 "manufacturer": "ClimateMaster",
 "manufacturer_slug": "climatemaster",
 "model": "Tranquility Large Water-to-Water (SWT) 20-80 ton",
 "short_model": "Tranquility SWT",
 "model_slug": "tranquility-swt-large-water-to-water",
 "aliases": [
  "SWT",
  "Tranquility SWT",
  "ClimateMaster SWT R-454B",
  "ClimateMaster large water-to-water BACnet",
  "C97B0004N07"
 ],
 "equipment_type": "Modular water-to-water heat pump",
 "applies_to": "ClimateMaster Tranquility Large Water-to-Water (SWT) modules, 20-80 tons, R-454B, with the factory module controller.",
 "summary": "Each SWT module controller works under a bank controller and can be read by a BMS over BACnet MS/TP or BACnet IP (Gig-E port only). The 159-point list is mostly status: circuit pressures, temperatures, superheat and subcool, EEV positions, loop valves and flows, compressor status and run time, out-of-range sensor flags and alarms, plus manual-mode test commands and the bank's leaving-water targets.",
 "bacnet_transport": [
  "BACnet MS/TP",
  "BACnet IP"
 ],
 "firmware": null,
 "default_device_instance": null,
 "access_inferred": true,
 "notes": [
  "The list has no read/write or units column. Access is inferred from the description: setpoints, targets, manual-mode controls, resets and enables are marked writable, everything else read-only.",
  "Descriptions are the list's own Description column; when the Name column says something different it is shown in brackets.",
  "Several points (EEV, valve, solenoid and reversing-valve 'Manual' objects) only act when the module is in manual mode.",
  "The list has some label slips that are kept as printed: c1_man_hgs_1 and c1_man_li_1 are both labelled Manual C1 Hot Gas Solenoid, c2_man_li_1 is labelled Manual C1 Liquid Injection, and BV:2174 c2_minimum_off_1 is labelled C1 Compressor Off Delay.",
  "AV:2239 manual_sysmode_1 and BV:2239 c1_disable_1 share instance 2239 in different object types, as printed.",
  "Object names end in _1 as printed."
 ],
 "source": {
  "title": "Tranquility Large Water-to-Water SWT Series - Installation, Operation & Maintenance Manual (Controller Points List)",
  "doc_number": "C97B0004N07",
  "revision_date": "2026-03-09",
  "url": "https://files.climatemaster.com/Commercial/Water-to-Water-Units/Tranquility/SWT/Resources/C97B0004N07-SWT-IOM.pdf"
 },
 "integration": {
  "summary": "Set the module controller address on its three rotary switches and choose MS/TP with the Comm Selector rotary (position 1), or use the Gig-E port for BACnet IP. The modules are run by their bank controller; a BMS mainly monitors module status and alarms and can read or adjust the bank's leaving-water targets.",
  "minimum_points": [
   {
    "ref": "AV 2156",
    "name": "cool_temp_stp_1",
    "why": "Bank chilled water target"
   },
   {
    "ref": "AV 2155",
    "name": "heat_temp_stp_1",
    "why": "Bank hot water target"
   },
   {
    "ref": "BV 2069",
    "name": "reset_alarms_1",
    "why": "Reset all module alarms"
   },
   {
    "ref": "BV 2073",
    "name": "module_run_1",
    "why": "Module running"
   },
   {
    "ref": "AV 2158",
    "name": "sysmode_1",
    "why": "Module mode"
   },
   {
    "ref": "BV 2074",
    "name": "module_ok_1",
    "why": "Module condition"
   },
   {
    "ref": "AV 2147",
    "name": "loop1_leaving_temp_1",
    "why": "Loop 1 leaving water temperature"
   },
   {
    "ref": "BV 2075",
    "name": "manager_lockout_alrm_1",
    "why": "Module locked out"
   },
   {
    "ref": "AV 2167",
    "name": "mod_act_mod_alarms_1",
    "why": "Active module alarms"
   }
  ],
  "enable": "BV 2076 chiller_run_1 is the module enable from the bank controller; the manual does not describe a separate BMS enable.",
  "heartbeat": "BV 2068 comm_lost_1 alarms when the module loses communication with the bank controller; BV 2152 mod_comm_tx_stat_1 shows the module's communication transmit status.",
  "remote_sensors": null,
  "setup": [
   "Address: set the hundreds, tens and ones rotary switches to the controller address (for example 0-0-1 for 001), before powering the unit.",
   "Comm Selector rotary switch at 1 = BACnet MS/TP.",
   "BACnet IP is only on the Gig-E Ethernet port; connect a CAT 5e cable there."
  ],
  "gotchas": [
   "Manual-mode objects override normal control; check BV 2210 manual_mode_1 and AV 2175 man_mode_remain_time_1 before leaving a module.",
   "The list gives no engineering units; check them on the device."
  ]
 },
 "points": [
  {
   "type": "AV",
   "instance": 2143,
   "name": "c1_cl_ll_temp_1",
   "description": "Circuit 1's Cooling Liquid Line Temperature (C1 Cooling Liquid Line Temperature)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2087,
   "name": "c1_cool_mode_subcool_1",
   "description": "Circuit 1's Subcool Temperature in Cool Mode (C1 Cool Mode SubCool)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2139,
   "name": "c1_disc_temp_1",
   "description": "Circuit 1's Discharge Temperature (C1 Discharge Temperature)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2135,
   "name": "c1_disc_pres_1",
   "description": "Circuit 1's Discharge Pressure (C1 Disch Pressure)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2145,
   "name": "c1_ht_ll_temp_1",
   "description": "Circuit 1's Heating Liquid Line Temperature (C1 Heating Liquid Line Temperature)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2088,
   "name": "c1_heat_mode_subcool_1",
   "description": "Circuit 1's Subcool Temperature in Heat Mode (C1 Heat Mode SubCool)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2163,
   "name": "c1_ll_pressure_1",
   "description": "Circuit 1's Liquid Line Pressure in Cool Mode (C1 Liquid Line Pressure)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2116,
   "name": "c1_ll_press_heat_1",
   "description": "Circuit 1's Liquid Line Pressure in Heat Mode (C1 Liquid Line Pressure Heat Stat)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2137,
   "name": "c1_suct_pres_1",
   "description": "Circuit 1's Suction Pressure (C1 Suction Pressure)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2141,
   "name": "c1_suct_temp_1",
   "description": "Circuit 1's Suction Temperature (C1 Suction Temperature)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2144,
   "name": "c2_cl_ll_temp_1",
   "description": "Circuit 2's Cooling Liquid Line Temperature (C2 Cooling Liquid Line Temperature)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2086,
   "name": "c2_cool_mode_subcool_1",
   "description": "Circuit 2's Subcool Temperature in Cool Mode (C2 Cool Mode SubCool)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2140,
   "name": "c2_disc_temp_1",
   "description": "Circuit 2's Discharge Temperature (C2 Discharge Temperature)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2136,
   "name": "c2_disc_pres_1",
   "description": "Circuit 2's Discharge Pressure (C2 Disch Pressure)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2146,
   "name": "c2_ht_ll_temp_1",
   "description": "Circuit 2's Heating Liquid Line Temperature (C2 Heating Liquid Line Temperature)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2089,
   "name": "c2_heat_mode_subcool_1",
   "description": "Circuit 2's Subcool Temperature in Heat Mode (C2 Heat Mode SubCool)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2164,
   "name": "c2_ll_pressure_1",
   "description": "Circuit 2's Liquid Line Pressure in Cool Mode (C2 Liquid Line Pressure)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2117,
   "name": "c2_ll_press_heat_1",
   "description": "Circuit 2's Liquid Line Pressure in Heat Mode (C2 Liquid Line PressureHeat Stat)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2138,
   "name": "c2_suct_pres_1",
   "description": "Circuit 2's Suction Pressure (C2 Suction Pressure)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2142,
   "name": "c2_suct_temp_1",
   "description": "Circuit 2's Suction Temperature (C2 Suction Temperature)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2035,
   "name": "c1_suc_superheat_1",
   "description": "Circuit 1's Suction Superheat Temperature (Calc C1 Suc Superheat)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2036,
   "name": "c2_suc_superheat_1",
   "description": "Circuit 2's Suction Superheat Temperature (Calc C2 Suc Superheat)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2160,
   "name": "chilled_design_delta_1",
   "description": "Chilled Water Design Delta",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2077,
   "name": "chiller_config_1",
   "description": "Circuit 1's Module Type (Chiller Module Type)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2037,
   "name": "c1_runtime_1",
   "description": "Compressor 1 Runtime (Comp 1 Runtime)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2039,
   "name": "c2_runtime_1",
   "description": "Compressor 2 Runtime (Comp 2 Runtime)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2161,
   "name": "cooling_type_1",
   "description": "Sets the Pressure Control Setpoints (Cooling Type)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2156,
   "name": "cool_temp_stp_1",
   "description": "Bank's Chilled Water Target Setpoint (COOL LVG TRG)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2004,
   "name": "exv1_man_percent_1",
   "description": "Circuit 1's EEV A Manual Percentage ONLY IN MANUAL Mode (EEV1 Manual Percentage)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2006,
   "name": "exv2_man_percent_1",
   "description": "Circuit 1's EEV A Manual Percentage ONLY IN MANUAL Mode (EEV2 Manual Percentage)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2240,
   "name": "exvb1_man_percent_1",
   "description": "Circuit 1's EEV B Manual Percentage ONLY IN MANUAL Mode (EEV B C1 Manual Percentage)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2241,
   "name": "exvb2_man_percent_1",
   "description": "Circuit 1's EEV B Manual Percentage ONLY IN MANUAL Mode (EEV B C2 Manual Percentage)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2371,
   "name": "exv_a_c1_val_pos_1",
   "description": "Circuit 1's EEV A Valve Position (EXVA C1 Valve position)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2372,
   "name": "exv_a_c2_val_pos_1",
   "description": "Circuit 2's EEV A Valve Position (EXVA C2 Valve position)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2242,
   "name": "exva_c1_sh_1",
   "description": "Circuit 1's EEV A Superheat (EXV A C1 Superheat)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2243,
   "name": "exva_c2_sh_1",
   "description": "Circuit 2's EEV A Superheat (EXV A C2 Superheat)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2373,
   "name": "exv_b_c1_val_pos_1",
   "description": "Circuit 1's EEV B Valve Position (EXVB C1 Valve position)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2374,
   "name": "exv_b_c2_val_pos_1",
   "description": "Circuit 2's EEV B Valve Position (EXVB C2 Valve position)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2244,
   "name": "exvb_c1_sh_1",
   "description": "Circuit 1's EEV B Superheat (EXV B C1 Superheat)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2245,
   "name": "exvb_c2_sh_1",
   "description": "Circuit 2's EEV B Superheat (EXV B C2 Superheat)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2155,
   "name": "heat_temp_stp_1",
   "description": "Hot Water Target Setpoint (HEAT LVG TRG)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2159,
   "name": "heating_design_delta_1",
   "description": "Hot Water Design Delta",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2114,
   "name": "loop2_man_percentage_1",
   "description": "Loop 2 Valve Manual Percentage ONLY IN MANUAL Mode (Local Loop 2 Manual Percentage)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2064,
   "name": "loop1_entering_temp_1",
   "description": "Loop1 Entering Water Temp",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2147,
   "name": "loop1_leaving_temp_1",
   "description": "Loop1 Leaving Water Temp",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2112,
   "name": "loop1_man_percentage_1",
   "description": "Loop 1 Valve Manual Percentage ONLY IN MANUAL Mode (Loop1 Manual Percentage)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2091,
   "name": "flow1_stat_1",
   "description": "Loop 1 Flow Status",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2020,
   "name": "loop1_mwv_out_1",
   "description": "Loop 1 Valve Position Control (Loop 1 Motorized Water Valve Output)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2084,
   "name": "loop1_mwv1_stat_1",
   "description": "Loop 1 Valve Position Status (Loop 1 MWV Status)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2093,
   "name": "flow2_stat_1",
   "description": "Loop 2 Flow Status",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2126,
   "name": "loop2_leaving_temp_1",
   "description": "Loop 2 Leaving Water Temperature (Loop 2 Leaving Water Temp)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2021,
   "name": "loop2_mwv_out_1",
   "description": "Loop 2 Valve Position Control (Loop 2 Motorized Water Valve Output)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2085,
   "name": "loop2_mwv1_stat_1",
   "description": "Loop 2 Valve Position Status (Loop 2 MWV 2 Status)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2175,
   "name": "man_mode_remain_time_1",
   "description": "Manual Mode Expiry Timer (Manual Mode Remaining Time)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2239,
   "name": "manual_sysmode_1",
   "description": "Manual Mode Status (Manual Module Mode)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2167,
   "name": "mod_act_mod_alarms_1",
   "description": "Module Active Alarms",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2166,
   "name": "mod_act_comp_alarms_1",
   "description": "Module Active Compressor Alarms",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2165,
   "name": "mod_act_oor_alarms_1",
   "description": "Module Active OOR Alarms",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2070,
   "name": "mod_unload_stat_1",
   "description": "Module Active Retries",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2151,
   "name": "mod_comm_rx_stat_1",
   "description": "Module Comm Read Status",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2157,
   "name": "mod_lead_lag_order_1",
   "description": "Module Lead Lag Order",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2158,
   "name": "sysmode_1",
   "description": "Module Mode",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2024,
   "name": "alarm_out_1",
   "description": "Alarm_Output",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2154,
   "name": "brine_used_1",
   "description": "Antifreeze",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2019,
   "name": "c1_exv_a_en_out_1",
   "description": "Circuit 1's EEV A Enable Status (C1 A EEV Enable Output)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2239,
   "name": "c1_disable_1",
   "description": "Circuit 1's Disable Status (C1 Disable)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2022,
   "name": "c1_en_out_1",
   "description": "Circuit 1's EEV B Enable Status (C1 Enable Output)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2071,
   "name": "c1_manual_1",
   "description": "C1 Manual Enable (C1 Manual)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2171,
   "name": "c1_min_runtime_1",
   "description": "Compressor 1 Minimum Required Runtime (C1 Minimum Run Time)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2174,
   "name": "c2_minimum_off_1",
   "description": "Compressor 2 Off Delay Elapsed (C1 Compressor Off Delay)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2031,
   "name": "c1_ref_iso_solenoid_1",
   "description": "Circuit 1's Refrigerant Isolation Solenoid Enable (C1 Ref Isolation Solenoid)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2067,
   "name": "c1_unload_1",
   "description": "Compressor 1 in Retry (C1 Retry)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2169,
   "name": "c1_rv_out_1",
   "description": "Circuit 1's Reversing Valve Enable (C1 RV Out)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2190,
   "name": "c1_shutdown_1",
   "description": "Circuit 1's Shutdown Status (C1 Shutdown Status)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2240,
   "name": "c2_disable_1",
   "description": "Compressor 2 Disabled (C2 Disable)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2148,
   "name": "c2_exv_a_en_out_1",
   "description": "Circuit 2's EEV A Enable Status (C2 EEV A Enable Output)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2023,
   "name": "c2_en_out_1",
   "description": "Circuit 2's EEV B Enable Status (C2 Enable Output)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2029,
   "name": "c2_exv_b_en_out_1",
   "description": "Circuit 2's Heat EEV (C2 Heat EEV)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2072,
   "name": "c2_manual_1",
   "description": "C2 Manual Enable (C2 Manual)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2172,
   "name": "c2_min_runtime_1",
   "description": "Compressor 2 Minimum Required Runtime (C2 Minimum Run Time)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2032,
   "name": "c2_ref_iso_solenoid_1",
   "description": "Circuit 2's Refrigerant Isolation Solenoid Enable (C2 Ref Isolation Solenoid Stat)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2041,
   "name": "reset_c2_runtime_1",
   "description": "Compressor 2 Runtime Reset (C2 Runtime Reset)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2170,
   "name": "c2_rv_out_1",
   "description": "Circuit 2's Reversing Valve Enable (C2 RV Out)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2191,
   "name": "c2_shutdown_1",
   "description": "Circuit 2's Shutdown Status (C2 Shutdown Status)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2076,
   "name": "chiller_run_1",
   "description": "Module enable from Bank (Chiller Run)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2168,
   "name": "clear_fault_history_1",
   "description": "Module Fault History Clear (Clear Fault History)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2123,
   "name": "comp1_fail_1",
   "description": "Compressor 1 Fail (Comp 1 Fail)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2054,
   "name": "comp_1_go_1",
   "description": "Compressor 1 Bank Command (Comp 1 Go Command)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2056,
   "name": "c1_stat_1",
   "description": "Compressor 1 Status (Comp 1 Status)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2055,
   "name": "comp_2_go_1",
   "description": "Compressor 2 Bank Command (Comp 2 Go Command)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2057,
   "name": "c2_stat_1",
   "description": "Compressor 2 Status (Comp 2 Status)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2040,
   "name": "comp2_fail_1",
   "description": "Compressor 2 Fail",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2173,
   "name": "c1_minimum_off_1",
   "description": "Compresor Required Minimum Off Time (Compressor Off Delay)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2005,
   "name": "exv1_manual_1",
   "description": "Circuit 1's EEV A Manual Control (EEV1 Manual Control)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2007,
   "name": "exv2_manual_1",
   "description": "Circuit 2's EEV A Manual Control (EEV2 Manual Control)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2242,
   "name": "exvb1_manual_1",
   "description": "Circuit 1's EEV B Manual Control (EEV B C1 Manual Control)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2243,
   "name": "exvb2_manual_1",
   "description": "Circuit 2's EEV B Manual Control (EEV B C2 Manual Control)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2000,
   "name": "bbvp_eev_c1_man_en_1",
   "description": "EEV A Fully Open Manual (EEV C1 Manual EN)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2001,
   "name": "bbvp_eev_c2_man_en_1",
   "description": "EEV B Fully Open Manual (EEV C2 Manual EN)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2162,
   "name": "fixed_disc_press_en_1",
   "description": "Fixed Head Pressure Control (Enable Fixed Head Pressure Control)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2177,
   "name": "enable_ftr_1",
   "description": "StandAlone Mode (Fail to Run Enable)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2209,
   "name": "lock_loop1_open_1",
   "description": "Lock Loop 1 Open",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2113,
   "name": "loop1_manual_1",
   "description": "Loop1 Manual Control",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2111,
   "name": "loop1_bypass_mod_1",
   "description": "Loop1 Valve Bypass Module",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2108,
   "name": "loop1_valve_status_1",
   "description": "Loop 1 Valve Status",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2115,
   "name": "loop2_manual_1",
   "description": "Loop 2 Manual Valve Control",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2109,
   "name": "loop2_valve_status_1",
   "description": "Loop 2 Valve Status",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2180,
   "name": "c1_man_hgs_1",
   "description": "Manual C1 Hot Gas Solenoid",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2002,
   "name": "c1_man_li_1",
   "description": "Manual C1 Hot Gas Solenoid",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2003,
   "name": "c2_man_li_1",
   "description": "Manual C1 Liquid Injection",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2184,
   "name": "c1_man_ref_iso_1",
   "description": "Manual C1 Refrigeration Isolation Solenoid",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2182,
   "name": "c1_man_rev_valve_1",
   "description": "Manual C1 Reversing Valve",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2181,
   "name": "c2_man_hgs_1",
   "description": "Manual C2 Hot Gas Solenoid",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2185,
   "name": "c2_man_ref_iso_1",
   "description": "Manual C2 Refrigeration Isolation Solenoid",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2183,
   "name": "c2_man_rev_valve_1",
   "description": "Manual C2 Reversing Valve",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2210,
   "name": "manual_mode_1",
   "description": "Operating Mode in Manual Mode (Manual Mode)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2152,
   "name": "mod_comm_tx_stat_1",
   "description": "Bank Module Communication Watchdog Timer (Module Communication Transmit Status)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2110,
   "name": "mot_wtr_vlv_fail_1",
   "description": "Motorized Valve Failure in Module (Module Failure Mot Valve)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2090,
   "name": "modflow1_1",
   "description": "Flow Detection on Loop 1 (Module Flow 1 Status)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2246,
   "name": "modflow2_1",
   "description": "Flow Detection on Loop 2 (Module Flow Status 2)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2074,
   "name": "module_ok_1",
   "description": "Module Condition (Module Ok)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2073,
   "name": "module_run_1",
   "description": "Module Run Status (Module Run)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2134,
   "name": "phase_stat_1",
   "description": "Module Phase Status (Phase OK Status)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2178,
   "name": "rds_alarm_1",
   "description": "Module RDS Alarm (RDS Alarm)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2069,
   "name": "reset_alarms_1",
   "description": "Reset All Module Alarms",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2049,
   "name": "c1_discharge_pressure_oor_1",
   "description": "Circuit 1 Discharge Pressure OOR (C1 Discharge Pressure OOR)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2605,
   "name": "c1_discharge_temperature_oor_1",
   "description": "Circuit 1 Discharge Temperature OOR (C1 Discharge Temperature OOR)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2062,
   "name": "c1_liquid_pressure_oor_1",
   "description": "Circuit 1 Liquid Line pressure OOR (C1 Liquid Line pressure OOR)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2060,
   "name": "c1_liquid_line_temp_oor_1",
   "description": "Circuit 1 Liquid Line Temp OOR (C1 Liquid Line Temp OOR)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2130,
   "name": "c1p2_oor_1",
   "description": "Circuit 1 Suction Pressure Out of Range (C1 Suction Pressure Out of Range)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2052,
   "name": "c1_suction_temperature_oor_1",
   "description": "Circuit 1 Suction Temperature OOR (C1 Suction Temperature OOR)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2050,
   "name": "c2_discharge_pressure_oor_1",
   "description": "Circuit 2 Discharge Pressure OOR (C2 Discharge Pressure OOR)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2051,
   "name": "c2_discharge_temperature_oor_1",
   "description": "Circuit 2 Discharge Temperature OOR (C2 Discharge Temperature OOR)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2063,
   "name": "c2lp_oor_1",
   "description": "Circuit 2 Liquid Line Press Out of Range (C2 Liquid Line Press Out of Range)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2061,
   "name": "c2_liquid_line_temperature_oor_1",
   "description": "Circuit 2 Liquid Line Temperature OOR (C2 Liquid Line Temperature OOR)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2131,
   "name": "c2p2_oor_1",
   "description": "Circuit 2 Suction Pressure Out of Range (C2 Suction Pressure Out of Range)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2053,
   "name": "c2_suction_temperature_oor_1",
   "description": "Circuit 2 Suction Temperature OOR (C2 Suction Temperature OOR)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2068,
   "name": "comm_lost_1",
   "description": "No communication with Bank alarm (Communications Alarm)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2132,
   "name": "c1_eev_comm_loss_alarm_1",
   "description": "Circuit 1 EEV Comm Loss Alarm (Compressor 1 EEV Comm Loss Alarm)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2045,
   "name": "c1_hi_disch_tmp_1",
   "description": "Circuit 1 High Discharge Temperature Alarm (Compressor 1 High Discharge Temp)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2048,
   "name": "c1_hi_pres_alm_1",
   "description": "Circuit 1 High Discharge Pressure Alarm (Compressor 1 High Pressure Alarm)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2046,
   "name": "c1_low_suc_pres_alm_1",
   "description": "Circuit 1 Low Suction Pressure Alarm (Compressor 1 Low Suction Pressure Alarm)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2042,
   "name": "c1_no_run_1",
   "description": "Compressor 1 NO-Run Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2133,
   "name": "c2_eev_comm_loss_alarm_1",
   "description": "Circuit 2 EEV Comm Loss Alarm (Compressor 2 EEV Comm Loss Alarm)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2044,
   "name": "c2_hi_disch_tmp_1",
   "description": "Circuit 2 High Discharge Temperature Alarm (Compressor 2 High Discharge Temp)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2047,
   "name": "c2_hi_pres_alm_1",
   "description": "Circuit 2 High Discharge Pressure Alarm (Compressor 2 High Pressure Alarm)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2118,
   "name": "c2_low_suc_pres_alm_1",
   "description": "Circuit 2 Low Suction Pressure Alarm (Compressor 2 Low Suction Pressure Alarm)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2043,
   "name": "c2_no_run_1",
   "description": "Compressor 2 NO-Run Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2106,
   "name": "loop1_valve_alarm_1",
   "description": "Loop 1 Motorized Valve Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2107,
   "name": "loop2_valve_alarm_1",
   "description": "Loop 2 Motorized Valve Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2094,
   "name": "module_flow1_alarm_1",
   "description": "Module Flow 1 Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2247,
   "name": "module_flow2_alarm_1",
   "description": "Module Flow 2 Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2075,
   "name": "manager_lockout_alrm_1",
   "description": "Module Locked Out (Module Lockout)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2120,
   "name": "phase_loss_alarm_1",
   "description": "Phase Loss Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2179,
   "name": "rds_shutdown_alarm_1",
   "description": "RDS Shutdown Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2186,
   "name": "vfd1_genfault_alm_1",
   "description": "VFD 1 General Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2188,
   "name": "vfd1_sto_alm_1",
   "description": "VFD 1 STO Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2187,
   "name": "vfd2_genfault_alm_1",
   "description": "VFD 2 General Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2189,
   "name": "vfd2_sto_alm_1",
   "description": "VFD 2 STO Alarm",
   "units": "",
   "access": "R",
   "states": ""
  }
 ],
 "page": "https://easybacnet.com/bacnet-points-lists/climatemaster/tranquility-swt-large-water-to-water",
 "note": "Provided as-is. Point availability varies by firmware and options; verify against the live device.",
 "disclaimer": "DISCLAIMER: reference only, provided AS IS with no warranty. May contain errors or be out of date. You must verify every point against the manufacturer's current documentation and the live device before use. easybacnet.com accepts no liability for its use and is not affiliated with the manufacturer. Terms: https://easybacnet.com/terms#content"
}