Condensing boiler gateway · BACnet points list
Bosch Buderus SSB800 / SSB1000 / SSB1000TL boiler (ProtoNode FPC-N38) BACnet points list
Updated 28 October 2026
The SSB boilers reach a BMS through a ProtoNode FPC-N38, which reads the D_Platform boiler control over a serial Modbus RTU link and serves BACnet MS/TP or BACnet IP (Metasys N2 and Modbus TCP also selectable). The list has 147 objects: cascade/system values, per-boiler and per-burner status, temperatures, power level, flow, fan speed, burn hours and error data for up to four boilers. Only the reset-curve, warm weather shutdown, night setback, cascade setpoint and boiler address objects are writable.
This page lists 147 BACnet objects for the Bosch Buderus SSB800 / SSB1000 / SSB1000TL boiler (ProtoNode FPC-N38) — 10 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Bosch’s own free documentation, linked below.
- Manufacturer
- Bosch
- Model
- Buderus SSB800 / SSB1000 / SSB1000TL boiler (ProtoNode FPC-N38)
- Equipment
- Condensing boiler gateway
- Equipment type
- Boilers & water heaters
- BACnet objects
- 147 (10 writable)
- Transport
- BACnet MS/TP, BACnet IP
- Firmware
- Not stated
- Default device instance
- 50000 + boiler station address (station address 1 gives 50001)
- Also known as
- SSB800, SSB1000, SSB1000TL, Buderus SSB, Bosch SSB, ProtoNode FPC-N38, D_Platform
BMS integration notes: Bosch Buderus SSB800 / SSB1000 / SSB1000TL boiler (ProtoNode FPC-N38)
Set the boiler station address to 1, pick BACnet MS/TP or BACnet IP on the ProtoNode S DIP switches, set the MS/TP MAC and baud rate, then select the boiler profile in the ProtoNode web configurator. The list is mostly monitoring: system supply setpoint and temperature, outdoor temperature, power level, per-boiler active/error/service flags and the error number. The writable objects are the cascade setpoint and heating-curve settings; the guide describes no enable or start/stop command.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AV 10 | Cascade Ch Mode X SP | Cascade central-heating mode setpoint | Write |
| AI 11 | System Supply SP | Active system supply setpoint | Read |
| AI 12 | System Supply Sensor Temp | System supply water temperature | Read |
| AI 13 | Outdoor Sensor Temp | Outdoor air temperature | Read |
| AI 9 | Power Level For Entire System | System power level, % | Read |
| BI 19 | Boiler 1 Is Active / Heating | Boiler 1 firing | Read |
| BI 23 | Boiler 1 Has Error | Boiler 1 in error | Read |
| AI 136 | Error Number | Active error code | Read |
Network setup
- Boiler side: Modbus RTU at 9600 baud; set the station address of the device attached to the ProtoNode to 1.
- S bank DIP switches S0-S3 select BACnet IP, BACnet MS/TP, Metasys N2, Modbus TCP or single-node BACnet MS/TP (power off when changing them).
- BACnet MS/TP: MAC address 1-127 on the A bank DIP switches; baud rate on B0-B3 (9600-76800, factory default 38400).
- Device instance = station address + Node_Offset (default 50,000); Node_Offset can be changed in the web configurator.
- The ProtoNode web configurator defaults to 192.168.1.24 / 255.255.255.0; change the IP address there for BACnet IP.
Watch out for
- Point count follows the selected profile (1-4 boilers); objects for missing boilers or burners will not be present.
- Most writable objects are boiler heating-curve settings (reset curve, warm weather shutdown, night setback), not run commands.
Bosch Buderus SSB800 / SSB1000 / SSB1000TL boiler (ProtoNode FPC-N38) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AImin | 9 | Power Level For Entire System | Read | |||
| AImin | 11 | System Supply SP | Read | |||
| AImin | 12 | System Supply Sensor Temp | Read | |||
| AImin | 13 | Outdoor Sensor Temp | Read | |||
| AI | 32 | Power Level For The Boiler | Read | |||
| AI | 33 | Boiler Supply SP | Read | |||
| AI | 34 | Heat Demand Type | Read | |||
| AI | 35 | System Sensor Temp | Read | |||
| AI | 36 | Dhw Temp | Read | |||
| AI | 39 | Total Burn Hours | Read | |||
| AI | 48 | Blr 1 - Burner 1 Current State | Read | |||
| AI | 49 | Blr 1 - Burner 1 Error | Read | |||
| AI | 50 | Blr 1 - Burner 1 Supply SP | Read | |||
| AI | 51 | Blr 1 - Burner 1 Power Level | Read | |||
| AI | 53 | Blr 1 - Burner 1 CH Flow Rate | Read | |||
| AI | 54 | Blr 1 - Burner 1 Actual Fan Speed | Read | |||
| AI | 55 | Blr 1 - Burner 1 Supply Sensor Temp | Read | |||
| AI | 56 | Blr 1 - Burner 1 Return Sensor Temp | Read | |||
| AI | 57 | Blr 1 - Burner 1 Flue Sensor Temp | Read | |||
| AI | 58 | Blr 1 - Burner 1 Total Burn Hours | Read | |||
| AI | 59 | Blr 1 - Burner 2 Current State | Read | |||
| AI | 60 | Blr 1 - Burner 2 Error | Read | |||
| AI | 61 | Blr 1 - Burner 2 Supply SP | Read | |||
| AI | 62 | Blr 1 - Burner 2 Power Level | Read | |||
| AI | 64 | Blr 1 - Burner 2 CH Flow Rate | Read | |||
| AI | 65 | Blr 1 - Burner 2 Actual Fan Speed | Read | |||
| AI | 66 | Blr 1 - Burner 2 Supply Sensor Temp | Read | |||
| AI | 67 | Blr 1 - Burner 2 Return Sensor Temp | Read | |||
| AI | 68 | Blr 1 - Burner 2 Flue Sensor Temp | Read | |||
| AI | 69 | Blr 1 - Burner 2 Total Burn Hours | Read | |||
| AI | 70 | Blr 2 - Burner 1 Current State | Read | |||
| AI | 71 | Blr 2 - Burner 1 Error | Read | |||
| AI | 72 | Blr 2 - Burner 1 Supply SP | Read | |||
| AI | 73 | Blr 2 - Burner 1 Power Level | Read | |||
| AI | 75 | Blr 2 - Burner 1 CH Flow Rate | Read | |||
| AI | 76 | Blr 2 - Burner 1 Actual Fan Speed | Read | |||
| AI | 77 | Blr 2 - Burner 1 Supply Sensor Temp | Read | |||
| AI | 78 | Blr 2 - Burner 1 Return Sensor Temp | Read | |||
| AI | 79 | Blr 2 - Burner 1 Flue Sensor Temp | Read | |||
| AI | 80 | Blr 2 - Burner 1 Total Burn Hours | Read | |||
| AI | 81 | Blr 2 - Burner 2 Current State | Read | |||
| AI | 82 | Blr 2 - Burner 2 Error | Read | |||
| AI | 83 | Blr 2 - Burner 2 Supply SP | Read | |||
| AI | 84 | Blr 2 - Burner 2 Power Level | Read | |||
| AI | 86 | Blr 2 - Burner 2 CH Flow Rate | Read | |||
| AI | 87 | Blr 2 - Burner 2 Actual Fan Speed | Read | |||
| AI | 88 | Blr 2 - Burner 2 Supply Sensor Temp | Read | |||
| AI | 89 | Blr 2 - Burner 2 Return Sensor Temp | Read | |||
| AI | 90 | Blr 2 - Burner 2 Flue Sensor Temp | Read | |||
| AI | 91 | Blr 2 - Burner 2 Total Burn Hours | Read | |||
| AI | 92 | Blr 3 - Burner 1 Current State | Read | |||
| AI | 93 | Blr 3 - Burner 1 Error | Read | |||
| AI | 94 | Blr 3 - Burner 1 Supply SP | Read | |||
| AI | 95 | Blr 3 - Burner 1 Power Level | Read | |||
| AI | 97 | Blr 3 - Burner 1 CH Flow Rate | Read | |||
| AI | 98 | Blr 3 - Burner 1 Actual Fan Speed | Read | |||
| AI | 99 | Blr 3 - Burner 1 Supply Sensor Temp | Read | |||
| AI | 100 | Blr 3 - Burner 1 Return Sensor Temp | Read | |||
| AI | 101 | Blr 3 - Burner 1 Flue Sensor Temp | Read | |||
| AI | 102 | Blr 3 - Burner 1 Total Burn Hours | Read | |||
| AI | 103 | Blr 3 - Burner 2 Current State | Read | |||
| AI | 104 | Blr 3 - Burner 2 Error | Read | |||
| AI | 105 | Blr 3 - Burner 2 Supply SP | Read | |||
| AI | 106 | Blr 3 - Burner 2 Power Level | Read | |||
| AI | 108 | Blr 3 - Burner 2 CH Flow Rate | Read | |||
| AI | 109 | Blr 3 - Burner 2 Actual Fan Speed | Read | |||
| AI | 110 | Blr 3 - Burner 2 Supply Sensor Temp | Read | |||
| AI | 111 | Blr 3 - Burner 2 Return Sensor Temp | Read | |||
| AI | 112 | Blr 3 - Burner 2 Flue Sensor Temp | Read | |||
| AI | 113 | Blr 3 - Burner 2 Total Burn Hours | Read | |||
| AI | 114 | Blr 4 - Burner 1 Current State | Read | |||
| AI | 115 | Blr 4 - Burner 1 Error | Read | |||
| AI | 116 | Blr 4 - Burner 1 Supply SP | Read | |||
| AI | 117 | Blr 4 - Burner 1 Power Level | Read | |||
| AI | 119 | Blr 4 - Burner 1 CH Flow Rate | Read | |||
| AI | 120 | Blr 4 - Burner 1 Actual Fan Speed | Read | |||
| AI | 121 | Blr 4 - Burner 1 Supply Sensor Temp | Read | |||
| AI | 122 | Blr 4 - Burner 1 Return Sensor Temp | Read | |||
| AI | 123 | Blr 4 - Burner 1 Flue Sensor Temp | Read | |||
| AI | 124 | Blr 4 - Burner 1 Total Burn Hours | Read | |||
| AI | 125 | Blr 4 - Burner 2 Current State | Read | |||
| AI | 126 | Blr 4 - Burner 2 Error | Read | |||
| AI | 127 | Blr 4 - Burner 2 Supply SP | Read | |||
| AI | 128 | Blr 4 - Burner 2 Power Level | Read | |||
| AI | 130 | Blr 4 - Burner 2 CH Flow Rate | Read | |||
| AI | 131 | Blr 4 - Burner 2 Actual Fan Speed | Read | |||
| AI | 132 | Blr 4 - Burner 2 Supply Sensor Temp | Read | |||
| AI | 133 | Blr 4 - Burner 2 Return Sensor Temp | Read | |||
| AI | 134 | Blr 4 - Burner 2 Flue Sensor Temp | Read | |||
| AI | 135 | Blr 4 - Burner 2 Total Burn Hours | Read | |||
| AImin | 136 | Error Number | Read | |||
| AI | 137 | Boiler ID | Read | |||
| AI | 138 | Timestamp: Day Of Week | Read | |||
| AI | 139 | Timestamp: Day Of Month | Read | |||
| AI | 140 | Timestamp: Month | Read | |||
| AI | 141 | Timestamp: Year | Read | |||
| AI | 142 | Timestamp: Hour | Read | |||
| AI | 143 | Timestamp: Minute | Read | |||
| AI | 144 | Burn Hours Since Last Service | Read | |||
| AI | 145 | Burn Hours Till Service Is Required | Read | |||
| AI | 146 | Overdue Counter 0 | Read | |||
| AI | 147 | Service Interval | Read | |||
| AV | 1 | Reset Curve Boiler Design | Write | |||
| AV | 2 | Reset Curve Boiler Mild Weather | Write | |||
| AV | 3 | Reset Curve Outdoor Mild Weather | Write | |||
| AV | 4 | Reset Curve Outdoor Design | Write | |||
| AV | 5 | Warm Weather Shutdown | Write | |||
| AV | 6 | Reset Curve Boiler Maximum | Write | |||
| AV | 7 | Reset Curve Boiler Minimum | Write | |||
| AV | 8 | Night Setback | Write | |||
| AVmin | 10 | Cascade Ch Mode X SP | Write | |||
| AV | 31 | Boiler Address | Write | |||
| BI | 14 | Cascade Pump Status | Read | |||
| BI | 15 | Boiler 1 Available / Present | Read | |||
| BI | 16 | Boiler 2 Available / Present | Read | |||
| BI | 17 | Boiler 3 Available / Present | Read | |||
| BI | 18 | Boiler 4 Available / Present | Read | |||
| BImin | 19 | Boiler 1 Is Active / Heating | Read | |||
| BI | 20 | Boiler 2 Is Active / Heating | Read | |||
| BI | 21 | Boiler 3 Is Active / Heating | Read | |||
| BI | 22 | Boiler 4 Is Active / Heating | Read | |||
| BImin | 23 | Boiler 1 Has Error | Read | |||
| BI | 24 | Boiler 2 Has Error | Read | |||
| BI | 25 | Boiler 3 Has Error | Read | |||
| BI | 26 | Boiler 4 Has Error | Read | |||
| BI | 27 | Boiler 1 Requires Service | Read | |||
| BI | 28 | Boiler 2 Requires Service | Read | |||
| BI | 29 | Boiler 3 Requires Service | Read | |||
| BI | 30 | Boiler 4 Requires Service | Read | |||
| BI | 37 | Ch Pump Running | Read | |||
| BI | 38 | Dhw Pump Status | Read | |||
| BI | 40 | Blr 1 - Burner 1 Available/Present | Read | |||
| BI | 41 | Blr 1 - Burner 2 Available/Present | Read | |||
| BI | 42 | Blr 2 - Burner 1 Available/Present | Read | |||
| BI | 43 | Blr 2 - Burner 2 Available/Present | Read | |||
| BI | 44 | Blr 3 - Burner 1 Available/Present | Read | |||
| BI | 45 | Blr 3 - Burner 2 Available/Present | Read | |||
| BI | 46 | Blr 4 - Burner 1 Available/Present | Read | |||
| BI | 47 | Blr 4 - Burner 2 Available/Present | Read | |||
| BI | 52 | Blr 1 - Burner 1 Gen Pump Status | Read | |||
| BI | 63 | Blr 1 - Burner 2 Gen Pump Status | Read | |||
| BI | 74 | Blr 2 - Burner 1 Gen Pump Status | Read | |||
| BI | 85 | Blr 2 - Burner 2 Gen Pump Status | Read | |||
| BI | 96 | Blr 3 - Burner 1 Gen Pump Status | Read | |||
| BI | 107 | Blr 3 - Burner 2 Gen Pump Status | Read | |||
| BI | 118 | Blr 4 - Burner 1 Gen Pump Status | Read | |||
| BI | 129 | Blr 4 - Burner 2 Gen Pump Status | Read |
No points match these filters.
Integration notes
- The table has no read/write column. Objects whose LonWorks variable is an input/output pair (nvi/nvo) and that map to N2 AO are marked writable; the rest are read-only.
- The gateway profile depends on how many boilers the managing D_Platform runs: 63 points for one boiler, 91 for two, 119 for three and 147 for four. This file lists the full four-boiler table.
- Blr 1-4 / Burner 1-2 objects only exist for boilers and burners that are present.
- The table gives no engineering units; the LonWorks types (temperature, percent, hours, count) hint at the value type.
- The same table also maps Metasys N2 and LonWorks (FPC-N39); only the BACnet side is listed here.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Buderus SSB800 / SSB1000 / SSB1000TL boiler (ProtoNode FPC-N38) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Bosch Buderus SSB800 / SSB1000 / SSB1000TL boiler (ProtoNode FPC-N38)
How many BACnet points does the Bosch Buderus SSB800 / SSB1000 / SSB1000TL boiler (ProtoNode FPC-N38) have?
This list has 147 BACnet objects: 102 analog inputs, 10 analog values, 35 binary inputs. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Bosch Buderus SSB800 / SSB1000 / SSB1000TL boiler (ProtoNode FPC-N38) BACnet points are writable?
10 of the 147 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.
Where is the official Bosch Buderus SSB800 / SSB1000 / SSB1000TL boiler (ProtoNode FPC-N38) BACnet documentation?
The source is ProtoNode FPC-N38 and ProtoNode FPC-N39 Start-up Guide for Interfacing Bosch Products: Bosch Buderus SSB800, SSB1000, SSB1000TL (Appendix B.1 D_Platform Modbus RTU Mappings to BACnet, Metasys N2 and LonWorks) (Document Revision 4.B (Web Configurator Template Revision 70)), revision 2018-03, published free by Bosch at https://www.bosch-homecomfort.com/us/media/country_pool/service/technical_guides/ssb800-1000-1000tl_bacnet_and_lonworks_start-up_guide_03.2018_us_1.pdf.
What are the minimum BACnet points to integrate the Bosch Buderus SSB800 / SSB1000 / SSB1000TL boiler (ProtoNode FPC-N38)?
Start with AV 10 Cascade Ch Mode X SP (Cascade central-heating mode setpoint); AI 11 System Supply SP (Active system supply setpoint); AI 12 System Supply Sensor Temp (System supply water temperature); AI 13 Outdoor Sensor Temp (Outdoor air temperature); AI 9 Power Level For Entire System (System power level, %); BI 19 Boiler 1 Is Active / Heating (Boiler 1 firing); BI 23 Boiler 1 Has Error (Boiler 1 in error); AI 136 Error Number (Active error code).
How do I check these points on the real Buderus SSB800 / SSB1000 / SSB1000TL boiler (ProtoNode FPC-N38)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Bosch BACnet points lists
- Water-source heat pump controller
Bosch Control Air 5600 - Water to Air (WAZ software)
Bosch water-to-air (water source) heat pumps fitted with the Control Air 5600 DDC controller running WAZ zone software.
Also known as: Control Air 5600, WAZ 1.03, Bosch WSHP DDC, Bosch water source heat pump BACnet, Bosch TT Water to Air - Water-to-water heat pump controller
Bosch Control Air 5600 - Water to Water (WWZ software)
Bosch water-to-water heat pumps fitted with the Control Air 5600 DDC controller running WWZ software.
Also known as: Control Air 5600, WWZ 1.03, Bosch water to water heat pump BACnet, Bosch TT Water to Water - Commercial water-source heat pump controller
Bosch Control Air 6120 - Water to Air (WAF software)
Bosch commercial water-to-air heat pumps (up to 4 compressor stages) with the Control Air 6120 DDC controller and WAF software.
Also known as: Control Air 6120, WAF 1.01, Bosch commercial WSHP DDC, Bosch TT Water to Air
Source: ProtoNode FPC-N38 and ProtoNode FPC-N39 Start-up Guide for Interfacing Bosch Products: Bosch Buderus SSB800, SSB1000, SSB1000TL (Appendix B.1 D_Platform Modbus RTU Mappings to BACnet, Metasys N2 and LonWorks) · Document Revision 4.B (Web Configurator Template Revision 70) · rev. 2018-03. Object names, instances and units are reproduced as published; descriptions are our own.