Easy BACnet
  1. Home
  2. BACnet points lists
  3. EBTRON
  4. HTN104 Thermal Dispersion Airflow / Temperature Transmitter (firmware 1.x)

Thermal dispersion airflow measuring station · BACnet points list

EBTRON HTN104 Thermal Dispersion Airflow / Temperature Transmitter (firmware 1.x) BACnet points list

Updated 7 November 2026

Short answer

The HTN104 is an EBTRON thermal dispersion airflow and temperature transmitter with a BACnet MS/TP port. Its PICS object table lists three analog inputs (airflow, pressure, temperature) and four analog values (free area, baud rate, airflow and temperature traverse).

This page lists 7 BACnet objects for the EBTRON HTN104 Thermal Dispersion Airflow / Temperature Transmitter (firmware 1.x) — 2 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from EBTRON’s own free documentation, linked below.

Manufacturer
EBTRON
Model
HTN104 Thermal Dispersion Airflow / Temperature Transmitter (firmware 1.x)
Equipment
Thermal dispersion airflow measuring station
Equipment type
Thermostats, sensors & meters
BACnet objects
7 (2 writable)
Transport
BACnet MS/TP
Firmware
1.23 (application 1.0)
Also known as
HTN104, HTN104-1.x, EBTRON HTN104
Source document
HTN104 BACnet Protocol Implementation Conformance Statement · PIC_HTN104_1.x_R1C · rev. 2011-03-24
Download CSV 7 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against EBTRON’s current documentation and the live device before use. Not official EBTRON information. Terms of use.

BMS integration notes: EBTRON HTN104 Thermal Dispersion Airflow / Temperature Transmitter (firmware 1.x)

Integration in brief

Read airflow (AI 1), temperature (AI 3) and pressure (AI 2). Set the duct free area (AV 1) so the airflow reading is right.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AI 1AirflowAirflow (FPM, CFM, MPS or LPS)Read
AI 3TemperatureAir temperatureRead
AI 2PressurePressure (iWC or Pa)Read

Network setup

EBTRON HTN104 Thermal Dispersion Airflow / Temperature Transmitter (firmware 1.x) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

7 of 7 shown
Type
Access
Show
EBTRON HTN104 Thermal Dispersion Airflow / Temperature Transmitter (firmware 1.x) BACnet Points List
DescriptionStates
AImin1AirflowUnits FPM, CFM, MPS or LPSCFMRead
AImin2PressureUnits iWC or PainH2ORead
AImin3Temperature°C or °F°FRead
AV1Free AreaDuct free area used for the airflow calculationWrite
AV2Baud RateMS/TP baud rate: 9600, 19200, 38400 or 76800Write
AV3Airflow TraverseAirflow traverse valueRead
AV4Temperature TraverseTemperature traverse valueRead
Object ID lookup: EBTRON HTN104 Thermal Dispersion Airflow / Temperature Transmitter point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the HTN104 Thermal Dispersion Airflow / Temperature Transmitter (firmware 1.x) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the EBTRON HTN104 Thermal Dispersion Airflow / Temperature Transmitter (firmware 1.x)

How many BACnet points does the EBTRON HTN104 Thermal Dispersion Airflow / Temperature Transmitter (firmware 1.x) have?

This list has 7 BACnet objects: 3 analog inputs, 4 analog values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which EBTRON HTN104 Thermal Dispersion Airflow / Temperature Transmitter (firmware 1.x) BACnet points are writable?

2 of the 7 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official EBTRON HTN104 Thermal Dispersion Airflow / Temperature Transmitter (firmware 1.x) BACnet documentation?

The source is HTN104 BACnet Protocol Implementation Conformance Statement (PIC_HTN104_1.x_R1C), revision 2011-03-24, published free by EBTRON at https://ebtron.com/wp-content/uploads/HTN104-1.x-BACnet-PICS.pdf.

What are the minimum BACnet points to integrate the EBTRON HTN104 Thermal Dispersion Airflow / Temperature Transmitter (firmware 1.x)?

Start with AI 1 Airflow (Airflow (FPM, CFM, MPS or LPS)); AI 3 Temperature (Air temperature); AI 2 Pressure (Pressure (iWC or Pa)).

How do I check these points on the real HTN104 Thermal Dispersion Airflow / Temperature Transmitter (firmware 1.x)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More EBTRON BACnet points lists

Source: HTN104 BACnet Protocol Implementation Conformance Statement · PIC_HTN104_1.x_R1C · rev. 2011-03-24. Object names, instances and units are reproduced as published; descriptions are our own.