | Zone 2 DX modulated unit heating | Read | 0=stop, 1=run | ||
| BOmin | 22 | Alarm DOUT | Read | 0=no alarm, 1=alarm | ||
| BO | 23 | AQC active | Read | 0=stop, 1=run | ||
| BO | 24 | OCV active | Read | 0=stop, 1=run | ||
| BO | 25 | MTC active | Read | 0=stop, 1=run | ||
| BO | 26 | OVR active | Read | 0=stop, 1=run | ||
| BO | 27 | SNC active | Read | 0=stop, 1=run | ||
| BO | 28 | OOD active | Read | 0=stop, 1=run | ||
| BO | 29 | REC active | Read | 0=stop, 1=run | ||
| BO | 30 | HUM active | Read | 0=stop, 1=run | ||
| BO | 31 | Defrost active | Read | 0=stop, 1=run | ||
| BV | 0 | Low supply air flow | Read | |||
| BV | 1 | Low extract air flow | Read | |||
| BV | 2 | VAV calibration fail | Read | |||
| BV | 3 | Change outdoor air filter | Read | |||
| BV | 4 | Change extract air filter | Read | |||
| BV | 5 | Electric heater off | Read | |||
| BV | 6 | High pressure on compressor | Read | |||
| BV | 7 | Low pressure on compressor | Read | |||
| BV | 8 | Service time | Read | |||
| BV | 9 | Service mode | Read | |||
| BV | 10 | Supply air temp. sensor failure | Read | |||
| BV | 11 | Extract air temp. sensor failure | Read | |||
| BV | 12 | Outdoor air temp. sensor failure | Read | |||
| BV | 13 | Exhaust air temp. sensor failure | Read | |||
| BV | 14 | Water temp. sensor failure | Read | |||
| BV | 15 | Return water temp low | Read | |||
| BV | 16 | Internal fire alarm | Read | |||
| BV | 17 | External fire alarm | Read | |||
| BV | 18 | External stop | Read | |||
| BV | 19 | Heat exchanger failure | Read | |||
| BV | 20 | Heat exchanger icing | Read | |||
| BV | 21 | Low supply air temperature | Read | |||
| BV | 22 | High supply air temperature | Read | |||
| BV | 23 | Electric heater overheat | Read | |||
| BV | 24 | Evaporator air temp. sensor failure | Read | |||
| BV | 25 | Evaporator coil temp. sensor failure | Read | |||
| BV | 26 | Compressor failure | Read | |||
| BV | 27 | Supply fan drive failure | Read | |||
| BV | 28 | Supply fan drive overload | Read | |||
| BV | 29 | Supply fan motor failure | Read | |||
| BV | 30 | Supply fan motor overload | Read | |||
| BV | 31 | Exhaust drive failure | Read | |||
| BV | 32 | Exhaust fan drive overload | Read | |||
| BV | 33 | Exhaust fan motor failure | Read | |||
| BV | 34 | Exhaust fan motor overload | Read | |||
| BV | 35 | Rotor drive failure | Read | |||
| BV | 36 | Rotor drive overload | Read | |||
| BV | 37 | Rotor motor failure | Read | |||
| BV | 38 | Rotor motor overload | Read | |||
| BV | 39 | Communication error | Read | |||
| BV | 40 | Controller failure | Read | |||
| BV | 41 | Compressor off | Read | |||
| BV | 42 | Evaporator icing | Read | |||
| BV | 43 | Zone 1 TK100 alarm | Read | |||
| BV | 44 | Zone 1 TK70 alarm | Read | |||
| BV | 45 | Zone 1 TK60 alarm | Read | |||
| BV | 46 | Zone 1 low water temperature | Read | |||
| BV | 47 | Zone 1 external stop | Read | |||
| BV | 48 | Zone 2 TK100 alarm | Read | |||
| BV | 49 | Zone 2 TK70 alarm | Read | |||
| BV | 50 | Zone 2 TK60 alarm | Read | |||
| BV | 51 | Zone 2 low water temperature | Read | |||
| BV | 52 | Zone 2 external stop | Read | |||
| BV | 53 | Low heat exchanger efficiency | Read | |||
| BV | 54 | Water pump / coil alarm | Read | |||
| AVmin | 0 | Unit On/Off | Write | 0=Off, 1=On | ||
| AVmin | 1 | Current mode | Read | 0=Off/Standby, 1=Comfort1, 2=Comfort2, 3=Economy1, 4=Economy2, 5=Special | ||
| AVmin | 2 | Mode selection | Write | 1=Comfort1, 2=Comfort2, 3=Economy1, 4=Economy2, 5=Special, 6=Program | ||
| AV | 3 | Comfort1 Supply flow | Range 0..200000 | m3/h, l/s, m3/s or Pa (per AV 72) | Write | |
| AV | 4 | Comfort1 Extract flow | Range 0..200000 | m3/h, l/s, m3/s or Pa (per AV 72) | Write | |
| AVmin | 5 | Comfort1 Setpoint | Range +5..+40 | °C | Write | |
| AV | 6 | Comfort2 Supply flow | Range 0..200000 | m3/h, l/s, m3/s or Pa (per AV 72) | Write | |
| AV | 7 | Comfort2 Extract flow | Range 0..200000 | m3/h, l/s, m3/s or Pa (per AV 72) | Write | |
| AV | 8 | Comfort2 Setpoint | Range +5..+40 | °C | Write | |
| AV | 9 | Economy1 Supply flow | Range 0..200000 | m3/h, l/s, m3/s or Pa (per AV 72) | Write | |
| AV | 10 | Economy1 Extract flow | Range 0..200000 | m3/h, l/s, m3/s or Pa (per AV 72) | Write | |
| AV | 11 | Economy1 Setpoint | Range +5..+40 | °C | Write | |
| AV | 12 | Economy2 Supply flow | Range 0..200000 | m3/h, l/s, m3/s or Pa (per AV 72) | Write | |
| AV | 13 | Economy2 Extract flow | Range 0..200000 | m3/h, l/s, m3/s or Pa (per AV 72) | Write | |
| AV | 14 | Economy2 Setpoint | Range +5..+40 | °C | Write | |
| AV | 15 | Special Supply flow | Range 0..200000 | m3/h, l/s, m3/s or Pa (per AV 72) | Write | |
| AV | 16 | Special Extract flow | Range 0..200000 | m3/h, l/s, m3/s or Pa (per AV 72) | Write | |
| AV | 17 | Special Setpoint | Range +5..+40 | °C | Write | |
| AV | 18 | Special mode Heating | Write | 0=Disable, 1=Enable | ||
| AV | 19 | Special mode Cooling | Write | 0=Disable, 1=Enable | ||
| AV | 20 | Special mode Recirculation | Write | 0=Disable, 1=Enable | ||
| AV | 21 | Special mode Humidifying | Write | 0=Disable, 1=Enable | ||
| AV | 22 | Special mode Dehumidifying | Write | 0=Disable, 1=Enable | ||
| AV | 23 | Flow control mode | Write | 0=CAV, 1=VAV, 2=DCV | ||
| AV | 24 | Temp. control mode | Write | 0=Supply, 1=Extract, 2=Room, 3=Balance | ||
| AV | 25 | AQC Enable | Write | 0=Disable, 1=Enable | ||
| AV | 26 | AQC Setpoint 1 | 200-1800 ppm, 10-90 % or 5-45 °C by sensor type | ppm, % or °C (by sensor type) | Write | |
| AV | 27 | AQC Mode 1 | Write | 1=Comfort1, 2=Comfort2, 3=Economy1, 4=Economy2, 5=Special | ||
| AV | 28 | AQC Setpoint 2 | 200-1800 ppm, 10-90 % or 5-45 °C by sensor type | ppm, % or °C (by sensor type) | Write | |
| AV | 29 | AQC Mode 2 | Write | 1=Comfort1, 2=Comfort2, 3=Economy1, 4=Economy2, 5=Special | ||
| AV | 30 | OCV Enable | Write | 0=Disable, 1=Enable | ||
| AV | 31 | OCV Winter compensation stop | Range -40.0..+50.0 | °C | Write | |
| AV | 32 | OCV Winter compensation start | Range -40.0..+50.0 | °C | Write | |
| AV | 33 | OCV Summer compensation start | Range -40.0..+50.0 | °C | Write | |
| AV | 34 | OCV Summer compensation stop | Range -40.0..+50.0 | °C | Write | |
| AV | 35 | MTC Enable | Write | 0=Disable, 1=Enable | ||
| AV | 36 | MTC Setpoint | Range -40.0..+50.0 | °C | Write | |
| AV | 37 | OVR Enable | Write | 0=Disable, 1=Enable | ||
| AV | 38 | OVR Type | Write | 0=Alltime, 1=If on, 2=If off | ||
| AV | 39 | OVR Mode | Write | 0=Standby, 1=Comfort1, 2=Comfort2, 3=Economy1, 4=Economy2, 5=Special, 6=Program | ||
| AV | 40 | SNC Enable | Write | 0=Disable, 1=Enable | ||
| AV | 41 | SNC Start temperature | Range 15.0..+50.0 | °C | Write | |
| AV | 42 | SNC Stop temperature | Range 15.0..+50.0 | °C | Write | |
| AV | 43 | OOD Enable | Write | 0=Disable, 1=Enable | ||
| AV | 44 | OOD Setpoint | 200-1800 ppm, 10-90 % or 5-45 °C by sensor type | ppm, % or °C (by sensor type) | Write | |
| AV | 45 | REC Enable | Write | 0=Disable, 1=Enable | ||
| AV | 46 | REC Setpoint 1 | 200-1800 ppm, 10-90 % or 5-45 °C by sensor type | ppm, % or °C (by sensor type) | Write | |
| AV | 47 | REC Mode 1 | Write | 1=Comfort1, 2=Comfort2, 3=Economy1, 4=Economy2, 5=Special | ||
| AV | 48 | REC Setpoint 2 | 200-1800 ppm, 10-90 % or 5-45 °C by sensor type | ppm, % or °C (by sensor type) | Write | |
| AV | 49 | REC Mode 2 | Write | 1=Comfort1, 2=Comfort2, 3=Economy1, 4=Economy2, 5=Special | ||
| AV | 50 | REC Min. Fresh Air 1 | Range 0..100 | % | Write | |
| AV | 51 | REC Min. Fresh Air 2 | Range 0..100 | % | Write | |
| AV | 52 | REC Winter end | Range -40.0..+50.0 | °C | Write | |
| AV | 53 | REC Winter start | Range -40.0..+50.0 | °C | Write | |
| AV | 54 | REC Summer start | Range -40.0..+50.0 | °C | Write | |
| AV | 55 | REC Summer end | Range -40.0..+50.0 | °C | Write | |
| AV | 56 | REC Default recirculation | Range 0..100 | % | Write | |
| AV | 57 | REC Activated recirculation | Range 0..100 | % | Write | |
| AV | 77 | HUM Enable | Write | 0=Disable, 1=Enable | ||
| AV | 78 | HUM Setpoint 1 | Range 10..90 | % | Write | |
| AV | 79 | HUM Mode 1 | Write | 1=Comfort1, 2=Comfort2, 3=Economy1, 4=Economy2, 5=Special | ||
| AV | 80 | HUM Setpoint 2 | Range 10..90 | % | Write | |
| AV | 81 | HUM Mode 2 | Write | 1=Comfort1, 2=Comfort2, 3=Economy1, 4=Economy2 | ||
| AV | 84 | CF heatexchanger calibration | Write 1 to start heat exchanger calibration | Write | 0=No calibration, 1=Calibrated, 2=Calibrating | |
| AV | 85 | HUM mode | Write | 0=Supply, 1=Indoor+Supply, 2=Indoor | ||
| AV | 86 | HUM Type | Write | 0=RH, 1=AH | ||
| AV | 87 | HUM Units | Write | 0=g/m3, 1=g/kg | ||
| AV | 88 | OCV Minimum airflow | Range 20..100 | % | Write | |
| AV | 89 | Water heater: Enable/Disable | Write | 0=Disable, 1=Enable | ||
| AV | 90 | Water cooler: Enable/Disable | Write | 0=Disable, 1=Enable | ||
| AVmin | 58 | Actual alarms reset | Write 1 to reset current alarms | Write | 1=Reset current alarm | |
| AV | 59 | Air heater operation | Range 0..2^32 | hours | Write | |
| AV | 60 | Supply fan operation | Range 0..2^32 | hours | Write | |
| AV | 61 | Exhaust fan operation | Range 0..2^32 | hours | Write | |
| AV | 62 | Heat exchanger thermal efficiency | Range 1-100; 255 = none | % | Read | |
| AV | 63 | Heat exchanger recovery | Range 0..2^32 | watt | Read | |
| AV | 64 | Thermal energy saving | Range 0..100 | % | Read | |
| AV | 65 | Supply SFP | Range 0..655 | Read | ||
| AV | 66 | Exhaust SFP | Range 0..655 | Read | ||
| AV | 67 | Day | Range 1..31 | days | Write | |
| AV | 68 | Month | Range 1..12 | months | Write | |
| AV | 69 | Year | Range 2000..2250 | years | Write | |
| AV | 70 | Hours | Range 0..23 | hours | Write | |
| AV | 71 | Minutes | Range 0..59 | minutes | Write | |
| AV | 72 | Flow units | Write | 0=m3/h, 1=l/s, 2=m3/s, 3=Pa | ||
| AV | 73 | External room temperature sensor | Value from BMS; outside range disables override | °C | Write | |
| AV | 74 | Zone 1 setpoint | Range -50.0..+40.0 | °C | Write | |
| AV | 75 | Zone 2 setpoint | Range -50.0..+40.0 | °C | Write | |
| AV | 76 | Digital input IN4 override | Write | -1=disabled, 0=heating, 1=cooling, 2=error | ||
| AV | 82 | Daylight saving time | Write | 0=Disable, 1=Enable | ||
| AV | 83 | BACnet Broadcast Management Device | Write | 0=Disable, 1=Enable |
No points match these filters.
Object ID lookup: Komfovent C5 controller point IDs by name
AI0Supply air temperatureAI1Extract air temperatureAI2Outdoor air temperatureAI3Exhaust air temperatureAI4Water temperatureAI5Air qualityAI6Supply air humidityAI7Supply air flowAI8Exhaust air flowAI9Outdoor air filter pressureAI10Extract air filter pressureAI11Zone 1 supply air temperatureAI12Zone 1 water temperatureAI13Zone 2 supply air temperatureAI14Zone 2 water temperatureAI15Internal supply air temperatureAI16Zone 1 air qualityAI17Zone 1 heater temperatureAI18Zone 2 air qualityAI19Zone 2 heater temperatureAI20Supply temperature set-pointAI21Supply air absolute humidityAI22Supply air pressureAI23Extract air pressureAO0Water heater levelAO1Water cooler levelAO2Humidifier levelAO3Heat exchanger levelAO4Recirculation levelAO5Supply fan levelAO6Exhaust fan levelAO7Outdoor air damper levelAO8Exhaust air damper levelAO9El. Heater levelAO10DX levelAO11Heat pump levelAO12Zone 1 level/heater levelAO13Zone 2 level/heater levelAO14Zone 1 cooler levelAO15Zone 2 cooler levelAO16Zone 1 temperature setpoint/errorAO17Zone 2 temperature setpoint/errorBI0OVRBI1External stopBI2Zone 1 electric heater TK100BI3Zone 1 electric heater TK60BI4Zone 1 electric heater TK70BI5Zone 1 low water temperatureBI6Zone 1 combined coilBI7Zone 1 external stopBI8Zone 2 electric heater TK100BI9Zone 2 electric heater TK60BI10Zone 2 electric heater TK70BI11Zone 2 low water temperatureBI12Zone 2 combined coilBI13Zone 2 external stopBI14Outdoor air filterBI15Extract air filterBI16C5 ControlBO0Water heating pumpBO1Water cooling pumpBO2Zone 1 stage 1BO3Zone 1 stage 2BO4Zone 1 stage 3BO5Zone 1 stage 4BO6Zone 1 heating water pumpBO7Zone 1 cooling water pumpBO8Zone 1 DX level unit reverseBO9Zone 1 DX modulated unit operationBO10Zone 1 DX modulated unit coolingBO11Zone 1 DX modulated unit heatingBO12Zone 2 stage 1BO13Zone 2 stage 2BO14Zone 2 stage 3BO15Zone 2 stage 4BO16Zone 2 heating water pumpBO17Zone 2 cooling water pumpBO18Zone 2 DX level unit reverseBO19Zone 2 DX modulated unit operationBO20Zone 2 DX modulated unit coolingBO21Zone 2 DX modulated unit heatingBO22Alarm DOUTBO23AQC activeBO24OCV activeBO25MTC activeBO26OVR activeBO27SNC activeBO28OOD activeBO29REC activeBO30HUM activeBO31Defrost activeBV0Low supply air flowBV1Low extract air flowBV2VAV calibration failBV3Change outdoor air filterBV4Change extract air filterBV5Electric heater offBV6High pressure on compressorBV7Low pressure on compressorBV8Service timeBV9Service modeBV10Supply air temp. sensor failureBV11Extract air temp. sensor failureBV12Outdoor air temp. sensor failureBV13Exhaust air temp. sensor failureBV14Water temp. sensor failureBV15Return water temp lowBV16Internal fire alarmBV17External fire alarmBV18External stopBV19Heat exchanger failureBV20Heat exchanger icingBV21Low supply air temperatureBV22High supply air temperatureBV23Electric heater overheatBV24Evaporator air temp. sensor failureBV25Evaporator coil temp. sensor failureBV26Compressor failureBV27Supply fan drive failureBV28Supply fan drive overloadBV29Supply fan motor failureBV30Supply fan motor overloadBV31Exhaust drive failureBV32Exhaust fan drive overloadBV33Exhaust fan motor failureBV34Exhaust fan motor overloadBV35Rotor drive failureBV36Rotor drive overloadBV37Rotor motor failureBV38Rotor motor overloadBV39Communication errorBV40Controller failureBV41Compressor offBV42Evaporator icingBV43Zone 1 TK100 alarmBV44Zone 1 TK70 alarmBV45Zone 1 TK60 alarmBV46Zone 1 low water temperatureBV47Zone 1 external stopBV48Zone 2 TK100 alarmBV49Zone 2 TK70 alarmBV50Zone 2 TK60 alarmBV51Zone 2 low water temperatureBV52Zone 2 external stopBV53Low heat exchanger efficiencyBV54Water pump / coil alarmAV0Unit On/OffAV1Current modeAV2Mode selectionAV3Comfort1 Supply flowAV4Comfort1 Extract flowAV5Comfort1 SetpointAV6Comfort2 Supply flowAV7Comfort2 Extract flowAV8Comfort2 SetpointAV9Economy1 Supply flowAV10Economy1 Extract flowAV11Economy1 SetpointAV12Economy2 Supply flowAV13Economy2 Extract flowAV14Economy2 SetpointAV15Special Supply flowAV16Special Extract flowAV17Special SetpointAV18Special mode HeatingAV19Special mode CoolingAV20Special mode RecirculationAV21Special mode HumidifyingAV22Special mode DehumidifyingAV23Flow control modeAV24Temp. control modeAV25AQC EnableAV26AQC Setpoint 1AV27AQC Mode 1AV28AQC Setpoint 2AV29AQC Mode 2AV30OCV EnableAV31OCV Winter compensation stopAV32OCV Winter compensation startAV33OCV Summer compensation startAV34OCV Summer compensation stopAV35MTC EnableAV36MTC SetpointAV37OVR EnableAV38OVR TypeAV39OVR ModeAV40SNC EnableAV41SNC Start temperatureAV42SNC Stop temperatureAV43OOD EnableAV44OOD SetpointAV45REC EnableAV46REC Setpoint 1AV47REC Mode 1AV48REC Setpoint 2AV49REC Mode 2AV50REC Min. Fresh Air 1AV51REC Min. Fresh Air 2AV52REC Winter endAV53REC Winter startAV54REC Summer startAV55REC Summer endAV56REC Default recirculationAV57REC Activated recirculationAV77HUM EnableAV78HUM Setpoint 1AV79HUM Mode 1AV80HUM Setpoint 2AV81HUM Mode 2AV84CF heatexchanger calibrationAV85HUM modeAV86HUM TypeAV87HUM UnitsAV88OCV Minimum airflowAV89Water heater: Enable/DisableAV90Water cooler: Enable/DisableAV58Actual alarms resetAV59Air heater operationAV60Supply fan operationAV61Exhaust fan operationAV62Heat exchanger thermal efficiencyAV63Heat exchanger recoveryAV64Thermal energy savingAV65Supply SFPAV66Exhaust SFPAV67DayAV68MonthAV69YearAV70HoursAV71MinutesAV72Flow unitsAV73External room temperature sensorAV74Zone 1 setpointAV75Zone 2 setpointAV76Digital input IN4 overrideAV82Daylight saving timeAV83BACnet Broadcast Management Device
Integration notes
- AIs, AOs, BIs, BOs and BVs are read-only; most AVs are R/W.
- Flow AVs and AIs use the unit chosen in AV 72 Flow units (m3/h, l/s, m3/s or Pa).
- AQC, OOD and REC setpoints take ppm, % or °C depending on the air quality sensor type fitted.
- AV numbers have gaps by section: function settings use 0-57 and 77-90; alarm reset, counters and user settings use 58-76, 82 and 83.
- Zone 1 / Zone 2 objects only matter when the extra zones are configured.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the C5 controller and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Komfovent C5 controller
How many BACnet points does the Komfovent C5 controller have?
This list has 237 BACnet objects: 24 analog inputs, 18 analog outputs, 91 analog values, 17 binary inputs, 32 binary outputs, 55 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Komfovent C5 controller BACnet points are writable?
85 of the 237 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Komfovent C5 controller BACnet documentation?
The source is BACnet Connection C5 - Installation and Service Manual (BACnet-C5_25-07), revision 2025-07, published free by Komfovent at https://komfovent.com/en/downloads/Bacnet_connection_C5_EN.pdf.
What are the minimum BACnet points to integrate the Komfovent C5 controller?
Start with AV 0 Unit On/Off (Unit on/off command (1 = on)); AV 2 Mode selection (Ventilation mode command, 1-6); AV 5 Comfort1 Setpoint (Comfort1 supply temperature setpoint); AV 58 Actual alarms reset (Write 1 to reset current alarms); AV 1 Current mode (Active mode (0 = off/standby)); AI 0 Supply air temperature (Supply air temperature); AI 1 Extract air temperature (Extract air temperature); AI 2 Outdoor air temperature (Outdoor air temperature); BO 22 Alarm DOUT (Common alarm output (1 = alarm)).
How do I enable BMS control of the Komfovent C5 controller?
AV 0 Unit On/Off switches the unit (0 = off, 1 = on). AV 2 Mode selection picks the operating mode; 6 = Program hands control to the unit's own schedule.
Can the BMS supply sensor values to the Komfovent C5 controller?
AV 73 External room temperature sensor accepts a room temperature from the BMS; a value outside -50..+120 °C disables the override.
How do I check these points on the real C5 controller?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Komfovent BACnet points lists
- Air handling unit controller
Komfovent C6 / C6M controller
Komfovent air handling units fitted with the C6 / C6M controller.
Also known as: Komfovent C6, Komfovent C6M, C6M, C6.1, BACnet-C6 - Air handling unit controller
Komfovent C8 controller
Komfovent air handling units fitted with the C8 controller.
Also known as: Komfovent C8, BACnet-C8
Source: BACnet Connection C5 - Installation and Service Manual · BACnet-C5_25-07 · rev. 2025-07. Object names, instances and units are reproduced as published; descriptions are our own.