Modular water-to-water heat pump · BACnet points list
ClimateMaster Tranquility Large Water-to-Water (SWT) 20-80 ton BACnet points list
Updated 11 November 2026
Each SWT module controller works under a bank controller and can be read by a BMS over BACnet MS/TP or BACnet IP (Gig-E port only). The 159-point list is mostly status: circuit pressures, temperatures, superheat and subcool, EEV positions, loop valves and flows, compressor status and run time, out-of-range sensor flags and alarms, plus manual-mode test commands and the bank's leaving-water targets.
This page lists 159 BACnet objects for the ClimateMaster Tranquility Large Water-to-Water (SWT) 20-80 ton — 41 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from ClimateMaster’s own free documentation, linked below.
- Manufacturer
- ClimateMaster
- Model
- Tranquility Large Water-to-Water (SWT) 20-80 ton
- Equipment
- Modular water-to-water heat pump
- Equipment type
- Heat pumps
- BACnet objects
- 159 (41 writable)
- Transport
- BACnet MS/TP, BACnet IP
- Firmware
- Not stated
- Also known as
- SWT, Tranquility SWT, ClimateMaster SWT R-454B, ClimateMaster large water-to-water BACnet, C97B0004N07
Reference only, provided as-is: verify against ClimateMaster’s current documentation and the live device before use. Not official ClimateMaster information. Terms of use.
BMS integration notes: ClimateMaster Tranquility Large Water-to-Water (SWT) 20-80 ton
Set the module controller address on its three rotary switches and choose MS/TP with the Comm Selector rotary (position 1), or use the Gig-E port for BACnet IP. The modules are run by their bank controller; a BMS mainly monitors module status and alarms and can read or adjust the bank's leaving-water targets.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AV 2156 | cool_temp_stp_1 | Bank chilled water target | Write |
| AV 2155 | heat_temp_stp_1 | Bank hot water target | Write |
| BV 2069 | reset_alarms_1 | Reset all module alarms | Write |
| BV 2073 | module_run_1 | Module running | Read |
| AV 2158 | sysmode_1 | Module mode | Read |
| BV 2074 | module_ok_1 | Module condition | Read |
| AV 2147 | loop1_leaving_temp_1 | Loop 1 leaving water temperature | Read |
| BV 2075 | manager_lockout_alrm_1 | Module locked out | Read |
| AV 2167 | mod_act_mod_alarms_1 | Active module alarms | Read |
Enable & remote start
BV 2076 chiller_run_1 is the module enable from the bank controller; the manual does not describe a separate BMS enable.
Heartbeat & communication loss
BV 2068 comm_lost_1 alarms when the module loses communication with the bank controller; BV 2152 mod_comm_tx_stat_1 shows the module's communication transmit status.
Network setup
- Address: set the hundreds, tens and ones rotary switches to the controller address (for example 0-0-1 for 001), before powering the unit.
- Comm Selector rotary switch at 1 = BACnet MS/TP.
- BACnet IP is only on the Gig-E Ethernet port; connect a CAT 5e cable there.
Watch out for
- Manual-mode objects override normal control; check BV 2210 manual_mode_1 and AV 2175 man_mode_remain_time_1 before leaving a module.
- The list gives no engineering units; check them on the device.
ClimateMaster Tranquility Large Water-to-Water (SWT) 20-80 ton BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AV | 2143 | c1_cl_ll_temp_1 | Circuit 1's Cooling Liquid Line Temperature (C1 Cooling Liquid Line Temperature) | Read | ||
| AV | 2087 | c1_cool_mode_subcool_1 | Circuit 1's Subcool Temperature in Cool Mode (C1 Cool Mode SubCool) | Read | ||
| AV | 2139 | c1_disc_temp_1 | Circuit 1's Discharge Temperature (C1 Discharge Temperature) | Read | ||
| AV | 2135 | c1_disc_pres_1 | Circuit 1's Discharge Pressure (C1 Disch Pressure) | Read | ||
| AV | 2145 | c1_ht_ll_temp_1 | Circuit 1's Heating Liquid Line Temperature (C1 Heating Liquid Line Temperature) | Read | ||
| AV | 2088 | c1_heat_mode_subcool_1 | Circuit 1's Subcool Temperature in Heat Mode (C1 Heat Mode SubCool) | Read | ||
| AV | 2163 | c1_ll_pressure_1 | Circuit 1's Liquid Line Pressure in Cool Mode (C1 Liquid Line Pressure) | Read | ||
| AV | 2116 | c1_ll_press_heat_1 | Circuit 1's Liquid Line Pressure in Heat Mode (C1 Liquid Line Pressure Heat Stat) | Read | ||
| AV | 2137 | c1_suct_pres_1 | Circuit 1's Suction Pressure (C1 Suction Pressure) | Read | ||
| AV | 2141 | c1_suct_temp_1 | Circuit 1's Suction Temperature (C1 Suction Temperature) | Read | ||
| AV | 2144 | c2_cl_ll_temp_1 | Circuit 2's Cooling Liquid Line Temperature (C2 Cooling Liquid Line Temperature) | Read | ||
| AV | 2086 | c2_cool_mode_subcool_1 | Circuit 2's Subcool Temperature in Cool Mode (C2 Cool Mode SubCool) | Read | ||
| AV | 2140 | c2_disc_temp_1 | Circuit 2's Discharge Temperature (C2 Discharge Temperature) | Read | ||
| AV | 2136 | c2_disc_pres_1 | Circuit 2's Discharge Pressure (C2 Disch Pressure) | Read | ||
| AV | 2146 | c2_ht_ll_temp_1 | Circuit 2's Heating Liquid Line Temperature (C2 Heating Liquid Line Temperature) | Read | ||
| AV | 2089 | c2_heat_mode_subcool_1 | Circuit 2's Subcool Temperature in Heat Mode (C2 Heat Mode SubCool) | Read | ||
| AV | 2164 | c2_ll_pressure_1 | Circuit 2's Liquid Line Pressure in Cool Mode (C2 Liquid Line Pressure) | Read | ||
| AV | 2117 | c2_ll_press_heat_1 | Circuit 2's Liquid Line Pressure in Heat Mode (C2 Liquid Line PressureHeat Stat) | Read | ||
| AV | 2138 | c2_suct_pres_1 | Circuit 2's Suction Pressure (C2 Suction Pressure) | Read | ||
| AV | 2142 | c2_suct_temp_1 | Circuit 2's Suction Temperature (C2 Suction Temperature) | Read | ||
| AV | 2035 | c1_suc_superheat_1 | Circuit 1's Suction Superheat Temperature (Calc C1 Suc Superheat) | Read | ||
| AV | 2036 | c2_suc_superheat_1 | Circuit 2's Suction Superheat Temperature (Calc C2 Suc Superheat) | Read | ||
| AV | 2160 | chilled_design_delta_1 | Chilled Water Design Delta | Write | ||
| AV | 2077 | chiller_config_1 | Circuit 1's Module Type (Chiller Module Type) | Read | ||
| AV | 2037 | c1_runtime_1 | Compressor 1 Runtime (Comp 1 Runtime) | Read | ||
| AV | 2039 | c2_runtime_1 | Compressor 2 Runtime (Comp 2 Runtime) | Read | ||
| AV | 2161 | cooling_type_1 | Sets the Pressure Control Setpoints (Cooling Type) | Write | ||
| AVmin | 2156 | cool_temp_stp_1 | Bank's Chilled Water Target Setpoint (COOL LVG TRG) | Write | ||
| AV | 2004 | exv1_man_percent_1 | Circuit 1's EEV A Manual Percentage ONLY IN MANUAL Mode (EEV1 Manual Percentage) | Write | ||
| AV | 2006 | exv2_man_percent_1 | Circuit 1's EEV A Manual Percentage ONLY IN MANUAL Mode (EEV2 Manual Percentage) | Write | ||
| AV | 2240 | exvb1_man_percent_1 | Circuit 1's EEV B Manual Percentage ONLY IN MANUAL Mode (EEV B C1 Manual Percentage) | Write | ||
| AV | 2241 | exvb2_man_percent_1 | Circuit 1's EEV B Manual Percentage ONLY IN MANUAL Mode (EEV B C2 Manual Percentage) | Write | ||
| AV | 2371 | exv_a_c1_val_pos_1 | Circuit 1's EEV A Valve Position (EXVA C1 Valve position) | Read | ||
| AV | 2372 | exv_a_c2_val_pos_1 | Circuit 2's EEV A Valve Position (EXVA C2 Valve position) | Read | ||
| AV | 2242 | exva_c1_sh_1 | Circuit 1's EEV A Superheat (EXV A C1 Superheat) | Read | ||
| AV | 2243 | exva_c2_sh_1 | Circuit 2's EEV A Superheat (EXV A C2 Superheat) | Read | ||
| AV | 2373 | exv_b_c1_val_pos_1 | Circuit 1's EEV B Valve Position (EXVB C1 Valve position) | Read | ||
| AV | 2374 | exv_b_c2_val_pos_1 | Circuit 2's EEV B Valve Position (EXVB C2 Valve position) | Read | ||
| AV | 2244 | exvb_c1_sh_1 | Circuit 1's EEV B Superheat (EXV B C1 Superheat) | Read | ||
| AV | 2245 | exvb_c2_sh_1 | Circuit 2's EEV B Superheat (EXV B C2 Superheat) | Read | ||
| AVmin | 2155 | heat_temp_stp_1 | Hot Water Target Setpoint (HEAT LVG TRG) | Write | ||
| AV | 2159 | heating_design_delta_1 | Hot Water Design Delta | Write | ||
| AV | 2114 | loop2_man_percentage_1 | Loop 2 Valve Manual Percentage ONLY IN MANUAL Mode (Local Loop 2 Manual Percentage) | Write | ||
| AV | 2064 | loop1_entering_temp_1 | Loop1 Entering Water Temp | Read | ||
| AVmin | 2147 | loop1_leaving_temp_1 | Loop1 Leaving Water Temp | Read | ||
| AV | 2112 | loop1_man_percentage_1 | Loop 1 Valve Manual Percentage ONLY IN MANUAL Mode (Loop1 Manual Percentage) | Write | ||
| AV | 2091 | flow1_stat_1 | Loop 1 Flow Status | Read | ||
| AV | 2020 | loop1_mwv_out_1 | Loop 1 Valve Position Control (Loop 1 Motorized Water Valve Output) | Read | ||
| AV | 2084 | loop1_mwv1_stat_1 | Loop 1 Valve Position Status (Loop 1 MWV Status) | Read | ||
| AV | 2093 | flow2_stat_1 | Loop 2 Flow Status | Read | ||
| AV | 2126 | loop2_leaving_temp_1 | Loop 2 Leaving Water Temperature (Loop 2 Leaving Water Temp) | Read | ||
| AV | 2021 | loop2_mwv_out_1 | Loop 2 Valve Position Control (Loop 2 Motorized Water Valve Output) | Read | ||
| AV | 2085 | loop2_mwv1_stat_1 | Loop 2 Valve Position Status (Loop 2 MWV 2 Status) | Read | ||
| AV | 2175 | man_mode_remain_time_1 | Manual Mode Expiry Timer (Manual Mode Remaining Time) | Read | ||
| AV | 2239 | manual_sysmode_1 | Manual Mode Status (Manual Module Mode) | Write | ||
| AVmin | 2167 | mod_act_mod_alarms_1 | Module Active Alarms | Read | ||
| AV | 2166 | mod_act_comp_alarms_1 | Module Active Compressor Alarms | Read | ||
| AV | 2165 | mod_act_oor_alarms_1 | Module Active OOR Alarms | Read | ||
| AV | 2070 | mod_unload_stat_1 | Module Active Retries | Read | ||
| AV | 2151 | mod_comm_rx_stat_1 | Module Comm Read Status | Read | ||
| AV | 2157 | mod_lead_lag_order_1 | Module Lead Lag Order | Read | ||
| AVmin | 2158 | sysmode_1 | Module Mode | Read | ||
| BV | 2024 | alarm_out_1 | Alarm_Output | Read | ||
| BV | 2154 | brine_used_1 | Antifreeze | Read | ||
| BV | 2019 | c1_exv_a_en_out_1 | Circuit 1's EEV A Enable Status (C1 A EEV Enable Output) | Read | ||
| BV | 2239 | c1_disable_1 | Circuit 1's Disable Status (C1 Disable) | Read | ||
| BV | 2022 | c1_en_out_1 | Circuit 1's EEV B Enable Status (C1 Enable Output) | Read | ||
| BV | 2071 | c1_manual_1 | C1 Manual Enable (C1 Manual) | Write | ||
| BV | 2171 | c1_min_runtime_1 | Compressor 1 Minimum Required Runtime (C1 Minimum Run Time) | Read | ||
| BV | 2174 | c2_minimum_off_1 | Compressor 2 Off Delay Elapsed (C1 Compressor Off Delay) | Read | ||
| BV | 2031 | c1_ref_iso_solenoid_1 | Circuit 1's Refrigerant Isolation Solenoid Enable (C1 Ref Isolation Solenoid) | Read | ||
| BV | 2067 | c1_unload_1 | Compressor 1 in Retry (C1 Retry) | Read | ||
| BV | 2169 | c1_rv_out_1 | Circuit 1's Reversing Valve Enable (C1 RV Out) | Read | ||
| BV | 2190 | c1_shutdown_1 | Circuit 1's Shutdown Status (C1 Shutdown Status) | Read | ||
| BV | 2240 | c2_disable_1 | Compressor 2 Disabled (C2 Disable) | Read | ||
| BV | 2148 | c2_exv_a_en_out_1 | Circuit 2's EEV A Enable Status (C2 EEV A Enable Output) | Read | ||
| BV | 2023 | c2_en_out_1 | Circuit 2's EEV B Enable Status (C2 Enable Output) | Read | ||
| BV | 2029 | c2_exv_b_en_out_1 | Circuit 2's Heat EEV (C2 Heat EEV) | Read | ||
| BV | 2072 | c2_manual_1 | C2 Manual Enable (C2 Manual) | Write | ||
| BV | 2172 | c2_min_runtime_1 | Compressor 2 Minimum Required Runtime (C2 Minimum Run Time) | Read | ||
| BV | 2032 | c2_ref_iso_solenoid_1 | Circuit 2's Refrigerant Isolation Solenoid Enable (C2 Ref Isolation Solenoid Stat) | Read | ||
| BV | 2041 | reset_c2_runtime_1 | Compressor 2 Runtime Reset (C2 Runtime Reset) | Write | ||
| BV | 2170 | c2_rv_out_1 | Circuit 2's Reversing Valve Enable (C2 RV Out) | Read | ||
| BV | 2191 | c2_shutdown_1 | Circuit 2's Shutdown Status (C2 Shutdown Status) | Read | ||
| BV | 2076 | chiller_run_1 | Module enable from Bank (Chiller Run) | Write | ||
| BV | 2168 | clear_fault_history_1 | Module Fault History Clear (Clear Fault History) | Write | ||
| BV | 2123 | comp1_fail_1 | Compressor 1 Fail (Comp 1 Fail) | Read | ||
| BV | 2054 | comp_1_go_1 | Compressor 1 Bank Command (Comp 1 Go Command) | Write | ||
| BV | 2056 | c1_stat_1 | Compressor 1 Status (Comp 1 Status) | Read | ||
| BV | 2055 | comp_2_go_1 | Compressor 2 Bank Command (Comp 2 Go Command) | Write | ||
| BV | 2057 | c2_stat_1 | Compressor 2 Status (Comp 2 Status) | Read | ||
| BV | 2040 | comp2_fail_1 | Compressor 2 Fail | Read | ||
| BV | 2173 | c1_minimum_off_1 | Compresor Required Minimum Off Time (Compressor Off Delay) | Read | ||
| BV | 2005 | exv1_manual_1 | Circuit 1's EEV A Manual Control (EEV1 Manual Control) | Write | ||
| BV | 2007 | exv2_manual_1 | Circuit 2's EEV A Manual Control (EEV2 Manual Control) | Write | ||
| BV | 2242 | exvb1_manual_1 | Circuit 1's EEV B Manual Control (EEV B C1 Manual Control) | Write | ||
| BV | 2243 | exvb2_manual_1 | Circuit 2's EEV B Manual Control (EEV B C2 Manual Control) | Write | ||
| BV | 2000 | bbvp_eev_c1_man_en_1 | EEV A Fully Open Manual (EEV C1 Manual EN) | Write | ||
| BV | 2001 | bbvp_eev_c2_man_en_1 | EEV B Fully Open Manual (EEV C2 Manual EN) | Write | ||
| BV | 2162 | fixed_disc_press_en_1 | Fixed Head Pressure Control (Enable Fixed Head Pressure Control) | Write | ||
| BV | 2177 | enable_ftr_1 | StandAlone Mode (Fail to Run Enable) | Write | ||
| BV | 2209 | lock_loop1_open_1 | Lock Loop 1 Open | Write | ||
| BV | 2113 | loop1_manual_1 | Loop1 Manual Control | Write | ||
| BV | 2111 | loop1_bypass_mod_1 | Loop1 Valve Bypass Module | Write | ||
| BV | 2108 | loop1_valve_status_1 | Loop 1 Valve Status | Read | ||
| BV | 2115 | loop2_manual_1 | Loop 2 Manual Valve Control | Write | ||
| BV | 2109 | loop2_valve_status_1 | Loop 2 Valve Status | Read | ||
| BV | 2180 | c1_man_hgs_1 | Manual C1 Hot Gas Solenoid | Write | ||
| BV | 2002 | c1_man_li_1 | Manual C1 Hot Gas Solenoid | Write | ||
| BV | 2003 | c2_man_li_1 | Manual C1 Liquid Injection | Write | ||
| BV | 2184 | c1_man_ref_iso_1 | Manual C1 Refrigeration Isolation Solenoid | Write | ||
| BV | 2182 | c1_man_rev_valve_1 | Manual C1 Reversing Valve | Write | ||
| BV | 2181 | c2_man_hgs_1 | Manual C2 Hot Gas Solenoid | Write | ||
| BV | 2185 | c2_man_ref_iso_1 | Manual C2 Refrigeration Isolation Solenoid | Write | ||
| BV | 2183 | c2_man_rev_valve_1 | Manual C2 Reversing Valve | Write | ||
| BV | 2210 | manual_mode_1 | Operating Mode in Manual Mode (Manual Mode) | Write | ||
| BV | 2152 | mod_comm_tx_stat_1 | Bank Module Communication Watchdog Timer (Module Communication Transmit Status) | Read | ||
| BV | 2110 | mot_wtr_vlv_fail_1 | Motorized Valve Failure in Module (Module Failure Mot Valve) | Read | ||
| BV | 2090 | modflow1_1 | Flow Detection on Loop 1 (Module Flow 1 Status) | Read | ||
| BV | 2246 | modflow2_1 | Flow Detection on Loop 2 (Module Flow Status 2) | Read | ||
| BVmin | 2074 | module_ok_1 | Module Condition (Module Ok) | Read | ||
| BVmin | 2073 | module_run_1 | Module Run Status (Module Run) | Read | ||
| BV | 2134 | phase_stat_1 | Module Phase Status (Phase OK Status) | Read | ||
| BV | 2178 | rds_alarm_1 | Module RDS Alarm (RDS Alarm) | Read | ||
| BVmin | 2069 | reset_alarms_1 | Reset All Module Alarms | Write | ||
| BV | 2049 | c1_discharge_pressure_oor_1 | Circuit 1 Discharge Pressure OOR (C1 Discharge Pressure OOR) | Read | ||
| BV | 2605 | c1_discharge_temperature_oor_1 | Circuit 1 Discharge Temperature OOR (C1 Discharge Temperature OOR) | Read | ||
| BV | 2062 | c1_liquid_pressure_oor_1 | Circuit 1 Liquid Line pressure OOR (C1 Liquid Line pressure OOR) | Read | ||
| BV | 2060 | c1_liquid_line_temp_oor_1 | Circuit 1 Liquid Line Temp OOR (C1 Liquid Line Temp OOR) | Read | ||
| BV | 2130 | c1p2_oor_1 | Circuit 1 Suction Pressure Out of Range (C1 Suction Pressure Out of Range) | Read | ||
| BV | 2052 | c1_suction_temperature_oor_1 | Circuit 1 Suction Temperature OOR (C1 Suction Temperature OOR) | Read | ||
| BV | 2050 | c2_discharge_pressure_oor_1 | Circuit 2 Discharge Pressure OOR (C2 Discharge Pressure OOR) | Read | ||
| BV | 2051 | c2_discharge_temperature_oor_1 | Circuit 2 Discharge Temperature OOR (C2 Discharge Temperature OOR) | Read | ||
| BV | 2063 | c2lp_oor_1 | Circuit 2 Liquid Line Press Out of Range (C2 Liquid Line Press Out of Range) | Read | ||
| BV | 2061 | c2_liquid_line_temperature_oor_1 | Circuit 2 Liquid Line Temperature OOR (C2 Liquid Line Temperature OOR) | Read | ||
| BV | 2131 | c2p2_oor_1 | Circuit 2 Suction Pressure Out of Range (C2 Suction Pressure Out of Range) | Read | ||
| BV | 2053 | c2_suction_temperature_oor_1 | Circuit 2 Suction Temperature OOR (C2 Suction Temperature OOR) | Read | ||
| BV | 2068 | comm_lost_1 | No communication with Bank alarm (Communications Alarm) | Read | ||
| BV | 2132 | c1_eev_comm_loss_alarm_1 | Circuit 1 EEV Comm Loss Alarm (Compressor 1 EEV Comm Loss Alarm) | Read | ||
| BV | 2045 | c1_hi_disch_tmp_1 | Circuit 1 High Discharge Temperature Alarm (Compressor 1 High Discharge Temp) | Read | ||
| BV | 2048 | c1_hi_pres_alm_1 | Circuit 1 High Discharge Pressure Alarm (Compressor 1 High Pressure Alarm) | Read | ||
| BV | 2046 | c1_low_suc_pres_alm_1 | Circuit 1 Low Suction Pressure Alarm (Compressor 1 Low Suction Pressure Alarm) | Read | ||
| BV | 2042 | c1_no_run_1 | Compressor 1 NO-Run Alarm | Read | ||
| BV | 2133 | c2_eev_comm_loss_alarm_1 | Circuit 2 EEV Comm Loss Alarm (Compressor 2 EEV Comm Loss Alarm) | Read | ||
| BV | 2044 | c2_hi_disch_tmp_1 | Circuit 2 High Discharge Temperature Alarm (Compressor 2 High Discharge Temp) | Read | ||
| BV | 2047 | c2_hi_pres_alm_1 | Circuit 2 High Discharge Pressure Alarm (Compressor 2 High Pressure Alarm) | Read | ||
| BV | 2118 | c2_low_suc_pres_alm_1 | Circuit 2 Low Suction Pressure Alarm (Compressor 2 Low Suction Pressure Alarm) | Read | ||
| BV | 2043 | c2_no_run_1 | Compressor 2 NO-Run Alarm | Read | ||
| BV | 2106 | loop1_valve_alarm_1 | Loop 1 Motorized Valve Alarm | Read | ||
| BV | 2107 | loop2_valve_alarm_1 | Loop 2 Motorized Valve Alarm | Read | ||
| BV | 2094 | module_flow1_alarm_1 | Module Flow 1 Alarm | Read | ||
| BV | 2247 | module_flow2_alarm_1 | Module Flow 2 Alarm | Read | ||
| BVmin | 2075 | manager_lockout_alrm_1 | Module Locked Out (Module Lockout) | Read | ||
| BV | 2120 | phase_loss_alarm_1 | Phase Loss Alarm | Read | ||
| BV | 2179 | rds_shutdown_alarm_1 | RDS Shutdown Alarm | Read | ||
| BV | 2186 | vfd1_genfault_alm_1 | VFD 1 General Alarm | Read | ||
| BV | 2188 | vfd1_sto_alm_1 | VFD 1 STO Alarm | Read | ||
| BV | 2187 | vfd2_genfault_alm_1 | VFD 2 General Alarm | Read | ||
| BV | 2189 | vfd2_sto_alm_1 | VFD 2 STO Alarm | Read |
No points match these filters.
Object ID lookup: ClimateMaster Tranquility SWT point IDs by name
AV2143c1_cl_ll_temp_1AV2087c1_cool_mode_subcool_1AV2139c1_disc_temp_1AV2135c1_disc_pres_1AV2145c1_ht_ll_temp_1AV2088c1_heat_mode_subcool_1AV2163c1_ll_pressure_1AV2116c1_ll_press_heat_1AV2137c1_suct_pres_1AV2141c1_suct_temp_1AV2144c2_cl_ll_temp_1AV2086c2_cool_mode_subcool_1AV2140c2_disc_temp_1AV2136c2_disc_pres_1AV2146c2_ht_ll_temp_1AV2089c2_heat_mode_subcool_1AV2164c2_ll_pressure_1AV2117c2_ll_press_heat_1AV2138c2_suct_pres_1AV2142c2_suct_temp_1AV2035c1_suc_superheat_1AV2036c2_suc_superheat_1AV2160chilled_design_delta_1AV2077chiller_config_1AV2037c1_runtime_1AV2039c2_runtime_1AV2161cooling_type_1AV2156cool_temp_stp_1AV2004exv1_man_percent_1AV2006exv2_man_percent_1AV2240exvb1_man_percent_1AV2241exvb2_man_percent_1AV2371exv_a_c1_val_pos_1AV2372exv_a_c2_val_pos_1AV2242exva_c1_sh_1AV2243exva_c2_sh_1AV2373exv_b_c1_val_pos_1AV2374exv_b_c2_val_pos_1AV2244exvb_c1_sh_1AV2245exvb_c2_sh_1AV2155heat_temp_stp_1AV2159heating_design_delta_1AV2114loop2_man_percentage_1AV2064loop1_entering_temp_1AV2147loop1_leaving_temp_1AV2112loop1_man_percentage_1AV2091flow1_stat_1AV2020loop1_mwv_out_1AV2084loop1_mwv1_stat_1AV2093flow2_stat_1AV2126loop2_leaving_temp_1AV2021loop2_mwv_out_1AV2085loop2_mwv1_stat_1AV2175man_mode_remain_time_1AV2239manual_sysmode_1AV2167mod_act_mod_alarms_1AV2166mod_act_comp_alarms_1AV2165mod_act_oor_alarms_1AV2070mod_unload_stat_1AV2151mod_comm_rx_stat_1AV2157mod_lead_lag_order_1AV2158sysmode_1BV2024alarm_out_1BV2154brine_used_1BV2019c1_exv_a_en_out_1BV2239c1_disable_1BV2022c1_en_out_1BV2071c1_manual_1BV2171c1_min_runtime_1BV2174c2_minimum_off_1BV2031c1_ref_iso_solenoid_1BV2067c1_unload_1BV2169c1_rv_out_1BV2190c1_shutdown_1BV2240c2_disable_1BV2148c2_exv_a_en_out_1BV2023c2_en_out_1BV2029c2_exv_b_en_out_1BV2072c2_manual_1BV2172c2_min_runtime_1BV2032c2_ref_iso_solenoid_1BV2041reset_c2_runtime_1BV2170c2_rv_out_1BV2191c2_shutdown_1BV2076chiller_run_1BV2168clear_fault_history_1BV2123comp1_fail_1BV2054comp_1_go_1BV2056c1_stat_1BV2055comp_2_go_1BV2057c2_stat_1BV2040comp2_fail_1BV2173c1_minimum_off_1BV2005exv1_manual_1BV2007exv2_manual_1BV2242exvb1_manual_1BV2243exvb2_manual_1BV2000bbvp_eev_c1_man_en_1BV2001bbvp_eev_c2_man_en_1BV2162fixed_disc_press_en_1BV2177enable_ftr_1BV2209lock_loop1_open_1BV2113loop1_manual_1BV2111loop1_bypass_mod_1BV2108loop1_valve_status_1BV2115loop2_manual_1BV2109loop2_valve_status_1BV2180c1_man_hgs_1BV2002c1_man_li_1BV2003c2_man_li_1BV2184c1_man_ref_iso_1BV2182c1_man_rev_valve_1BV2181c2_man_hgs_1BV2185c2_man_ref_iso_1BV2183c2_man_rev_valve_1BV2210manual_mode_1BV2152mod_comm_tx_stat_1BV2110mot_wtr_vlv_fail_1BV2090modflow1_1BV2246modflow2_1BV2074module_ok_1BV2073module_run_1BV2134phase_stat_1BV2178rds_alarm_1BV2069reset_alarms_1BV2049c1_discharge_pressure_oor_1BV2605c1_discharge_temperature_oor_1BV2062c1_liquid_pressure_oor_1BV2060c1_liquid_line_temp_oor_1BV2130c1p2_oor_1BV2052c1_suction_temperature_oor_1BV2050c2_discharge_pressure_oor_1BV2051c2_discharge_temperature_oor_1BV2063c2lp_oor_1BV2061c2_liquid_line_temperature_oor_1BV2131c2p2_oor_1BV2053c2_suction_temperature_oor_1BV2068comm_lost_1BV2132c1_eev_comm_loss_alarm_1BV2045c1_hi_disch_tmp_1BV2048c1_hi_pres_alm_1BV2046c1_low_suc_pres_alm_1BV2042c1_no_run_1BV2133c2_eev_comm_loss_alarm_1BV2044c2_hi_disch_tmp_1BV2047c2_hi_pres_alm_1BV2118c2_low_suc_pres_alm_1BV2043c2_no_run_1BV2106loop1_valve_alarm_1BV2107loop2_valve_alarm_1BV2094module_flow1_alarm_1BV2247module_flow2_alarm_1BV2075manager_lockout_alrm_1BV2120phase_loss_alarm_1BV2179rds_shutdown_alarm_1BV2186vfd1_genfault_alm_1BV2188vfd1_sto_alm_1BV2187vfd2_genfault_alm_1BV2189vfd2_sto_alm_1
Integration notes
- The list has no read/write or units column. Access is inferred from the description: setpoints, targets, manual-mode controls, resets and enables are marked writable, everything else read-only.
- Descriptions are the list's own Description column; when the Name column says something different it is shown in brackets.
- Several points (EEV, valve, solenoid and reversing-valve 'Manual' objects) only act when the module is in manual mode.
- The list has some label slips that are kept as printed: c1_man_hgs_1 and c1_man_li_1 are both labelled Manual C1 Hot Gas Solenoid, c2_man_li_1 is labelled Manual C1 Liquid Injection, and BV:2174 c2_minimum_off_1 is labelled C1 Compressor Off Delay.
- AV:2239 manual_sysmode_1 and BV:2239 c1_disable_1 share instance 2239 in different object types, as printed.
- Object names end in _1 as printed.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Tranquility Large Water-to-Water (SWT) 20-80 ton and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the ClimateMaster Tranquility Large Water-to-Water (SWT) 20-80 ton
How many BACnet points does the ClimateMaster Tranquility Large Water-to-Water (SWT) 20-80 ton have?
This list has 159 BACnet objects: 62 analog values, 97 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which ClimateMaster Tranquility Large Water-to-Water (SWT) 20-80 ton BACnet points are writable?
41 of the 159 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.
Where is the official ClimateMaster Tranquility Large Water-to-Water (SWT) 20-80 ton BACnet documentation?
The source is Tranquility Large Water-to-Water SWT Series - Installation, Operation & Maintenance Manual (Controller Points List) (C97B0004N07), revision 2026-03-09, published free by ClimateMaster at https://files.climatemaster.com/Commercial/Water-to-Water-Units/Tranquility/SWT/Resources/C97B0004N07-SWT-IOM.pdf.
What are the minimum BACnet points to integrate the ClimateMaster Tranquility Large Water-to-Water (SWT) 20-80 ton?
Start with AV 2156 cool_temp_stp_1 (Bank chilled water target); AV 2155 heat_temp_stp_1 (Bank hot water target); BV 2069 reset_alarms_1 (Reset all module alarms); BV 2073 module_run_1 (Module running); AV 2158 sysmode_1 (Module mode); BV 2074 module_ok_1 (Module condition); AV 2147 loop1_leaving_temp_1 (Loop 1 leaving water temperature); BV 2075 manager_lockout_alrm_1 (Module locked out); AV 2167 mod_act_mod_alarms_1 (Active module alarms).
How do I enable BMS control of the ClimateMaster Tranquility Large Water-to-Water (SWT) 20-80 ton?
BV 2076 chiller_run_1 is the module enable from the bank controller; the manual does not describe a separate BMS enable.
Does the ClimateMaster Tranquility Large Water-to-Water (SWT) 20-80 ton need a BACnet heartbeat or have a communication timeout?
BV 2068 comm_lost_1 alarms when the module loses communication with the bank controller; BV 2152 mod_comm_tx_stat_1 shows the module's communication transmit status.
How do I check these points on the real Tranquility Large Water-to-Water (SWT) 20-80 ton?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More ClimateMaster BACnet points lists
- DOAS (dedicated outdoor air system) controller
ClimateMaster Commercial DOAS with CM3500 controller
ClimateMaster commercial dedicated outdoor air units with the CM3500 controller, program version 3.2.0 and later.
Also known as: CM3500, ClimateMaster DOAS, DOAS CM3500 Controller, 97B0065N01 - Water-source heat pump controller
ClimateMaster MPC Multi-Protocol DDC Controller - Water-to-Air (Gen 7 and newer)
ClimateMaster water-to-air (water-source) heat pumps with the MPC controller, Gen 7 and newer.
Also known as: MPC, ClimateMaster MPC, 97B0031N01, Multi-Protocol Controller, CXM2, DXM2.6 - Water-to-water heat pump controller
ClimateMaster MPC Multi-Protocol DDC Controller - Water-to-Water (Gen 8 and newer)
ClimateMaster water-to-water heat pumps with the MPC controller, Gen 8 and newer.
Also known as: MPC, ClimateMaster MPC, 97B0031N01, Multi-Protocol Controller, CXM2, DXM2.6 - Modular water-to-water heat pump
ClimateMaster Tranquility Large Water-to-Water (TMW) 360-840
ClimateMaster Tranquility Large Water-to-Water (TMW) modules, models 360-840, with the factory IO FLEX6126 + EX8160 controller.
Also known as: TMW, TMW360, TMW600, TMW840, Tranquility TMW, ClimateMaster modular water-to-water BACnet, IO FLEX6126, 97B0090N01
Source: Tranquility Large Water-to-Water SWT Series - Installation, Operation & Maintenance Manual (Controller Points List) · C97B0004N07 · rev. 2026-03-09. Object names, instances and units are reproduced as published; descriptions are our own.