  4. Room Sensor RS485 BACnet (TES201, HTS201, CDS201)

Room sensor (temperature, humidity, CO2) · BACnet points list

E+E Elektronik Room Sensor RS485 BACnet (TES201, HTS201, CDS201) BACnet points list

Updated 4 November 2026

Short answer

The TES201, HTS201 and CDS201 are room sensors that report their measurements as BACnet MS/TP Analog Input objects. Which inputs exist depends on the model: temperature only, temperature plus humidity and dew point, or all of those plus CO2 (averaged and raw).

This page lists 6 BACnet objects for the E+E Elektronik Room Sensor RS485 BACnet (TES201, HTS201, CDS201) — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from E+E Elektronik’s own free documentation, linked below.

Manufacturer
E+E Elektronik
Model
Room Sensor RS485 BACnet (TES201, HTS201, CDS201)
Equipment
Room sensor (temperature, humidity, CO2)
Equipment type
Thermostats, sensors & meters
BACnet objects
6 (0 writable)
Transport
BACnet MS/TP
Firmware
1.0
Also known as
TES201, HTS201, CDS201, E+E Room Sensor RS485, E+E room sensor BACnet MS/TP
Source document
BACnet PICS Room Sensor RS485 · rev. 25.06.2021
Download CSV 6 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against E+E Elektronik’s current documentation and the live device before use. Not official E+E Elektronik information. Terms of use.

BMS integration notes: E+E Elektronik Room Sensor RS485 BACnet (TES201, HTS201, CDS201)

Integration in brief

Give the sensor a unique device instance and MAC address, then poll or subscribe to the Analog Inputs for the model's measurements. Write a COV_Increment if you want COV notifications; it is off by default.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AI 0TRoom temperatureRead
AI 1RHRelative humidity (HTS201, CDS201)Read
AI 3CO2Room CO2, averaged (CDS201)Read

Network setup

Watch out for

E+E Elektronik Room Sensor RS485 BACnet (TES201, HTS201, CDS201) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

6 of 6 shown
Type
AnalogOther
Show
E+E Elektronik Room Sensor RS485 BACnet (TES201, HTS201, CDS201) BACnet Points List
DescriptionStates
DEVTES201_XXXXXXXX / HTS201_XXXXXXXX / CDS201_XXXXXXXXDevice object; name = model + unique characters, instance set by the userRead
AImin0TRoom temperature°CRead
AImin1RHRelative humidity (HTS201, CDS201)%rHRead
AI2TdDew point temperature (HTS201, CDS201)°CRead
AImin3CO2CO2, averaged value (CDS201)ppmRead
AI4CO2rawCO2, raw value (CDS201)ppmRead
Object ID lookup: E+E Elektronik TES201 / HTS201 / CDS201 point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Room Sensor RS485 BACnet (TES201, HTS201, CDS201) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the E+E Elektronik Room Sensor RS485 BACnet (TES201, HTS201, CDS201)

How many BACnet points does the E+E Elektronik Room Sensor RS485 BACnet (TES201, HTS201, CDS201) have?

This list has 6 BACnet objects: 5 analog inputs, 1 device. The exact set on a given unit depends on its firmware, installed options and configuration.

Which E+E Elektronik Room Sensor RS485 BACnet (TES201, HTS201, CDS201) BACnet points are writable?

None of the listed objects are marked writable in the source documentation.

Where is the official E+E Elektronik Room Sensor RS485 BACnet (TES201, HTS201, CDS201) BACnet documentation?

The source is BACnet PICS Room Sensor RS485, revision 25.06.2021, published free by E+E Elektronik at https://downloads.epluse.com/fileadmin/data/product/PICS/PICS_RoomSensor.pdf.

What are the minimum BACnet points to integrate the E+E Elektronik Room Sensor RS485 BACnet (TES201, HTS201, CDS201)?

Start with AI 0 T (Room temperature); AI 1 RH (Relative humidity (HTS201, CDS201)); AI 3 CO2 (Room CO2, averaged (CDS201)).

How do I check these points on the real Room Sensor RS485 BACnet (TES201, HTS201, CDS201)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

Source: BACnet PICS Room Sensor RS485 · rev. 25.06.2021. Object names, instances and units are reproduced as published; descriptions are our own.