- EE600D / EE610D differential pressure transmitter (BACnet MS/TP)
Differential pressure sensor · BACnet points list
E+E Elektronik EE600D / EE610D differential pressure transmitter (BACnet MS/TP) BACnet points list
Updated 12 November 2026Unofficial source
The EE600D and EE610D are differential pressure transmitters that report over BACnet MS/TP as a smart sensor. The EE600D exposes pressure plus calculated air velocity, volume flow, filter contamination and level; the EE610D (+/-100 Pa) only exposes differential pressure.
This page lists 5 BACnet objects for the E+E Elektronik EE600D / EE610D differential pressure transmitter (BACnet MS/TP) — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from a copy of E+E Elektronik’s documentation hosted by Instrumart, not by E+E Elektronik itself, so treat it as unofficial.
- Manufacturer
- E+E Elektronik
- Model
- EE600D / EE610D differential pressure transmitter (BACnet MS/TP)
- Equipment
- Differential pressure sensor
- Equipment type
- Thermostats, sensors & meters
- BACnet objects
- 5 (0 writable)
- Transport
- BACnet MS/TP
- Firmware
- 1.0
- Also known as
- EE600D, EE610D, EE600, EE610, E+E EE600 BACnet
- Source document
- BACnet PICS EE600D / EE610D · PICS_EE600D_EE610D v1.0 · rev. 22.10.2019 (unofficial copy, hosted by Instrumart)
Reference only, provided as-is: verify against E+E Elektronik’s current documentation and the live device before use. Not official E+E Elektronik information. Terms of use.
BMS integration notes: E+E Elektronik EE600D / EE610D differential pressure transmitter (BACnet MS/TP)
Give the transmitter a unique device instance and MAC address, then poll AI 0 for differential pressure. On the EE600D the calculated velocity, flow, filter and level values are on AI 1-4 if the application uses them.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AI 0 | p | Differential pressure | Read |
| AI 2 | V' | Volume flow (EE600D only) | Read |
| AI 3 | fc | Filter contamination, % (EE600D only) | Read |
Network setup
- Device instance (0-4194302) and device name are writable and kept in non-volatile memory; the default name is the model plus 8 unique characters.
- RS485 settings are one writable string property, default "38400-8n1"; baud 9600-115200, 8 data bits, no parity, 1 stop bit fixed.
- Max Master is writable, up to 127.
- ReinitializeDevice and DeviceCommunicationControl need the password printed in the PICS.
Watch out for
- COV reporting stays off until COV_Increment is set; COV messages are broadcast (no subscription list).
- Present_Value is only writable while Out_Of_Service is true; the value then defaults to 50.0.
- Reliability reads NO_SENSOR when the sensing element is damaged or missing.
E+E Elektronik EE600D / EE610D differential pressure transmitter (BACnet MS/TP) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AImin | 0 | p | Differential pressure | Pa / kPa / mbar / mm WC / in WC | Read | |
| AI | 1 | v | Air velocity (EE600D only) | m/s / ft/min | Read | |
| AImin | 2 | V' | Volumetric flow (EE600D only) | m³/h / m³/s / l/s / ft³/min | Read | |
| AImin | 3 | fc | Filter contamination (EE600D only) | % | Read | |
| AI | 4 | li | Level indicator (EE600D only) | cm / in | Read |
No points match these filters.
Integration notes
- Object list from the PICS sections 11-12; the EE610D supports only AI 0 and the device object.
- Units are selectable per object; the object description changes with the unit (for example "Differential pressure [Pa]").
- All objects are read-only except Present_Value while Out_Of_Service is true.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the EE600D / EE610D differential pressure transmitter (BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the E+E Elektronik EE600D / EE610D differential pressure transmitter (BACnet MS/TP)
How many BACnet points does the E+E Elektronik EE600D / EE610D differential pressure transmitter (BACnet MS/TP) have?
This list has 5 BACnet objects: 5 analog inputs. The exact set on a given unit depends on its firmware, installed options and configuration.
Which E+E Elektronik EE600D / EE610D differential pressure transmitter (BACnet MS/TP) BACnet points are writable?
None of the listed objects are marked writable in the source documentation.
Where is the official E+E Elektronik EE600D / EE610D differential pressure transmitter (BACnet MS/TP) BACnet documentation?
E+E Elektronik does not publish it on its own website. This list comes from BACnet PICS EE600D / EE610D (PICS_EE600D_EE610D v1.0), revision 22.10.2019, a copy hosted by Instrumart at https://core.instrumart.com/assets/ee-ee600-differential-pressure-sensor-bacnet-protocol-implementation.pdf. Ask E+E Elektronik or its representative for the current revision.
What are the minimum BACnet points to integrate the E+E Elektronik EE600D / EE610D differential pressure transmitter (BACnet MS/TP)?
Start with AI 0 p (Differential pressure); AI 2 V' (Volume flow (EE600D only)); AI 3 fc (Filter contamination, % (EE600D only)).
How do I check these points on the real EE600D / EE610D differential pressure transmitter (BACnet MS/TP)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More E+E Elektronik BACnet points lists
- Room sensor (CO2, humidity, temperature)
E+E Elektronik EE800D room CO2, humidity and temperature transmitter (BACnet MS/TP)
E+E EE800 room transmitters with the RS485 BACnet MS/TP output.
Also known as: EE800D, EE800, E+E EE800 BACnet - Duct sensor (CO2, humidity, temperature)
E+E Elektronik EE850D / EE820D duct CO2 transmitter (BACnet MS/TP)
E+E EE850 CO2 / humidity / temperature duct transmitters and EE820 CO2 transmitters with the RS485 BACnet MS/TP output.
Also known as: EE850D, EE820D, EE850, EE820, E+E EE850 BACnet, E+E EE820 BACnet - CO2 sensor probe (CO2, humidity, temperature, pressure)
E+E Elektronik EE872 OM CO2 probe (BACnet MS/TP)
E+E EE872 CO2 probes with the BACnet MS/TP output: EE872-M10 (CO2 only) and EE872-M13 (CO2 plus temperature, humidity and pressure).
Also known as: EE872, EE872OM, EE872-M10, EE872-M13, E+E EE872 BACnet - Room sensor (temperature, humidity, CO2)
E+E Elektronik Room Sensor RS485 BACnet (TES201, HTS201, CDS201)
E+E Elektronik room sensors with RS485 BACnet MS/TP: TES201 (temperature), HTS201 (humidity/temperature) and CDS201 (CO2/humidity/temperature).
Also known as: TES201, HTS201, CDS201, E+E Room Sensor RS485, E+E room sensor BACnet MS/TP
Source: BACnet PICS EE600D / EE610D · PICS_EE600D_EE610D v1.0 · rev. 22.10.2019. Object names, instances and units are reproduced as published; descriptions are our own.