 "manufacturer": "Komfovent",
 "manufacturer_slug": "komfovent",
 "model": "C5 controller",
 "model_slug": "c5-controller",
 "aliases": [
  "Komfovent C5",
  "C5.1",
  "BACnet-C5"
 ],
 "equipment_type": "Air handling unit controller",
 "applies_to": "Komfovent air handling units fitted with the C5 controller.",
 "summary": "The Komfovent C5 is the built-in controller of Komfovent air handling units. It speaks BACnet IP on its RJ-45 Ethernet port (no MS/TP). The list has 237 objects: sensor readings as AIs, output signals as AOs, wired contacts as BIs, relay outputs as BOs, alarms as BVs, and all commands, setpoints and function settings as AVs. On/off, modes and enable flags are AVs with numeric codes, not binary or multistate objects.",
 "bacnet_transport": [
  "BACnet IP"
 ],
 "firmware": null,
 "default_device_instance": 1100,
 "access_inferred": false,
 "notes": [
  "AIs, AOs, BIs, BOs and BVs are read-only; most AVs are R/W.",
  "Flow AVs and AIs use the unit chosen in AV 72 Flow units (m3/h, l/s, m3/s or Pa).",
  "AQC, OOD and REC setpoints take ppm, % or °C depending on the air quality sensor type fitted.",
  "AV numbers have gaps by section: function settings use 0-57 and 77-90; alarm reset, counters and user settings use 58-76, 82 and 83.",
  "Zone 1 / Zone 2 objects only matter when the extra zones are configured."
 ],
 "source": {
  "title": "BACnet Connection C5 - Installation and Service Manual",
  "doc_number": "BACnet-C5_25-07",
  "revision_date": "2025-07",
  "url": "https://komfovent.com/en/downloads/Bacnet_connection_C5_EN.pdf"
 },
 "integration": {
  "summary": "Start and stop the unit with AV 0 Unit On/Off and pick the ventilation mode with AV 2 Mode selection (Comfort1/2, Economy1/2, Special, Program). Each mode has its own supply/extract flow and temperature setpoint AVs. Read AV 1 Current mode, the supply, extract and outdoor temperatures (AI 0-2), the alarm BVs and BO 22 Alarm DOUT; reset alarms by writing 1 to AV 58.",
  "minimum_points": [
   {
    "ref": "AV 0",
    "name": "Unit On/Off",
    "why": "Unit on/off command (1 = on)"
   },
   {
    "ref": "AV 2",
    "name": "Mode selection",
    "why": "Ventilation mode command, 1-6"
   },
   {
    "ref": "AV 5",
    "name": "Comfort1 Setpoint",
    "why": "Comfort1 supply temperature setpoint"
   },
   {
    "ref": "AV 58",
    "name": "Actual alarms reset",
    "why": "Write 1 to reset current alarms"
   },
   {
    "ref": "AV 1",
    "name": "Current mode",
    "why": "Active mode (0 = off/standby)"
   },
   {
    "ref": "AI 0",
    "name": "Supply air temperature",
    "why": "Supply air temperature"
   },
   {
    "ref": "AI 1",
    "name": "Extract air temperature",
    "why": "Extract air temperature"
   },
   {
    "ref": "AI 2",
    "name": "Outdoor air temperature",
    "why": "Outdoor air temperature"
   },
   {
    "ref": "BO 22",
    "name": "Alarm DOUT",
    "why": "Common alarm output (1 = alarm)"
   }
  ],
  "enable": "AV 0 Unit On/Off switches the unit (0 = off, 1 = on). AV 2 Mode selection picks the operating mode; 6 = Program hands control to the unit's own schedule.",
  "heartbeat": null,
  "remote_sensors": "AV 73 External room temperature sensor accepts a room temperature from the BMS; a value outside -50..+120 °C disables the override.",
  "setup": [
   "Factory network settings: IP 192.168.0.50, mask 255.255.0.0, BACnet port 47808, BACnet ID 1100.",
   "Change them in the controller web server (Settings > Connectivity) or on the C5.1 panel (Settings > Air handling unit > Connectivity).",
   "Komfovent recommends a polling interval of at least 1 second.",
   "AV 83 enables BBMD (BACnet Broadcast Management Device) on the controller."
  ],
  "gotchas": [
   "Commands and enable flags are AVs holding 0/1 or mode codes, not BVs or MVs.",
   "Flow setpoint units follow AV 72; check it before writing flows.",
   "AV 59-61 run-hour counters and AV 67-71 clock values are writable; don't write them cyclically.",
   "AV 84 starts a heat exchanger calibration when 1 is written."
  ]
 },
 "points": [
  {
   "type": "AI",
   "instance": 0,
   "name": "Supply air temperature",
   "description": "Range -50.0..+120.0",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 1,
   "name": "Extract air temperature",
   "description": "Range -50.0..+120.0",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 2,
   "name": "Outdoor air temperature",
   "description": "Range -50.0..+120.0",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 3,
   "name": "Exhaust air temperature",
   "description": "Range -50.0..+120.0",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 4,
   "name": "Water temperature",
   "description": "Range -50.0..+120.0",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 5,
   "name": "Air quality",
   "description": "Range 0..100",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 6,
   "name": "Supply air humidity",
   "description": "Range 0..100",
   "units": "%RH",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 7,
   "name": "Supply air flow",
   "description": "Range 0..1000000",
   "units": "m3/h, l/s, m3/s or Pa (per AV 72)",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 8,
   "name": "Exhaust air flow",
   "description": "Range 0..1000000",
   "units": "m3/h, l/s, m3/s or Pa (per AV 72)",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 9,
   "name": "Outdoor air filter pressure",
   "description": "Range 0..5500",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 10,
   "name": "Extract air filter pressure",
   "description": "Range 0..5500",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 11,
   "name": "Zone 1 supply air temperature",
   "description": "Range -50.0..+120.0",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 12,
   "name": "Zone 1 water temperature",
   "description": "Range -30.0..+120.0",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 13,
   "name": "Zone 2 supply air temperature",
   "description": "Range -50.0..+120.0",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 14,
   "name": "Zone 2 water temperature",
   "description": "Range -30.0..+120.0",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 15,
   "name": "Internal supply air temperature",
   "description": "Range -50.0..+120.0",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 16,
   "name": "Zone 1 air quality",
   "description": "Range 0..100",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 17,
   "name": "Zone 1 heater temperature",
   "description": "Range 0..+120.0",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 18,
   "name": "Zone 2 air quality",
   "description": "Range 0..100",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 19,
   "name": "Zone 2 heater temperature",
   "description": "Range 0..+120.0",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 20,
   "name": "Supply temperature set-point",
   "description": "Range +5..+45",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 21,
   "name": "Supply air absolute humidity",
   "description": "Range 0..40.0",
   "units": "g/m3 or g/kg",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 22,
   "name": "Supply air pressure",
   "description": "Range 0..5500",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 23,
   "name": "Extract air pressure",
   "description": "Range 0..5500",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 0,
   "name": "Water heater level",
   "description": "Range 0..100",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 1,
   "name": "Water cooler level",
   "description": "Range 0..100",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 2,
   "name": "Humidifier level",
   "description": "Range 0..100",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 3,
   "name": "Heat exchanger level",
   "description": "Range 0..100",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 4,
   "name": "Recirculation level",
   "description": "Range 0..100",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 5,
   "name": "Supply fan level",
   "description": "Range 0..100",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 6,
   "name": "Exhaust fan level",
   "description": "Range 0..100",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 7,
   "name": "Outdoor air damper level",
   "description": "Range 0..100",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 8,
   "name": "Exhaust air damper level",
   "description": "Range 0..100",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 9,
   "name": "El. Heater level",
   "description": "Range 0..100",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 10,
   "name": "DX level",
   "description": "Range -100..+100",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 11,
   "name": "Heat pump level",
   "description": "Range -100..+100",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 12,
   "name": "Zone 1 level/heater level",
   "description": "Range -100..+100",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 13,
   "name": "Zone 2 level/heater level",
   "description": "Range -100..+100",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 14,
   "name": "Zone 1 cooler level",
   "description": "Range 0..100",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 15,
   "name": "Zone 2 cooler level",
   "description": "Range 0..100",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 16,
   "name": "Zone 1 temperature setpoint/error",
   "description": "Setpoint (+5..+40 °C) or error (0..100 %)",
   "units": "°C or %",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 17,
   "name": "Zone 2 temperature setpoint/error",
   "description": "Setpoint (+5..+40 °C) or error (0..100 %)",
   "units": "°C or %",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 0,
   "name": "OVR",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=open, 1=closed"
  },
  {
   "type": "BI",
   "instance": 1,
   "name": "External stop",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=open, 1=closed"
  },
  {
   "type": "BI",
   "instance": 2,
   "name": "Zone 1 electric heater TK100",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=open, 1=closed"
  },
  {
   "type": "BI",
   "instance": 3,
   "name": "Zone 1 electric heater TK60",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=open, 1=closed"
  },
  {
   "type": "BI",
   "instance": 4,
   "name": "Zone 1 electric heater TK70",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=open, 1=closed"
  },
  {
   "type": "BI",
   "instance": 5,
   "name": "Zone 1 low water temperature",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=open, 1=closed"
  },
  {
   "type": "BI",
   "instance": 6,
   "name": "Zone 1 combined coil",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=open, 1=closed"
  },
  {
   "type": "BI",
   "instance": 7,
   "name": "Zone 1 external stop",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=open, 1=closed"
  },
  {
   "type": "BI",
   "instance": 8,
   "name": "Zone 2 electric heater TK100",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=open, 1=closed"
  },
  {
   "type": "BI",
   "instance": 9,
   "name": "Zone 2 electric heater TK60",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=open, 1=closed"
  },
  {
   "type": "BI",
   "instance": 10,
   "name": "Zone 2 electric heater TK70",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=open, 1=closed"
  },
  {
   "type": "BI",
   "instance": 11,
   "name": "Zone 2 low water temperature",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=open, 1=closed"
  },
  {
   "type": "BI",
   "instance": 12,
   "name": "Zone 2 combined coil",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=open, 1=closed"
  },
  {
   "type": "BI",
   "instance": 13,
   "name": "Zone 2 external stop",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=open, 1=closed"
  },
  {
   "type": "BI",
   "instance": 14,
   "name": "Outdoor air filter",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=open, 1=closed"
  },
  {
   "type": "BI",
   "instance": 15,
   "name": "Extract air filter",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=open, 1=closed"
  },
  {
   "type": "BI",
   "instance": 16,
   "name": "C5 Control",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=open, 1=closed"
  },
  {
   "type": "BO",
   "instance": 0,
   "name": "Water heating pump",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=stop, 1=run"
  },
  {
   "type": "BO",
   "instance": 1,
   "name": "Water cooling pump",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=stop, 1=run"
  },
  {
   "type": "BO",
   "instance": 2,
   "name": "Zone 1 stage 1",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=stop, 1=run"
  },
  {
   "type": "BO",
   "instance": 3,
   "name": "Zone 1 stage 2",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=stop, 1=run"
  },
  {
   "type": "BO",
   "instance": 4,
   "name": "Zone 1 stage 3",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=stop, 1=run"
  },
  {
   "type": "BO",
   "instance": 5,
   "name": "Zone 1 stage 4",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=stop, 1=run"
  },
  {
   "type": "BO",
   "instance": 6,
   "name": "Zone 1 heating water pump",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=stop, 1=run"
  },
  {
   "type": "BO",
   "instance": 7,
   "name": "Zone 1 cooling water pump",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=stop, 1=run"
  },
  {
   "type": "BO",
   "instance": 8,
   "name": "Zone 1 DX level unit reverse",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=stop, 1=run"
  },
  {
   "type": "BO",
   "instance": 9,
   "name": "Zone 1 DX modulated unit operation",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=stop, 1=run"
  },
  {
   "type": "BO",
   "instance": 10,
   "name": "Zone 1 DX modulated unit cooling",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=stop, 1=run"
  },
  {
   "type": "BO",
   "instance": 11,
   "name": "Zone 1 DX modulated unit heating",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=stop, 1=run"
  },
  {
   "type": "BO",
   "instance": 12,
   "name": "Zone 2 stage 1",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=stop, 1=run"
  },
  {
   "type": "BO",
   "instance": 13,
   "name": "Zone 2 stage 2",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=stop, 1=run"
  },
  {
   "type": "BO",
   "instance": 14,
   "name": "Zone 2 stage 3",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=stop, 1=run"
  },
  {
   "type": "BO",
   "instance": 15,
   "name": "Zone 2 stage 4",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=stop, 1=run"
  },
  {
   "type": "BO",
   "instance": 16,
   "name": "Zone 2 heating water pump",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=stop, 1=run"
  },
  {
   "type": "BO",
   "instance": 17,
   "name": "Zone 2 cooling water pump",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=stop, 1=run"
  },
  {
   "type": "BO",
   "instance": 18,
   "name": "Zone 2 DX level unit reverse",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=stop, 1=run"
  },
  {
   "type": "BO",
   "instance": 19,
   "name": "Zone 2 DX modulated unit operation",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=stop, 1=run"
  },
  {
   "type": "BO",
   "instance": 20,
   "name": "Zone 2 DX modulated unit cooling",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=stop, 1=run"
  },
  {
   "type": "BO",
   "instance": 21,
   "name": "Zone 2 DX modulated unit heating",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=stop, 1=run"
  },
  {
   "type": "BO",
   "instance": 22,
   "name": "Alarm DOUT",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=no alarm, 1=alarm"
  },
  {
   "type": "BO",
   "instance": 23,
   "name": "AQC active",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=stop, 1=run"
  },
  {
   "type": "BO",
   "instance": 24,
   "name": "OCV active",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=stop, 1=run"
  },
  {
   "type": "BO",
   "instance": 25,
   "name": "MTC active",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=stop, 1=run"
  },
  {
   "type": "BO",
   "instance": 26,
   "name": "OVR active",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=stop, 1=run"
  },
  {
   "type": "BO",
   "instance": 27,
   "name": "SNC active",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=stop, 1=run"
  },
  {
   "type": "BO",
   "instance": 28,
   "name": "OOD active",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=stop, 1=run"
  },
  {
   "type": "BO",
   "instance": 29,
   "name": "REC active",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=stop, 1=run"
  },
  {
   "type": "BO",
   "instance": 30,
   "name": "HUM active",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=stop, 1=run"
  },
  {
   "type": "BO",
   "instance": 31,
   "name": "Defrost active",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=stop, 1=run"
  },
  {
   "type": "BV",
   "instance": 0,
   "name": "Low supply air flow",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 1,
   "name": "Low extract air flow",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2,
   "name": "VAV calibration fail",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 3,
   "name": "Change outdoor air filter",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 4,
   "name": "Change extract air filter",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 5,
   "name": "Electric heater off",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 6,
   "name": "High pressure on compressor",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 7,
   "name": "Low pressure on compressor",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 8,
   "name": "Service time",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 9,
   "name": "Service mode",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 10,
   "name": "Supply air temp. sensor failure",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 11,
   "name": "Extract air temp. sensor failure",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 12,
   "name": "Outdoor air temp. sensor failure",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 13,
   "name": "Exhaust air temp. sensor failure",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 14,
   "name": "Water temp. sensor failure",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 15,
   "name": "Return water temp low",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 16,
   "name": "Internal fire alarm",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 17,
   "name": "External fire alarm",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 18,
   "name": "External stop",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 19,
   "name": "Heat exchanger failure",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 20,
   "name": "Heat exchanger icing",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 21,
   "name": "Low supply air temperature",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 22,
   "name": "High supply air temperature",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 23,
   "name": "Electric heater overheat",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 24,
   "name": "Evaporator air temp. sensor failure",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 25,
   "name": "Evaporator coil temp. sensor failure",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 26,
   "name": "Compressor failure",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 27,
   "name": "Supply fan drive failure",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 28,
   "name": "Supply fan drive overload",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 29,
   "name": "Supply fan motor failure",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 30,
   "name": "Supply fan motor overload",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 31,
   "name": "Exhaust drive failure",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 32,
   "name": "Exhaust fan drive overload",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 33,
   "name": "Exhaust fan motor failure",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 34,
   "name": "Exhaust fan motor overload",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 35,
   "name": "Rotor drive failure",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 36,
   "name": "Rotor drive overload",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 37,
   "name": "Rotor motor failure",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 38,
   "name": "Rotor motor overload",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 39,
   "name": "Communication error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 40,
   "name": "Controller failure",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 41,
   "name": "Compressor off",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 42,
   "name": "Evaporator icing",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 43,
   "name": "Zone 1 TK100 alarm",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 44,
   "name": "Zone 1 TK70 alarm",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 45,
   "name": "Zone 1 TK60 alarm",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 46,
   "name": "Zone 1 low water temperature",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 47,
   "name": "Zone 1 external stop",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 48,
   "name": "Zone 2 TK100 alarm",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 49,
   "name": "Zone 2 TK70 alarm",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 50,
   "name": "Zone 2 TK60 alarm",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 51,
   "name": "Zone 2 low water temperature",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 52,
   "name": "Zone 2 external stop",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 53,
   "name": "Low heat exchanger efficiency",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 54,
   "name": "Water pump / coil alarm",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 0,
   "name": "Unit On/Off",
   "description": "",
   "units": "",
   "access": "W",
   "states": "0=Off, 1=On"
  },
  {
   "type": "AV",
   "instance": 1,
   "name": "Current mode",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off/Standby, 1=Comfort1, 2=Comfort2, 3=Economy1, 4=Economy2, 5=Special"
  },
  {
   "type": "AV",
   "instance": 2,
   "name": "Mode selection",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Comfort1, 2=Comfort2, 3=Economy1, 4=Economy2, 5=Special, 6=Program"
  },
  {
   "type": "AV",
   "instance": 3,
   "name": "Comfort1 Supply flow",
   "description": "Range 0..200000",
   "units": "m3/h, l/s, m3/s or Pa (per AV 72)",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 4,
   "name": "Comfort1 Extract flow",
   "description": "Range 0..200000",
   "units": "m3/h, l/s, m3/s or Pa (per AV 72)",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 5,
   "name": "Comfort1 Setpoint",
   "description": "Range +5..+40",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 6,
   "name": "Comfort2 Supply flow",
   "description": "Range 0..200000",
   "units": "m3/h, l/s, m3/s or Pa (per AV 72)",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 7,
   "name": "Comfort2 Extract flow",
   "description": "Range 0..200000",
   "units": "m3/h, l/s, m3/s or Pa (per AV 72)",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 8,
   "name": "Comfort2 Setpoint",
   "description": "Range +5..+40",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 9,
   "name": "Economy1 Supply flow",
   "description": "Range 0..200000",
   "units": "m3/h, l/s, m3/s or Pa (per AV 72)",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10,
   "name": "Economy1 Extract flow",
   "description": "Range 0..200000",
   "units": "m3/h, l/s, m3/s or Pa (per AV 72)",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 11,
   "name": "Economy1 Setpoint",
   "description": "Range +5..+40",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 12,
   "name": "Economy2 Supply flow",
   "description": "Range 0..200000",
   "units": "m3/h, l/s, m3/s or Pa (per AV 72)",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 13,
   "name": "Economy2 Extract flow",
   "description": "Range 0..200000",
   "units": "m3/h, l/s, m3/s or Pa (per AV 72)",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 14,
   "name": "Economy2 Setpoint",
   "description": "Range +5..+40",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 15,
   "name": "Special Supply flow",
   "description": "Range 0..200000",
   "units": "m3/h, l/s, m3/s or Pa (per AV 72)",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 16,
   "name": "Special Extract flow",
   "description": "Range 0..200000",
   "units": "m3/h, l/s, m3/s or Pa (per AV 72)",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 17,
   "name": "Special Setpoint",
   "description": "Range +5..+40",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 18,
   "name": "Special mode Heating",
   "description": "",
   "units": "",
   "access": "W",
   "states": "0=Disable, 1=Enable"
  },
  {
   "type": "AV",
   "instance": 19,
   "name": "Special mode Cooling",
   "description": "",
   "units": "",
   "access": "W",
   "states": "0=Disable, 1=Enable"
  },
  {
   "type": "AV",
   "instance": 20,
   "name": "Special mode Recirculation",
   "description": "",
   "units": "",
   "access": "W",
   "states": "0=Disable, 1=Enable"
  },
  {
   "type": "AV",
   "instance": 21,
   "name": "Special mode Humidifying",
   "description": "",
   "units": "",
   "access": "W",
   "states": "0=Disable, 1=Enable"
  },
  {
   "type": "AV",
   "instance": 22,
   "name": "Special mode Dehumidifying",
   "description": "",
   "units": "",
   "access": "W",
   "states": "0=Disable, 1=Enable"
  },
  {
   "type": "AV",
   "instance": 23,
   "name": "Flow control mode",
   "description": "",
   "units": "",
   "access": "W",
   "states": "0=CAV, 1=VAV, 2=DCV"
  },
  {
   "type": "AV",
   "instance": 24,
   "name": "Temp. control mode",
   "description": "",
   "units": "",
   "access": "W",
   "states": "0=Supply, 1=Extract, 2=Room, 3=Balance"
  },
  {
   "type": "AV",
   "instance": 25,
   "name": "AQC Enable",
   "description": "",
   "units": "",
   "access": "W",
   "states": "0=Disable, 1=Enable"
  },
  {
   "type": "AV",
   "instance": 26,
   "name": "AQC Setpoint 1",
   "description": "200-1800 ppm, 10-90 % or 5-45 °C by sensor type",
   "units": "ppm, % or °C (by sensor type)",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 27,
   "name": "AQC Mode 1",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Comfort1, 2=Comfort2, 3=Economy1, 4=Economy2, 5=Special"
  },
  {
   "type": "AV",
   "instance": 28,
   "name": "AQC Setpoint 2",
   "description": "200-1800 ppm, 10-90 % or 5-45 °C by sensor type",
   "units": "ppm, % or °C (by sensor type)",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 29,
   "name": "AQC Mode 2",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Comfort1, 2=Comfort2, 3=Economy1, 4=Economy2, 5=Special"
  },
  {
   "type": "AV",
   "instance": 30,
   "name": "OCV Enable",
   "description": "",
   "units": "",
   "access": "W",
   "states": "0=Disable, 1=Enable"
  },
  {
   "type": "AV",
   "instance": 31,
   "name": "OCV Winter compensation stop",
   "description": "Range -40.0..+50.0",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 32,
   "name": "OCV Winter compensation start",
   "description": "Range -40.0..+50.0",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 33,
   "name": "OCV Summer compensation start",
   "description": "Range -40.0..+50.0",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 34,
   "name": "OCV Summer compensation stop",
   "description": "Range -40.0..+50.0",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 35,
   "name": "MTC Enable",
   "description": "",
   "units": "",
   "access": "W",
   "states": "0=Disable, 1=Enable"
  },
  {
   "type": "AV",
   "instance": 36,
   "name": "MTC Setpoint",
   "description": "Range -40.0..+50.0",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 37,
   "name": "OVR Enable",
   "description": "",
   "units": "",
   "access": "W",
   "states": "0=Disable, 1=Enable"
  },
  {
   "type": "AV",
   "instance": 38,
   "name": "OVR Type",
   "description": "",
   "units": "",
   "access": "W",
   "states": "0=Alltime, 1=If on, 2=If off"
  },
  {
   "type": "AV",
   "instance": 39,
   "name": "OVR Mode",
   "description": "",
   "units": "",
   "access": "W",
   "states": "0=Standby, 1=Comfort1, 2=Comfort2, 3=Economy1, 4=Economy2, 5=Special, 6=Program"
  },
  {
   "type": "AV",
   "instance": 40,
   "name": "SNC Enable",
   "description": "",
   "units": "",
   "access": "W",
   "states": "0=Disable, 1=Enable"
  },
  {
   "type": "AV",
   "instance": 41,
   "name": "SNC Start temperature",
   "description": "Range 15.0..+50.0",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 42,
   "name": "SNC Stop temperature",
   "description": "Range 15.0..+50.0",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 43,
   "name": "OOD Enable",
   "description": "",
   "units": "",
   "access": "W",
   "states": "0=Disable, 1=Enable"
  },
  {
   "type": "AV",
   "instance": 44,
   "name": "OOD Setpoint",
   "description": "200-1800 ppm, 10-90 % or 5-45 °C by sensor type",
   "units": "ppm, % or °C (by sensor type)",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 45,
   "name": "REC Enable",
   "description": "",
   "units": "",
   "access": "W",
   "states": "0=Disable, 1=Enable"
  },
  {
   "type": "AV",
   "instance": 46,
   "name": "REC Setpoint 1",
   "description": "200-1800 ppm, 10-90 % or 5-45 °C by sensor type",
   "units": "ppm, % or °C (by sensor type)",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 47,
   "name": "REC Mode 1",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Comfort1, 2=Comfort2, 3=Economy1, 4=Economy2, 5=Special"
  },
  {
   "type": "AV",
   "instance": 48,
   "name": "REC Setpoint 2",
   "description": "200-1800 ppm, 10-90 % or 5-45 °C by sensor type",
   "units": "ppm, % or °C (by sensor type)",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 49,
   "name": "REC Mode 2",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Comfort1, 2=Comfort2, 3=Economy1, 4=Economy2, 5=Special"
  },
  {
   "type": "AV",
   "instance": 50,
   "name": "REC Min. Fresh Air 1",
   "description": "Range 0..100",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 51,
   "name": "REC Min. Fresh Air 2",
   "description": "Range 0..100",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 52,
   "name": "REC Winter end",
   "description": "Range -40.0..+50.0",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 53,
   "name": "REC Winter start",
   "description": "Range -40.0..+50.0",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 54,
   "name": "REC Summer start",
   "description": "Range -40.0..+50.0",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 55,
   "name": "REC Summer end",
   "description": "Range -40.0..+50.0",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 56,
   "name": "REC Default recirculation",
   "description": "Range 0..100",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 57,
   "name": "REC Activated recirculation",
   "description": "Range 0..100",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 77,
   "name": "HUM Enable",
   "description": "",
   "units": "",
   "access": "W",
   "states": "0=Disable, 1=Enable"
  },
  {
   "type": "AV",
   "instance": 78,
   "name": "HUM Setpoint 1",
   "description": "Range 10..90",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 79,
   "name": "HUM Mode 1",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Comfort1, 2=Comfort2, 3=Economy1, 4=Economy2, 5=Special"
  },
  {
   "type": "AV",
   "instance": 80,
   "name": "HUM Setpoint 2",
   "description": "Range 10..90",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 81,
   "name": "HUM Mode 2",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Comfort1, 2=Comfort2, 3=Economy1, 4=Economy2"
  },
  {
   "type": "AV",
   "instance": 84,
   "name": "CF heatexchanger calibration",
   "description": "Write 1 to start heat exchanger calibration",
   "units": "",
   "access": "W",
   "states": "0=No calibration, 1=Calibrated, 2=Calibrating"
  },
  {
   "type": "AV",
   "instance": 85,
   "name": "HUM mode",
   "description": "",
   "units": "",
   "access": "W",
   "states": "0=Supply, 1=Indoor+Supply, 2=Indoor"
  },
  {
   "type": "AV",
   "instance": 86,
   "name": "HUM Type",
   "description": "",
   "units": "",
   "access": "W",
   "states": "0=RH, 1=AH"
  },
  {
   "type": "AV",
   "instance": 87,
   "name": "HUM Units",
   "description": "",
   "units": "",
   "access": "W",
   "states": "0=g/m3, 1=g/kg"
  },
  {
   "type": "AV",
   "instance": 88,
   "name": "OCV Minimum airflow",
   "description": "Range 20..100",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 89,
   "name": "Water heater: Enable/Disable",
   "description": "",
   "units": "",
   "access": "W",
   "states": "0=Disable, 1=Enable"
  },
  {
   "type": "AV",
   "instance": 90,
   "name": "Water cooler: Enable/Disable",
   "description": "",
   "units": "",
   "access": "W",
   "states": "0=Disable, 1=Enable"
  },
  {
   "type": "AV",
   "instance": 58,
   "name": "Actual alarms reset",
   "description": "Write 1 to reset current alarms",
   "units": "",
   "access": "W",
   "states": "1=Reset current alarm"
  },
  {
   "type": "AV",
   "instance": 59,
   "name": "Air heater operation",
   "description": "Range 0..2^32",
   "units": "hours",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 60,
   "name": "Supply fan operation",
   "description": "Range 0..2^32",
   "units": "hours",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 61,
   "name": "Exhaust fan operation",
   "description": "Range 0..2^32",
   "units": "hours",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 62,
   "name": "Heat exchanger thermal efficiency",
   "description": "Range 1-100; 255 = none",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 63,
   "name": "Heat exchanger recovery",
   "description": "Range 0..2^32",
   "units": "watt",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 64,
   "name": "Thermal energy saving",
   "description": "Range 0..100",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 65,
   "name": "Supply SFP",
   "description": "Range 0..655",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 66,
   "name": "Exhaust SFP",
   "description": "Range 0..655",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 67,
   "name": "Day",
   "description": "Range 1..31",
   "units": "days",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 68,
   "name": "Month",
   "description": "Range 1..12",
   "units": "months",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 69,
   "name": "Year",
   "description": "Range 2000..2250",
   "units": "years",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 70,
   "name": "Hours",
   "description": "Range 0..23",
   "units": "hours",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 71,
   "name": "Minutes",
   "description": "Range 0..59",
   "units": "minutes",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 72,
   "name": "Flow units",
   "description": "",
   "units": "",
   "access": "W",
   "states": "0=m3/h, 1=l/s, 2=m3/s, 3=Pa"
  },
  {
   "type": "AV",
   "instance": 73,
   "name": "External room temperature sensor",
   "description": "Value from BMS; outside range disables override",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 74,
   "name": "Zone 1 setpoint",
   "description": "Range -50.0..+40.0",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 75,
   "name": "Zone 2 setpoint",
   "description": "Range -50.0..+40.0",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 76,
   "name": "Digital input IN4 override",
   "description": "",
   "units": "",
   "access": "W",
   "states": "-1=disabled, 0=heating, 1=cooling, 2=error"
  },
  {
   "type": "AV",
   "instance": 82,
   "name": "Daylight saving time",
   "description": "",
   "units": "",
   "access": "W",
   "states": "0=Disable, 1=Enable"
  },
  {
   "type": "AV",
   "instance": 83,
   "name": "BACnet Broadcast Management Device",
   "description": "",
   "units": "",
   "access": "W",
   "states": "0=Disable, 1=Enable"
  }
 ],
 "page": "https://easybacnet.com/bacnet-points-lists/komfovent/c5-controller",
 "note": "Provided as-is. Point availability varies by firmware and options; verify against the live device.",
 "disclaimer": "DISCLAIMER: reference only, provided AS IS with no warranty. May contain errors or be out of date. You must verify every point against the manufacturer's current documentation and the live device before use. easybacnet.com accepts no liability for its use and is not affiliated with the manufacturer. Terms: https://easybacnet.com/terms#content"
}