Modular water-to-water heat pump · BACnet points list

ClimateMaster Tranquility Large Water-to-Water (SWT) 20-80 ton BACnet points list

Updated 11 November 2026

Short answer

Each SWT module controller works under a bank controller and can be read by a BMS over BACnet MS/TP or BACnet IP (Gig-E port only). The 159-point list is mostly status: circuit pressures, temperatures, superheat and subcool, EEV positions, loop valves and flows, compressor status and run time, out-of-range sensor flags and alarms, plus manual-mode test commands and the bank's leaving-water targets.

This page lists 159 BACnet objects for the ClimateMaster Tranquility Large Water-to-Water (SWT) 20-80 ton — 41 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from ClimateMaster’s own free documentation, linked below.

Manufacturer
ClimateMaster
Model
Tranquility Large Water-to-Water (SWT) 20-80 ton
Equipment
Modular water-to-water heat pump
Equipment type
Heat pumps
BACnet objects
159 (41 writable)
Transport
BACnet MS/TP, BACnet IP
Firmware
Not stated
Also known as
SWT, Tranquility SWT, ClimateMaster SWT R-454B, ClimateMaster large water-to-water BACnet, C97B0004N07
Source document
Tranquility Large Water-to-Water SWT Series - Installation, Operation & Maintenance Manual (Controller Points List) · C97B0004N07 · rev. 2026-03-09
Download CSV 159 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against ClimateMaster’s current documentation and the live device before use. Not official ClimateMaster information. Terms of use.

BMS integration notes: ClimateMaster Tranquility Large Water-to-Water (SWT) 20-80 ton

Integration in brief

Set the module controller address on its three rotary switches and choose MS/TP with the Comm Selector rotary (position 1), or use the Gig-E port for BACnet IP. The modules are run by their bank controller; a BMS mainly monitors module status and alarms and can read or adjust the bank's leaving-water targets.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AV 2156cool_temp_stp_1Bank chilled water targetWrite
AV 2155heat_temp_stp_1Bank hot water targetWrite
BV 2069reset_alarms_1Reset all module alarmsWrite
BV 2073module_run_1Module runningRead
AV 2158sysmode_1Module modeRead
BV 2074module_ok_1Module conditionRead
AV 2147loop1_leaving_temp_1Loop 1 leaving water temperatureRead
BV 2075manager_lockout_alrm_1Module locked outRead
AV 2167mod_act_mod_alarms_1Active module alarmsRead

Enable & remote start

BV 2076 chiller_run_1 is the module enable from the bank controller; the manual does not describe a separate BMS enable.

Heartbeat & communication loss

BV 2068 comm_lost_1 alarms when the module loses communication with the bank controller; BV 2152 mod_comm_tx_stat_1 shows the module's communication transmit status.

Network setup

Watch out for

ClimateMaster Tranquility Large Water-to-Water (SWT) 20-80 ton BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

159 of 159 shown
Type
AnalogBinary
Access
Show
ClimateMaster Tranquility Large Water-to-Water (SWT) 20-80 ton BACnet Points List
DescriptionStates
AV2143c1_cl_ll_temp_1Circuit 1's Cooling Liquid Line Temperature (C1 Cooling Liquid Line Temperature)Read
AV2087c1_cool_mode_subcool_1Circuit 1's Subcool Temperature in Cool Mode (C1 Cool Mode SubCool)Read
AV2139c1_disc_temp_1Circuit 1's Discharge Temperature (C1 Discharge Temperature)Read
AV2135c1_disc_pres_1Circuit 1's Discharge Pressure (C1 Disch Pressure)Read
AV2145c1_ht_ll_temp_1Circuit 1's Heating Liquid Line Temperature (C1 Heating Liquid Line Temperature)Read
AV2088c1_heat_mode_subcool_1Circuit 1's Subcool Temperature in Heat Mode (C1 Heat Mode SubCool)Read
AV2163c1_ll_pressure_1Circuit 1's Liquid Line Pressure in Cool Mode (C1 Liquid Line Pressure)Read
AV2116c1_ll_press_heat_1Circuit 1's Liquid Line Pressure in Heat Mode (C1 Liquid Line Pressure Heat Stat)Read
AV2137c1_suct_pres_1Circuit 1's Suction Pressure (C1 Suction Pressure)Read
AV2141c1_suct_temp_1Circuit 1's Suction Temperature (C1 Suction Temperature)Read
AV2144c2_cl_ll_temp_1Circuit 2's Cooling Liquid Line Temperature (C2 Cooling Liquid Line Temperature)Read
AV2086c2_cool_mode_subcool_1Circuit 2's Subcool Temperature in Cool Mode (C2 Cool Mode SubCool)Read
AV2140c2_disc_temp_1Circuit 2's Discharge Temperature (C2 Discharge Temperature)Read
AV2136c2_disc_pres_1Circuit 2's Discharge Pressure (C2 Disch Pressure)Read
AV2146c2_ht_ll_temp_1Circuit 2's Heating Liquid Line Temperature (C2 Heating Liquid Line Temperature)Read
AV2089c2_heat_mode_subcool_1Circuit 2's Subcool Temperature in Heat Mode (C2 Heat Mode SubCool)Read
AV2164c2_ll_pressure_1Circuit 2's Liquid Line Pressure in Cool Mode (C2 Liquid Line Pressure)Read
AV2117c2_ll_press_heat_1Circuit 2's Liquid Line Pressure in Heat Mode (C2 Liquid Line PressureHeat Stat)Read
AV2138c2_suct_pres_1Circuit 2's Suction Pressure (C2 Suction Pressure)Read
AV2142c2_suct_temp_1Circuit 2's Suction Temperature (C2 Suction Temperature)Read
AV2035c1_suc_superheat_1Circuit 1's Suction Superheat Temperature (Calc C1 Suc Superheat)Read
AV2036c2_suc_superheat_1Circuit 2's Suction Superheat Temperature (Calc C2 Suc Superheat)Read
AV2160chilled_design_delta_1Chilled Water Design DeltaWrite
AV2077chiller_config_1Circuit 1's Module Type (Chiller Module Type)Read
AV2037c1_runtime_1Compressor 1 Runtime (Comp 1 Runtime)Read
AV2039c2_runtime_1Compressor 2 Runtime (Comp 2 Runtime)Read
AV2161cooling_type_1Sets the Pressure Control Setpoints (Cooling Type)Write
AVmin2156cool_temp_stp_1Bank's Chilled Water Target Setpoint (COOL LVG TRG)Write
AV2004exv1_man_percent_1Circuit 1's EEV A Manual Percentage ONLY IN MANUAL Mode (EEV1 Manual Percentage)Write
AV2006exv2_man_percent_1Circuit 1's EEV A Manual Percentage ONLY IN MANUAL Mode (EEV2 Manual Percentage)Write
AV2240exvb1_man_percent_1Circuit 1's EEV B Manual Percentage ONLY IN MANUAL Mode (EEV B C1 Manual Percentage)Write
AV2241exvb2_man_percent_1Circuit 1's EEV B Manual Percentage ONLY IN MANUAL Mode (EEV B C2 Manual Percentage)Write
AV2371exv_a_c1_val_pos_1Circuit 1's EEV A Valve Position (EXVA C1 Valve position)Read
AV2372exv_a_c2_val_pos_1Circuit 2's EEV A Valve Position (EXVA C2 Valve position)Read
AV2242exva_c1_sh_1Circuit 1's EEV A Superheat (EXV A C1 Superheat)Read
AV2243exva_c2_sh_1Circuit 2's EEV A Superheat (EXV A C2 Superheat)Read
AV2373exv_b_c1_val_pos_1Circuit 1's EEV B Valve Position (EXVB C1 Valve position)Read
AV2374exv_b_c2_val_pos_1Circuit 2's EEV B Valve Position (EXVB C2 Valve position)Read
AV2244exvb_c1_sh_1Circuit 1's EEV B Superheat (EXV B C1 Superheat)Read
AV2245exvb_c2_sh_1Circuit 2's EEV B Superheat (EXV B C2 Superheat)Read
AVmin2155heat_temp_stp_1Hot Water Target Setpoint (HEAT LVG TRG)Write
AV2159heating_design_delta_1Hot Water Design DeltaWrite
AV2114loop2_man_percentage_1Loop 2 Valve Manual Percentage ONLY IN MANUAL Mode (Local Loop 2 Manual Percentage)Write
AV2064loop1_entering_temp_1Loop1 Entering Water TempRead
AVmin2147loop1_leaving_temp_1Loop1 Leaving Water TempRead
AV2112loop1_man_percentage_1Loop 1 Valve Manual Percentage ONLY IN MANUAL Mode (Loop1 Manual Percentage)Write
AV2091flow1_stat_1Loop 1 Flow StatusRead
AV2020loop1_mwv_out_1Loop 1 Valve Position Control (Loop 1 Motorized Water Valve Output)Read
AV2084loop1_mwv1_stat_1Loop 1 Valve Position Status (Loop 1 MWV Status)Read
AV2093flow2_stat_1Loop 2 Flow StatusRead
AV2126loop2_leaving_temp_1Loop 2 Leaving Water Temperature (Loop 2 Leaving Water Temp)Read
AV2021loop2_mwv_out_1Loop 2 Valve Position Control (Loop 2 Motorized Water Valve Output)Read
AV2085loop2_mwv1_stat_1Loop 2 Valve Position Status (Loop 2 MWV 2 Status)Read
AV2175man_mode_remain_time_1Manual Mode Expiry Timer (Manual Mode Remaining Time)Read
AV2239manual_sysmode_1Manual Mode Status (Manual Module Mode)Write
AVmin2167mod_act_mod_alarms_1Module Active AlarmsRead
AV2166mod_act_comp_alarms_1Module Active Compressor AlarmsRead
AV2165mod_act_oor_alarms_1Module Active OOR AlarmsRead
AV2070mod_unload_stat_1Module Active RetriesRead
AV2151mod_comm_rx_stat_1Module Comm Read StatusRead
AV2157mod_lead_lag_order_1Module Lead Lag OrderRead
AVmin2158sysmode_1Module ModeRead
BV2024alarm_out_1Alarm_OutputRead
BV2154brine_used_1AntifreezeRead
BV2019c1_exv_a_en_out_1Circuit 1's EEV A Enable Status (C1 A EEV Enable Output)Read
BV2239c1_disable_1Circuit 1's Disable Status (C1 Disable)Read
BV2022c1_en_out_1Circuit 1's EEV B Enable Status (C1 Enable Output)Read
BV2071c1_manual_1C1 Manual Enable (C1 Manual)Write
BV2171c1_min_runtime_1Compressor 1 Minimum Required Runtime (C1 Minimum Run Time)Read
BV2174c2_minimum_off_1Compressor 2 Off Delay Elapsed (C1 Compressor Off Delay)Read
BV2031c1_ref_iso_solenoid_1Circuit 1's Refrigerant Isolation Solenoid Enable (C1 Ref Isolation Solenoid)Read
BV2067c1_unload_1Compressor 1 in Retry (C1 Retry)Read
BV2169c1_rv_out_1Circuit 1's Reversing Valve Enable (C1 RV Out)Read
BV2190c1_shutdown_1Circuit 1's Shutdown Status (C1 Shutdown Status)Read
BV2240c2_disable_1Compressor 2 Disabled (C2 Disable)Read
BV2148c2_exv_a_en_out_1Circuit 2's EEV A Enable Status (C2 EEV A Enable Output)Read
BV2023c2_en_out_1Circuit 2's EEV B Enable Status (C2 Enable Output)Read
BV2029c2_exv_b_en_out_1Circuit 2's Heat EEV (C2 Heat EEV)Read
BV2072c2_manual_1C2 Manual Enable (C2 Manual)Write
BV2172c2_min_runtime_1Compressor 2 Minimum Required Runtime (C2 Minimum Run Time)Read
BV2032c2_ref_iso_solenoid_1Circuit 2's Refrigerant Isolation Solenoid Enable (C2 Ref Isolation Solenoid Stat)Read
BV2041reset_c2_runtime_1Compressor 2 Runtime Reset (C2 Runtime Reset)Write
BV2170c2_rv_out_1Circuit 2's Reversing Valve Enable (C2 RV Out)Read
BV2191c2_shutdown_1Circuit 2's Shutdown Status (C2 Shutdown Status)Read
BV2076chiller_run_1Module enable from Bank (Chiller Run)Write
BV2168clear_fault_history_1Module Fault History Clear (Clear Fault History)Write
BV2123comp1_fail_1Compressor 1 Fail (Comp 1 Fail)Read
BV2054comp_1_go_1Compressor 1 Bank Command (Comp 1 Go Command)Write
BV2056c1_stat_1Compressor 1 Status (Comp 1 Status)Read
BV2055comp_2_go_1Compressor 2 Bank Command (Comp 2 Go Command)Write
BV2057c2_stat_1Compressor 2 Status (Comp 2 Status)Read
BV2040comp2_fail_1Compressor 2 FailRead
BV2173c1_minimum_off_1Compresor Required Minimum Off Time (Compressor Off Delay)Read
BV2005exv1_manual_1Circuit 1's EEV A Manual Control (EEV1 Manual Control)Write
BV2007exv2_manual_1Circuit 2's EEV A Manual Control (EEV2 Manual Control)Write
BV2242exvb1_manual_1Circuit 1's EEV B Manual Control (EEV B C1 Manual Control)Write
BV2243exvb2_manual_1Circuit 2's EEV B Manual Control (EEV B C2 Manual Control)Write
BV2000bbvp_eev_c1_man_en_1EEV A Fully Open Manual (EEV C1 Manual EN)Write
BV2001bbvp_eev_c2_man_en_1EEV B Fully Open Manual (EEV C2 Manual EN)Write
BV2162fixed_disc_press_en_1Fixed Head Pressure Control (Enable Fixed Head Pressure Control)Write
BV2177enable_ftr_1StandAlone Mode (Fail to Run Enable)Write
BV2209lock_loop1_open_1Lock Loop 1 OpenWrite
BV2113loop1_manual_1Loop1 Manual ControlWrite
BV2111loop1_bypass_mod_1Loop1 Valve Bypass ModuleWrite
BV2108loop1_valve_status_1Loop 1 Valve StatusRead
BV2115loop2_manual_1Loop 2 Manual Valve ControlWrite
BV2109loop2_valve_status_1Loop 2 Valve StatusRead
BV2180c1_man_hgs_1Manual C1 Hot Gas SolenoidWrite
BV2002c1_man_li_1Manual C1 Hot Gas SolenoidWrite
BV2003c2_man_li_1Manual C1 Liquid InjectionWrite
BV2184c1_man_ref_iso_1Manual C1 Refrigeration Isolation SolenoidWrite
BV2182c1_man_rev_valve_1Manual C1 Reversing ValveWrite
BV2181c2_man_hgs_1Manual C2 Hot Gas SolenoidWrite
BV2185c2_man_ref_iso_1Manual C2 Refrigeration Isolation SolenoidWrite
BV2183c2_man_rev_valve_1Manual C2 Reversing ValveWrite
BV2210manual_mode_1Operating Mode in Manual Mode (Manual Mode)Write
BV2152mod_comm_tx_stat_1Bank Module Communication Watchdog Timer (Module Communication Transmit Status)Read
BV2110mot_wtr_vlv_fail_1Motorized Valve Failure in Module (Module Failure Mot Valve)Read
BV2090modflow1_1Flow Detection on Loop 1 (Module Flow 1 Status)Read
BV2246modflow2_1Flow Detection on Loop 2 (Module Flow Status 2)Read
BVmin2074module_ok_1Module Condition (Module Ok)Read
BVmin2073module_run_1Module Run Status (Module Run)Read
BV2134phase_stat_1Module Phase Status (Phase OK Status)Read
BV2178rds_alarm_1Module RDS Alarm (RDS Alarm)Read
BVmin2069reset_alarms_1Reset All Module AlarmsWrite
BV2049c1_discharge_pressure_oor_1Circuit 1 Discharge Pressure OOR (C1 Discharge Pressure OOR)Read
BV2605c1_discharge_temperature_oor_1Circuit 1 Discharge Temperature OOR (C1 Discharge Temperature OOR)Read
BV2062c1_liquid_pressure_oor_1Circuit 1 Liquid Line pressure OOR (C1 Liquid Line pressure OOR)Read
BV2060c1_liquid_line_temp_oor_1Circuit 1 Liquid Line Temp OOR (C1 Liquid Line Temp OOR)Read
BV2130c1p2_oor_1Circuit 1 Suction Pressure Out of Range (C1 Suction Pressure Out of Range)Read
BV2052c1_suction_temperature_oor_1Circuit 1 Suction Temperature OOR (C1 Suction Temperature OOR)Read
BV2050c2_discharge_pressure_oor_1Circuit 2 Discharge Pressure OOR (C2 Discharge Pressure OOR)Read
BV2051c2_discharge_temperature_oor_1Circuit 2 Discharge Temperature OOR (C2 Discharge Temperature OOR)Read
BV2063c2lp_oor_1Circuit 2 Liquid Line Press Out of Range (C2 Liquid Line Press Out of Range)Read
BV2061c2_liquid_line_temperature_oor_1Circuit 2 Liquid Line Temperature OOR (C2 Liquid Line Temperature OOR)Read
BV2131c2p2_oor_1Circuit 2 Suction Pressure Out of Range (C2 Suction Pressure Out of Range)Read
BV2053c2_suction_temperature_oor_1Circuit 2 Suction Temperature OOR (C2 Suction Temperature OOR)Read
BV2068comm_lost_1No communication with Bank alarm (Communications Alarm)Read
BV2132c1_eev_comm_loss_alarm_1Circuit 1 EEV Comm Loss Alarm (Compressor 1 EEV Comm Loss Alarm)Read
BV2045c1_hi_disch_tmp_1Circuit 1 High Discharge Temperature Alarm (Compressor 1 High Discharge Temp)Read
BV2048c1_hi_pres_alm_1Circuit 1 High Discharge Pressure Alarm (Compressor 1 High Pressure Alarm)Read
BV2046c1_low_suc_pres_alm_1Circuit 1 Low Suction Pressure Alarm (Compressor 1 Low Suction Pressure Alarm)Read
BV2042c1_no_run_1Compressor 1 NO-Run AlarmRead
BV2133c2_eev_comm_loss_alarm_1Circuit 2 EEV Comm Loss Alarm (Compressor 2 EEV Comm Loss Alarm)Read
BV2044c2_hi_disch_tmp_1Circuit 2 High Discharge Temperature Alarm (Compressor 2 High Discharge Temp)Read
BV2047c2_hi_pres_alm_1Circuit 2 High Discharge Pressure Alarm (Compressor 2 High Pressure Alarm)Read
BV2118c2_low_suc_pres_alm_1Circuit 2 Low Suction Pressure Alarm (Compressor 2 Low Suction Pressure Alarm)Read
BV2043c2_no_run_1Compressor 2 NO-Run AlarmRead
BV2106loop1_valve_alarm_1Loop 1 Motorized Valve AlarmRead
BV2107loop2_valve_alarm_1Loop 2 Motorized Valve AlarmRead
BV2094module_flow1_alarm_1Module Flow 1 AlarmRead
BV2247module_flow2_alarm_1Module Flow 2 AlarmRead
BVmin2075manager_lockout_alrm_1Module Locked Out (Module Lockout)Read
BV2120phase_loss_alarm_1Phase Loss AlarmRead
BV2179rds_shutdown_alarm_1RDS Shutdown AlarmRead
BV2186vfd1_genfault_alm_1VFD 1 General AlarmRead
BV2188vfd1_sto_alm_1VFD 1 STO AlarmRead
BV2187vfd2_genfault_alm_1VFD 2 General AlarmRead
BV2189vfd2_sto_alm_1VFD 2 STO AlarmRead
Object ID lookup: ClimateMaster Tranquility SWT point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Tranquility Large Water-to-Water (SWT) 20-80 ton and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the ClimateMaster Tranquility Large Water-to-Water (SWT) 20-80 ton

How many BACnet points does the ClimateMaster Tranquility Large Water-to-Water (SWT) 20-80 ton have?

This list has 159 BACnet objects: 62 analog values, 97 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which ClimateMaster Tranquility Large Water-to-Water (SWT) 20-80 ton BACnet points are writable?

41 of the 159 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official ClimateMaster Tranquility Large Water-to-Water (SWT) 20-80 ton BACnet documentation?

The source is Tranquility Large Water-to-Water SWT Series - Installation, Operation & Maintenance Manual (Controller Points List) (C97B0004N07), revision 2026-03-09, published free by ClimateMaster at https://files.climatemaster.com/Commercial/Water-to-Water-Units/Tranquility/SWT/Resources/C97B0004N07-SWT-IOM.pdf.

What are the minimum BACnet points to integrate the ClimateMaster Tranquility Large Water-to-Water (SWT) 20-80 ton?

Start with AV 2156 cool_temp_stp_1 (Bank chilled water target); AV 2155 heat_temp_stp_1 (Bank hot water target); BV 2069 reset_alarms_1 (Reset all module alarms); BV 2073 module_run_1 (Module running); AV 2158 sysmode_1 (Module mode); BV 2074 module_ok_1 (Module condition); AV 2147 loop1_leaving_temp_1 (Loop 1 leaving water temperature); BV 2075 manager_lockout_alrm_1 (Module locked out); AV 2167 mod_act_mod_alarms_1 (Active module alarms).

How do I enable BMS control of the ClimateMaster Tranquility Large Water-to-Water (SWT) 20-80 ton?

BV 2076 chiller_run_1 is the module enable from the bank controller; the manual does not describe a separate BMS enable.

Does the ClimateMaster Tranquility Large Water-to-Water (SWT) 20-80 ton need a BACnet heartbeat or have a communication timeout?

BV 2068 comm_lost_1 alarms when the module loses communication with the bank controller; BV 2152 mod_comm_tx_stat_1 shows the module's communication transmit status.

How do I check these points on the real Tranquility Large Water-to-Water (SWT) 20-80 ton?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More ClimateMaster BACnet points lists

Source: Tranquility Large Water-to-Water SWT Series - Installation, Operation & Maintenance Manual (Controller Points List) · C97B0004N07 · rev. 2026-03-09. Object names, instances and units are reproduced as published; descriptions are our own.