Room air quality sensor · BACnet points list

EBTRON IAQ-N300 wall-mount IAQ sensor BACnet points list

Updated 4 November 2026

Short answer

The IAQ-N300 is an EBTRON wall-mount room sensor for CO2, relative humidity and temperature with an RS-485 port that runs BACnet MS/TP (or Modbus RTU when set by DIP switch). Its BACnet objects are a few Analog Inputs for the measurements plus Analog and Binary Values for elevation, sampling, baud rate and calibration.

This page lists 18 BACnet objects for the EBTRON IAQ-N300 wall-mount IAQ sensor — 15 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from EBTRON’s own free documentation, linked below.

Manufacturer
EBTRON
Model
IAQ-N300 wall-mount IAQ sensor
Equipment
Room air quality sensor
Equipment type
Thermostats, sensors & meters
BACnet objects
18 (15 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Default device instance
2
Also known as
IAQ-N300, IAQN300, IAQ-N300-W, IAQ-Ny00-W
Source document
IAQ-Ny00-W Quick Installation Guide - Wall Mount Indoor Air Quality Sensors with RS-485 Network Output (Appendix A) · IG_IAQ-Ny00-W_R1B · rev. 2016-05-12
Download CSV 18 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against EBTRON’s current documentation and the live device before use. Not official EBTRON information. Terms of use.

BMS integration notes: EBTRON IAQ-N300 wall-mount IAQ sensor

Integration in brief

Set the MS/TP MAC address and baud rate on DIP switch SW1 before power-up, then read the measurement AIs. The AVs and BVs are only for calibration and setup.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AI 1CO2 PPMSpace CO2, ppmRead
AI 2RHSpace relative humidity, %Read
AI 3TemperatureSpace temperature (°F unless set to °C)Read

Network setup

Watch out for

EBTRON IAQ-N300 wall-mount IAQ sensor BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

18 of 18 shown
Type
Binary
Access
Show
EBTRON IAQ-N300 wall-mount IAQ sensor BACnet Points List
DescriptionStates
AImin1CO2 PPMPresent CO2 concentrationppmRead
AImin2RHPresent relative humidity%Read
AImin3TemperaturePresent room temperature (°F, can be set to °C)°FRead
AI4Lowest PPMLowest CO2 in the past 24 h; any write resets itppmWrite
AV1ElevationInstalled elevation above sea level (default 0)ftWrite
AV2CO2 Sample RateCO2 sampling interval, 1-600 s (default 10)sWrite
AV3Baud RateMS/TP baud rate (default 76800)Write
AV4Single Point PPMSingle-point CO2 calibration value; -1/-2/-3 report the resultppmWrite
AV5ABC Logic StatusABC automatic background calibration, 1 = on, 0 = offWrite
AV6CO2 GainGain applied to the raw CO2 reading (default 1)Write
AV7Relative Humidity GainGain applied to the raw humidity reading (default 1)Write
AV8Temperature GainGain applied to the raw temperature reading (default 1)Write
AV9CO2 OffsetOffset applied to the raw CO2 reading (default 0)Write
AV10Relative Humidity OffsetOffset applied to the raw humidity reading (default 0)Write
AV11Temperature OffsetOffset applied to the raw temperature reading (default 0)Write
BV1Factory CO2 Gain/Offset StatusActive = use the factory CO2 gain/offset calibrationWrite0=Inactive; 1=Active
BV2Factory Relative Humidity Gain/Offset StatusActive = use the factory humidity gain/offset calibrationWrite0=Inactive; 1=Active
BV3Factory Temperature Gain/Offset StatusActive = use the factory temperature gain/offset calibrationWrite0=Inactive; 1=Active
Object ID lookup: EBTRON IAQ-N300 wall-mount IAQ sensor point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the IAQ-N300 wall-mount IAQ sensor and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the EBTRON IAQ-N300 wall-mount IAQ sensor

How many BACnet points does the EBTRON IAQ-N300 wall-mount IAQ sensor have?

This list has 18 BACnet objects: 4 analog inputs, 11 analog values, 3 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which EBTRON IAQ-N300 wall-mount IAQ sensor BACnet points are writable?

15 of the 18 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official EBTRON IAQ-N300 wall-mount IAQ sensor BACnet documentation?

The source is IAQ-Ny00-W Quick Installation Guide - Wall Mount Indoor Air Quality Sensors with RS-485 Network Output (Appendix A) (IG_IAQ-Ny00-W_R1B), revision 2016-05-12, published free by EBTRON at https://ebtron.com/wp-content/uploads/documents/IG_IAQ-Ny00-W.pdf.

What are the minimum BACnet points to integrate the EBTRON IAQ-N300 wall-mount IAQ sensor?

Start with AI 1 CO2 PPM (Space CO2, ppm); AI 2 RH (Space relative humidity, %); AI 3 Temperature (Space temperature (°F unless set to °C)).

How do I check these points on the real IAQ-N300 wall-mount IAQ sensor?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More EBTRON BACnet points lists

Source: IAQ-Ny00-W Quick Installation Guide - Wall Mount Indoor Air Quality Sensors with RS-485 Network Output (Appendix A) · IG_IAQ-Ny00-W_R1B · rev. 2016-05-12. Object names, instances and units are reproduced as published; descriptions are our own.