DOAS (dedicated outdoor air system) controller · BACnet points list

ClimateMaster Commercial DOAS with CM3500 controller BACnet points list

Updated 12 November 2026

Short answer

The CM3500 controller in ClimateMaster commercial DOAS units has a short fixed BACnet list: Binary Values for the network occupancy command, alarm reset and on/off status of fans, wheel, compressors and condenser fans, and Analog Values for pressures, air temperatures, humidity, output commands and two writable setpoints.

This page lists 38 BACnet objects for the ClimateMaster Commercial DOAS with CM3500 controller — 4 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from ClimateMaster’s own free documentation, linked below.

Manufacturer
ClimateMaster
Model
ClimateMaster Commercial DOAS with CM3500 controller
Equipment
DOAS (dedicated outdoor air system) controller
Equipment type
Rooftop units, AHUs & DOAS
BACnet objects
38 (4 writable)
Transport
—
Firmware
Program version 3.2.0 and later
Also known as
CM3500, ClimateMaster DOAS, DOAS CM3500 Controller, 97B0065N01
Source document
DOAS CM3500 Controller - Application, Operation & Maintenance (BACNET Points List) · 97B0065N01 · rev. 2016-02-17
Download CSV 38 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against ClimateMaster’s current documentation and the live device before use. Not official ClimateMaster information. Terms of use.

BMS integration notes: ClimateMaster Commercial DOAS with CM3500 controller

Integration in brief

Write BV 1 Network Occupied Input to switch the unit between occupied and unoccupied, and adjust AV 21 Supply Air Setpoint and AV 22 Zone Air Setpoint if the BMS owns the setpoints. Read BV 2 to confirm occupancy, BV 3 for alarms (0 = alarm), and the supply, zone and outside air values. BV 16 resets alarms remotely.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 1Network Occupied InputOccupancy command (0=Unoccupied, 1=Occupied)Write
AV 21Supply Air SetpointSupply air temperature setpoint, °F (45.0-99.9)Write
AV 22Zone Air SetpointZone temperature setpoint, °F (55.0-95.0)Write
BV 16Remote ResetWrite 1 to reset alarmsWrite
BV 2OccupiedOccupied status feedbackRead
BV 5Supply FanSupply fan on/off statusRead
AV 6Supply Air TemperatureSupply air temperature, °FRead
AV 7Zone Air TemperatureZone temperature, °FRead
AV 18Outside Air TemperatureOutdoor air temperature, °FRead
BV 3Alarm ActiveUnit alarm (0=Alarm, 1=Normal)Read

Enable & remote start

BV 1 Network Occupied Input (read/write) sets occupied or unoccupied mode from the BMS.

Watch out for

ClimateMaster Commercial DOAS with CM3500 controller BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

38 of 38 shown
Type
AnalogBinary
Access
Show
ClimateMaster Commercial DOAS with CM3500 controller BACnet Points List
DescriptionStates
AV1Suction PressureValue in tenths, 0 to 250 psigpsigRead
AV2Discharge PressureValue in tenths, 0 to 650 psigpsigRead
AV3Intake Air Relative HumidityValue in tenths, 0 to 100 %%Read
AV4Intake Air TemperatureValue in tenths, -42 to 137 °F°FRead
AV5Intake Air DewpointValue in tenths, calculated°FRead
AVmin6Supply Air TemperatureValue in tenths, -58 to 212 °F°FRead
AVmin7Zone Air TemperatureValue in tenths, -58 to 212 °F°FRead
AV8Zone Air Relative HumidityValue in tenths, 0 to 100 %%Read
AV9Suction Press Circuit BValue in tenths, 0 to 250 psigpsigRead
AV10Discharge Press Circuit BValue in tenths, 0 to 650 psigpsigRead
AV11Supply Fan Speed CommandValue in tenths, 0 to 100 %%Read
AV12Auxiliary Heating Comm.Value in tenths, 0 to 100 %%Read
AV13Outside Air Damper Comm.Value in tenths, 0 to 100 %%Read
AV14Recirc. Damper CommandValue in tenths, 0 to 100 %%Read
AV15Exhaust Fan Speed Comm.Value in tenths, 0 to 100 %%Read
AV16Wheel Speed CommandValue in tenths, 0 to 100 %%Read
AV17Outside Air Relative HumidityValue in tenths, 0 to 100 %%Read
AVmin18Outside Air TemperatureValue in tenths, -42 to 137 °F°FRead
AV19Return Air Relative HumidityValue in tenths, 0 to 100 %%Read
AV20Return Air TemperatureValue in tenths, -42 to 137 °F°FRead
AVmin21Supply Air SetpointSetpoint, settable 45.0 to 99.9 °F°FWrite
AVmin22Zone Air SetpointSetpoint, settable 55.0 to 95.0 °F°FWrite
BVmin1Network Occupied InputOccupancy command from the BMSWrite0=Unoccupied, 1=Occupied
BVmin2OccupiedOccupied status feedbackRead
BVmin3Alarm ActiveAlarm statusRead0=Alarm, 1=Normal
BV4Air FlowAirflow provenRead0=No Flow, 1=Flow
BVmin5Supply FanSupply Fan on/off statusRead0=Off, 1=On
BV6Exhaust FanExhaust Fan on/off statusRead0=Off, 1=On
BV7Wheel MotorWheel Motor on/off statusRead0=Off, 1=On
BV8Compressor #1Compressor #1 on/off statusRead0=Off, 1=On
BV9Compressor #2Compressor #2 on/off statusRead0=Off, 1=On
BV10Compressor #3Compressor #3 on/off statusRead0=Off, 1=On
BV11Compressor #4Compressor #4 on/off statusRead0=Off, 1=On
BV12Condenser Fan #1Condenser Fan #1 on/off statusRead0=Off, 1=On
BV13Condenser Fan #2Condenser Fan #2 on/off statusRead0=Off, 1=On
BV14Condenser Fan #3Condenser Fan #3 on/off statusRead0=Off, 1=On
BV15Condenser Fan #4Condenser Fan #4 on/off statusRead0=Off, 1=On
BVmin16Remote ResetWrite 1 to reset alarms; returns to 0 after a program scanWrite
Object ID lookup: ClimateMaster Commercial DOAS with CM3500 controller point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the ClimateMaster Commercial DOAS with CM3500 controller and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the ClimateMaster Commercial DOAS with CM3500 controller

How many BACnet points does the ClimateMaster Commercial DOAS with CM3500 controller have?

This list has 38 BACnet objects: 22 analog values, 16 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which ClimateMaster Commercial DOAS with CM3500 controller BACnet points are writable?

4 of the 38 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official ClimateMaster Commercial DOAS with CM3500 controller BACnet documentation?

The source is DOAS CM3500 Controller - Application, Operation & Maintenance (BACNET Points List) (97B0065N01), revision 2016-02-17, published free by ClimateMaster at https://files.climatemaster.com/97b0065n01-climatemaster-commercial-doas-cm3500-controller-installation-manual.pdf.

What are the minimum BACnet points to integrate the ClimateMaster Commercial DOAS with CM3500 controller?

Start with BV 1 Network Occupied Input (Occupancy command (0=Unoccupied, 1=Occupied)); AV 21 Supply Air Setpoint (Supply air temperature setpoint, °F (45.0-99.9)); AV 22 Zone Air Setpoint (Zone temperature setpoint, °F (55.0-95.0)); BV 16 Remote Reset (Write 1 to reset alarms); BV 2 Occupied (Occupied status feedback); BV 5 Supply Fan (Supply fan on/off status); AV 6 Supply Air Temperature (Supply air temperature, °F); AV 7 Zone Air Temperature (Zone temperature, °F); AV 18 Outside Air Temperature (Outdoor air temperature, °F); BV 3 Alarm Active (Unit alarm (0=Alarm, 1=Normal)).

How do I enable BMS control of the ClimateMaster Commercial DOAS with CM3500 controller?

BV 1 Network Occupied Input (read/write) sets occupied or unoccupied mode from the BMS.

How do I check these points on the real ClimateMaster Commercial DOAS with CM3500 controller?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More ClimateMaster BACnet points lists

Source: DOAS CM3500 Controller - Application, Operation & Maintenance (BACNET Points List) · 97B0065N01 · rev. 2016-02-17. Object names, instances and units are reproduced as published; descriptions are our own.