Easy BACnet
  1. Home
  2. BACnet points lists
  3. EBTRON
  4. IAQ-N100 wall-mount IAQ sensor

Room air quality sensor · BACnet points list

EBTRON IAQ-N100 wall-mount IAQ sensor BACnet points list

Updated 4 November 2026

Short answer

The IAQ-N100 is an EBTRON wall-mount room sensor for CO2 with an RS-485 port that runs BACnet MS/TP (or Modbus RTU when set by DIP switch). Its BACnet objects are a few Analog Inputs for the measurements plus Analog and Binary Values for elevation, sampling, baud rate and calibration.

This page lists 10 BACnet objects for the EBTRON IAQ-N100 wall-mount IAQ sensor — 9 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from EBTRON’s own free documentation, linked below.

Manufacturer
EBTRON
Model
IAQ-N100 wall-mount IAQ sensor
Equipment
Room air quality sensor
Equipment type
Thermostats, sensors & meters
BACnet objects
10 (9 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Default device instance
2
Also known as
IAQ-N100, IAQN100, IAQ-N100-W, IAQ-Ny00-W
Source document
IAQ-Ny00-W Quick Installation Guide - Wall Mount Indoor Air Quality Sensors with RS-485 Network Output (Appendix A) · IG_IAQ-Ny00-W_R1B · rev. 2016-05-12
Download CSV 10 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against EBTRON’s current documentation and the live device before use. Not official EBTRON information. Terms of use.

BMS integration notes: EBTRON IAQ-N100 wall-mount IAQ sensor

Integration in brief

Set the MS/TP MAC address and baud rate on DIP switch SW1 before power-up, then read the measurement AIs. The AVs and BVs are only for calibration and setup.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AI 1CO2 PPMSpace CO2, ppmRead

Network setup

Watch out for

EBTRON IAQ-N100 wall-mount IAQ sensor BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

10 of 10 shown
Type
Binary
Access
Show
EBTRON IAQ-N100 wall-mount IAQ sensor BACnet Points List
DescriptionStates
AImin1CO2 PPMPresent CO2 concentrationppmRead
AI2Lowest PPMLowest CO2 in the past 24 h; any write resets itppmWrite
AV1ElevationInstalled elevation above sea level (default 0)ftWrite
AV2CO2 Sample RateCO2 sampling interval, 1-600 s (default 10)sWrite
AV3Baud RateMS/TP baud rate (default 76800)Write
AV4Single Point PPMSingle-point CO2 calibration value; -1/-2/-3 report the resultppmWrite
AV5ABC Logic StatusABC automatic background calibration, 1 = on, 0 = offWrite
AV6CO2 GainGain applied to the raw CO2 reading (default 1)Write
AV7CO2 OffsetOffset applied to the raw CO2 reading (default 0)Write
BV1Factory CO2 Gain/Offset StatusActive = use the factory CO2 gain/offset calibrationWrite0=Inactive; 1=Active
Object ID lookup: EBTRON IAQ-N100 wall-mount IAQ sensor point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the IAQ-N100 wall-mount IAQ sensor and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the EBTRON IAQ-N100 wall-mount IAQ sensor

How many BACnet points does the EBTRON IAQ-N100 wall-mount IAQ sensor have?

This list has 10 BACnet objects: 2 analog inputs, 7 analog values, 1 binary value. The exact set on a given unit depends on its firmware, installed options and configuration.

Which EBTRON IAQ-N100 wall-mount IAQ sensor BACnet points are writable?

9 of the 10 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official EBTRON IAQ-N100 wall-mount IAQ sensor BACnet documentation?

The source is IAQ-Ny00-W Quick Installation Guide - Wall Mount Indoor Air Quality Sensors with RS-485 Network Output (Appendix A) (IG_IAQ-Ny00-W_R1B), revision 2016-05-12, published free by EBTRON at https://ebtron.com/wp-content/uploads/documents/IG_IAQ-Ny00-W.pdf.

What are the minimum BACnet points to integrate the EBTRON IAQ-N100 wall-mount IAQ sensor?

Start with AI 1 CO2 PPM (Space CO2, ppm).

How do I check these points on the real IAQ-N100 wall-mount IAQ sensor?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More EBTRON BACnet points lists

Source: IAQ-Ny00-W Quick Installation Guide - Wall Mount Indoor Air Quality Sensors with RS-485 Network Output (Appendix A) · IG_IAQ-Ny00-W_R1B · rev. 2016-05-12. Object names, instances and units are reproduced as published; descriptions are our own.