 "manufacturer": "Komfovent",
 "manufacturer_slug": "komfovent",
 "model": "C6 / C6M controller",
 "model_slug": "c6-controller",
 "aliases": [
  "Komfovent C6",
  "Komfovent C6M",
  "C6M",
  "C6.1",
  "BACnet-C6"
 ],
 "equipment_type": "Air handling unit controller",
 "applies_to": "Komfovent air handling units fitted with the C6 / C6M controller.",
 "summary": "The Komfovent C6 / C6M controller exposes its settings and readings over BACnet IP on its RJ-45 Ethernet port (no MS/TP). The list has 154 objects: temperatures and setpoints as AVs, on/off, enables and alarms as BVs, modes and settings as multistate values, and flows, timers and energy figures as positive integer values. Two date values hold the holiday period, and a time value gives the next scheduled mode change.",
 "bacnet_transport": [
  "BACnet IP"
 ],
 "firmware": null,
 "default_device_instance": 60,
 "access_inferred": false,
 "notes": [
  "The two Date Value objects (HOLIDAYS: from / till, instances 0-1) are listed with type Other. The doc also has a Time Value object 0, SCHEDULER: next mode start time (read-only, 00:00-24:00), left out here because it would clash with Other 0.",
  "Mode-specific setpoints, flows and heating flags exist for each mode (away, normal, intensive, boost, kitchen, fireplace, override, holidays).",
  "Flows are in m3/h or l/s as set by MV 12 SETTINGS: flow units; the away, normal, intensive and boost flows also list Pa as a unit.",
  "The same document covers both the C6 and the C6M controller boards."
 ],
 "source": {
  "title": "BACnet Connection C6 / C6M - Installation and Service Manual",
  "doc_number": "BACnet-C6_26-08",
  "revision_date": "2026-08",
  "url": "https://komfovent.com/en/downloads/Bacnet_connection_C6_EN.pdf"
 },
 "integration": {
  "summary": "Switch the unit with BV 0 CONTROL: ON/OFF status and select the mode with MV 1 CONTROL: current mode (only away, normal, intensive and boost can be written). Each mode has its own temperature setpoint AV and supply/extract flow PIVs. Read the INFO temperatures and flows, the ALARMS BVs and the active alarm count; writing 39366 to that count resets alarms.",
  "minimum_points": [
   {
    "ref": "BV 0",
    "name": "CONTROL: ON/OFF status",
    "why": "On/off command (1 = on)"
   },
   {
    "ref": "MV 1",
    "name": "CONTROL: current mode",
    "why": "Mode command; writable values 2-5 (away to boost)"
   },
   {
    "ref": "AV 1",
    "name": "NORMAL: setpoint",
    "why": "Temperature setpoint for NORMAL mode"
   },
   {
    "ref": "AV 11",
    "name": "INFO: supply temperature",
    "why": "Supply air temperature"
   },
   {
    "ref": "AV 12",
    "name": "INFO: extract temperature",
    "why": "Extract air temperature"
   },
   {
    "ref": "AV 13",
    "name": "INFO: outdoor temperature",
    "why": "Outdoor air temperature"
   },
   {
    "ref": "PIV 30",
    "name": "INFO: current supply flow",
    "why": "Supply air flow, m3/h or l/s"
   },
   {
    "ref": "BV 32",
    "name": "INFO: alarm",
    "why": "Any active alarm"
   },
   {
    "ref": "PIV 28",
    "name": "ALARMS: active alarms count",
    "why": "Active alarms (0-10); write 39366 to reset"
   }
  ],
  "enable": "BV 0 CONTROL: ON/OFF status turns the unit on (1) or off (0). BV 2 CONTROL: AUTO mode hands mode selection to the schedule or air quality control (MV 0 shows which).",
  "heartbeat": null,
  "remote_sensors": null,
  "setup": [
   "Factory network settings: DHCP off, IP 192.168.0.60, mask 255.255.255.0, gateway 192.168.0.1, BACnet ID 60.",
   "Change them in the controller web server (Connectivity) or on the C6.1 panel (Advanced settings > Connectivity).",
   "Komfovent recommends a polling interval of at least 1 second."
  ],
  "gotchas": [
   "MV 1 CONTROL: current mode accepts only values 2-5 (away, normal, intensive, boost) as writes.",
   "Writing 39366 to the ALARMS: active alarms count PIV resets alarms.",
   "CONNECTIVITY IP address and mask PIVs are writable; a wrong write can drop the controller off the network.",
   "The RESET SETTINGS multistate value restores factory settings for the chosen group; keep it out of normal BMS writes."
  ]
 },
 "points": [
  {
   "type": "AV",
   "instance": 0,
   "name": "AWAY: setpoint",
   "description": "Range 5.0 – 40.0",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1,
   "name": "NORMAL: setpoint",
   "description": "Range 5.0 – 40.0",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2,
   "name": "INTENSIVE: setpoint",
   "description": "Range 5.0 – 40.0",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3,
   "name": "BOOST: setpoint",
   "description": "Range 5.0 – 40.0",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 4,
   "name": "KITCHEN: setpoint",
   "description": "Range 5.0 – 40.0",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 5,
   "name": "FIREPLACE: setpoint",
   "description": "Range 5.0 – 40.0",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 6,
   "name": "OVERRIDE: setpoint",
   "description": "Range 5.0 – 40.0",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 7,
   "name": "HOLIDAYS: setpoint",
   "description": "Range 5.0 – 40.0",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 8,
   "name": "ECO: minimum supply air temperature",
   "description": "Range 5.0 – 40.0",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 9,
   "name": "ECO: maximum supply air temperature",
   "description": "Range 5.0 – 40.0",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10,
   "name": "AIR QUALITY: temperature setpoint",
   "description": "Range 5.0 – 40.0",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 11,
   "name": "INFO: supply temperature",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 12,
   "name": "INFO: extract temperature",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 13,
   "name": "INFO: outdoor temperature",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 14,
   "name": "INFO: water temperature",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 15,
   "name": "INFO: panel 1 temperature",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 16,
   "name": "INFO: panel 2 temperature",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 17,
   "name": "INFO: current supply fan intensivity",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 18,
   "name": "INFO: current extract fan intensivity",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 19,
   "name": "INFO: heat exchanger",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 20,
   "name": "INFO: electric heater",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 21,
   "name": "INFO: water heater",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 22,
   "name": "INFO: water cooler",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 23,
   "name": "INFO: DX unit",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 24,
   "name": "EFFICIENCY/STATUS: SPI",
   "description": "",
   "units": "W/(m3/h)",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 25,
   "name": "EFFICIENCY/STATUS: SPI (day)",
   "description": "",
   "units": "W/(m3/h)",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 26,
   "name": "THERMOSTAT 1: Temperature",
   "description": "Range 5.0 – 40.0",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 27,
   "name": "THERMOSTAT 1: Hysteresis",
   "description": "Range 0.1 – 5.0",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 28,
   "name": "THERMOSTAT 2: Temperature",
   "description": "Range 5.0 – 40.0",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 29,
   "name": "THERMOSTAT 2: Hysteresis",
   "description": "Range 0.1 – 5.0",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 0,
   "name": "CONTROL: ON/OFF status",
   "description": "",
   "units": "",
   "access": "W",
   "states": "0=off, 1=on"
  },
  {
   "type": "BV",
   "instance": 1,
   "name": "CONTROL: ECO mode",
   "description": "",
   "units": "",
   "access": "W",
   "states": "0=off, 1=on"
  },
  {
   "type": "BV",
   "instance": 2,
   "name": "CONTROL: AUTO mode",
   "description": "",
   "units": "",
   "access": "W",
   "states": "0=off, 1=on"
  },
  {
   "type": "BV",
   "instance": 3,
   "name": "AWAY: heating",
   "description": "",
   "units": "",
   "access": "W",
   "states": "0=off, 1=on"
  },
  {
   "type": "BV",
   "instance": 4,
   "name": "NORMAL: heating",
   "description": "",
   "units": "",
   "access": "W",
   "states": "0=off, 1=on"
  },
  {
   "type": "BV",
   "instance": 5,
   "name": "INTENSIVE: heating",
   "description": "",
   "units": "",
   "access": "W",
   "states": "0=off, 1=on"
  },
  {
   "type": "BV",
   "instance": 6,
   "name": "BOOST: heating",
   "description": "",
   "units": "",
   "access": "W",
   "states": "0=off, 1=on"
  },
  {
   "type": "BV",
   "instance": 7,
   "name": "KITCHEN: heating",
   "description": "",
   "units": "",
   "access": "W",
   "states": "0=off, 1=on"
  },
  {
   "type": "BV",
   "instance": 8,
   "name": "FIREPLACE: heating",
   "description": "",
   "units": "",
   "access": "W",
   "states": "0=off, 1=on"
  },
  {
   "type": "BV",
   "instance": 9,
   "name": "OVERRIDE: heating",
   "description": "",
   "units": "",
   "access": "W",
   "states": "0=off, 1=on"
  },
  {
   "type": "BV",
   "instance": 10,
   "name": "HOLIDAYS: heating",
   "description": "",
   "units": "",
   "access": "W",
   "states": "0=off, 1=on"
  },
  {
   "type": "BV",
   "instance": 11,
   "name": "ECO: free heating/cooling",
   "description": "",
   "units": "",
   "access": "W",
   "states": "0=off, 1=on"
  },
  {
   "type": "BV",
   "instance": 12,
   "name": "ECO: heating enable denied",
   "description": "",
   "units": "",
   "access": "W",
   "states": "0=off, 1=on"
  },
  {
   "type": "BV",
   "instance": 13,
   "name": "ECO: cooling enable denied",
   "description": "",
   "units": "",
   "access": "W",
   "states": "0=off, 1=on"
  },
  {
   "type": "BV",
   "instance": 14,
   "name": "AIR QUALITY: enabled",
   "description": "",
   "units": "",
   "access": "W",
   "states": "0=disabled, 1=enabled"
  },
  {
   "type": "BV",
   "instance": 15,
   "name": "AIR QUALITY: heating",
   "description": "",
   "units": "",
   "access": "W",
   "states": "0=off, 1=on"
  },
  {
   "type": "BV",
   "instance": 16,
   "name": "ALARMS: low supply air flow",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=no, 1=yes"
  },
  {
   "type": "BV",
   "instance": 17,
   "name": "ALARMS: low extract air flow",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=no, 1=yes"
  },
  {
   "type": "BV",
   "instance": 18,
   "name": "ALARMS: return water temperature low",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=no, 1=yes"
  },
  {
   "type": "BV",
   "instance": 19,
   "name": "ALARMS: low supply air temperature",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=no, 1=yes"
  },
  {
   "type": "BV",
   "instance": 20,
   "name": "ALARMS: high supply air temperature",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=no, 1=yes"
  },
  {
   "type": "BV",
   "instance": 21,
   "name": "ALARMS: electric heater overheat",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=no, 1=yes"
  },
  {
   "type": "BV",
   "instance": 22,
   "name": "ALARMS: heat exchanger failure",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=no, 1=yes"
  },
  {
   "type": "BV",
   "instance": 23,
   "name": "ALARMS: heat exchanger icing",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=no, 1=yes"
  },
  {
   "type": "BV",
   "instance": 24,
   "name": "ALARMS: internal fire alarm",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=no, 1=yes"
  },
  {
   "type": "BV",
   "instance": 25,
   "name": "ALARMS: external fire alarm",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=no, 1=yes"
  },
  {
   "type": "BV",
   "instance": 26,
   "name": "ALARMS: temperature sensor failure",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=no, 1=yes"
  },
  {
   "type": "BV",
   "instance": 27,
   "name": "ALARMS: controller failure",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=no, 1=yes"
  },
  {
   "type": "BV",
   "instance": 28,
   "name": "ALARMS: service mode",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=no, 1=yes"
  },
  {
   "type": "BV",
   "instance": 29,
   "name": "ALARMS: clogged air filters",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=no, 1=yes"
  },
  {
   "type": "BV",
   "instance": 30,
   "name": "ALARMS: heat exchanger low efficiency",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=no, 1=yes"
  },
  {
   "type": "BV",
   "instance": 31,
   "name": "ALARMS: air flow sensor failure",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=no, 1=yes"
  },
  {
   "type": "BV",
   "instance": 32,
   "name": "INFO: alarm",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=off, 1=on"
  },
  {
   "type": "BV",
   "instance": 33,
   "name": "INFO: heating",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=off, 1=on"
  },
  {
   "type": "BV",
   "instance": 34,
   "name": "INFO: cooling",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=off, 1=on"
  },
  {
   "type": "BV",
   "instance": 35,
   "name": "CLEAN FILTERS CALIBRATION",
   "description": "",
   "units": "",
   "access": "W",
   "states": "0=no, 1=yes"
  },
  {
   "type": "BV",
   "instance": 36,
   "name": "THERMOSTAT 1: Enable",
   "description": "",
   "units": "",
   "access": "W",
   "states": "0=no, 1=yes"
  },
  {
   "type": "BV",
   "instance": 37,
   "name": "THERMOSTAT 2: Enable",
   "description": "",
   "units": "",
   "access": "W",
   "states": "0=no, 1=yes"
  },
  {
   "type": "BV",
   "instance": 38,
   "name": "ALARMS: humidity sensor failure",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=no, 1=yes"
  },
  {
   "type": "BV",
   "instance": 39,
   "name": "ALARMS: communication error",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=no, 1=yes"
  },
  {
   "type": "BV",
   "instance": 40,
   "name": "ALARMS: supply fan failure",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=no, 1=yes"
  },
  {
   "type": "BV",
   "instance": 41,
   "name": "ALARMS: exhaust fan failure",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=no, 1=yes"
  },
  {
   "type": "Other",
   "instance": 0,
   "name": "HOLIDAYS: from",
   "description": "BACnet Date Value object; 2017-01-01 – 2035-12-31",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "Other",
   "instance": 1,
   "name": "HOLIDAYS: till",
   "description": "BACnet Date Value object; 2017-01-01 – 2035-12-31",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 0,
   "name": "CONTROL: auto mode control",
   "description": "",
   "units": "",
   "access": "R",
   "states": "1=scheduling, 2=air quality"
  },
  {
   "type": "MV",
   "instance": 1,
   "name": "CONTROL: current mode",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=standby, 2=away, 3=normal, 4=intensive, 5=boost, 6=kitchen, 7=fireplace, 8=override, 9=holiday, 10=auto, 11=off"
  },
  {
   "type": "MV",
   "instance": 2,
   "name": "SCHEDULER: operation program",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=stay at home, 2=working week, 3=office, 4=custom"
  },
  {
   "type": "MV",
   "instance": 3,
   "name": "SCHEDULER: next mode",
   "description": "",
   "units": "",
   "access": "R",
   "states": "1=standby, 2=away, 3=normal, 4=intensive, 5=boost"
  },
  {
   "type": "MV",
   "instance": 4,
   "name": "SCHEDULER: next mode weekday",
   "description": "",
   "units": "",
   "access": "R",
   "states": "1=today, 2=mo, 3=tu, 4=we, 5=th, 6=fr, 7=sa, 8=su"
  },
  {
   "type": "MV",
   "instance": 5,
   "name": "CONTROL: temperature control",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=supply, 2=extract, 3=room, 4=balance"
  },
  {
   "type": "MV",
   "instance": 6,
   "name": "CONTROL: flow control",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=CAV, 2=VAV, 3=DCV"
  },
  {
   "type": "MV",
   "instance": 7,
   "name": "CONTROL SEQEUENCE: stage 1",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=none, 2=external coil, 3=electric heater, 4=external DX unit"
  },
  {
   "type": "MV",
   "instance": 8,
   "name": "CONTROL SEQEUENCE: stage 2",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=none, 2=external coil, 3=electric heater, 4=external DX unit"
  },
  {
   "type": "MV",
   "instance": 9,
   "name": "CONTROL SEQEUENCE: stage 3",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=none, 2=external coil, 3=electric heater, 4=external DX unit"
  },
  {
   "type": "MV",
   "instance": 10,
   "name": "SETTINGS: coil type",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=hot water, 2=cold water"
  },
  {
   "type": "MV",
   "instance": 11,
   "name": "SETTINGS: language",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=en, 2=lt, 3=ru, 4=pl, 5=sk, 6=de, 7=fr, 8=hu, 9=it, 10=ee, 11=nl, 12=lv, 13=pt, 14=se, 15=fi, 16=hr"
  },
  {
   "type": "MV",
   "instance": 12,
   "name": "SETTINGS: flow units",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=m3/h, 2=l/s"
  },
  {
   "type": "MV",
   "instance": 13,
   "name": "OVERRIDE: mode",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=all time, 2=if on, 3=if off"
  },
  {
   "type": "MV",
   "instance": 14,
   "name": "HOLIDAYS: microventilation",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=1 t. per day, 2=2 t. per day, 3=3 t. per day, 4=4 t. per day"
  },
  {
   "type": "MV",
   "instance": 15,
   "name": "AIR QUALITY: sensor type B8",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=none, 2=CO2, 3=VOC, 4=RH"
  },
  {
   "type": "MV",
   "instance": 16,
   "name": "AIR QUALITY: sensor type B9",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=none, 2=CO2, 3=VOC, 4=RH"
  },
  {
   "type": "MV",
   "instance": 17,
   "name": "RESET SETTINGS",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=none, 2=\"away\", 3=\"normal\", 4=\"intensive\", 5=\"boost\", 6=\"holidays\", 7=\"override\", 8=\"kitchen\", 9=\"fireplace\", 10=air quality, 11=eco, 12=advanced"
  },
  {
   "type": "MV",
   "instance": 18,
   "name": "ECO: heat recovery control",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Auto, 2=Constant, 3=Non stop"
  },
  {
   "type": "MV",
   "instance": 19,
   "name": "THERMOSTAT 1: output",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Heating, 2=Cooling"
  },
  {
   "type": "MV",
   "instance": 20,
   "name": "THERMOSTAT 1: output type",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=NO, 2=NC"
  },
  {
   "type": "MV",
   "instance": 21,
   "name": "THERMOSTAT 2: output",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Heating, 2=Cooling"
  },
  {
   "type": "MV",
   "instance": 22,
   "name": "THERMOSTAT 2: output type",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=NO, 2=NC"
  },
  {
   "type": "PIV",
   "instance": 0,
   "name": "CONTROL: maximum supply flow",
   "description": "",
   "units": "m3/h, l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 1,
   "name": "CONTROL: maximum extract flow",
   "description": "",
   "units": "m3/h, l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 2,
   "name": "CONTROL: maximum supply pressure",
   "description": "Range 0 – 1000",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 3,
   "name": "CONTROL: maximum extract pressure",
   "description": "Range 0 – 1000",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 4,
   "name": "CONNECTIVITY: IP address",
   "description": "Range 0 – 4294967295",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 5,
   "name": "CONNECTIVITY: mask",
   "description": "Range 0 – 4294967295",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 6,
   "name": "AWAY: supply flow",
   "description": "Range 0.2×max – max",
   "units": "m3/h, l/s, Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 7,
   "name": "AWAY: extract flow",
   "description": "Range 0.2×max – max",
   "units": "m3/h, l/s, Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 8,
   "name": "NORMAL: supply flow",
   "description": "Range 0.2×max – max",
   "units": "m3/h, l/s, Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 9,
   "name": "NORMAL: extract flow",
   "description": "Range 0.2×max – max",
   "units": "m3/h, l/s, Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 10,
   "name": "INTENSIVE: supply flow",
   "description": "Range 0.2×max – max",
   "units": "m3/h, l/s, Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 11,
   "name": "INTENSIVE: extract flow",
   "description": "Range 0.2×max – max",
   "units": "m3/h, l/s, Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 12,
   "name": "BOOST: supply flow",
   "description": "Range 0.2×max – max",
   "units": "m3/h, l/s, Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 13,
   "name": "BOOST: extract flow",
   "description": "Range 0.2×max – max",
   "units": "m3/h, l/s, Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 14,
   "name": "KITCHEN: supply flow",
   "description": "Range 0.2×max – max",
   "units": "m3/h, l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 15,
   "name": "KITCHEN: extract flow",
   "description": "Range 0.2×max – max",
   "units": "m3/h, l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 16,
   "name": "FIREPLACE: supply flow",
   "description": "Range 0.2×max – max",
   "units": "m3/h, l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 17,
   "name": "FIREPLACE: extract flow",
   "description": "Range 0.2×max – max",
   "units": "m3/h, l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 18,
   "name": "OVERRIDE: supply flow",
   "description": "Range 0.2×max – max",
   "units": "m3/h, l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 19,
   "name": "OVERRIDE: extract flow",
   "description": "Range 0.2×max – max",
   "units": "m3/h, l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 20,
   "name": "KITCHEN: timer",
   "description": "Range 0 – 300",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 21,
   "name": "FIREPLACE: timer",
   "description": "Range 0 – 300",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 22,
   "name": "OVERRIDE: timer",
   "description": "Range 0 – 300",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 23,
   "name": "AIR QUALITY: air quality setpoint",
   "description": "0-2000 ppm or 0-100 %",
   "units": "ppm, %",
   "access": "W",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 24,
   "name": "AIR QUALITY: humidity setpoint",
   "description": "Range 0 – 100",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 25,
   "name": "AIR QUALITY: minimum intensivity",
   "description": "Range 0, 20 – 100",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 26,
   "name": "AIR QUALITY: maximum intensivity",
   "description": "Range 0, 20 – 100",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 27,
   "name": "AIR QUALITY: check period",
   "description": "Range 1 – 24",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 28,
   "name": "ALARMS: active alarms count",
   "description": "Range 0-10; write 39366 to reset alarms",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 29,
   "name": "ALARMS: alarm history count",
   "description": "Range 0 – 50",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 30,
   "name": "INFO: current supply flow",
   "description": "",
   "units": "m3/h, l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 31,
   "name": "INFO: current extract flow",
   "description": "",
   "units": "m3/h, l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 32,
   "name": "INFO: filters impurity",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 33,
   "name": "INFO: air dampers",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 34,
   "name": "INFO: supply pressure",
   "description": "",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 35,
   "name": "INFO: extract pressure",
   "description": "",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 36,
   "name": "INFO: air quality/humidity sensor 1",
   "description": "",
   "units": "ppm, %",
   "access": "R",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 37,
   "name": "INFO: air quality/humidity sensor 2",
   "description": "",
   "units": "ppm, %",
   "access": "R",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 38,
   "name": "INFO: panel 1 humidity",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 39,
   "name": "INFO: panel 2 humidity",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 40,
   "name": "INFO: panel 1 air quality",
   "description": "",
   "units": "ppm",
   "access": "R",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 41,
   "name": "INFO: panel 2 air quality",
   "description": "",
   "units": "ppm",
   "access": "R",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 42,
   "name": "EFFICIENCY/STATUS: power consumption",
   "description": "",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 43,
   "name": "EFFICIENCY/STATUS: heater power",
   "description": "",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 44,
   "name": "EFFICIENCY/STATUS: heat exchanger recovery",
   "description": "",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 45,
   "name": "EFFICIENCY/STATUS: heat exchanger efficiency",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 46,
   "name": "EFFICIENCY/STATUS: energy saving",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 47,
   "name": "EFFICIENCY/STATUS: recovered energy (day)",
   "description": "",
   "units": "Wh",
   "access": "R",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 48,
   "name": "EFFICIENCY/STATUS: recovered energy (month)",
   "description": "",
   "units": "Wh",
   "access": "R",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 49,
   "name": "EFFICIENCY/STATUS: recovered energy (total)",
   "description": "",
   "units": "Wh",
   "access": "R",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 50,
   "name": "CONSUMPTION: AHU (day)",
   "description": "",
   "units": "Wh",
   "access": "R",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 51,
   "name": "CONSUMPTION: AHU (month)",
   "description": "",
   "units": "Wh",
   "access": "R",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 52,
   "name": "CONSUMPTION: AHU (total)",
   "description": "",
   "units": "Wh",
   "access": "R",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 53,
   "name": "CONSUMPTION: add. air heater (day)",
   "description": "",
   "units": "Wh",
   "access": "R",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 54,
   "name": "CONSUMPTION: add. air heater (month)",
   "description": "",
   "units": "Wh",
   "access": "R",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 55,
   "name": "CONSUMPTION: add. air heater (total)",
   "description": "",
   "units": "Wh",
   "access": "R",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 56,
   "name": "INFO: extract humidity",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  }
 ],
 "page": "https://easybacnet.com/bacnet-points-lists/komfovent/c6-controller",
 "note": "Provided as-is. Point availability varies by firmware and options; verify against the live device.",
 "disclaimer": "DISCLAIMER: reference only, provided AS IS with no warranty. May contain errors or be out of date. You must verify every point against the manufacturer's current documentation and the live device before use. easybacnet.com accepts no liability for its use and is not affiliated with the manufacturer. Terms: https://easybacnet.com/terms#content"
}