 "manufacturer": "Bosch",
 "manufacturer_slug": "bosch",
 "model": "Control Air 6120 - Water to Air (WAF software)",
 "model_slug": "control-air-6120-water-to-air",
 "aliases": [
  "Control Air 6120",
  "WAF 1.01",
  "Bosch commercial WSHP DDC",
  "Bosch TT Water to Air"
 ],
 "equipment_type": "Commercial water-source heat pump controller",
 "applies_to": "Bosch commercial water-to-air heat pumps (up to 4 compressor stages) with the Control Air 6120 DDC controller and WAF software.",
 "summary": "The Control Air 6120 is Bosch's DDC controller for larger commercial water-to-air heat pumps, including discharge-air control, VFD fans, economizer/boilerless options, hot gas reheat and auxiliary heat. It is a BACnet Advanced Application Controller on MS/TP, PTP or ARC156 (also Modbus and N2). Many points only apply with the Control Air 6120 Point Expander and the matching options.",
 "bacnet_transport": [
  "BACnet MS/TP",
  "BACnet ARC156",
  "BACnet PTP"
 ],
 "firmware": "WAF.1.01",
 "default_device_instance": null,
 "access_inferred": false,
 "notes": [
  "Object names end in _1 as printed; the LP3 alarm is printed with the name x_1 (BV 6).",
  "Alarms are reported through current_alarm_1 (AV 17); high-static lockout is reported as code 100 on sys_status_1 (AV 16) and can only be reset from BACview.",
  "Points for compressor stages 3-4, auxiliary heat 2-4 and second UPM only apply to units built with them.",
  "AV 2001-2005 hold factory serial / part number data."
 ],
 "source": {
  "title": "Bosch TT - Water to Air Network Integration Points List",
  "doc_number": "WAF.1.01",
  "revision_date": "2019-08-12",
  "url": "https://www.bosch-homecomfort.com/us/media/country_pool/service/technical_guides/ipl_waf_1_01_us.pdf"
 },
 "integration": {
  "summary": "Command occupancy over the network with occupancy_cmd_1 (Control Source = BAS), write occupied setpoints, and choose the temperature source; supply BAS values (zone temp, DAT, RH, CO2, OAT) if the BMS owns the sensors. Monitor current_alarm_1, alm_status_1 and sys_status_1.",
  "minimum_points": [
   {
    "ref": "BV 1",
    "name": "occupancy_cmd_1",
    "why": "BAS occupied command; 1 enables unit operation"
   },
   {
    "ref": "AV 15",
    "name": "ctrl_source_1",
    "why": "Occupancy source; 2 = BAS occupancy command (default)"
   },
   {
    "ref": "AV 4",
    "name": "occ_clg_stpt_1",
    "why": "Occupied cooling setpoint"
   },
   {
    "ref": "AV 2",
    "name": "occ_htg_stpt_1",
    "why": "Occupied heating setpoint"
   },
   {
    "ref": "AV 16",
    "name": "sys_status_1",
    "why": "Unoccupied / occupied / fan only / heating / cooling state"
   },
   {
    "ref": "AV 57",
    "name": "eff_zone_temp_1",
    "why": "Zone temperature in use"
   },
   {
    "ref": "AV 17",
    "name": "current_alarm_1",
    "why": "Active alarm code"
   },
   {
    "ref": "BV 24",
    "name": "alm_status_1",
    "why": "Alarm present flag"
   }
  ],
  "enable": "Control Source (ctrl_source_1, AV 15) defaults to 2 = BAS Occupancy Command; write occupancy_cmd_1 (BV 1) to occupy the unit. Alternatives are digital input IN-1, keypad schedule, manual on or the ZS push-button override. loop_enabled_1 (BV 23) must be 1 to allow heating and cooling.",
  "heartbeat": null,
  "remote_sensors": "BMS values can be written to bas_sen_val_1 (AV 7, zone temperature), bas_dat_val_1 (AV 90, discharge air; select with dat_sel_1 AV 81 = 3), bas_rh_sen_val_1 (AV 56), bas_co2_val_1 (AV 49) and bas_oat_1 (AV 29).",
  "setup": [
   "BACnet MS/TP runs on the EIA-485 port; the BAS Port Settings DIP switches select the protocol (BACnet MS/TP, N2, Modbus) and baud rate (9.6 to 76.8 kbps), the same for every controller on the trunk.",
   "The two rotary dials set the MAC address (tens and ones); the controller only reads them at power-up, so change them with power off.",
   "Port 2a is set to EIA-485 or EIA-232 and 2-wire or 4-wire with jumpers; Port 1 is ARC156 only.",
   "The controller is a BACnet Advanced Application Controller (B-AAC)."
  ],
  "gotchas": [
   "High static shutdowns follow a three-strike rule; once locked out (code 100) the unit can only be reset from the BACview terminal, not over BACnet.",
   "Wall-sensor setpoint adjustment is limited to ±3 °F by stpt_adj_lim_1.",
   "Auxiliary heat (and several other options) needs the Control Air 6120 Point Expander.",
   "Configuration AVs (input selectors, unit mode, stages, coil configuration) are commissioning settings; avoid cyclic writes."
  ]
 },
 "points": [
  {
   "type": "BV",
   "instance": 51,
   "name": "zn_co2_fail_1",
   "description": "CO2 Hardware Failure Alarm",
   "units": "",
   "access": "R",
   "states": "0 = Normal 1 = Sensor Failure (Check Sensor Hardware)"
  },
  {
   "type": "AV",
   "instance": 105,
   "name": "bkup_elect_ht_pos_1",
   "description": "Backup Electric Heating Coil Position",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 35,
   "name": "bkup_ht_lock_val_1",
   "description": "Backup Heat Lock Value",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 49,
   "name": "bas_co2_val_1",
   "description": "BAS CO2 Sensor Value",
   "units": "ppm",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 90,
   "name": "bas_dat_val_1",
   "description": "BAS DAT Sensor",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 5,
   "name": "eff_clg_stpt_1",
   "description": "Effective Cooling Setpoint",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 56,
   "name": "bas_rh_sen_val_1",
   "description": "BAS RH Sensor Value",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 34,
   "name": "econ_boil_mode_stat_1",
   "description": "Boilerless-Economizer Status",
   "units": "",
   "access": "R",
   "states": "0 = Disabled 1 = Boilerless 2 = Water Side Economizer"
  },
  {
   "type": "AV",
   "instance": 336,
   "name": "coil_cfg_1",
   "description": "Coil Configuration",
   "units": "",
   "access": "W",
   "states": "0 = Parallel (Default) 1 = Series"
  },
  {
   "type": "AV",
   "instance": 337,
   "name": "coil_cfg_status_1",
   "description": "Coil Configuration Status",
   "units": "",
   "access": "R",
   "states": "0 = Parallel 1 = Series"
  },
  {
   "type": "AV",
   "instance": 60,
   "name": "comp_ctrl_status_1",
   "description": "compressor control status",
   "units": "",
   "access": "R",
   "states": "0 = Zone Control 1 = Discharge Air Control"
  },
  {
   "type": "AV",
   "instance": 14,
   "name": "cmp_stgs_1",
   "description": "Compressor Stages",
   "units": "",
   "access": "R",
   "states": "1 = 1 Compressor 1 Stage 2 = 2 Compressor 2 Stages 3 = 3 Compressor 3 Stages (3 and 4 Stage units only) 4 = 4 Compressor 4 Stages (4 Compressor units only) 5 = 1 Compressor 2 Stages"
  },
  {
   "type": "AV",
   "instance": 15,
   "name": "ctrl_source_1",
   "description": "Control Source",
   "units": "",
   "access": "W",
   "states": "0 = Digital Input 1 1 = Keypad Schedule 2 = BAS Occupancy Command (Default) 3 = Factory Use 4 = Manual On-Continuous"
  },
  {
   "type": "BV",
   "instance": 22,
   "name": "nsb_status_1",
   "description": "Night Setback (NSB) Status",
   "units": "",
   "access": "R",
   "states": "0 = Disabled 1 = Night Setback Enabled"
  },
  {
   "type": "AV",
   "instance": 303,
   "name": "sat_stpt_cl_1",
   "description": "Cooling Setpoint",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 17,
   "name": "current_alarm_1",
   "description": "Current Alarm",
   "units": "",
   "access": "R",
   "states": "0 = No Alarm 1-7 = UPM Fault Code 20 = Output Overridden via Keypad 30 = Sensor Failure 40 = Leaving Water Temp Alarm 50 = Zone Temp Alarm 60 = Discharge Air Temperature 70 = Filter Alarm/Compressors 1 & 2 Runtime 80 = Zone Humidity Alarm 90 = High CO2 Level Alarm"
  },
  {
   "type": "AV",
   "instance": 81,
   "name": "dat_sel_1",
   "description": "DAT Sensor Selection",
   "units": "",
   "access": "W",
   "states": "0 = Zone DAT (Default) 1 = DAT Sensor 2 = SAT Sensor 3 = BAS Supplied DAT"
  },
  {
   "type": "AV",
   "instance": 82,
   "name": "dat_sel_sta_1",
   "description": "DAT Sensor Source Selection Status",
   "units": "",
   "access": "R",
   "states": "0 = Zone DAT 1 = DAT Sensor 2 = SAT Sensor 3 = BAS Supplied DAT"
  },
  {
   "type": "AV",
   "instance": 64,
   "name": "demand_level_1",
   "description": "Demand Level",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 28,
   "name": "eff_hgr_mod_vlv1_1",
   "description": "Eff HGR Mod Valve 1",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 53,
   "name": "eff_sa_sta_press_1",
   "description": "Eff SA Static Pressure",
   "units": "in. W.C.",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 25,
   "name": "eff_zn_co2_lev_1",
   "description": "Eff Zone Co2 Lev",
   "units": "ppm",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 42,
   "name": "zrem_lo_1",
   "description": "Low Remote Temperature Alarm",
   "units": "",
   "access": "R",
   "states": "0 = Normal 1 = Low Zone Temperature (Default: 10 °F Below Setpoint)"
  },
  {
   "type": "AV",
   "instance": 10,
   "name": "eff_dat_1",
   "description": "Effect Disch Air Temp",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 62,
   "name": "eff_ewt_1",
   "description": "Effect EW Temp",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 27,
   "name": "ztmp_lo_1",
   "description": "Low ZS Zone Sensor Temperature Alarm",
   "units": "",
   "access": "R",
   "states": "0 = Normal 1 = Low Zone Temperature (Default: 10 °F Below Setpoint)"
  },
  {
   "type": "AV",
   "instance": 11,
   "name": "eff_lwt_1",
   "description": "Effect Leaving Wtr Temp",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 32,
   "name": "eff_load_tmp_1",
   "description": "Effect Load Temp",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 75,
   "name": "eff_oat_1",
   "description": "Effect Outdoor Air Temp",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 20,
   "name": "eff_zone_humid_1",
   "description": "Effective Zone Humidity",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 68,
   "name": "enabled_clstages_1",
   "description": "Enabled Stages",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 101,
   "name": "ewlt_low_trip_1",
   "description": "EWLT Low Trip Point",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 102,
   "name": "ewlt_low_trip_hyst_1",
   "description": "EWLT Low Trip Point Hyst",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 103,
   "name": "ewlt_trip_timer_1",
   "description": "EWLT Timer Above Limit",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 93,
   "name": "in10_cfg_sel_1",
   "description": "IN 10 HW CFG",
   "units": "",
   "access": "W",
   "states": "0 = DPS 1 = FSS 2 = OAT 3 = Not installed (Default)"
  },
  {
   "type": "AV",
   "instance": 94,
   "name": "in_10_mode_stat_1",
   "description": "Input 10 Status",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 36,
   "name": "in_4_mode_stat_1",
   "description": "Input 4 Status",
   "units": "",
   "access": "R",
   "states": "0 = VFD Over Current Hardware (From VFD Controller) 1 = CO2 Hardware 2 = Not Installed (Default) 3 = CWV Feedback"
  },
  {
   "type": "AV",
   "instance": 37,
   "name": "in_7_mode_stat_1",
   "description": "Input 7 Status",
   "units": "",
   "access": "R",
   "states": "0 = VFD Overvoltage Hardware (From VFD Controller) 1 = Entering Water Temperature Sensor 2 = Not Installed (Default)"
  },
  {
   "type": "AV",
   "instance": 38,
   "name": "in_9_mode_stat_1",
   "description": "Input 9 Status",
   "units": "",
   "access": "R",
   "states": "0 = VFD Overload Hardware (From VFD Controller) 2 = Not Installed (Default)"
  },
  {
   "type": "AV",
   "instance": 95,
   "name": "ms_status_1",
   "description": "M/S CFG Status",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 96,
   "name": "ms_cfg_1",
   "description": "Master/Slave HW CFG",
   "units": "",
   "access": "W",
   "states": "0 = Normal Operation (Default) 1 = Master 2 = Slave"
  },
  {
   "type": "AV",
   "instance": 24,
   "name": "mode_status_1",
   "description": "mode status",
   "units": "",
   "access": "R",
   "states": "0 = Cooling only 1 = Aux Heat 2 = Heat Pump (Default) 3 = Heat Pump + Aux Heat 4 = Heat Pump + Hot Gas Re-Heat 5 = Cooling + Hot Gas Re-Heat 6 = Heat Pump + Hot Gas Reheat + Auxiliary Heat"
  },
  {
   "type": "AV",
   "instance": 80,
   "name": "oat_reset1_1",
   "description": "OAT Reset",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 72,
   "name": "oat_reset2_1",
   "description": "OAT Reset 2",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 74,
   "name": "oat_reset3_1",
   "description": "OAT Reset 3",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 76,
   "name": "oat_reset4_1",
   "description": "OAT Reset 4",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 79,
   "name": "oat_reset5_1",
   "description": "OAT Reset 5",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 92,
   "name": "oat_reset_ht_1",
   "description": "OAT Reset MA",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 71,
   "name": "oat_rst_mode_1",
   "description": "OAT Reset Mode",
   "units": "",
   "access": "W",
   "states": "0 = Single Temperature 1 = Multiple Temperature (Default)"
  },
  {
   "type": "AV",
   "instance": 73,
   "name": "oat_sel_1",
   "description": "OAT Reset Selection",
   "units": "",
   "access": "W",
   "states": "0 = BAS supplied OAT 1 = Hardwired OAT Sensor (Default)"
  },
  {
   "type": "AV",
   "instance": 78,
   "name": "oat_sel_sta_1",
   "description": "OAT Select",
   "units": "",
   "access": "R",
   "states": "0 = BAS OAT 1 = Hardwired OAT"
  },
  {
   "type": "AV",
   "instance": 21,
   "name": "occ_zhumid_stpt_1",
   "description": "Occupied Zone Humidity Setpoint",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 39,
   "name": "htg_ovrde_1",
   "description": "Output Override",
   "units": "",
   "access": "W",
   "states": "0 = Off 1 = Override Heating (% Required via BACview Terminal)"
  },
  {
   "type": "AV",
   "instance": 40,
   "name": "clg_ovrde_1",
   "description": "Output Override",
   "units": "",
   "access": "W",
   "states": "0 = Off 1 = Override Cooling (% Required via BACview Terminal)"
  },
  {
   "type": "AV",
   "instance": 89,
   "name": "oat_rst_mode_stat_1",
   "description": "Outside Air Reset Mode Status",
   "units": "",
   "access": "R",
   "states": "0 = Single 1 = Multiple"
  },
  {
   "type": "AV",
   "instance": 54,
   "name": "sa_sta_hi_trip_1",
   "description": "SA Static Press High Trip",
   "units": "in. W.C.",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 41,
   "name": "stpt_adj_dem_1",
   "description": "Setpoint Adjust",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 52,
   "name": "sta_press_stpt_1",
   "description": "Static Press Setpoint",
   "units": "in. W.C.",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 69,
   "name": "st_press_trip_1",
   "description": "Static Pressure Shutdown",
   "units": "in. W.C.",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 59,
   "name": "saf_min_speed_1",
   "description": "Suplpy Air Fan min speed",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 67,
   "name": "eff_sat_1",
   "description": "Supply Air Temperature",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 77,
   "name": "sat_lo_trip_1",
   "description": "supply air low trip",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 65,
   "name": "sat_stpt_diff_1",
   "description": "Supply Air Setpoint Differential",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 31,
   "name": "sa_setpt_1",
   "description": "Supply Air Temp Setpoint",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 16,
   "name": "sys_status_1",
   "description": "System Status",
   "units": "",
   "access": "R",
   "states": "0 = Unoccupied 1 = Occupied 2 = Fan Only 3 = Heating 4 = Cooling 5 = Transition to Cool 6 = Transition to Heat 7 = Manual Cool 8 = Manual Heat 9 = Aux Heat 10 = Re-Heat 11 = Manual Re-Heat 12 = Transition to Re-Heat"
  },
  {
   "type": "AV",
   "instance": 23,
   "name": "unit_mode_1",
   "description": "Unit_mode",
   "units": "",
   "access": "W",
   "states": "0 = Cooling only 1 = Aux Heat 2 = Heat Pump (Default) 3 = Heat Pump + Aux Heat 4 = Heat Pump + Hot Gas Re-Heat 5 = Cooling + Hot Gas Re-Heat 6 = Heat Pump + Hot Gas Re-Heat +Auxiliary Electric Heat"
  },
  {
   "type": "AV",
   "instance": 27,
   "name": "zn_co2_hi_trip_1",
   "description": "Zone Co2 High Trip",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 22,
   "name": "zhumid_stpt_diff_1",
   "description": "Zone Humidity Stpt Diff",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 24,
   "name": "alm_status_1",
   "description": "Alarm Status",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 106,
   "name": "allow_cwv_alrm_1",
   "description": "Allow CWV Alarm",
   "units": "",
   "access": "W",
   "states": "0 = Off 1 = Enable CWV Alarm"
  },
  {
   "type": "BV",
   "instance": 20,
   "name": "aux_htg_cmd_1",
   "description": "Aux Heat Output Cmd",
   "units": "",
   "access": "R",
   "states": "0 = Off 1 = Heat On"
  },
  {
   "type": "BV",
   "instance": 86,
   "name": "aux_htg3_cmd_1",
   "description": "Aux Heat Output Cmd",
   "units": "",
   "access": "R",
   "states": "0 = Off 1 = Heat On"
  },
  {
   "type": "BV",
   "instance": 88,
   "name": "aux_htg4_cmd_1",
   "description": "Aux Heat Output Cmd",
   "units": "",
   "access": "R",
   "states": "0 = Off 1 = Heat On"
  },
  {
   "type": "BV",
   "instance": 84,
   "name": "aux_htg2_cmd_1",
   "description": "Aux Heat Output Cmd",
   "units": "",
   "access": "R",
   "states": "0 = Off 1 = Heat On"
  },
  {
   "type": "BV",
   "instance": 97,
   "name": "aux_htg1_fo_1",
   "description": "Aux Heat Output Cmd Flex Only",
   "units": "",
   "access": "R",
   "states": "0 = Off 1 = Heat On"
  },
  {
   "type": "BV",
   "instance": 98,
   "name": "aux_htg2_fo_1",
   "description": "Aux Heat Output Cmd Flex Only",
   "units": "",
   "access": "R",
   "states": "0 = Off 1 = Heat On"
  },
  {
   "type": "BV",
   "instance": 2,
   "name": "bkup_ht_lock_1",
   "description": "Backup Heat Lock?",
   "units": "",
   "access": "W",
   "states": "0 = Off 1 = On (Heating % must be provided via BACview)"
  },
  {
   "type": "BV",
   "instance": 91,
   "name": "bas_sd_in_1",
   "description": "BAS SD Input",
   "units": "",
   "access": "W",
   "states": "0 = Normal 1 = Smoke Alarm Active"
  },
  {
   "type": "BV",
   "instance": 10,
   "name": "brn_2st_1",
   "description": "BRN",
   "units": "",
   "access": "R",
   "states": "0 = Normal 1 = Brownout Alarm Active"
  },
  {
   "type": "BV",
   "instance": 58,
   "name": "brn_4st_1",
   "description": "BRN2",
   "units": "",
   "access": "R",
   "states": "0 = Normal 1 = Brownout Alarm Active"
  },
  {
   "type": "BV",
   "instance": 1,
   "name": "occupancy_cmd_1",
   "description": "BV Occupancy Command (BAS)",
   "units": "",
   "access": "W",
   "states": "0 = Disable Unit Operation 1 = Enable Unit Operation"
  },
  {
   "type": "BV",
   "instance": 35,
   "name": "comp1_rntm_1",
   "description": "CMP1_RNTM",
   "units": "",
   "access": "R",
   "states": "0 = Off 1 = Timer Has Expired"
  },
  {
   "type": "BV",
   "instance": 36,
   "name": "comp2_rntm_1",
   "description": "CMP2_RNTM",
   "units": "",
   "access": "R",
   "states": "0 = Off 1 = Timer Has Expired"
  },
  {
   "type": "BV",
   "instance": 69,
   "name": "comp3_rntm_1",
   "description": "CMP3_RNTM",
   "units": "",
   "access": "R",
   "states": "0 = Off 1 = Timer Has Expired"
  },
  {
   "type": "BV",
   "instance": 71,
   "name": "comp4_rntm_1",
   "description": "CMP4_RNTM",
   "units": "",
   "access": "R",
   "states": "0 = Off 1 = Timer Has Expired"
  },
  {
   "type": "BV",
   "instance": 11,
   "name": "cmp_stg1_cmd_1",
   "description": "Comp Stage1 Output Cmd",
   "units": "",
   "access": "R",
   "states": "0 = Compressor Stage 1 Off 1 = Compressor 1 On"
  },
  {
   "type": "BV",
   "instance": 12,
   "name": "cmp_stg2_cmd_1",
   "description": "Comp Stage2 Output Cmd",
   "units": "",
   "access": "R",
   "states": "0 = Compressor 2 Off 1 = Compressor 2 On"
  },
  {
   "type": "BV",
   "instance": 66,
   "name": "cmp_stg3_cmd_1",
   "description": "Comp Stage3 Output Cmd",
   "units": "",
   "access": "R",
   "states": "0 = Compressor 3 Off 1 = Compressor 2 On"
  },
  {
   "type": "BV",
   "instance": 67,
   "name": "cmp_stg4_cmd_1",
   "description": "Comp Stage4 Output Cmd",
   "units": "",
   "access": "R",
   "states": "0 = Compressor 2 Off 1 = Compressor 2 On"
  },
  {
   "type": "BV",
   "instance": 13,
   "name": "cmp1_rntm_rst_1",
   "description": "Comp1 Runtime Rst",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 14,
   "name": "cmp2_rntm_rst_1",
   "description": "Comp2 Runtime Rst",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 68,
   "name": "cmp3_rntm_rst_1",
   "description": "Comp3 Runtime Rst",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 70,
   "name": "cmp4_rntm_rst_1",
   "description": "Comp4 Runtime Rst",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 9,
   "name": "con_2st_1",
   "description": "CON",
   "units": "",
   "access": "R",
   "states": "0 = Normal 1 = Condensate Alarm"
  },
  {
   "type": "BV",
   "instance": 57,
   "name": "con_4st_1",
   "description": "CON2",
   "units": "",
   "access": "R",
   "states": "0 = Normal 1 = Condensate Alarm"
  },
  {
   "type": "BV",
   "instance": 105,
   "name": "cond_vlv_status_1",
   "description": "Condenser Valve Status",
   "units": "",
   "access": "R",
   "states": "0 = Compressor Operation Disabled 1 = Compressor Operation Enabled"
  },
  {
   "type": "BV",
   "instance": 18,
   "name": "Cont_fan_1",
   "description": "Continous Fan",
   "units": "",
   "access": "W",
   "states": "0 = Cycle Fan with Compressor Operation 1 = Run Fan when Occupied (Default)"
  },
  {
   "type": "BV",
   "instance": 63,
   "name": "clg_econ_1",
   "description": "Cooling Econo",
   "units": "",
   "access": "R",
   "states": "0 = Off 1 = On"
  },
  {
   "type": "BV",
   "instance": 80,
   "name": "csat_hi_1",
   "description": "CSAT_HI",
   "units": "",
   "access": "R",
   "states": "0 = Normal 1 = High Supply Temperature Alarm Active"
  },
  {
   "type": "BV",
   "instance": 109,
   "name": "cwv_command_1",
   "description": "CWV Command",
   "units": "",
   "access": "R",
   "states": "0 = Off 1 = On"
  },
  {
   "type": "BV",
   "instance": 107,
   "name": "cwv_fail_1",
   "description": "CWV_FAIL",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 108,
   "name": "cwv_hand_1",
   "description": "CWV_HAND",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 31,
   "name": "da_sen_1",
   "description": "DA_SENS_FAIL",
   "units": "",
   "access": "R",
   "states": "0 = Sensor Connected 1 = Sensor Not Installed"
  },
  {
   "type": "BV",
   "instance": 49,
   "name": "damper_cmd_1",
   "description": "Damper Output Cmd",
   "units": "",
   "access": "R",
   "states": "0 = Closed 1 = Open"
  },
  {
   "type": "BV",
   "instance": 29,
   "name": "dat_hi_1",
   "description": "DAT_HI",
   "units": "",
   "access": "R",
   "states": "0 = Normal 1 = High DAT (Default: >70 °F)"
  },
  {
   "type": "BV",
   "instance": 30,
   "name": "dat_lo_1",
   "description": "DAT_LO",
   "units": "",
   "access": "R",
   "states": "0 = Normal 1 = Low DAT (Default: >75 °F)"
  },
  {
   "type": "BV",
   "instance": 37,
   "name": "do_lock_1",
   "description": "DO_LOCK",
   "units": "",
   "access": "R",
   "states": "0 = Normal 1 = Digital Override Has Been Enabled"
  },
  {
   "type": "BV",
   "instance": 77,
   "name": "DPS_alarm_1",
   "description": "DPS Alarm",
   "units": "",
   "access": "R",
   "states": "0 = Normal 1 = Active DPS"
  },
  {
   "type": "BV",
   "instance": 79,
   "name": "dx_rntm_1",
   "description": "DX_RNTM",
   "units": "",
   "access": "R",
   "states": "0 = Normal 1 = Compressor Time Expired (Default: 8760 Hrs)"
  },
  {
   "type": "BV",
   "instance": 44,
   "name": "eff_hgrv_cmd_1",
   "description": "Effect HGR Vlv Command",
   "units": "",
   "access": "R",
   "states": "0 = Off 1 = Valve Enabled"
  },
  {
   "type": "BV",
   "instance": 72,
   "name": "elw_sen_1",
   "description": "ELW_SENS_FAIL",
   "units": "",
   "access": "R",
   "states": "0 = Normal 1 = Sensor Failure Alarm (Check Hardware Configuration)"
  },
  {
   "type": "BV",
   "instance": 40,
   "name": "filter_1",
   "description": "FILTER",
   "units": "",
   "access": "R",
   "states": "0 = Normal 1 = Active"
  },
  {
   "type": "BV",
   "instance": 50,
   "name": "filter_status_1",
   "description": "Filter Status",
   "units": "",
   "access": "R",
   "states": "0 = Normal 1 = Clean Filter"
  },
  {
   "type": "BV",
   "instance": 8,
   "name": "frz_2st_1",
   "description": "FRE",
   "units": "",
   "access": "R",
   "states": "0 = Normal 1 = Active Freeze Condition"
  },
  {
   "type": "BV",
   "instance": 56,
   "name": "frz_4st_1",
   "description": "FRE2",
   "units": "",
   "access": "R",
   "states": "0 = Normal 1 = Active Freeze Condition"
  },
  {
   "type": "BV",
   "instance": 62,
   "name": "htg_econ_1",
   "description": "Heating Econo",
   "units": "",
   "access": "R",
   "states": "0 = Off 1 = Compressors Off & Electric Heat Enabled"
  },
  {
   "type": "BV",
   "instance": 96,
   "name": "blw_static_status_1",
   "description": "High Static Status",
   "units": "",
   "access": "R",
   "states": "0 = Normal 1 = High Static Pressure"
  },
  {
   "type": "BV",
   "instance": 5,
   "name": "hp1_2st_1",
   "description": "HP1",
   "units": "",
   "access": "R",
   "states": "0 = Normal 1 = Active High Pressure 1 Alarm"
  },
  {
   "type": "BV",
   "instance": 52,
   "name": "hp2_2st_1",
   "description": "HP2",
   "units": "",
   "access": "R",
   "states": "0 = Normal 1 = Active High Pressure 3 Alarm"
  },
  {
   "type": "BV",
   "instance": 7,
   "name": "hp3_3st_1",
   "description": "HP3",
   "units": "",
   "access": "R",
   "states": "0 = Normal 1 = High Pressure 2 Alarm"
  },
  {
   "type": "BV",
   "instance": 54,
   "name": "hp4_4st_1",
   "description": "HP4",
   "units": "",
   "access": "R",
   "states": "0 = Normal 1 = High Pressure 4 Alarm"
  },
  {
   "type": "BV",
   "instance": 61,
   "name": "hsat_lo_1",
   "description": "HSAT_LO",
   "units": "",
   "access": "R",
   "states": "0 = Normal 1 = Active (Default: <80 °F)"
  },
  {
   "type": "BV",
   "instance": 38,
   "name": "input_lock_1",
   "description": "INPUT_LOCK",
   "units": "",
   "access": "R",
   "states": "0 = Normal 1 = Software Lock Enabled"
  },
  {
   "type": "BV",
   "instance": 23,
   "name": "loop_enabled_1",
   "description": "Loop Enabled",
   "units": "",
   "access": "W",
   "states": "0 = Disable Heat/Cool 1 = Allow Heating and Cooling"
  },
  {
   "type": "BV",
   "instance": 81,
   "name": "sta_press_low_1",
   "description": "LOW SP",
   "units": "",
   "access": "R",
   "states": "0 = Normal 1 = Alarm Active (Default: 0.25\")"
  },
  {
   "type": "BV",
   "instance": 4,
   "name": "lp1_2st_1",
   "description": "LP1",
   "units": "",
   "access": "R",
   "states": "0 = Normal 1 = LP1 Alarm Active"
  },
  {
   "type": "BV",
   "instance": 53,
   "name": "lp2_2st_1",
   "description": "LP2",
   "units": "",
   "access": "R",
   "states": "0 = Normal 1 = LP3 Alarm Active"
  },
  {
   "type": "BV",
   "instance": 6,
   "name": "x_1",
   "description": "LP3",
   "units": "",
   "access": "R",
   "states": "0 = Normal 1 =Low Pressure 2 Alarm"
  },
  {
   "type": "BV",
   "instance": 55,
   "name": "lp4_4st_1",
   "description": "LP4",
   "units": "",
   "access": "R",
   "states": "0 = Normal 1 = LP4 Alarm Active"
  },
  {
   "type": "BV",
   "instance": 32,
   "name": "lvg_hi_1",
   "description": "LVG_HI",
   "units": "",
   "access": "R",
   "states": "0 = Normal 1 = High LWT Alarm Active (Default: >135 °F)"
  },
  {
   "type": "BV",
   "instance": 33,
   "name": "lvg_lo_1",
   "description": "LVG_LO",
   "units": "",
   "access": "R",
   "states": "0 = Normal 1 = Low LWT Alarm Active (Default: <21 °F)"
  },
  {
   "type": "BV",
   "instance": 34,
   "name": "lvg_sen_1",
   "description": "LVG_SENS_FAIL",
   "units": "",
   "access": "R",
   "states": "0 = Normal 1 = Sensor Failure (Check Sensor Hardware Configuration)"
  },
  {
   "type": "BV",
   "instance": 99,
   "name": "oat_sen_1",
   "description": "OA_SENS_FAIL",
   "units": "",
   "access": "R",
   "states": "0 = Normal 1 = Sensor Failure (Check Sensor Hardware Configuration)"
  },
  {
   "type": "BV",
   "instance": 82,
   "name": "clg_ovrde_lock_1",
   "description": "Output Override Lock",
   "units": "",
   "access": "W",
   "states": "0 = Off 1 = On"
  },
  {
   "type": "BV",
   "instance": 93,
   "name": "blw_ovrc_status_1",
   "description": "Overcurrent Status",
   "units": "",
   "access": "R",
   "states": "0 = Normal 1 = Over Current Detected"
  },
  {
   "type": "BV",
   "instance": 75,
   "name": "blwr_ovrload_alm_1",
   "description": "Overload",
   "units": "",
   "access": "R",
   "states": "0 = Normal 1 = Overload Detected"
  },
  {
   "type": "BV",
   "instance": 74,
   "name": "blw_ovrload_status_1",
   "description": "Overload Status",
   "units": "",
   "access": "R",
   "states": "0 = Normal 1 = Active Blower Overload"
  },
  {
   "type": "BV",
   "instance": 95,
   "name": "blw_ovrv_status_1",
   "description": "Overvoltage Status",
   "units": "",
   "access": "R",
   "states": "0 = Normal 1 = Overvoltage Detected"
  },
  {
   "type": "BV",
   "instance": 92,
   "name": "blwr_ovrcurrent_alm_1",
   "description": "Ovrcurrent",
   "units": "",
   "access": "R",
   "states": "0 = Normal 1 = Over Current Detected"
  },
  {
   "type": "BV",
   "instance": 94,
   "name": "blwr_ovrv_alm_1",
   "description": "Ovrvoltage",
   "units": "",
   "access": "R",
   "states": "0 = Normal 1 = Overvoltage Detected"
  },
  {
   "type": "BV",
   "instance": 19,
   "name": "fan_rntm_rst_1",
   "description": "Reset Fan Rntm",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 16,
   "name": "rev_vlv_act_1",
   "description": "Rev Valve Action",
   "units": "",
   "access": "W",
   "states": "0 = Heating is enabled 1 = Cooling is enabled (Default)"
  },
  {
   "type": "BV",
   "instance": 90,
   "name": "sa_config_error_1",
   "description": "SA_CFG",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 65,
   "name": "sas_sen_1",
   "description": "SA_SENS_FAIL",
   "units": "",
   "access": "R",
   "states": "0 = Normal 1 = Sensor Failure (Check Sensor Hardware)"
  },
  {
   "type": "BV",
   "instance": 64,
   "name": "sas_hi_1",
   "description": "SAS_HI",
   "units": "",
   "access": "R",
   "states": "0 = Normal 1 = High Static Pressure (Default: 4.0\" H20)"
  },
  {
   "type": "BV",
   "instance": 73,
   "name": "sat-sen_1",
   "description": "SAT SENS FAIL",
   "units": "",
   "access": "R",
   "states": "0 = Normal 1 = Sensor Failure (Check Sensor Hardware)"
  },
  {
   "type": "BV",
   "instance": 78,
   "name": "sat_hi_1",
   "description": "SAT_HI",
   "units": "",
   "access": "R",
   "states": "0 = Normal 1 = High SAT Alarm Active"
  },
  {
   "type": "BV",
   "instance": 206,
   "name": "sat_lo_1",
   "description": "SAT_LO",
   "units": "",
   "access": "R",
   "states": "0 = Normal 1 = Low SAT Alarm Active"
  },
  {
   "type": "BV",
   "instance": 89,
   "name": "smoke_1",
   "description": "Smk Det Alarm",
   "units": "",
   "access": "R",
   "states": "0 = Normal 1 = Alarm"
  },
  {
   "type": "BV",
   "instance": 87,
   "name": "smoke_status_1",
   "description": "smoke detector status",
   "units": "",
   "access": "R",
   "states": "0 = Normal 1 = Smoke Detector Active"
  },
  {
   "type": "BV",
   "instance": 39,
   "name": "upm_input_1",
   "description": "UPM INPUT",
   "units": "",
   "access": "R",
   "states": "0 = UPM Connected 1 = UPM Connection Failure"
  },
  {
   "type": "BV",
   "instance": 59,
   "name": "upm2_input_1",
   "description": "UPM2 INPUT",
   "units": "",
   "access": "R",
   "states": "0 = UPM Connected 1 = UPM Connection Failure"
  },
  {
   "type": "BV",
   "instance": 25,
   "name": "upm_rst_1",
   "description": "UPM Reset",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 60,
   "name": "upm2_rst_1",
   "description": "UPM Reset",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 45,
   "name": "zhumid_hi_1",
   "description": "ZHUM_HI",
   "units": "",
   "access": "R",
   "states": "0 = Normal 1 = High Humidity (Default: 10% above Setpoint)"
  },
  {
   "type": "BV",
   "instance": 46,
   "name": "zhumid_lo_1",
   "description": "ZHUM_LO",
   "units": "",
   "access": "R",
   "states": "0 = Normal 1 = Low Humidity (Default: 30% below Setpoint)"
  },
  {
   "type": "BV",
   "instance": 47,
   "name": "zhumid_sen_1",
   "description": "ZHUM_SENS_FAIL",
   "units": "",
   "access": "R",
   "states": "0 = Normal 1 = Sensor Failure (Check Sensor Failure)"
  },
  {
   "type": "BV",
   "instance": 48,
   "name": "zn_co2_hi_1",
   "description": "ZN_CO2_HI",
   "units": "",
   "access": "R",
   "states": "0 = Normal 1 = High CO2 Level (Default: >1200 PPM)"
  },
  {
   "type": "BV",
   "instance": 15,
   "name": "rev_vlv_cmd_1",
   "description": "Rev Valve Output Cmd",
   "units": "",
   "access": "R",
   "states": "0 = Valve De- energized 1 = Valve Energized"
  },
  {
   "type": "AV",
   "instance": 8000,
   "name": "version_1",
   "description": "Software Version",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 21,
   "name": "occ_status_1",
   "description": "Occupancy Status",
   "units": "",
   "access": "R",
   "states": "0 = Unoccupied 1 = Occupied"
  },
  {
   "type": "AV",
   "instance": 13,
   "name": "clg_pct_1",
   "description": "Cooling Demand Percentage",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 12,
   "name": "htg_pct_1",
   "description": "Heating Demand Percentage",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 26,
   "name": "ztmp_hi_1",
   "description": "High ZS Zone Sensor Temperature Alarm",
   "units": "",
   "access": "R",
   "states": "0 = Normal 1 = High Zone Temperature (Default: 10 °F Above Setpoint)"
  },
  {
   "type": "BV",
   "instance": 28,
   "name": "zone_sen_1",
   "description": "ZS Zone Sensor Hardware Failure Alarm",
   "units": "",
   "access": "R",
   "states": "0 = Normal 1 = Sensor Failure (Check Sensor Hardware)"
  },
  {
   "type": "BV",
   "instance": 41,
   "name": "zrem_hi_1",
   "description": "High Remote Temperature Alarm",
   "units": "",
   "access": "R",
   "states": "0 = Normal 1 = High Zone Temperature (Default: 10 °F Above Setpoint)"
  },
  {
   "type": "BV",
   "instance": 43,
   "name": "zrem_sen_1",
   "description": "Remote Temperature Sensor Hardware Failure Alarm",
   "units": "",
   "access": "R",
   "states": "0 = Normal 1 = Sensor Failure (Check Sensor Hardware)"
  },
  {
   "type": "AV",
   "instance": 42,
   "name": "stpt_adj_lim_1",
   "description": "ZS Sensor Setpoint Adjustment Limit",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 6,
   "name": "eff_htg_stpt_1",
   "description": "Effective Heating Setpoint",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 4,
   "name": "occ_clg_stpt_1",
   "description": "Setpoint",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2,
   "name": "occ_htg_stpt_1",
   "description": "Setpoint",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1,
   "name": "unocc_clg_stpt_1",
   "description": "Setpoint",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3,
   "name": "unocc_htg_stpt_1",
   "description": "Setpoint",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 115,
   "name": "tlo_rem_1",
   "description": "Override Time Remaining",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 8,
   "name": "comp_mode_1",
   "description": "Compressor Control Mode",
   "units": "",
   "access": "W",
   "states": "0 = Zone (Default) 1 = Discharge Air Control 2 = Zone (BAS) 3 = Zone (Remote)"
  },
  {
   "type": "BV",
   "instance": 76,
   "name": "override_status_1",
   "description": "Override Status",
   "units": "",
   "access": "R",
   "states": "0 = Normal 1 = ZS Sensor in Override Mode"
  },
  {
   "type": "AV",
   "instance": 9,
   "name": "eff_remzone_temp_1",
   "description": "Effect Zone Remote Temperature",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 116,
   "name": "zt_reset_1",
   "description": "Effective ZS Sensor Temperature",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 29,
   "name": "bas_oat_1",
   "description": "BAS Outdoor Air Temp",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 55,
   "name": "eff_sa_fan_speed_1",
   "description": "Eff SA Fan Speed",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 7,
   "name": "bas_sen_val_1",
   "description": "BAS Temperature Sensor Value",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 18,
   "name": "in3_cfg_sel_1",
   "description": "Input 3 configuration selector",
   "units": "",
   "access": "W",
   "states": "0 = Not installed (Default) 1 = Leaving Water temperature sensor"
  },
  {
   "type": "AV",
   "instance": 19,
   "name": "in3_cfg_sta_1",
   "description": "Input 3 Configuration status",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 26,
   "name": "zone_rem_sen_val_1",
   "description": "Remote Temp or Return Air Temp Value",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 30,
   "name": "sat_hi_trip_1",
   "description": "Supply Air High Differential Trip",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 57,
   "name": "eff_zone_temp_1",
   "description": "Zone Temperature",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 58,
   "name": "zs_sen_combo_sel_1",
   "description": "ZS Sensor Combo Selector",
   "units": "",
   "access": "W",
   "states": "0 = Temp Only 1 = RH Only 2 = CO2 Only 3 = Temp + RH 4 = Temp + CO2 5 = RH + CO2 6 = Temp + RH + CO2 (Default) 7 = No ZS Sensor"
  },
  {
   "type": "AV",
   "instance": 61,
   "name": "zs_sensor_en_1",
   "description": "ZS Sensor Enable",
   "units": "",
   "access": "W",
   "states": "0 = No ZS sensors 1 = ZS sensors enabled (Default)"
  },
  {
   "type": "BV",
   "instance": 3,
   "name": "da_stpt_reset_1",
   "description": "DAT Sepoint reset",
   "units": "",
   "access": "W",
   "states": "0 = Disabled (Default) 1 = Enabled"
  },
  {
   "type": "BV",
   "instance": 17,
   "name": "lckout_resp_1",
   "description": "Fan Response for Comp Lockout",
   "units": "",
   "access": "W",
   "states": "0 = Do not lock fan upon compressor lockout (Default) 1 = Lock fan upon compressor lockout"
  },
  {
   "type": "AV",
   "instance": 2004,
   "name": "serial_number_1",
   "description": "Counter No Serial",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2003,
   "name": "counter_no_local_1",
   "description": "Counter Number local",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2005,
   "name": "bosch_pn1_1",
   "description": "Part Number",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2001,
   "name": "factory_pc_1",
   "description": "Plant Code",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 114,
   "name": "stages_1",
   "description": "Stages",
   "units": "",
   "access": "W",
   "states": "1 = 1 Compressor 1 Stage 2 = 2 Compressor 2 Stages 3 = 3 Compressor 3 Stages (3 and 4 Stage units only) 4 = 4 Compressor 4 Stages (4 Compressor units only) (Default) 5 = 1 Compressor 2 Stages"
  },
  {
   "type": "AV",
   "instance": 2002,
   "name": "mfg_date_1",
   "description": "Warranty",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 1,
   "name": "sa_temp_1",
   "description": "SAT 8",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 109,
   "name": "in1_cfg_sta_1",
   "description": "Input 1 Configuration Status",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 50,
   "name": "Fan_mode_1",
   "description": "Fan_mode",
   "units": "",
   "access": "W",
   "states": "1 = Standard Fan Configuration (default) 2 = Variable Frequency Drive Configuration"
  },
  {
   "type": "AV",
   "instance": 51,
   "name": "fan_mode_status_1",
   "description": "fan mode status",
   "units": "",
   "access": "R",
   "states": "0 = Start / Stop Fan Operation 1 = Variable Frequency Drive Fan Operation"
  }
 ],
 "page": "https://easybacnet.com/bacnet-points-lists/bosch/control-air-6120-water-to-air",
 "note": "Re-typed from the manufacturer's public documentation (see source). Point availability varies by firmware and options; verify against the live device."
}