Duct sensor (CO2, humidity, temperature) · BACnet points list

E+E Elektronik EE850D / EE820D duct CO2 transmitter (BACnet MS/TP) BACnet points list

Updated 12 November 2026Unofficial source

Short answer

The EE850D (CO2, humidity and temperature) and EE820D (CO2 only) are transmitters that work as BACnet MS/TP smart sensors. CO2 comes first in the object list (AI 0-1); the EE850D adds temperature, humidity and the calculated humidity values on AI 2-9.

This page lists 10 BACnet objects for the E+E Elektronik EE850D / EE820D duct CO2 transmitter (BACnet MS/TP) — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from a copy of E+E Elektronik’s documentation hosted by Instrumart, not by E+E Elektronik itself, so treat it as unofficial.

Manufacturer
E+E Elektronik
Model
EE850D / EE820D duct CO2 transmitter (BACnet MS/TP)
Equipment
Duct sensor (CO2, humidity, temperature)
Equipment type
Thermostats, sensors & meters
BACnet objects
10 (0 writable)
Transport
BACnet MS/TP
Firmware
1.0
Also known as
EE850D, EE820D, EE850, EE820, E+E EE850 BACnet, E+E EE820 BACnet
Source document
BACnet PICS EE850D & EE820D · PICS_EE850D_EE820D v1.1 · rev. 03.07.2018 (unofficial copy, hosted by Instrumart)
Download CSV 10 rows Download EDE B.I.G.-EU JSON Source PDF (unofficial copy) ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against E+E Elektronik’s current documentation and the live device before use. Not official E+E Elektronik information. Terms of use.

BMS integration notes: E+E Elektronik EE850D / EE820D duct CO2 transmitter (BACnet MS/TP)

Integration in brief

Set a unique device instance and MAC address, then poll AI 0 for CO2. On the EE850D also read temperature (AI 2) and humidity (AI 3).

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AI 0CO2CO2, averagedRead
AI 2TTemperature (EE850D only)Read
AI 3RHRelative humidity (EE850D only)Read

Network setup

Watch out for

E+E Elektronik EE850D / EE820D duct CO2 transmitter (BACnet MS/TP) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

10 of 10 shown
Type
Analog
Show
E+E Elektronik EE850D / EE820D duct CO2 transmitter (BACnet MS/TP) BACnet Points List
DescriptionStates
AImin0CO2CO2, averagedppmRead
AI1CO2rawCO2 raw valueppmRead
AImin2TTemperature (EE850D only)°C / °F / KRead
AImin3RHRelative humidity (EE850D only)%rHRead
AI4eWater vapor partial pressure (EE850D only)mbar / psiRead
AI5TdDew point temperature (EE850D only)°C / °F / KRead
AI6dvAbsolute humidity (EE850D only)g/m³ / g/ft³Read
AI7rMixing ratio (EE850D only)g/kg / gr/lbRead
AI8hEnthalpy (EE850D only)kJ/kg / ft·lbf/lb / BTU/lbRead
AI9TfFrost point temperature (EE850D only)°C / °F / KRead
Object ID lookup: E+E Elektronik EE850D / EE820D point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the EE850D / EE820D duct CO2 transmitter (BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the E+E Elektronik EE850D / EE820D duct CO2 transmitter (BACnet MS/TP)

How many BACnet points does the E+E Elektronik EE850D / EE820D duct CO2 transmitter (BACnet MS/TP) have?

This list has 10 BACnet objects: 10 analog inputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which E+E Elektronik EE850D / EE820D duct CO2 transmitter (BACnet MS/TP) BACnet points are writable?

None of the listed objects are marked writable in the source documentation.

Where is the official E+E Elektronik EE850D / EE820D duct CO2 transmitter (BACnet MS/TP) BACnet documentation?

E+E Elektronik does not publish it on its own website. This list comes from BACnet PICS EE850D & EE820D (PICS_EE850D_EE820D v1.1), revision 03.07.2018, a copy hosted by Instrumart at https://www.instrumart.com/assets/ee-ee820-co2-transmitter-bacnet-protocol-implementation.pdf. Ask E+E Elektronik or its representative for the current revision.

What are the minimum BACnet points to integrate the E+E Elektronik EE850D / EE820D duct CO2 transmitter (BACnet MS/TP)?

Start with AI 0 CO2 (CO2, averaged); AI 2 T (Temperature (EE850D only)); AI 3 RH (Relative humidity (EE850D only)).

How do I check these points on the real EE850D / EE820D duct CO2 transmitter (BACnet MS/TP)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More E+E Elektronik BACnet points lists

Source: BACnet PICS EE850D & EE820D · PICS_EE850D_EE820D v1.1 · rev. 03.07.2018. Object names, instances and units are reproduced as published; descriptions are our own.