Commercial water-source heat pump controller · BACnet points list

Bosch Control Air 6120 - Water to Air (WAF software) BACnet points list

Updated 28 October 2026

Short answer

The Control Air 6120 is Bosch's DDC controller for larger commercial water-to-air heat pumps, including discharge-air control, VFD fans, economizer/boilerless options, hot gas reheat and auxiliary heat. It is a BACnet Advanced Application Controller on MS/TP, PTP or ARC156 (also Modbus and N2). Many points only apply with the Control Air 6120 Point Expander and the matching options.

This page lists 200 BACnet objects for the Bosch Control Air 6120 - Water to Air (WAF software) — 70 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Bosch’s own free documentation, linked below.

Manufacturer
Bosch
Model
Control Air 6120 - Water to Air (WAF software)
Equipment
Commercial water-source heat pump controller
Equipment type
Heat pumps
BACnet objects
200 (70 writable)
Transport
BACnet MS/TP, BACnet ARC156, BACnet PTP
Firmware
WAF.1.01
Also known as
Control Air 6120, WAF 1.01, Bosch commercial WSHP DDC, Bosch TT Water to Air
Source document
Bosch TT - Water to Air Network Integration Points List · WAF.1.01 · rev. 2019-08-12
Download CSV 200 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Bosch Control Air 6120 - Water to Air (WAF software)

Integration in brief

Command occupancy over the network with occupancy_cmd_1 (Control Source = BAS), write occupied setpoints, and choose the temperature source; supply BAS values (zone temp, DAT, RH, CO2, OAT) if the BMS owns the sensors. Monitor current_alarm_1, alm_status_1 and sys_status_1.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 1occupancy_cmd_1BAS occupied command; 1 enables unit operationWrite
AV 15ctrl_source_1Occupancy source; 2 = BAS occupancy command (default)Write
AV 4occ_clg_stpt_1Occupied cooling setpointWrite
AV 2occ_htg_stpt_1Occupied heating setpointWrite
AV 16sys_status_1Unoccupied / occupied / fan only / heating / cooling stateRead
AV 57eff_zone_temp_1Zone temperature in useRead
AV 17current_alarm_1Active alarm codeRead
BV 24alm_status_1Alarm present flagRead

Enable & remote start

Control Source (ctrl_source_1, AV 15) defaults to 2 = BAS Occupancy Command; write occupancy_cmd_1 (BV 1) to occupy the unit. Alternatives are digital input IN-1, keypad schedule, manual on or the ZS push-button override. loop_enabled_1 (BV 23) must be 1 to allow heating and cooling.

Sensors & values from the BMS

BMS values can be written to bas_sen_val_1 (AV 7, zone temperature), bas_dat_val_1 (AV 90, discharge air; select with dat_sel_1 AV 81 = 3), bas_rh_sen_val_1 (AV 56), bas_co2_val_1 (AV 49) and bas_oat_1 (AV 29).

Network setup

Watch out for

Bosch Control Air 6120 - Water to Air (WAF software) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

200 of 200 shown
Type
Binary
Access
Show
Bosch Control Air 6120 - Water to Air (WAF software) BACnet Points List
DescriptionStates
BV51zn_co2_fail_1CO2 Hardware Failure AlarmRead0 = Normal 1 = Sensor Failure (Check Sensor Hardware)
AV105bkup_elect_ht_pos_1Backup Electric Heating Coil Position%Read
AV35bkup_ht_lock_val_1Backup Heat Lock Value%Write
AV49bas_co2_val_1BAS CO2 Sensor ValueppmWrite
AV90bas_dat_val_1BAS DAT Sensor°FWrite
AV5eff_clg_stpt_1Effective Cooling Setpoint°FRead
AV56bas_rh_sen_val_1BAS RH Sensor Value%Write
AV34econ_boil_mode_stat_1Boilerless-Economizer StatusRead0 = Disabled 1 = Boilerless 2 = Water Side Economizer
AV336coil_cfg_1Coil ConfigurationWrite0 = Parallel (Default) 1 = Series
AV337coil_cfg_status_1Coil Configuration StatusRead0 = Parallel 1 = Series
AV60comp_ctrl_status_1compressor control statusRead0 = Zone Control 1 = Discharge Air Control
AV14cmp_stgs_1Compressor StagesRead1 = 1 Compressor 1 Stage 2 = 2 Compressor 2 Stages 3 = 3 Compressor 3 Stages (3 and 4 Stage units only) 4 = 4 Compressor 4 Stages (4 Compressor units only) 5 = 1 Compressor 2 Stages
AVmin15ctrl_source_1Control SourceWrite0 = Digital Input 1 1 = Keypad Schedule 2 = BAS Occupancy Command (Default) 3 = Factory Use 4 = Manual On-Continuous
BV22nsb_status_1Night Setback (NSB) StatusRead0 = Disabled 1 = Night Setback Enabled
AV303sat_stpt_cl_1Cooling Setpoint°FWrite
AVmin17current_alarm_1Current AlarmRead0 = No Alarm 1-7 = UPM Fault Code 20 = Output Overridden via Keypad 30 = Sensor Failure 40 = Leaving Water Temp Alarm 50 = Zone Temp Alarm 60 = Discharge Air Temperature 70 = Filter Alarm/Compressors 1 & 2 Runtime 80 = Zone Humidity Alarm 90 = High CO2 Level Alarm
AV81dat_sel_1DAT Sensor SelectionWrite0 = Zone DAT (Default) 1 = DAT Sensor 2 = SAT Sensor 3 = BAS Supplied DAT
AV82dat_sel_sta_1DAT Sensor Source Selection StatusRead0 = Zone DAT 1 = DAT Sensor 2 = SAT Sensor 3 = BAS Supplied DAT
AV64demand_level_1Demand Level°FWrite
AV28eff_hgr_mod_vlv1_1Eff HGR Mod Valve 1%Read
AV53eff_sa_sta_press_1Eff SA Static Pressurein. W.C.Read
AV25eff_zn_co2_lev_1Eff Zone Co2 LevppmRead
BV42zrem_lo_1Low Remote Temperature AlarmRead0 = Normal 1 = Low Zone Temperature (Default: 10 °F Below Setpoint)
AV10eff_dat_1Effect Disch Air Temp°FRead
AV62eff_ewt_1Effect EW Temp°FRead
BV27ztmp_lo_1Low ZS Zone Sensor Temperature AlarmRead0 = Normal 1 = Low Zone Temperature (Default: 10 °F Below Setpoint)
AV11eff_lwt_1Effect Leaving Wtr Temp°FRead
AV32eff_load_tmp_1Effect Load Temp°FRead
AV75eff_oat_1Effect Outdoor Air Temp°FRead
AV20eff_zone_humid_1Effective Zone Humidity%Read
AV68enabled_clstages_1Enabled StagesRead
AV101ewlt_low_trip_1EWLT Low Trip Point°FWrite
AV102ewlt_low_trip_hyst_1EWLT Low Trip Point Hyst°FWrite
AV103ewlt_trip_timer_1EWLT Timer Above LimitminWrite
AV93in10_cfg_sel_1IN 10 HW CFGWrite0 = DPS 1 = FSS 2 = OAT 3 = Not installed (Default)
AV94in_10_mode_stat_1Input 10 StatusRead
AV36in_4_mode_stat_1Input 4 StatusRead0 = VFD Over Current Hardware (From VFD Controller) 1 = CO2 Hardware 2 = Not Installed (Default) 3 = CWV Feedback
AV37in_7_mode_stat_1Input 7 StatusRead0 = VFD Overvoltage Hardware (From VFD Controller) 1 = Entering Water Temperature Sensor 2 = Not Installed (Default)
AV38in_9_mode_stat_1Input 9 StatusRead0 = VFD Overload Hardware (From VFD Controller) 2 = Not Installed (Default)
AV95ms_status_1M/S CFG StatusRead
AV96ms_cfg_1Master/Slave HW CFGWrite0 = Normal Operation (Default) 1 = Master 2 = Slave
AV24mode_status_1mode statusRead0 = Cooling only 1 = Aux Heat 2 = Heat Pump (Default) 3 = Heat Pump + Aux Heat 4 = Heat Pump + Hot Gas Re-Heat 5 = Cooling + Hot Gas Re-Heat 6 = Heat Pump + Hot Gas Reheat + Auxiliary Heat
AV80oat_reset1_1OAT Reset°FWrite
AV72oat_reset2_1OAT Reset 2°FWrite
AV74oat_reset3_1OAT Reset 3°FWrite
AV76oat_reset4_1OAT Reset 4°FWrite
AV79oat_reset5_1OAT Reset 5°FWrite
AV92oat_reset_ht_1OAT Reset MA°FWrite
AV71oat_rst_mode_1OAT Reset ModeWrite0 = Single Temperature 1 = Multiple Temperature (Default)
AV73oat_sel_1OAT Reset SelectionWrite0 = BAS supplied OAT 1 = Hardwired OAT Sensor (Default)
AV78oat_sel_sta_1OAT SelectRead0 = BAS OAT 1 = Hardwired OAT
AV21occ_zhumid_stpt_1Occupied Zone Humidity Setpoint%Write
AV39htg_ovrde_1Output OverrideWrite0 = Off 1 = Override Heating (% Required via BACview Terminal)
AV40clg_ovrde_1Output OverrideWrite0 = Off 1 = Override Cooling (% Required via BACview Terminal)
AV89oat_rst_mode_stat_1Outside Air Reset Mode StatusRead0 = Single 1 = Multiple
AV54sa_sta_hi_trip_1SA Static Press High Tripin. W.C.Write
AV41stpt_adj_dem_1Setpoint Adjust°FRead
AV52sta_press_stpt_1Static Press Setpointin. W.C.Write
AV69st_press_trip_1Static Pressure Shutdownin. W.C.Write
AV59saf_min_speed_1Suplpy Air Fan min speedWrite
AV67eff_sat_1Supply Air Temperature°FRead
AV77sat_lo_trip_1supply air low trip°FWrite
AV65sat_stpt_diff_1Supply Air Setpoint Differential°FWrite
AV31sa_setpt_1Supply Air Temp Setpoint°FRead
AVmin16sys_status_1System StatusRead0 = Unoccupied 1 = Occupied 2 = Fan Only 3 = Heating 4 = Cooling 5 = Transition to Cool 6 = Transition to Heat 7 = Manual Cool 8 = Manual Heat 9 = Aux Heat 10 = Re-Heat 11 = Manual Re-Heat 12 = Transition to Re-Heat
AV23unit_mode_1Unit_modeWrite0 = Cooling only 1 = Aux Heat 2 = Heat Pump (Default) 3 = Heat Pump + Aux Heat 4 = Heat Pump + Hot Gas Re-Heat 5 = Cooling + Hot Gas Re-Heat 6 = Heat Pump + Hot Gas Re-Heat +Auxiliary Electric Heat
AV27zn_co2_hi_trip_1Zone Co2 High TripWrite
AV22zhumid_stpt_diff_1Zone Humidity Stpt Diff%Write
BVmin24alm_status_1Alarm StatusRead
BV106allow_cwv_alrm_1Allow CWV AlarmWrite0 = Off 1 = Enable CWV Alarm
BV20aux_htg_cmd_1Aux Heat Output CmdRead0 = Off 1 = Heat On
BV86aux_htg3_cmd_1Aux Heat Output CmdRead0 = Off 1 = Heat On
BV88aux_htg4_cmd_1Aux Heat Output CmdRead0 = Off 1 = Heat On
BV84aux_htg2_cmd_1Aux Heat Output CmdRead0 = Off 1 = Heat On
BV97aux_htg1_fo_1Aux Heat Output Cmd Flex OnlyRead0 = Off 1 = Heat On
BV98aux_htg2_fo_1Aux Heat Output Cmd Flex OnlyRead0 = Off 1 = Heat On
BV2bkup_ht_lock_1Backup Heat Lock?Write0 = Off 1 = On (Heating % must be provided via BACview)
BV91bas_sd_in_1BAS SD InputWrite0 = Normal 1 = Smoke Alarm Active
BV10brn_2st_1BRNRead0 = Normal 1 = Brownout Alarm Active
BV58brn_4st_1BRN2Read0 = Normal 1 = Brownout Alarm Active
BVmin1occupancy_cmd_1BV Occupancy Command (BAS)Write0 = Disable Unit Operation 1 = Enable Unit Operation
BV35comp1_rntm_1CMP1_RNTMRead0 = Off 1 = Timer Has Expired
BV36comp2_rntm_1CMP2_RNTMRead0 = Off 1 = Timer Has Expired
BV69comp3_rntm_1CMP3_RNTMRead0 = Off 1 = Timer Has Expired
BV71comp4_rntm_1CMP4_RNTMRead0 = Off 1 = Timer Has Expired
BV11cmp_stg1_cmd_1Comp Stage1 Output CmdRead0 = Compressor Stage 1 Off 1 = Compressor 1 On
BV12cmp_stg2_cmd_1Comp Stage2 Output CmdRead0 = Compressor 2 Off 1 = Compressor 2 On
BV66cmp_stg3_cmd_1Comp Stage3 Output CmdRead0 = Compressor 3 Off 1 = Compressor 2 On
BV67cmp_stg4_cmd_1Comp Stage4 Output CmdRead0 = Compressor 2 Off 1 = Compressor 2 On
BV13cmp1_rntm_rst_1Comp1 Runtime RstWrite
BV14cmp2_rntm_rst_1Comp2 Runtime RstWrite
BV68cmp3_rntm_rst_1Comp3 Runtime RstWrite
BV70cmp4_rntm_rst_1Comp4 Runtime RstWrite
BV9con_2st_1CONRead0 = Normal 1 = Condensate Alarm
BV57con_4st_1CON2Read0 = Normal 1 = Condensate Alarm
BV105cond_vlv_status_1Condenser Valve StatusRead0 = Compressor Operation Disabled 1 = Compressor Operation Enabled
BV18Cont_fan_1Continous FanWrite0 = Cycle Fan with Compressor Operation 1 = Run Fan when Occupied (Default)
BV63clg_econ_1Cooling EconoRead0 = Off 1 = On
BV80csat_hi_1CSAT_HIRead0 = Normal 1 = High Supply Temperature Alarm Active
BV109cwv_command_1CWV CommandRead0 = Off 1 = On
BV107cwv_fail_1CWV_FAILRead
BV108cwv_hand_1CWV_HANDRead
BV31da_sen_1DA_SENS_FAILRead0 = Sensor Connected 1 = Sensor Not Installed
BV49damper_cmd_1Damper Output CmdRead0 = Closed 1 = Open
BV29dat_hi_1DAT_HIRead0 = Normal 1 = High DAT (Default: >70 °F)
BV30dat_lo_1DAT_LORead0 = Normal 1 = Low DAT (Default: >75 °F)
BV37do_lock_1DO_LOCKRead0 = Normal 1 = Digital Override Has Been Enabled
BV77DPS_alarm_1DPS AlarmRead0 = Normal 1 = Active DPS
BV79dx_rntm_1DX_RNTMRead0 = Normal 1 = Compressor Time Expired (Default: 8760 Hrs)
BV44eff_hgrv_cmd_1Effect HGR Vlv CommandRead0 = Off 1 = Valve Enabled
BV72elw_sen_1ELW_SENS_FAILRead0 = Normal 1 = Sensor Failure Alarm (Check Hardware Configuration)
BV40filter_1FILTERRead0 = Normal 1 = Active
BV50filter_status_1Filter StatusRead0 = Normal 1 = Clean Filter
BV8frz_2st_1FRERead0 = Normal 1 = Active Freeze Condition
BV56frz_4st_1FRE2Read0 = Normal 1 = Active Freeze Condition
BV62htg_econ_1Heating EconoRead0 = Off 1 = Compressors Off & Electric Heat Enabled
BV96blw_static_status_1High Static StatusRead0 = Normal 1 = High Static Pressure
BV5hp1_2st_1HP1Read0 = Normal 1 = Active High Pressure 1 Alarm
BV52hp2_2st_1HP2Read0 = Normal 1 = Active High Pressure 3 Alarm
BV7hp3_3st_1HP3Read0 = Normal 1 = High Pressure 2 Alarm
BV54hp4_4st_1HP4Read0 = Normal 1 = High Pressure 4 Alarm
BV61hsat_lo_1HSAT_LORead0 = Normal 1 = Active (Default: <80 °F)
BV38input_lock_1INPUT_LOCKRead0 = Normal 1 = Software Lock Enabled
BV23loop_enabled_1Loop EnabledWrite0 = Disable Heat/Cool 1 = Allow Heating and Cooling
BV81sta_press_low_1LOW SPRead0 = Normal 1 = Alarm Active (Default: 0.25")
BV4lp1_2st_1LP1Read0 = Normal 1 = LP1 Alarm Active
BV53lp2_2st_1LP2Read0 = Normal 1 = LP3 Alarm Active
BV6x_1LP3Read0 = Normal 1 =Low Pressure 2 Alarm
BV55lp4_4st_1LP4Read0 = Normal 1 = LP4 Alarm Active
BV32lvg_hi_1LVG_HIRead0 = Normal 1 = High LWT Alarm Active (Default: >135 °F)
BV33lvg_lo_1LVG_LORead0 = Normal 1 = Low LWT Alarm Active (Default: <21 °F)
BV34lvg_sen_1LVG_SENS_FAILRead0 = Normal 1 = Sensor Failure (Check Sensor Hardware Configuration)
BV99oat_sen_1OA_SENS_FAILRead0 = Normal 1 = Sensor Failure (Check Sensor Hardware Configuration)
BV82clg_ovrde_lock_1Output Override LockWrite0 = Off 1 = On
BV93blw_ovrc_status_1Overcurrent StatusRead0 = Normal 1 = Over Current Detected
BV75blwr_ovrload_alm_1OverloadRead0 = Normal 1 = Overload Detected
BV74blw_ovrload_status_1Overload StatusRead0 = Normal 1 = Active Blower Overload
BV95blw_ovrv_status_1Overvoltage StatusRead0 = Normal 1 = Overvoltage Detected
BV92blwr_ovrcurrent_alm_1OvrcurrentRead0 = Normal 1 = Over Current Detected
BV94blwr_ovrv_alm_1OvrvoltageRead0 = Normal 1 = Overvoltage Detected
BV19fan_rntm_rst_1Reset Fan RntmWrite
BV16rev_vlv_act_1Rev Valve ActionWrite0 = Heating is enabled 1 = Cooling is enabled (Default)
BV90sa_config_error_1SA_CFGRead
BV65sas_sen_1SA_SENS_FAILRead0 = Normal 1 = Sensor Failure (Check Sensor Hardware)
BV64sas_hi_1SAS_HIRead0 = Normal 1 = High Static Pressure (Default: 4.0" H20)
BV73sat-sen_1SAT SENS FAILRead0 = Normal 1 = Sensor Failure (Check Sensor Hardware)
BV78sat_hi_1SAT_HIRead0 = Normal 1 = High SAT Alarm Active
BV206sat_lo_1SAT_LORead0 = Normal 1 = Low SAT Alarm Active
BV89smoke_1Smk Det AlarmRead0 = Normal 1 = Alarm
BV87smoke_status_1smoke detector statusRead0 = Normal 1 = Smoke Detector Active
BV39upm_input_1UPM INPUTRead0 = UPM Connected 1 = UPM Connection Failure
BV59upm2_input_1UPM2 INPUTRead0 = UPM Connected 1 = UPM Connection Failure
BV25upm_rst_1UPM ResetWrite
BV60upm2_rst_1UPM ResetWrite
BV45zhumid_hi_1ZHUM_HIRead0 = Normal 1 = High Humidity (Default: 10% above Setpoint)
BV46zhumid_lo_1ZHUM_LORead0 = Normal 1 = Low Humidity (Default: 30% below Setpoint)
BV47zhumid_sen_1ZHUM_SENS_FAILRead0 = Normal 1 = Sensor Failure (Check Sensor Failure)
BV48zn_co2_hi_1ZN_CO2_HIRead0 = Normal 1 = High CO2 Level (Default: >1200 PPM)
BV15rev_vlv_cmd_1Rev Valve Output CmdRead0 = Valve De- energized 1 = Valve Energized
AV8000version_1Software VersionRead
BV21occ_status_1Occupancy StatusRead0 = Unoccupied 1 = Occupied
AV13clg_pct_1Cooling Demand Percentage%Read
AV12htg_pct_1Heating Demand Percentage%Read
BV26ztmp_hi_1High ZS Zone Sensor Temperature AlarmRead0 = Normal 1 = High Zone Temperature (Default: 10 °F Above Setpoint)
BV28zone_sen_1ZS Zone Sensor Hardware Failure AlarmRead0 = Normal 1 = Sensor Failure (Check Sensor Hardware)
BV41zrem_hi_1High Remote Temperature AlarmRead0 = Normal 1 = High Zone Temperature (Default: 10 °F Above Setpoint)
BV43zrem_sen_1Remote Temperature Sensor Hardware Failure AlarmRead0 = Normal 1 = Sensor Failure (Check Sensor Hardware)
AV42stpt_adj_lim_1ZS Sensor Setpoint Adjustment Limit°FWrite
AV6eff_htg_stpt_1Effective Heating Setpoint°FRead
AVmin4occ_clg_stpt_1Setpoint°FWrite
AVmin2occ_htg_stpt_1Setpoint°FWrite
AV1unocc_clg_stpt_1Setpoint°FWrite
AV3unocc_htg_stpt_1Setpoint°FWrite
AV115tlo_rem_1Override Time RemainingRead
AV8comp_mode_1Compressor Control ModeWrite0 = Zone (Default) 1 = Discharge Air Control 2 = Zone (BAS) 3 = Zone (Remote)
BV76override_status_1Override StatusRead0 = Normal 1 = ZS Sensor in Override Mode
AV9eff_remzone_temp_1Effect Zone Remote TemperatureRead
AV116zt_reset_1Effective ZS Sensor TemperatureRead
AV29bas_oat_1BAS Outdoor Air TempWrite
AV55eff_sa_fan_speed_1Eff SA Fan Speed%Read
AV7bas_sen_val_1BAS Temperature Sensor Value°FWrite
AV18in3_cfg_sel_1Input 3 configuration selectorWrite0 = Not installed (Default) 1 = Leaving Water temperature sensor
AV19in3_cfg_sta_1Input 3 Configuration statusRead
AV26zone_rem_sen_val_1Remote Temp or Return Air Temp ValueRead
AV30sat_hi_trip_1Supply Air High Differential TripWrite
AVmin57eff_zone_temp_1Zone Temperature°FRead
AV58zs_sen_combo_sel_1ZS Sensor Combo SelectorWrite0 = Temp Only 1 = RH Only 2 = CO2 Only 3 = Temp + RH 4 = Temp + CO2 5 = RH + CO2 6 = Temp + RH + CO2 (Default) 7 = No ZS Sensor
AV61zs_sensor_en_1ZS Sensor EnableWrite0 = No ZS sensors 1 = ZS sensors enabled (Default)
BV3da_stpt_reset_1DAT Sepoint resetWrite0 = Disabled (Default) 1 = Enabled
BV17lckout_resp_1Fan Response for Comp LockoutWrite0 = Do not lock fan upon compressor lockout (Default) 1 = Lock fan upon compressor lockout
AV2004serial_number_1Counter No SerialWrite
AV2003counter_no_local_1Counter Number localWrite
AV2005bosch_pn1_1Part NumberWrite
AV2001factory_pc_1Plant CodeWrite
AV114stages_1StagesWrite1 = 1 Compressor 1 Stage 2 = 2 Compressor 2 Stages 3 = 3 Compressor 3 Stages (3 and 4 Stage units only) 4 = 4 Compressor 4 Stages (4 Compressor units only) (Default) 5 = 1 Compressor 2 Stages
AV2002mfg_date_1WarrantyWrite
AI1sa_temp_1SAT 8°FRead
AV109in1_cfg_sta_1Input 1 Configuration StatusRead
AV50Fan_mode_1Fan_modeWrite1 = Standard Fan Configuration (default) 2 = Variable Frequency Drive Configuration
AV51fan_mode_status_1fan mode statusRead0 = Start / Stop Fan Operation 1 = Variable Frequency Drive Fan Operation

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Control Air 6120 - Water to Air (WAF software) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Bosch Control Air 6120 - Water to Air (WAF software)

How many BACnet points does the Bosch Control Air 6120 - Water to Air (WAF software) have?

This list has 200 BACnet objects: 1 analog input, 96 analog values, 103 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Bosch Control Air 6120 - Water to Air (WAF software) BACnet points are writable?

70 of the 200 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Bosch Control Air 6120 - Water to Air (WAF software) BACnet documentation?

The source is Bosch TT - Water to Air Network Integration Points List (WAF.1.01), revision 2019-08-12, published free by Bosch at https://www.bosch-homecomfort.com/us/media/country_pool/service/technical_guides/ipl_waf_1_01_us.pdf.

What are the minimum BACnet points to integrate the Bosch Control Air 6120 - Water to Air (WAF software)?

Start with BV 1 occupancy_cmd_1 (BAS occupied command; 1 enables unit operation); AV 15 ctrl_source_1 (Occupancy source; 2 = BAS occupancy command (default)); AV 4 occ_clg_stpt_1 (Occupied cooling setpoint); AV 2 occ_htg_stpt_1 (Occupied heating setpoint); AV 16 sys_status_1 (Unoccupied / occupied / fan only / heating / cooling state); AV 57 eff_zone_temp_1 (Zone temperature in use); AV 17 current_alarm_1 (Active alarm code); BV 24 alm_status_1 (Alarm present flag).

How do I enable BMS control of the Bosch Control Air 6120 - Water to Air (WAF software)?

Control Source (ctrl_source_1, AV 15) defaults to 2 = BAS Occupancy Command; write occupancy_cmd_1 (BV 1) to occupy the unit. Alternatives are digital input IN-1, keypad schedule, manual on or the ZS push-button override. loop_enabled_1 (BV 23) must be 1 to allow heating and cooling.

Can the BMS supply sensor values to the Bosch Control Air 6120 - Water to Air (WAF software)?

BMS values can be written to bas_sen_val_1 (AV 7, zone temperature), bas_dat_val_1 (AV 90, discharge air; select with dat_sel_1 AV 81 = 3), bas_rh_sen_val_1 (AV 56), bas_co2_val_1 (AV 49) and bas_oat_1 (AV 29).

How do I check these points on the real Control Air 6120 - Water to Air (WAF software)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Bosch BACnet points lists

Source: Bosch TT - Water to Air Network Integration Points List · WAF.1.01 · rev. 2019-08-12. Object names, instances and units are reproduced as published; descriptions are our own.