Thermal dispersion airflow measuring station · BACnet points list

EBTRON Silver Series STN104 Airflow / Temperature Transmitter (RS-485 network version) BACnet points list

Updated 7 November 2026

Short answer

The STN104 is the RS-485 network version of the EBTRON Silver Series STx104 transmitter. On BACnet MS/TP it reports airflow, differential pressure and temperature as analog inputs, with writable analog values for the duct free area and the baud rate.

This page lists 5 BACnet objects for the EBTRON Silver Series STN104 Airflow / Temperature Transmitter (RS-485 network version) — 2 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from EBTRON’s own free documentation, linked below.

Manufacturer
EBTRON
Model
Silver Series STN104 Airflow / Temperature Transmitter (RS-485 network version)
Equipment
Thermal dispersion airflow measuring station
Equipment type
Thermostats, sensors & meters
BACnet objects
5 (2 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Also known as
STN104, STx104, Silver Series STx104, TM_STx104
Source document
Silver Series STx104 Transmitter - Installation, Operation and Maintenance Technical Manual · TM_STx104_R3A
Download CSV 5 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against EBTRON’s current documentation and the live device before use. Not official EBTRON information. Terms of use.

BMS integration notes: EBTRON Silver Series STN104 Airflow / Temperature Transmitter (RS-485 network version)

Integration in brief

Read airflow (AI 0), temperature (AI 2) and differential pressure (AI 1). Write the duct free area to AV 0 so airflow in CFM or LPS is right.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AI 0AirflowAirflow (FPM, CFM, MPS or LPS)Read
AI 2TemperatureAir temperatureRead
AI 1PressureDifferential pressure (in. H2O or Pa)Read

Network setup

EBTRON Silver Series STN104 Airflow / Temperature Transmitter (RS-485 network version) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

5 of 5 shown
Type
Access
Show
EBTRON Silver Series STN104 Airflow / Temperature Transmitter (RS-485 network version) BACnet Points List
DescriptionStates
AImin0AirflowUnits FPM, CFM, MPS or LPSfpmRead
AImin1PressureDifferential pressure; units in. H2O or PainH2ORead
AImin2Temperature°C or °F°FRead
AV0Free AreaDuct free area, sq.ft.ft²Write
AV1Baud RateMS/TP baud: 9.6, 19.2, 38.4 or 76.8 kbpsWrite
Object ID lookup: EBTRON Silver Series STN104 Airflow / Temperature Transmitter point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Silver Series STN104 Airflow / Temperature Transmitter (RS-485 network version) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the EBTRON Silver Series STN104 Airflow / Temperature Transmitter (RS-485 network version)

How many BACnet points does the EBTRON Silver Series STN104 Airflow / Temperature Transmitter (RS-485 network version) have?

This list has 5 BACnet objects: 3 analog inputs, 2 analog values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which EBTRON Silver Series STN104 Airflow / Temperature Transmitter (RS-485 network version) BACnet points are writable?

2 of the 5 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official EBTRON Silver Series STN104 Airflow / Temperature Transmitter (RS-485 network version) BACnet documentation?

The source is Silver Series STx104 Transmitter - Installation, Operation and Maintenance Technical Manual (TM_STx104_R3A), published free by EBTRON at https://ebtron.com/wp-content/uploads/TM_STx104.pdf.

What are the minimum BACnet points to integrate the EBTRON Silver Series STN104 Airflow / Temperature Transmitter (RS-485 network version)?

Start with AI 0 Airflow (Airflow (FPM, CFM, MPS or LPS)); AI 2 Temperature (Air temperature); AI 1 Pressure (Differential pressure (in. H2O or Pa)).

How do I check these points on the real Silver Series STN104 Airflow / Temperature Transmitter (RS-485 network version)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More EBTRON BACnet points lists

Source: Silver Series STx104 Transmitter - Installation, Operation and Maintenance Technical Manual · TM_STx104_R3A. Object names, instances and units are reproduced as published; descriptions are our own.