 "manufacturer": "E+E Elektronik",
 "manufacturer_slug": "e-e-elektronik",
 "model": "EE800D room CO2, humidity and temperature transmitter (BACnet MS/TP)",
 "model_slug": "ee800d-co2-humidity-temperature-transmitter",
 "short_model": "EE800D",
 "aliases": [
  "EE800D",
  "EE800",
  "E+E EE800 BACnet"
 ],
 "equipment_type": "Room sensor (CO2, humidity, temperature)",
 "applies_to": "E+E EE800 room transmitters with the RS485 BACnet MS/TP output.",
 "summary": "The EE800D is a room transmitter for CO2, relative humidity and temperature that works as a BACnet MS/TP smart sensor. Besides the measured values it calculates dew point, frost point, absolute humidity, mixing ratio, enthalpy and vapor pressure, each as its own Analog Input.",
 "bacnet_transport": [
  "BACnet MS/TP"
 ],
 "firmware": "1.2",
 "default_device_instance": null,
 "access_inferred": false,
 "notes": [
  "Object list from the PICS sections 11-12 (v1.2, dated 19.5.2015).",
  "The PICS says CO2raw is only for special applications that need a faster response.",
  "Units are selectable per object; the object description changes with the unit.",
  "All objects are read-only except Present_Value while Out_Of_Service is true."
 ],
 "source": {
  "title": "BACnet PICS EE800D",
  "doc_number": "PICS_EE800D v1.2",
  "revision_date": "19.5.2015",
  "url": "https://www.instrumart.com/assets/ee-ee800-co2-temperature-rh-transmitter-bacnet-protocol-implementation.pdf",
  "unofficial": true,
  "host": "Instrumart"
 },
 "integration": {
  "summary": "Set a unique device instance and MAC address, then poll the Analog Inputs. Most jobs only need temperature, humidity and averaged CO2.",
  "minimum_points": [
   {
    "ref": "AI 0",
    "name": "T",
    "why": "Room temperature"
   },
   {
    "ref": "AI 1",
    "name": "RH",
    "why": "Relative humidity"
   },
   {
    "ref": "AI 8",
    "name": "CO2",
    "why": "Room CO2, averaged"
   },
   {
    "ref": "AI 3",
    "name": "Td",
    "why": "Dew point, calculated"
   }
  ],
  "enable": null,
  "heartbeat": null,
  "remote_sensors": null,
  "setup": [
   "Device instance (0-4194302) and device name are writable and kept in non-volatile memory; the default name is the model plus 8 unique characters.",
   "RS485 settings are one writable string property, default \"38400-8n1\"; baud 9600-115200, 8 data bits, no parity, 1 stop bit fixed.",
   "Max Master is writable, up to 127.",
   "ReinitializeDevice and DeviceCommunicationControl need the password printed in the PICS."
  ],
  "gotchas": [
   "Present_Value is only writable while Out_Of_Service is true; the value then defaults to 50.0."
  ]
 },
 "points": [
  {
   "type": "AI",
   "instance": 0,
   "name": "T",
   "description": "Temperature",
   "units": "°C / °F / K",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 1,
   "name": "RH",
   "description": "Relative humidity",
   "units": "%rH",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 2,
   "name": "e",
   "description": "Water vapor partial pressure",
   "units": "mbar / psi",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 3,
   "name": "Td",
   "description": "Dew point temperature",
   "units": "°C / °F / K",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 4,
   "name": "dv",
   "description": "Absolute humidity",
   "units": "g/m³ / g/ft³",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 5,
   "name": "r",
   "description": "Mixing ratio",
   "units": "g/kg / gr/lb",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 6,
   "name": "h",
   "description": "Enthalpy",
   "units": "kJ/kg / ft·lbf/lb / BTU/lb",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 7,
   "name": "Tf",
   "description": "Frost point temperature",
   "units": "°C / °F / K",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 8,
   "name": "CO2",
   "description": "CO2, averaged",
   "units": "ppm",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 9,
   "name": "CO2raw",
   "description": "CO2 raw value, faster response",
   "units": "ppm",
   "access": "R",
   "states": ""
  }
 ],
 "page": "https://easybacnet.com/bacnet-points-lists/e-e-elektronik/ee800d-co2-humidity-temperature-transmitter",
 "note": "Provided as-is. Point availability varies by firmware and options; verify against the live device.",
 "disclaimer": "DISCLAIMER: reference only, provided AS IS with no warranty. May contain errors or be out of date. You must verify every point against the manufacturer's current documentation and the live device before use. easybacnet.com accepts no liability for its use and is not affiliated with the manufacturer. Terms: https://easybacnet.com/terms#content"
}