 "manufacturer": "E+E Elektronik",
 "manufacturer_slug": "e-e-elektronik",
 "model": "EE600D / EE610D differential pressure transmitter (BACnet MS/TP)",
 "model_slug": "ee600d-ee610d-differential-pressure",
 "short_model": "EE600D / EE610D",
 "aliases": [
  "EE600D",
  "EE610D",
  "EE600",
  "EE610",
  "E+E EE600 BACnet"
 ],
 "equipment_type": "Differential pressure sensor",
 "applies_to": "E+E EE600 and EE610 differential pressure transmitters with the RS485 BACnet MS/TP output.",
 "summary": "The EE600D and EE610D are differential pressure transmitters that report over BACnet MS/TP as a smart sensor. The EE600D exposes pressure plus calculated air velocity, volume flow, filter contamination and level; the EE610D (+/-100 Pa) only exposes differential pressure.",
 "bacnet_transport": [
  "BACnet MS/TP"
 ],
 "firmware": "1.0",
 "default_device_instance": null,
 "access_inferred": false,
 "notes": [
  "Object list from the PICS sections 11-12; the EE610D supports only AI 0 and the device object.",
  "Units are selectable per object; the object description changes with the unit (for example \"Differential pressure [Pa]\").",
  "All objects are read-only except Present_Value while Out_Of_Service is true."
 ],
 "source": {
  "title": "BACnet PICS EE600D / EE610D",
  "doc_number": "PICS_EE600D_EE610D v1.0",
  "revision_date": "22.10.2019",
  "url": "https://core.instrumart.com/assets/ee-ee600-differential-pressure-sensor-bacnet-protocol-implementation.pdf",
  "unofficial": true,
  "host": "Instrumart"
 },
 "integration": {
  "summary": "Give the transmitter a unique device instance and MAC address, then poll AI 0 for differential pressure. On the EE600D the calculated velocity, flow, filter and level values are on AI 1-4 if the application uses them.",
  "minimum_points": [
   {
    "ref": "AI 0",
    "name": "p",
    "why": "Differential pressure"
   },
   {
    "ref": "AI 2",
    "name": "V'",
    "why": "Volume flow (EE600D only)"
   },
   {
    "ref": "AI 3",
    "name": "fc",
    "why": "Filter contamination, % (EE600D only)"
   }
  ],
  "enable": null,
  "heartbeat": null,
  "remote_sensors": null,
  "setup": [
   "Device instance (0-4194302) and device name are writable and kept in non-volatile memory; the default name is the model plus 8 unique characters.",
   "RS485 settings are one writable string property, default \"38400-8n1\"; baud 9600-115200, 8 data bits, no parity, 1 stop bit fixed.",
   "Max Master is writable, up to 127.",
   "ReinitializeDevice and DeviceCommunicationControl need the password printed in the PICS."
  ],
  "gotchas": [
   "COV reporting stays off until COV_Increment is set; COV messages are broadcast (no subscription list).",
   "Present_Value is only writable while Out_Of_Service is true; the value then defaults to 50.0.",
   "Reliability reads NO_SENSOR when the sensing element is damaged or missing."
  ]
 },
 "points": [
  {
   "type": "AI",
   "instance": 0,
   "name": "p",
   "description": "Differential pressure",
   "units": "Pa / kPa / mbar / mm WC / in WC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 1,
   "name": "v",
   "description": "Air velocity (EE600D only)",
   "units": "m/s / ft/min",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 2,
   "name": "V'",
   "description": "Volumetric flow (EE600D only)",
   "units": "m³/h / m³/s / l/s / ft³/min",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 3,
   "name": "fc",
   "description": "Filter contamination (EE600D only)",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 4,
   "name": "li",
   "description": "Level indicator (EE600D only)",
   "units": "cm / in",
   "access": "R",
   "states": ""
  }
 ],
 "page": "https://easybacnet.com/bacnet-points-lists/e-e-elektronik/ee600d-ee610d-differential-pressure",
 "note": "Provided as-is. Point availability varies by firmware and options; verify against the live device.",
 "disclaimer": "DISCLAIMER: reference only, provided AS IS with no warranty. May contain errors or be out of date. You must verify every point against the manufacturer's current documentation and the live device before use. easybacnet.com accepts no liability for its use and is not affiliated with the manufacturer. Terms: https://easybacnet.com/terms#content"
}