Water-source heat pump controller · BACnet points list

ClimateMaster MPC Multi-Protocol DDC Controller - Water-to-Air (Gen 7 and newer) BACnet points list

Updated 28 October 2026

Short answer

The MPC is ClimateMaster's add-on DDC controller for water-source heat pumps. It sits on top of the CXM2/DXM2.6 unit board, acts as a thermostat with a wall sensor, and talks BACnet MS/TP, BACnet over ARC156, N2 or Modbus. The BMS commands occupancy, writes occupied and unoccupied heating and cooling setpoints (in °F or °C objects), can shut the unit down, and reads compressor, fan and temperature status plus fault counters and the lockout state. Units can share one wall sensor in a leader/follower setup.

This page lists 123 BACnet objects for the ClimateMaster MPC Multi-Protocol DDC Controller - Water-to-Air (Gen 7 and newer) — 68 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from ClimateMaster’s own free documentation, linked below.

Manufacturer
ClimateMaster
Model
MPC Multi-Protocol DDC Controller - Water-to-Air (Gen 7 and newer)
Equipment
Water-source heat pump controller
Equipment type
Heat pumps
BACnet objects
123 (68 writable)
Transport
BACnet MS/TP, BACnet ARC156
Firmware
Gen 7 and newer (some points Gen 8 only)
Default device instance
Auto-generated; last two digits = rotary address
Also known as
MPC, ClimateMaster MPC, 97B0031N01, Multi-Protocol Controller, CXM2, DXM2.6
Source document
MPC Multi-Protocol DDC Controls - Application, Operation & Maintenance Manual · 97B0031N01 · rev. 2025-12-11
Download CSV 123 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: ClimateMaster MPC Multi-Protocol DDC Controller - Water-to-Air (Gen 7 and newer)

Integration in brief

Address the MPC with the rotary switches and set the MS/TP baud with the DIP switches. Command occupancy with BV 12 (or a BMS schedule on BV 14) and write the occupied cooling and heating setpoints. Use BV 8 for an emergency stop and BV 4 to clear a lockout. Monitor fan and compressor status, space temperature, the Alarm State and the Fault text.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 12Occupied ModeOccupancy command (ON = occupied)Write
BV 8Emergency ShutdownEmergency stop; ON turns Y1, Y2, G and W offWrite
AV 3Occupied CL SP/ FahrenheitOccupied cooling setpoint, °FWrite
AV 21Occupied HT SetpointOccupied heating setpoint, °F (DB Mode off)Write
BV 4System ResetLockout reset; set ON then back OFFWrite
BV 10SF StatusSupply fan runningRead
BV 3C1 StatusCompressor 1 runningRead
AV 34Zone Temp StatusSpace temperatureRead
BV 1Alarm StateLockout condition (ON = lockout)Read
MV 1FaultCurrent alarm as textRead

Enable & remote start

Stand-alone, the MPC defaults to occupied. BV 12 Occupied Mode (default ON) sets occupied/unoccupied from the BMS; BV 14 Work Schedule can take a BMS schedule instead. BV 8 Emergency Shutdown turns the Y1, Y2, G and W outputs off. BV 53 Compressor Shutdown disables both compressors, and BV 61/BV 54 disable heating or cooling.

Sensors & values from the BMS

For units sharing one wall sensor, set BV 16 M/S Switch ON on each follower and map the leader's Zone Temp Status (AV 34), Actual HT/CL setpoints (AV 2, AV 1) and Occupied Status (BV 11) to the follower's Master ZT (AV 4), Subordinate HT/CL SP (AV 9, AV 10) and Occupied Mode (BV 12).

Network setup

Watch out for

ClimateMaster MPC Multi-Protocol DDC Controller - Water-to-Air (Gen 7 and newer) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

123 of 123 shown
Type
AnalogBinaryMulti-state
Access
Show
ClimateMaster MPC Multi-Protocol DDC Controller - Water-to-Air (Gen 7 and newer) BACnet Points List
DescriptionStates
AV1Actual CL SetpointCooling setpoint in use (occupancy, adjust, units applied)°F / °CRead
AV2Actual HT SetpointHeating setpoint in use (occupancy, adjust, units applied)°F / °CRead
AVmin3Occupied CL SP/ FahrenheitOccupied cooling setpoint, °F°FWrite
AV4Master ZT/ FahrenheitShared zone temperature for follower units, °F°FWrite
AV5Occupied Deadband/ FahrenheitOccupied heat/cool deadband in DB mode, min 2 °F°FWrite
AV6Pulse Signal ValueLast fault code from the CXM2/DXM2.6 boardRead
AV7Unoccupied CL SP/ FahrenheitUnoccupied cooling setpoint, °F°FWrite
AV8Override Time RemainingObsolete (Gen 3 and Gen 4 only)Read
AV9Subordinate HT SP/ FahrenheitHeating setpoint from the leader unit, °F°FWrite
AV10Subordinate CL SP/ FahrenheitCooling setpoint from the leader unit, °F°FWrite
AV11HP Fault CounterHigh pressure faults since start or resetRead
AV12LP Fault CounterLow pressure faults since start or resetRead
AV13LT1 Fault CounterLiquid temperature 1 faults since start or resetRead
AV14LT2 Fault CounterLiquid temperature 2 faults since start or resetRead
AV15CO Fault CounterCondensate overflow faults since start or resetRead
AV16Over/Under Voltage Fault CounterOver/under voltage faults since start or resetRead
AV17UPS Fault CounterUPS faults since start or resetRead
AV18Swapped LT1/LT2 Fault CounterSwapped LT1/LT2 faults since start or resetRead
AV19C1 Cycle CounterTimes C1 cycled over 6 times in an hourRead
AV20C2 Cycle CounterTimes C2 cycled over 6 times in an hourRead
AVmin21Occupied HT SetpointOccupied heating setpoint, °F°FWrite
AV22Occupied HT Setpoint CelsiusOccupied heating setpoint, °C°CWrite
AV23Unoccupied HT SetpointUnoccupied heating setpoint, °F°FWrite
AV24Unoccupied HT Setpoint CelsiusUnoccupied heating setpoint, °C°CWrite
AV28HT PIDHeating PID output%Read
AV29CL PIDCooling PID output%Read
AV30Dirty Filter IntervalFan hours before the dirty filter alarm; default 1500hWrite
AV31AUX CFGAUX (W) output function codeWrite
AV32TSTAT ModeTemperature control method (Gen 3 hardware)Write
AV33SF CFGSupply fan configurationWrite
AVmin34Zone Temp StatusSpace temperature°F / °CRead
AV35LVG Air Temp StatusLeaving air temperature°F / °CRead
AV36LVG Water Temp StatusLeaving water temperature°F / °CRead
AV37Manual SP AdjustSetpoint adjust range at the wall sensor, °F°FWrite
AV38Master ZT CelsiusShared zone temperature for follower units, °C°CWrite
AV39Unoccupied CL SP CelsiusUnoccupied cooling setpoint, °C°CWrite
AV40Occupied Deadband CelsiusOccupied heat/cool deadband in DB mode, °C°CWrite
AV41Subordinate CL Setpoint CelsiusCooling setpoint from the leader unit, °C°CWrite
AV42Subordinate HT Setpoint CelsiusHeating setpoint from the leader unit, °C°CWrite
AV43Occupied CL SP CelsiusOccupied cooling setpoint, °C°CWrite
AV44Manual Setpoint Adj CelsiusSetpoint adjust range at the wall sensor, °C°CWrite
AV45Unoccupied DeadbandUnoccupied heat/cool deadband in DB mode, °F°FWrite
AV46Unoccupied Deadband CelsiusUnoccupied heat/cool deadband in DB mode, °C°CWrite
AV47Relative Humidity SetpointRH above which AUX turns on (AUX CFG 12)%Write
AV48Relative Humidity DeadbandRH deadband for humidity control (AUX CFG 12)%Write
AV49Relative Humidity StatusSpace relative humidity%Read
AV50Aux 5 TempAuxiliary input 5 temperature (RNet mode)°F / °CRead
AV51Aux 6 TempAuxiliary input 6 temperature (RNet mode)°F / °CRead
AV52CO2 StatusSpace CO2ppmRead
AV53VOC StatusSpace VOC levelppmRead
AV54CO2 Trip pointCO2 level that turns AUX on (AUX CFG 13)ppmWrite
AV55VCO Trip pointVOC level that turns AUX on (AUX CFG 14)ppmWrite
AV56FAN Speed TriggerPID level that switches AUX high fan (AUX CFG 5)%Write
AV57Airflow Fault CounterAirflow faults since start or resetRead
AV58Pump Fault CounterPump faults since start or resetRead
AV59Load Balance Select ModeCompressor sequencing / runtime balancing modeWrite
AV99Application TypeFactory use onlyRead
BVmin1Alarm StateLockout condition presentReadOFF=Normal, ON=Lockout
BV2C1 ResetReset the C1 runtime alarmWrite
BVmin3C1 StatusCompressor 1 on/offRead
BVmin4System ResetLockout reset; set ON then OFFWrite
BV5C2 ResetReset the C2 runtime alarmWrite
BV6C2 StatusCompressor 2 on/offRead
BV7Dirty Filter ResetReset the dirty filter alarmWrite
BVmin8Emergency ShutdownEmergency stop: Y1, Y2, G and W relays offWriteOFF=Normal, ON=Shutdown
BV9Supply Fan Operational ModeFan auto/on (Gen 2-4 only)ReadOFF=Auto, ON=On
BVmin10SF StatusSupply fan on/offRead
BV11Occupied StatusOccupied stateReadOFF=Unoccupied, ON=Occupied
BVmin12Occupied ModeOccupancy command; default ONWriteOFF=Unoccupied, ON=Occupied
BV13RV StatusReversing valve on/offRead
BV14Work ScheduleSchedule from the BMS sets occupied/unoccupiedWriteOFF=Unoccupied, ON=Occupied
BV15UPS SignalUPS mode on/off (see CXM2/DXM2.6 manual)Read
BV16M/S SwitchLeader (OFF) or follower sharing a sensor (ON)WriteOFF=Leader, ON=Follower
BV17C1 Runtime AlarmC1 run hours over 5000; reset with BV 2Read
BV18C2 Runtime AlarmC2 run hours over 5000; reset with BV 5Read
BV19Dirty Filter AlarmFan hours past the dirty filter intervalRead
BV20Valid Sensor AlarmNo valid room sensor connectedRead
BV21C1 Cycle ResetReset the C1 cycle counterWrite
BV22C2 Cycle ResetReset the C2 cycle counterWrite
BV23Lockout AlarmCXM2/DXM2.6 board in lockoutRead
BV24Fault Counter ResetReset all fault countersWrite
BV25C1 Cycle AlarmC1 cycled more than 5 times in an hourRead
BV26C2 Cycle AlarmC2 cycled more than 5 times in an hourRead
BV27AUX StatusAUX (W) output on/offRead
BV28SF ManualSupply fan on/off in test modeWrite
BV29RV ManualReversing valve on/off in test modeWrite
BV30C1 ManualCompressor 1 on/off in test modeWrite
BV31C2 ManualCompressor 2 on/off in test modeWrite
BV32AUX ManualAUX (W) output on/off in test modeWrite
BV33TStat ResetObsolete (Gen 5 only)Write
BV34Test ModeManual test mode, 60 min maximumWrite
BV38Test Mode AlarmUnit still in test mode after the timerRead
BV39MetricEngineering units for inputs and outputsWriteOFF=Fahrenheit, ON=Celsius
BV40AUX ToggleSwitch AUX output when AUX CFG = 11Write
BV41Air Duct ModeControl on return duct temperature (Aux 5)Write
BV42AUX5Aux input 5 binary state (RNet mode)Read
BV43AUX6Aux input 6 binary state (RNet mode)Read
BV44RNet ModeCommunicating (ON) or LStat (OFF) wall sensorsWriteOFF=LStat, ON=RNet
BV45Humidity OccupancyEnable humidity control when AUX CFG = 12Write
BV46Aux 5 ConfigAux input 5 typeWriteOFF=Binary, ON=Temperature
BV47Aux 6 ConfigAux input 6 typeWriteOFF=Binary, ON=Temperature
BV48DB ModeDeadband setpoint modeWriteOFF=Separate setpoints, ON=Cooling SP + deadband
BV49CO2 AlarmCO2 above the trip pointRead
BV50VOC AlarmVOC above the trip pointRead
BV51Fan Speed EnableHigh fan via AUX when AUX CFG = 5Write
BV53Compressor ShutdownDisable both compressorsWriteOFF=Enabled, ON=Disabled
BV54Cooling ModeCooling enableWriteOFF=Disabled, ON=Enabled
BV57Electric Heat ModeFull-time electric heat via AUXReadOFF=Heat pump, ON=Electric heat
BV58Electric Heat DemandHeat demand in full-time electric heat modeRead
BV59Ext Occ/Dirty Filt SensBI 8 use: motion sensor or filter switchReadOCC=Occupancy, DFS=Dirty filter sense
BV60Dirty Filter ModeDirty filter by time or pressure switchWriteTIME, DFS
BV61Heating ModeHeating enableWriteOFF=Disabled, ON=Enabled
BV62Archive EnableArchive the current control programWrite
BV63RNet Sensor 1 EnableExpect RNet sensor 1 (enables its alarm)Write
BV64RNet Sensor 2 EnableExpect RNet sensor 2 (enables its alarm)Write
BV65RNet Sensor 3 EnableExpect RNet sensor 3 (enables its alarm)Write
BV66RNet Sensor 4 EnableExpect RNet sensor 4 (enables its alarm)Write
BV67RNet Sensor 5 EnableExpect RNet sensor 5 (enables its alarm)Write
BV68EQ Touch Temp EnableUse Equipment Touch sensor for space temperatureWrite
MVmin1FaultCurrent alarm as textRead
MV2AUX Config StatusAUX output configuration as textRead
MV3Zone Mode StatusCurrent operating mode as textRead
MV10Archive StatusStatus of the program archive processRead

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the MPC Multi-Protocol DDC Controller - Water-to-Air (Gen 7 and newer) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the ClimateMaster MPC Multi-Protocol DDC Controller - Water-to-Air (Gen 7 and newer)

How many BACnet points does the ClimateMaster MPC Multi-Protocol DDC Controller - Water-to-Air (Gen 7 and newer) have?

This list has 123 BACnet objects: 57 analog values, 62 binary values, 4 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which ClimateMaster MPC Multi-Protocol DDC Controller - Water-to-Air (Gen 7 and newer) BACnet points are writable?

68 of the 123 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official ClimateMaster MPC Multi-Protocol DDC Controller - Water-to-Air (Gen 7 and newer) BACnet documentation?

The source is MPC Multi-Protocol DDC Controls - Application, Operation & Maintenance Manual (97B0031N01), revision 2025-12-11, published free by ClimateMaster at https://files.climatemaster.com/97b0031n01-climatemaster-mpc-multiprotocol-ddc-controls-water-source-heat-pump-application-manual.pdf.

What are the minimum BACnet points to integrate the ClimateMaster MPC Multi-Protocol DDC Controller - Water-to-Air (Gen 7 and newer)?

Start with BV 12 Occupied Mode (Occupancy command (ON = occupied)); BV 8 Emergency Shutdown (Emergency stop; ON turns Y1, Y2, G and W off); AV 3 Occupied CL SP/ Fahrenheit (Occupied cooling setpoint, °F); AV 21 Occupied HT Setpoint (Occupied heating setpoint, °F (DB Mode off)); BV 4 System Reset (Lockout reset; set ON then back OFF); BV 10 SF Status (Supply fan running); BV 3 C1 Status (Compressor 1 running); AV 34 Zone Temp Status (Space temperature); BV 1 Alarm State (Lockout condition (ON = lockout)); MV 1 Fault (Current alarm as text).

How do I enable BMS control of the ClimateMaster MPC Multi-Protocol DDC Controller - Water-to-Air (Gen 7 and newer)?

Stand-alone, the MPC defaults to occupied. BV 12 Occupied Mode (default ON) sets occupied/unoccupied from the BMS; BV 14 Work Schedule can take a BMS schedule instead. BV 8 Emergency Shutdown turns the Y1, Y2, G and W outputs off. BV 53 Compressor Shutdown disables both compressors, and BV 61/BV 54 disable heating or cooling.

Can the BMS supply sensor values to the ClimateMaster MPC Multi-Protocol DDC Controller - Water-to-Air (Gen 7 and newer)?

For units sharing one wall sensor, set BV 16 M/S Switch ON on each follower and map the leader's Zone Temp Status (AV 34), Actual HT/CL setpoints (AV 2, AV 1) and Occupied Status (BV 11) to the follower's Master ZT (AV 4), Subordinate HT/CL SP (AV 9, AV 10) and Occupied Mode (BV 12).

How do I check these points on the real MPC Multi-Protocol DDC Controller - Water-to-Air (Gen 7 and newer)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More ClimateMaster BACnet points lists

Source: MPC Multi-Protocol DDC Controls - Application, Operation & Maintenance Manual · 97B0031N01 · rev. 2025-12-11. Object names, instances and units are reproduced as published; descriptions are our own.