Condensing boiler gateway · BACnet points list

Bosch Buderus SSB800 / SSB1000 / SSB1000TL boiler (ProtoNode FPC-N38) BACnet points list

Updated 28 October 2026

Short answer

The SSB boilers reach a BMS through a ProtoNode FPC-N38, which reads the D_Platform boiler control over a serial Modbus RTU link and serves BACnet MS/TP or BACnet IP (Metasys N2 and Modbus TCP also selectable). The list has 147 objects: cascade/system values, per-boiler and per-burner status, temperatures, power level, flow, fan speed, burn hours and error data for up to four boilers. Only the reset-curve, warm weather shutdown, night setback, cascade setpoint and boiler address objects are writable.

This page lists 147 BACnet objects for the Bosch Buderus SSB800 / SSB1000 / SSB1000TL boiler (ProtoNode FPC-N38) — 10 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Bosch’s own free documentation, linked below.

Manufacturer
Bosch
Model
Buderus SSB800 / SSB1000 / SSB1000TL boiler (ProtoNode FPC-N38)
Equipment
Condensing boiler gateway
Equipment type
Boilers & water heaters
BACnet objects
147 (10 writable)
Transport
BACnet MS/TP, BACnet IP
Firmware
Not stated
Default device instance
50000 + boiler station address (station address 1 gives 50001)
Also known as
SSB800, SSB1000, SSB1000TL, Buderus SSB, Bosch SSB, ProtoNode FPC-N38, D_Platform
Source document
ProtoNode FPC-N38 and ProtoNode FPC-N39 Start-up Guide for Interfacing Bosch Products: Bosch Buderus SSB800, SSB1000, SSB1000TL (Appendix B.1 D_Platform Modbus RTU Mappings to BACnet, Metasys N2 and LonWorks) · Document Revision 4.B (Web Configurator Template Revision 70) · rev. 2018-03
Download CSV 147 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Bosch Buderus SSB800 / SSB1000 / SSB1000TL boiler (ProtoNode FPC-N38)

Integration in brief

Set the boiler station address to 1, pick BACnet MS/TP or BACnet IP on the ProtoNode S DIP switches, set the MS/TP MAC and baud rate, then select the boiler profile in the ProtoNode web configurator. The list is mostly monitoring: system supply setpoint and temperature, outdoor temperature, power level, per-boiler active/error/service flags and the error number. The writable objects are the cascade setpoint and heating-curve settings; the guide describes no enable or start/stop command.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AV 10Cascade Ch Mode X SPCascade central-heating mode setpointWrite
AI 11System Supply SPActive system supply setpointRead
AI 12System Supply Sensor TempSystem supply water temperatureRead
AI 13Outdoor Sensor TempOutdoor air temperatureRead
AI 9Power Level For Entire SystemSystem power level, %Read
BI 19Boiler 1 Is Active / HeatingBoiler 1 firingRead
BI 23Boiler 1 Has ErrorBoiler 1 in errorRead
AI 136Error NumberActive error codeRead

Network setup

Watch out for

Bosch Buderus SSB800 / SSB1000 / SSB1000TL boiler (ProtoNode FPC-N38) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

147 of 147 shown
Type
Binary
Access
Show
Bosch Buderus SSB800 / SSB1000 / SSB1000TL boiler (ProtoNode FPC-N38) BACnet Points List
DescriptionStates
AImin9Power Level For Entire SystemRead
AImin11System Supply SPRead
AImin12System Supply Sensor TempRead
AImin13Outdoor Sensor TempRead
AI32Power Level For The BoilerRead
AI33Boiler Supply SPRead
AI34Heat Demand TypeRead
AI35System Sensor TempRead
AI36Dhw TempRead
AI39Total Burn HoursRead
AI48Blr 1 - Burner 1 Current StateRead
AI49Blr 1 - Burner 1 ErrorRead
AI50Blr 1 - Burner 1 Supply SPRead
AI51Blr 1 - Burner 1 Power LevelRead
AI53Blr 1 - Burner 1 CH Flow RateRead
AI54Blr 1 - Burner 1 Actual Fan SpeedRead
AI55Blr 1 - Burner 1 Supply Sensor TempRead
AI56Blr 1 - Burner 1 Return Sensor TempRead
AI57Blr 1 - Burner 1 Flue Sensor TempRead
AI58Blr 1 - Burner 1 Total Burn HoursRead
AI59Blr 1 - Burner 2 Current StateRead
AI60Blr 1 - Burner 2 ErrorRead
AI61Blr 1 - Burner 2 Supply SPRead
AI62Blr 1 - Burner 2 Power LevelRead
AI64Blr 1 - Burner 2 CH Flow RateRead
AI65Blr 1 - Burner 2 Actual Fan SpeedRead
AI66Blr 1 - Burner 2 Supply Sensor TempRead
AI67Blr 1 - Burner 2 Return Sensor TempRead
AI68Blr 1 - Burner 2 Flue Sensor TempRead
AI69Blr 1 - Burner 2 Total Burn HoursRead
AI70Blr 2 - Burner 1 Current StateRead
AI71Blr 2 - Burner 1 ErrorRead
AI72Blr 2 - Burner 1 Supply SPRead
AI73Blr 2 - Burner 1 Power LevelRead
AI75Blr 2 - Burner 1 CH Flow RateRead
AI76Blr 2 - Burner 1 Actual Fan SpeedRead
AI77Blr 2 - Burner 1 Supply Sensor TempRead
AI78Blr 2 - Burner 1 Return Sensor TempRead
AI79Blr 2 - Burner 1 Flue Sensor TempRead
AI80Blr 2 - Burner 1 Total Burn HoursRead
AI81Blr 2 - Burner 2 Current StateRead
AI82Blr 2 - Burner 2 ErrorRead
AI83Blr 2 - Burner 2 Supply SPRead
AI84Blr 2 - Burner 2 Power LevelRead
AI86Blr 2 - Burner 2 CH Flow RateRead
AI87Blr 2 - Burner 2 Actual Fan SpeedRead
AI88Blr 2 - Burner 2 Supply Sensor TempRead
AI89Blr 2 - Burner 2 Return Sensor TempRead
AI90Blr 2 - Burner 2 Flue Sensor TempRead
AI91Blr 2 - Burner 2 Total Burn HoursRead
AI92Blr 3 - Burner 1 Current StateRead
AI93Blr 3 - Burner 1 ErrorRead
AI94Blr 3 - Burner 1 Supply SPRead
AI95Blr 3 - Burner 1 Power LevelRead
AI97Blr 3 - Burner 1 CH Flow RateRead
AI98Blr 3 - Burner 1 Actual Fan SpeedRead
AI99Blr 3 - Burner 1 Supply Sensor TempRead
AI100Blr 3 - Burner 1 Return Sensor TempRead
AI101Blr 3 - Burner 1 Flue Sensor TempRead
AI102Blr 3 - Burner 1 Total Burn HoursRead
AI103Blr 3 - Burner 2 Current StateRead
AI104Blr 3 - Burner 2 ErrorRead
AI105Blr 3 - Burner 2 Supply SPRead
AI106Blr 3 - Burner 2 Power LevelRead
AI108Blr 3 - Burner 2 CH Flow RateRead
AI109Blr 3 - Burner 2 Actual Fan SpeedRead
AI110Blr 3 - Burner 2 Supply Sensor TempRead
AI111Blr 3 - Burner 2 Return Sensor TempRead
AI112Blr 3 - Burner 2 Flue Sensor TempRead
AI113Blr 3 - Burner 2 Total Burn HoursRead
AI114Blr 4 - Burner 1 Current StateRead
AI115Blr 4 - Burner 1 ErrorRead
AI116Blr 4 - Burner 1 Supply SPRead
AI117Blr 4 - Burner 1 Power LevelRead
AI119Blr 4 - Burner 1 CH Flow RateRead
AI120Blr 4 - Burner 1 Actual Fan SpeedRead
AI121Blr 4 - Burner 1 Supply Sensor TempRead
AI122Blr 4 - Burner 1 Return Sensor TempRead
AI123Blr 4 - Burner 1 Flue Sensor TempRead
AI124Blr 4 - Burner 1 Total Burn HoursRead
AI125Blr 4 - Burner 2 Current StateRead
AI126Blr 4 - Burner 2 ErrorRead
AI127Blr 4 - Burner 2 Supply SPRead
AI128Blr 4 - Burner 2 Power LevelRead
AI130Blr 4 - Burner 2 CH Flow RateRead
AI131Blr 4 - Burner 2 Actual Fan SpeedRead
AI132Blr 4 - Burner 2 Supply Sensor TempRead
AI133Blr 4 - Burner 2 Return Sensor TempRead
AI134Blr 4 - Burner 2 Flue Sensor TempRead
AI135Blr 4 - Burner 2 Total Burn HoursRead
AImin136Error NumberRead
AI137Boiler IDRead
AI138Timestamp: Day Of WeekRead
AI139Timestamp: Day Of MonthRead
AI140Timestamp: MonthRead
AI141Timestamp: YearRead
AI142Timestamp: HourRead
AI143Timestamp: MinuteRead
AI144Burn Hours Since Last ServiceRead
AI145Burn Hours Till Service Is RequiredRead
AI146Overdue Counter 0Read
AI147Service IntervalRead
AV1Reset Curve Boiler DesignWrite
AV2Reset Curve Boiler Mild WeatherWrite
AV3Reset Curve Outdoor Mild WeatherWrite
AV4Reset Curve Outdoor DesignWrite
AV5Warm Weather ShutdownWrite
AV6Reset Curve Boiler MaximumWrite
AV7Reset Curve Boiler MinimumWrite
AV8Night SetbackWrite
AVmin10Cascade Ch Mode X SPWrite
AV31Boiler AddressWrite
BI14Cascade Pump StatusRead
BI15Boiler 1 Available / PresentRead
BI16Boiler 2 Available / PresentRead
BI17Boiler 3 Available / PresentRead
BI18Boiler 4 Available / PresentRead
BImin19Boiler 1 Is Active / HeatingRead
BI20Boiler 2 Is Active / HeatingRead
BI21Boiler 3 Is Active / HeatingRead
BI22Boiler 4 Is Active / HeatingRead
BImin23Boiler 1 Has ErrorRead
BI24Boiler 2 Has ErrorRead
BI25Boiler 3 Has ErrorRead
BI26Boiler 4 Has ErrorRead
BI27Boiler 1 Requires ServiceRead
BI28Boiler 2 Requires ServiceRead
BI29Boiler 3 Requires ServiceRead
BI30Boiler 4 Requires ServiceRead
BI37Ch Pump RunningRead
BI38Dhw Pump StatusRead
BI40Blr 1 - Burner 1 Available/PresentRead
BI41Blr 1 - Burner 2 Available/PresentRead
BI42Blr 2 - Burner 1 Available/PresentRead
BI43Blr 2 - Burner 2 Available/PresentRead
BI44Blr 3 - Burner 1 Available/PresentRead
BI45Blr 3 - Burner 2 Available/PresentRead
BI46Blr 4 - Burner 1 Available/PresentRead
BI47Blr 4 - Burner 2 Available/PresentRead
BI52Blr 1 - Burner 1 Gen Pump StatusRead
BI63Blr 1 - Burner 2 Gen Pump StatusRead
BI74Blr 2 - Burner 1 Gen Pump StatusRead
BI85Blr 2 - Burner 2 Gen Pump StatusRead
BI96Blr 3 - Burner 1 Gen Pump StatusRead
BI107Blr 3 - Burner 2 Gen Pump StatusRead
BI118Blr 4 - Burner 1 Gen Pump StatusRead
BI129Blr 4 - Burner 2 Gen Pump StatusRead

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Buderus SSB800 / SSB1000 / SSB1000TL boiler (ProtoNode FPC-N38) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Bosch Buderus SSB800 / SSB1000 / SSB1000TL boiler (ProtoNode FPC-N38)

How many BACnet points does the Bosch Buderus SSB800 / SSB1000 / SSB1000TL boiler (ProtoNode FPC-N38) have?

This list has 147 BACnet objects: 102 analog inputs, 10 analog values, 35 binary inputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Bosch Buderus SSB800 / SSB1000 / SSB1000TL boiler (ProtoNode FPC-N38) BACnet points are writable?

10 of the 147 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Bosch Buderus SSB800 / SSB1000 / SSB1000TL boiler (ProtoNode FPC-N38) BACnet documentation?

The source is ProtoNode FPC-N38 and ProtoNode FPC-N39 Start-up Guide for Interfacing Bosch Products: Bosch Buderus SSB800, SSB1000, SSB1000TL (Appendix B.1 D_Platform Modbus RTU Mappings to BACnet, Metasys N2 and LonWorks) (Document Revision 4.B (Web Configurator Template Revision 70)), revision 2018-03, published free by Bosch at https://www.bosch-homecomfort.com/us/media/country_pool/service/technical_guides/ssb800-1000-1000tl_bacnet_and_lonworks_start-up_guide_03.2018_us_1.pdf.

What are the minimum BACnet points to integrate the Bosch Buderus SSB800 / SSB1000 / SSB1000TL boiler (ProtoNode FPC-N38)?

Start with AV 10 Cascade Ch Mode X SP (Cascade central-heating mode setpoint); AI 11 System Supply SP (Active system supply setpoint); AI 12 System Supply Sensor Temp (System supply water temperature); AI 13 Outdoor Sensor Temp (Outdoor air temperature); AI 9 Power Level For Entire System (System power level, %); BI 19 Boiler 1 Is Active / Heating (Boiler 1 firing); BI 23 Boiler 1 Has Error (Boiler 1 in error); AI 136 Error Number (Active error code).

How do I check these points on the real Buderus SSB800 / SSB1000 / SSB1000TL boiler (ProtoNode FPC-N38)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Bosch BACnet points lists

Source: ProtoNode FPC-N38 and ProtoNode FPC-N39 Start-up Guide for Interfacing Bosch Products: Bosch Buderus SSB800, SSB1000, SSB1000TL (Appendix B.1 D_Platform Modbus RTU Mappings to BACnet, Metasys N2 and LonWorks) · Document Revision 4.B (Web Configurator Template Revision 70) · rev. 2018-03. Object names, instances and units are reproduced as published; descriptions are our own.