Short answer

The EE800D is a room transmitter for CO2, relative humidity and temperature that works as a BACnet MS/TP smart sensor. Besides the measured values it calculates dew point, frost point, absolute humidity, mixing ratio, enthalpy and vapor pressure, each as its own Analog Input.

This page lists 10 BACnet objects for the E+E Elektronik EE800D room CO2, humidity and temperature transmitter (BACnet MS/TP) — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from a copy of E+E Elektronik’s documentation hosted by Instrumart, not by E+E Elektronik itself, so treat it as unofficial.

Manufacturer
E+E Elektronik
Model
EE800D room CO2, humidity and temperature transmitter (BACnet MS/TP)
Equipment
Room sensor (CO2, humidity, temperature)
Equipment type
Thermostats, sensors & meters
BACnet objects
10 (0 writable)
Transport
BACnet MS/TP
Firmware
1.2
Also known as
EE800D, EE800, E+E EE800 BACnet
Source document
BACnet PICS EE800D · PICS_EE800D v1.2 · rev. 19.5.2015 (unofficial copy, hosted by Instrumart)
Download CSV 10 rows Download EDE B.I.G.-EU JSON Source PDF (unofficial copy) ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against E+E Elektronik’s current documentation and the live device before use. Not official E+E Elektronik information. Terms of use.

BMS integration notes: E+E Elektronik EE800D room CO2, humidity and temperature transmitter (BACnet MS/TP)

Integration in brief

Set a unique device instance and MAC address, then poll the Analog Inputs. Most jobs only need temperature, humidity and averaged CO2.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AI 0TRoom temperatureRead
AI 1RHRelative humidityRead
AI 8CO2Room CO2, averagedRead
AI 3TdDew point, calculatedRead

Network setup

Watch out for

E+E Elektronik EE800D room CO2, humidity and temperature transmitter (BACnet MS/TP) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

10 of 10 shown
Type
Analog
Show
E+E Elektronik EE800D room CO2, humidity and temperature transmitter (BACnet MS/TP) BACnet Points List
DescriptionStates
AImin0TTemperature°C / °F / KRead
AImin1RHRelative humidity%rHRead
AI2eWater vapor partial pressurembar / psiRead
AImin3TdDew point temperature°C / °F / KRead
AI4dvAbsolute humidityg/m³ / g/ft³Read
AI5rMixing ratiog/kg / gr/lbRead
AI6hEnthalpykJ/kg / ft·lbf/lb / BTU/lbRead
AI7TfFrost point temperature°C / °F / KRead
AImin8CO2CO2, averagedppmRead
AI9CO2rawCO2 raw value, faster responseppmRead
Object ID lookup: E+E Elektronik EE800D point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the EE800D room CO2, humidity and temperature transmitter (BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the E+E Elektronik EE800D room CO2, humidity and temperature transmitter (BACnet MS/TP)

How many BACnet points does the E+E Elektronik EE800D room CO2, humidity and temperature transmitter (BACnet MS/TP) have?

This list has 10 BACnet objects: 10 analog inputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which E+E Elektronik EE800D room CO2, humidity and temperature transmitter (BACnet MS/TP) BACnet points are writable?

None of the listed objects are marked writable in the source documentation.

Where is the official E+E Elektronik EE800D room CO2, humidity and temperature transmitter (BACnet MS/TP) BACnet documentation?

E+E Elektronik does not publish it on its own website. This list comes from BACnet PICS EE800D (PICS_EE800D v1.2), revision 19.5.2015, a copy hosted by Instrumart at https://www.instrumart.com/assets/ee-ee800-co2-temperature-rh-transmitter-bacnet-protocol-implementation.pdf. Ask E+E Elektronik or its representative for the current revision.

What are the minimum BACnet points to integrate the E+E Elektronik EE800D room CO2, humidity and temperature transmitter (BACnet MS/TP)?

Start with AI 0 T (Room temperature); AI 1 RH (Relative humidity); AI 8 CO2 (Room CO2, averaged); AI 3 Td (Dew point, calculated).