  4. MPC Multi-Protocol DDC Controller - Water-to-Water (Gen 8 and newer)

Water-to-water heat pump controller · BACnet points list

ClimateMaster MPC Multi-Protocol DDC Controller - Water-to-Water (Gen 8 and newer) BACnet points list

Updated 28 October 2026

Short answer

In water-to-water units the MPC controls water temperature instead of space temperature. The BMS commands occupancy, selects heating or cooling with the MC Switch, writes occupied and unoccupied water setpoints and differentials, and can shut the unit down or take direct control of the compressors and reversing valve. Control is on entering water temperature by default and can be moved to leaving water temperature. The unit stays in the selected mode until the mode is changed.

This page lists 76 BACnet objects for the ClimateMaster MPC Multi-Protocol DDC Controller - Water-to-Water (Gen 8 and newer) — 42 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from ClimateMaster’s own free documentation, linked below.

Manufacturer
ClimateMaster
Model
MPC Multi-Protocol DDC Controller - Water-to-Water (Gen 8 and newer)
Equipment
Water-to-water heat pump controller
Equipment type
Heat pumps
BACnet objects
76 (42 writable)
Transport
BACnet MS/TP, BACnet ARC156
Firmware
Gen 8 and newer
Default device instance
Auto-generated; last two digits = rotary address
Also known as
MPC, ClimateMaster MPC, 97B0031N01, Multi-Protocol Controller, CXM2, DXM2.6
Source document
MPC Multi-Protocol DDC Controls - Application, Operation & Maintenance Manual · 97B0031N01 · rev. 2025-12-11
Download CSV 76 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: ClimateMaster MPC Multi-Protocol DDC Controller - Water-to-Water (Gen 8 and newer)

Integration in brief

Address the MPC with the rotary switches and set the MS/TP baud with the DIP switches. Command occupancy with BV 12, choose heating or cooling with BV 7 MC Switch, and write the occupied water setpoints. Use BV 8 for an emergency stop and BV 4 to clear a lockout. Monitor the compressor, load water temperatures and the Alarm State.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 12Occupied ModeOccupancy command (ON = occupied)Write
BV 8Emergency ShutdownEmergency stop; ON turns Y1, Y2, G and W offWrite
BV 7MC SwitchMode: ON = cooling, OFF = heatingWrite
AV 3Occupied CL SP/ FahrenheitOccupied cooling water setpoint, °FWrite
AV 5Occupied HT SetpointOccupied heating water setpoint, °FWrite
BV 4System ResetLockout reset; set ON then back OFFWrite
BV 3C1 StatusCompressor 1 runningRead
AV 35EWT Load StatusLoad entering water temp (default control)Read
AV 34LWT Load StatusLoad leaving water temperatureRead
BV 1Alarm StateLockout condition (ON = lockout)Read

Enable & remote start

BV 12 Occupied Mode (default ON) sets occupied/unoccupied; BV 14 Work Schedule can take a BMS schedule instead. BV 7 MC Switch selects cooling (ON) or heating (OFF) and the unit stays in that mode until it is changed. BV 8 Emergency Shutdown turns the outputs off. With BV 62 Multi Stage Enable ON the BMS can drive C1, C2 and the reversing valve directly through BV 61, BV 63 and BV 60.

Sensors & values from the BMS

BV 9 CC Mode and BV 10 HC Mode move cooling and heating control from entering (OFF, default) to leaving (ON) water temperature. Follower units (BV 16 ON) take the leader's water temperature in Master WT (AV 4/AV 27) and its setpoints in AV 9/AV 10.

Network setup

Watch out for

ClimateMaster MPC Multi-Protocol DDC Controller - Water-to-Water (Gen 8 and newer) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

76 of 76 shown
Type
AnalogBinary
Access
Show
ClimateMaster MPC Multi-Protocol DDC Controller - Water-to-Water (Gen 8 and newer) BACnet Points List
DescriptionStates
AV1Actual CL SetpointCooling setpoint in use (occupancy, adjust, units applied)°F / °CRead
AV2Actual HT SetpointHeating setpoint in use (occupancy, adjust, units applied)°F / °CRead
AVmin3Occupied CL SP/ FahrenheitOccupied cooling water setpoint, °F°FWrite
AV4Master WT/ FahrenheitShared water temperature for follower units, °F°FWrite
AVmin5Occupied HT SetpointOccupied heating water setpoint, °F°FWrite
AV6Pulse Signal ValueLast fault code from the CXM2/DXM2.6 boardRead
AV7Unoccupied CL SP/FahrenheitUnoccupied cooling water setpoint, °F°FWrite
AV9Subordinate HT SP/FahrenheitHeating setpoint from the leader unit, °F°FWrite
AV10Subordinate CL SP/FahrenheitCooling setpoint from the leader unit, °F°FWrite
AV11HP Fault CounterHigh pressure faults since start or resetRead
AV12LP Fault CounterLow pressure faults since start or resetRead
AV13LT1 Fault CounterLiquid temperature 1 faults since start or resetRead
AV14LT2 Fault CounterLiquid temperature 2 faults since start or resetRead
AV15CO Fault CounterCondensate overflow faults since start or resetRead
AV16Over/Under Voltage Fault CounterOver/under voltage faults since start or resetRead
AV17UPS Fault CounterUPS faults since start or resetRead
AV18Swapped LT1/LT2 Fault CounterSwapped LT1/LT2 faults since start or resetRead
AV19C1 Cycle CounterTimes C1 cycled over 6 times in an hourRead
AV20C2 Cycle CounterTimes C2 cycled over 6 times in an hourRead
AV21Unoccupied HT SetpointUnoccupied heating water setpoint, °F°FWrite
AV22CLDCooling differential: turns off at cooling SP - CLD°FWrite
AV23HTDHeating differential: turns off at heating SP + HTD°FWrite
AV24SUBORDINATE CLDFollower cooling differential (BV 16 on)°FWrite
AV25SUBORDINATE HTDFollower heating differential (BV 16 on)°FRead
AV26AUX CFGAUX (W) output function codeWrite
AV27Master WT/CelsiusShared water temperature for follower units, °C°CWrite
AV28Unoccupied HT Setpoint CelsiusUnoccupied heating water setpoint, °C°CWrite
AV29Occupied HT Setpoint CelsiusOccupied heating water setpoint, °C°CWrite
AV30Unoccupied CL SP CelsiusUnoccupied cooling water setpoint, °C°CWrite
AV31Occupied CL SP CelsiusOccupied cooling water setpoint, °C°CWrite
AV32Subordinate HT Setpoint CelsiusHeating setpoint from the leader unit, °C°CWrite
AV33Subordinate CL Setpoint CelsiusCooling setpoint from the leader unit, °C°CWrite
AVmin34LWT Load StatusLoad coil leaving water temperature°F / °CRead
AVmin35EWT Load StatusLoad coil entering water temperature°F / °CRead
AV36LWT Source StatusSource coil leaving water temperature°F / °CRead
AV37Zone Temp StatusSpace temperature°F / °CRead
AV38HT PIDHeating PID output%Read
AV39CL PIDCooling PID output%Read
AV59Load Balance ModeCompressor sequencing / runtime balancing modeWrite
AV60Compressor Swap timeCompressor swap time (fixed 24 h, AV 59 = 4)hRead
AV99Application TypeFactory use onlyRead
BVmin1Alarm StateLockout condition presentReadOFF=Normal, ON=Lockout
BV2C1 ResetReset the C1 runtime alarmWrite
BVmin3C1 StatusCompressor 1 on/offRead
BVmin4System ResetLockout reset; set ON then OFFWrite
BV5C2 ResetReset the C2 runtime alarmWrite
BV6C2 StatusCompressor 2 on/offRead
BVmin7MC SwitchWater-to-water modeWriteOFF=Heating, ON=Cooling
BVmin8Emergency ShutdownEmergency stop: Y1, Y2, G and W relays offWriteOFF=Normal, ON=Shutdown
BV9CC ModeCooling control sensorWriteOFF=EWT, ON=LWT
BV10HC ModeHeating control sensorWriteOFF=EWT, ON=LWT
BV11Occupied StatusOccupied stateReadOFF=Unoccupied, ON=Occupied
BVmin12Occupied ModeOccupancy command; default ONWriteOFF=Unoccupied, ON=Occupied
BV13RV StatusReversing valve on/offRead
BV14Work ScheduleSchedule from the BMS sets occupied/unoccupiedWriteOFF=Unoccupied, ON=Occupied
BV16M/S SwitchLeader (OFF) or follower sharing a sensor (ON)WriteOFF=Leader, ON=Follower
BV17C1 Runtime AlarmC1 run hours over 5000; reset with BV 2Read
BV18C2 Runtime AlarmC2 run hours over 5000; reset with BV 5Read
BV19C1 Cycle ResetReset the C1 cycle counterWrite
BV20C2 Cycle ResetReset the C2 cycle counterWrite
BV21Lockout AlarmCXM2/DXM2.6 board in lockoutRead
BV23C1 Cycle AlarmC1 cycled more than 5 times in an hourRead
BV24C2 Cycle AlarmC2 cycled more than 5 times in an hourRead
BV25RV ManualReversing valve on/off in test modeWrite
BV26C1 ManualCompressor 1 on/off in test modeWrite
BV27C2 ManualCompressor 2 on/off in test modeWrite
BV29Test ModeManual test mode, 60 min maximumWrite
BV30Test Mode AlarmUnit still in test mode after the timerRead
BV31AUX StatusAUX (W) output on/offRead
BV32AUX ManualAUX (W) output on/off in test modeWrite
BV33MetricEngineering units for inputs and outputsWriteOFF=Fahrenheit, ON=Celsius
BV60RV OverrideNetwork control of reversing valve (BV 62 on)Write
BV61C1 OverrideNetwork control of C1 (BV 62 on)Write
BV62Multi Stage EnableAllow network control of C1, C2 and RVWrite
BV63C2 OverrideNetwork control of C2 (BV 62 on)Write
BV70Archive EnableArchive the current control programWrite

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the MPC Multi-Protocol DDC Controller - Water-to-Water (Gen 8 and newer) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the ClimateMaster MPC Multi-Protocol DDC Controller - Water-to-Water (Gen 8 and newer)

How many BACnet points does the ClimateMaster MPC Multi-Protocol DDC Controller - Water-to-Water (Gen 8 and newer) have?

This list has 76 BACnet objects: 41 analog values, 35 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which ClimateMaster MPC Multi-Protocol DDC Controller - Water-to-Water (Gen 8 and newer) BACnet points are writable?

42 of the 76 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official ClimateMaster MPC Multi-Protocol DDC Controller - Water-to-Water (Gen 8 and newer) BACnet documentation?

The source is MPC Multi-Protocol DDC Controls - Application, Operation & Maintenance Manual (97B0031N01), revision 2025-12-11, published free by ClimateMaster at https://files.climatemaster.com/97b0031n01-climatemaster-mpc-multiprotocol-ddc-controls-water-source-heat-pump-application-manual.pdf.

What are the minimum BACnet points to integrate the ClimateMaster MPC Multi-Protocol DDC Controller - Water-to-Water (Gen 8 and newer)?

Start with BV 12 Occupied Mode (Occupancy command (ON = occupied)); BV 8 Emergency Shutdown (Emergency stop; ON turns Y1, Y2, G and W off); BV 7 MC Switch (Mode: ON = cooling, OFF = heating); AV 3 Occupied CL SP/ Fahrenheit (Occupied cooling water setpoint, °F); AV 5 Occupied HT Setpoint (Occupied heating water setpoint, °F); BV 4 System Reset (Lockout reset; set ON then back OFF); BV 3 C1 Status (Compressor 1 running); AV 35 EWT Load Status (Load entering water temp (default control)); AV 34 LWT Load Status (Load leaving water temperature); BV 1 Alarm State (Lockout condition (ON = lockout)).

How do I enable BMS control of the ClimateMaster MPC Multi-Protocol DDC Controller - Water-to-Water (Gen 8 and newer)?

BV 12 Occupied Mode (default ON) sets occupied/unoccupied; BV 14 Work Schedule can take a BMS schedule instead. BV 7 MC Switch selects cooling (ON) or heating (OFF) and the unit stays in that mode until it is changed. BV 8 Emergency Shutdown turns the outputs off. With BV 62 Multi Stage Enable ON the BMS can drive C1, C2 and the reversing valve directly through BV 61, BV 63 and BV 60.

Can the BMS supply sensor values to the ClimateMaster MPC Multi-Protocol DDC Controller - Water-to-Water (Gen 8 and newer)?

BV 9 CC Mode and BV 10 HC Mode move cooling and heating control from entering (OFF, default) to leaving (ON) water temperature. Follower units (BV 16 ON) take the leader's water temperature in Master WT (AV 4/AV 27) and its setpoints in AV 9/AV 10.

How do I check these points on the real MPC Multi-Protocol DDC Controller - Water-to-Water (Gen 8 and newer)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More ClimateMaster BACnet points lists

Source: MPC Multi-Protocol DDC Controls - Application, Operation & Maintenance Manual · 97B0031N01 · rev. 2025-12-11. Object names, instances and units are reproduced as published; descriptions are our own.