Water-to-water heat pump controller · BACnet points list

Bosch Control Air 5600 - Water to Water (WWZ software) BACnet points list

Updated 28 October 2026

Short answer

The Control Air 5600 also runs a water-to-water program (WWZ) for Bosch water-to-water heat pumps. Over BACnet MS/TP it exposes occupancy, control mode and source, Fahrenheit and Celsius setpoint pairs, load/leaving water temperatures, compressor and pump states and UPM safety alarms.

This page lists 67 BACnet objects for the Bosch Control Air 5600 - Water to Water (WWZ software) — 30 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Bosch’s own free documentation, linked below.

Manufacturer
Bosch
Model
Control Air 5600 - Water to Water (WWZ software)
Equipment
Water-to-water heat pump controller
Equipment type
Heat pumps
BACnet objects
67 (30 writable)
Transport
BACnet MS/TP, BACnet ARC156
Firmware
WWZ.1.03
Also known as
Control Air 5600, WWZ 1.03, Bosch water to water heat pump BACnet, Bosch TT Water to Water
Source document
Bosch TT - Water to Water Network Integration Points List · WWZ.1.03
Download CSV 67 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Bosch Control Air 5600 - Water to Water (WWZ software)

Integration in brief

Leave Control Source at BAS Occupancy Command, command occupancy with occupancy_cmd_1, pick the control mode (heat, cool, auto changeover or digital input) and write the occupied setpoints. Watch current_alarm_1 and alrm_status_1 plus the load and leaving water temperatures.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 1occupancy_cmd_1BAS occupied command; 1 enables unit operationWrite
AV 16ctrl_source_1Occupancy source; 2 = BAS occupancy command (default)Write
AV 17ctrl_mode_1Off / heat / cool / auto changeover / digital inputWrite
AV 4occ_clg_stpt_1Occupied cooling setpointWrite
AV 2occ_htg_stpt_1Occupied heating setpointWrite
AV 18sys_mode_1Operating state: 1 neutral, 2 heating, 3 coolingRead
AV 10eff_load_tmp_f_1Load water temperatureRead
AV 9eff_lvg_wtr_tmp_1Leaving water temperatureRead
AV 19current_alarm_1Active alarm codeRead
BV 20alrm_status_1Alarm present flagRead

Enable & remote start

Set ctrl_source_1 (AV 16) to 2 = BAS Occupancy Command (default) and write occupancy_cmd_1 (BV 1). ctrl_mode_1 (AV 17) defaults to 4 = digital input (off = heat, on = cool), so set it to heat, cool or auto changeover for network control.

Network setup

Watch out for

Bosch Control Air 5600 - Water to Water (WWZ software) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

67 of 67 shown
Type
AnalogBinary
Access
Show
Bosch Control Air 5600 - Water to Water (WWZ software) BACnet Points List
DescriptionStates
AV15cmp_stgs_1Compressor StagesRead1 = 1 Compressor 1 Stage 2 = 2 Compressor 2 Stages 5 = 1 Compressor 2 Stages (Default)
AV13cmp1_state_1Comp1 StateRead1 = Lead 2 = Lag 3 = Fault
AV14cmp2_state_1Comp2 StateRead1 = Lead 2 = Lag 3 = Fault
AVmin17ctrl_mode_1Control ModeWrite0 = Off 1 = Heat 2 = Cool 3 = Auto Changeover 4 = Digital Input (Off = Heat/On = Cool) (Default)
AVmin16ctrl_source_1Control SourceWrite0 = Digital Input Enable (e.g. Room Occupancy Sensor) 1 = Keypad Schedule 2 = BAS Occupancy Command (Default) 3 = Factory Use Only 4 = Manual On-Continuous
AVmin19current_alarm_1Current AlarmRead0 = No Alarm, 1-9 = UPM Fault Code (See UPM alarms below) 20 = Output Overridden via Keypad 30 = Sensor Failure 40 = Leaving Water Temperature High/Low Alarm 70 = Pump Runtime/Compressors 1 & 2 Runtime 110 = Load Water Temperature High/Low Alarm
AV11eff_clg_stpt_1Effect Cooling SetpointRead
AV12eff_htg_stpt_1Effect Heating SetpointRead
AVmin10eff_load_tmp_f_1Effect Load TempRead
AVmin9eff_lvg_wtr_tmp_1Effect Leaving Wtr TempRead
AV8eff_xovr_tmp_1Effect Changeover TempRead
AVmin4occ_clg_stpt_1Occ Clg Setpoint in Fahrenheit°FWrite
AV504occ_clg_stpt_c_1Occ Clg Setpoint in CelsiusWrite
AVmin2occ_htg_stpt_1Occ Htg Setpoint in Fahrenheit°FWrite
AV502occ_htg_stpt_c_1Occ Htg Setpoint in CelsiusWrite
AV5stpt_diff_1Setpoint Differential in FahrenheitWrite
AV505stpt_diff_c_1Setpoint Differential in CelsiusWrite
AVmin18sys_mode_1System ModeRead1 = Neutral 2 = Heating 3 = Cooling
AV550temp_unit_mode_1Temp Unit SelectionWrite0 = Fahrenheit (Default) 1 = Celsius
AV3unocc_clg_stpt_1Unocc Clg Setpoint in Fahrenheit°FWrite
AV503unocc_clg_stpt_c_1Unocc Clg Setpoint in CelsiusWrite
AV1unocc_htg_stpt_1Unocc Htg Setpoint in Fahrenheit°FWrite
AV501unocc_htg_stpt_c_1Unocc Htg Setpoint in CelsiusWrite
AV7xovr_dbnd_1Changeover Deadband in Fahrenheit°FWrite
AV507xovr_dbnd_c_1Changeover Deadband in CelsiusWrite
AV6xovr_stpt_1Changeover Setpoint in Fahrenheit°FWrite
AV506xovr_stpt_c_1Changeover Setpoint in CelsiusWrite
BVmin20alrm_status_1Alarm Status (Alarm or Normal)Read0 = System Normal 1 = System in Alarm
BV5hp1_2st_1UPM Safety - High Pressure AlarmRead0 = Normal 1 = High Pressure Alarm (UPM-I code = 1; UPM-II codes = 1,3)
BV4lp1_2st_1UPM Safety - Low Pressure AlarmRead0 = Normal 1 = Low Pressure Alarm (UPM-I code = 2; UPM-II codes = 2,4)
BV8frz_2st_1UPM Safety - Condenser Coil Freeze AlarmRead0 = Normal 1 = Condenser Freeze Alarm (UPM-I code = 3; UPM-II codes = 5,9)
BV3con_2st_1UPM Safety - High Condensate AlarmRead0 = Normal 1 = Condensate Overflow Alarm (UPM-I code = 4; UPM-II code = 6)
BV2brn_2st_1UPM Safety - Brownout AlarmRead0 = Normal 1 = Brownout Alarm (UPM-I code = 5; UPM-II code = 7)
BV9cmp1_cmd_1Comp1 Output CmdRead0 = Compressor 1 Off 1 = Compressor 1 On
BV11cmp1_rntm_rst_1Compressor 1 Runtime ResetWrite0 = Reset Off (Default) 1 = Reset On
BV10cmp2_cmd_1Comp2 Output CmdRead0 = Compressor 2 Off 1 = Compressor 2 On
BV12cmp2_rntm_rst_1Compressor 2 Runtime ResetWrite0 = Reset Off (Default) 1 = Reset On
BV16cont_pump_1Continous Pump(s)Write0 = Cycle With Compressors (Default) 1 = Run Continuously when in OCC or NSB
BV32do_lock_1Digital Override Lock AlarmRead0 = Normal 1 = Digital Override Enabled Alarm
BV33dx1_rntm_1Compressor 1 Stage Runtime Expired AlarmRead0 = Normal 1 = Timer Has Expired (Default: >8760 Hours)
BV34dx2_rntm_1Compressor 2 Stage Runtime Expired AlarmRead0 = Normal 1 = Timer Has Expired (Default: >8760 Hours)
BV22input_lock_1Inputs Override StatusRead0 = Normal 1 = Software Lock Enabled
BV23load_hi_1High Load Temp AlarmRead0 = Normal 1 = High Load Temperature (Default: 10 °F / 6 °C Above Setpoint)
BV24load_lo_1Low Load Temp AlarmRead0 = Normal 1 = Low Load Temperature (Default: 10 °F / 6 °C Below Setpoint)
BV25load_sen_1Load Sensor Failure AlarmRead0 = Normal 1 = Sensor Failure (Check Load Sensor Hardware)
BV26lvg_hi_1High Leaving Water TemperatureRead0 = Normal 1 = Alarm (Default: >135 °F / 65 °C)
BV27lvg_lo_1Low Leaving Water TemperatureRead0 = Normal 1 = Alarm (Default: <35 °F / 1 °C)
BV28lvg_sen_1Leaving Water Temperature Sensor FailureRead0 = Normal 1 = Sensor Failure (Check Source Sensor Hardware)
BV19nsb_status_1NSB StatusRead0 = Night Setback disabled 1 = Night Setback enabled
BV18occ_status_1Occupancy StatusRead0 = Unoccupied 1 = Occupied
BVmin1occupancy_cmd_1Occupancy Command (BAS)Write0 = Unoccupied (Default) 1 = Occupied (Enables Unit Operation when BAS is selected for Control Source)
BV15pump_cmd_1Circulation Pump Output CommandRead0 = Pump Running 1 = Pump Off
BV29pump_rntm_1Pump RuntimeRead0 = Normal 1 = Timer Has Expired (Default: >8760 Hours)
BV17pump_rntm_rst_1Reset Pump RntmWrite0 = Inactive (Default) 1 = Active Reset
BV14rev_vlv_action_1Rev Valve ActionWrite0 = Energize valve when Heating 1 = Energize valve when Cooling (Default)
BV13rev_vlv_cmd_1Reversing Valve Output StatusRead0 = Reversing Valve De-energized 1 = Reversing Valve Energized
BV39upm_input_1UPM Input AlarmRead0 = UPM Connected 1 = UPM Connection Failure
BV7upm_rst_1UPM ResetWrite0 = Reset Off (Default) 1 = Reset On
BV31xovr_sen_1Changeover Temperature Sensor FailureRead0 = Normal 1 = Sensor Failure (Check Changeover Sensor Hardware)
BV40a2l_2st_1UPM Safety - A2L AlarmRead0 = Normal 1 = A2L Alarm (UPM-I code = 7; UPM-II code = 11)
BV42comm_2st_1UPM Safety - Second Stage Communication AlarmRead0 = Normal 1 = Communication Alarm (UPM-II code = 12)
BV91001do_one_1Test DO-1Write
BV91002do_two_1Test DO-2Write
BV91003do_three_1Test DO-3Write
BV91004do_four_1Test DO-4Write
BV91005do_five_1Test DO-5Write
BV91000fac_test_enable_1EOL Factory TestWrite

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Control Air 5600 - Water to Water (WWZ software) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Bosch Control Air 5600 - Water to Water (WWZ software)

How many BACnet points does the Bosch Control Air 5600 - Water to Water (WWZ software) have?

This list has 67 BACnet objects: 27 analog values, 40 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Bosch Control Air 5600 - Water to Water (WWZ software) BACnet points are writable?

30 of the 67 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Bosch Control Air 5600 - Water to Water (WWZ software) BACnet documentation?

The source is Bosch TT - Water to Water Network Integration Points List (WWZ.1.03), published free by Bosch at https://www.bosch-homecomfort.com/us/media/country_pool/service/technical_guides/ipl_wwz_1_03.pdf.

What are the minimum BACnet points to integrate the Bosch Control Air 5600 - Water to Water (WWZ software)?

Start with BV 1 occupancy_cmd_1 (BAS occupied command; 1 enables unit operation); AV 16 ctrl_source_1 (Occupancy source; 2 = BAS occupancy command (default)); AV 17 ctrl_mode_1 (Off / heat / cool / auto changeover / digital input); AV 4 occ_clg_stpt_1 (Occupied cooling setpoint); AV 2 occ_htg_stpt_1 (Occupied heating setpoint); AV 18 sys_mode_1 (Operating state: 1 neutral, 2 heating, 3 cooling); AV 10 eff_load_tmp_f_1 (Load water temperature); AV 9 eff_lvg_wtr_tmp_1 (Leaving water temperature); AV 19 current_alarm_1 (Active alarm code); BV 20 alrm_status_1 (Alarm present flag).

How do I enable BMS control of the Bosch Control Air 5600 - Water to Water (WWZ software)?

Set ctrl_source_1 (AV 16) to 2 = BAS Occupancy Command (default) and write occupancy_cmd_1 (BV 1). ctrl_mode_1 (AV 17) defaults to 4 = digital input (off = heat, on = cool), so set it to heat, cool or auto changeover for network control.

How do I check these points on the real Control Air 5600 - Water to Water (WWZ software)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Bosch BACnet points lists

Source: Bosch TT - Water to Water Network Integration Points List · WWZ.1.03. Object names, instances and units are reproduced as published; descriptions are our own.