Water-source heat pump controller · BACnet points list

Bosch Control Air 5600 - Water to Air (WAZ software) BACnet points list

Updated 28 October 2026

Short answer

The Control Air 5600 is Bosch's factory-mounted DDC controller for water-source heat pumps. It speaks BACnet MS/TP (or BACnet over ARC156, Modbus, N2 and Lon) and exposes occupancy, mode, setpoint, sensor, configuration and alarm points as AV/BV/MSV objects. The same point list also documents Modbus registers and N2/LON equivalents.

This page lists 174 BACnet objects for the Bosch Control Air 5600 - Water to Air (WAZ software) — 73 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Bosch’s own free documentation, linked below.

Manufacturer
Bosch
Model
Control Air 5600 - Water to Air (WAZ software)
Equipment
Water-source heat pump controller
Equipment type
Heat pumps
BACnet objects
174 (73 writable)
Transport
BACnet MS/TP, BACnet ARC156
Firmware
WAZ.1.03
Also known as
Control Air 5600, WAZ 1.03, Bosch WSHP DDC, Bosch water source heat pump BACnet, Bosch TT Water to Air
Source document
Bosch TT - Water to Air Network Integration Points List · WAZ.1.03
Download CSV 174 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Bosch Control Air 5600 - Water to Air (WAZ software)

Integration in brief

Leave Control Source at its default (BAS Occupancy Command), then command occupied/unoccupied with occupancy_cmd_1 and set the occupied cooling/heating setpoints. Choose the zone temperature source (ZS sensor, remote sensor or BAS value) and, if the BMS supplies the temperature, write bas_sen_val_1. Monitor current_alarm_1, alm_status_1 and the effective zone temperature.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 1occupancy_cmd_1BAS occupied command; 1 enables unit operationWrite
AV 15ctrl_source_1Occupancy source; 2 = BAS occupancy command (default)Write
MV 3zone_mode_1Auto / heat / cool / offWrite
AV 4occ_clg_stpt_1Occupied cooling setpointWrite
AV 2occ_htg_stpt_1Occupied heating setpointWrite
AV 16sys_status_1Unoccupied / occupied / fan only / heating / cooling stateRead
AV 7eff_zone_temp_1Zone temperature in useRead
AV 17current_alarm_1Active alarm codeRead
BV 24alm_status_1Alarm present flagRead

Enable & remote start

Set ctrl_source_1 (AV 15) to 2 = BAS Occupancy Command (factory default) and write occupancy_cmd_1 (BV 1) = 1 to occupy the unit. Other sources are a digital input enable, keypad schedule or manual on. The BAS loop enable point (loop_enabled_1, BV 23) must be 1 to allow heating/cooling; it defaults to 1.

Heartbeat & communication loss

No communication timeout is described. If the BAS temperature source is used and nothing is ever written, the zone temperature defaults to 74 °F; after that the last written value is used indefinitely.

Sensors & values from the BMS

Set the compressor control mode (comp_mode_1, AV 64) to 2 = Zone Control - BAS Sensor and write the zone temperature to bas_sen_val_1 (AV 19). BAS humidity goes to bas_rh_sen_val_1 (AV 56) with rh_bas_sel_1 (AV 51); BAS CO2 to bas_co2_val_1 (AV 49) with co2_bas_ena_1 (AV 106); mixed air to bas_mat_1 (AV 86); outdoor air to effective_oat_1 (AV 29).

Network setup

Watch out for

Bosch Control Air 5600 - Water to Air (WAZ software) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

174 of 174 shown
Type
AnalogBinaryMulti-state
Access
Show
Bosch Control Air 5600 - Water to Air (WAZ software) BACnet Points List
DescriptionStates
AVmin15ctrl_source_1Control SourceWrite0 = Digital Input Enable (e.g. Room Occupancy Sensor) 1 = Keypad Schedule 2 = BAS Occupancy Command (Default) 3 = Factory Use Only 4 = Manual On-Continuous
BVmin1occupancy_cmd_1Occupancy Command (BAS)Write0 = Unoccupied (Default) 1 = Occupied (Enables Unit Operation)
BV75bas_smoke_1BAS Smoke Input / Emergency ShutdownWrite0 = Normal (Default)
MV4zone_mode_stat_1Zone Mode StatusRead1 = Auto (Default) 2 = Heat 3 = Cool 5 = Off
AV24mode_status_1Unit Mode StatusRead0 = Straight Cool 2 = Heat pump (Default)
MVmin3zone_mode_1Set Zone ModeWrite1 = Auto (Default) 2 = Heat 3 = Cool 5 = Off
AV64comp_mode_1Compressor Control ModeWrite0 = Zone Control - ZS (Default) 1 = Discharge Air Control 2 = Zone Control - BAS Sensor 3 = Zone Control - Remote Sensor
AV108ao3_cfg_sel_1Analog Output 3 Options ConfigurationWrite0 = Not Used (Default) 1 = Modulating Outdoor Air Damper Control
AV83ao2_cfg_sel_1Analog Output 2 Options ConfigurationWrite0 = Not Used (Default) 1 = Modulating Hot Gas Reheat Valve Control
AV82ao1_cfg_sel_1Analog Output 1 Options ConfigurationWrite0 = Not Used (Default) 1 =Variable Frequence Drive Signal Control 2 =Mixed Air SCR Preheat Control 3 =SCR Controlled Aux Electric Heat
AV113bo5_cfg_sel_1Output 5 Options ConfigurationWrite0 = Not Used (Default) 1 = Hot Gas Reheat for Humidity Control 2 = Auxiliary Electric Heat Control 3 = Fresh Air Damper Control 4 = Condenser Water Valve (Loop Valve) Control 6 = Water-Side Economizer Control 7 = Boilerless Electric Heat Control
AV112bo4_cfg_sel_1Output 4 Options ConfigurationWrite155 = "1" 0 = Not Used (Default) 1 = Economizer Valve 2 = Boilerless Control 3 = Fresh Air Damper Control
AV110in1_cfg_sel_1Input 1 ConfigurationWrite0 = Not Used (Default) 2 = Digital Input Enable (e.g. Room Occupancy Sensor) 3 = RH Probe Sensor
AV111in2_cfg_sel_1Input 2 ConfigurationWrite0 = Not Used 1 = Zone Remote Sensor 2 = Outdoor Air Temperature Sensor 3 = Entering Water Temperature Sensor (Default) 4 = Mixed Air Temperature Sensor 5 = Relative Humidity Sensor (Probe) 6 = Digital Enable (e.g. Room Occupancy Sensor) 7 = Return Air Temperature Sensor
AV60di5_mode_1DI5 Mode (Digital Input 5)Write0 = Dirty Filter Switch 1 = Entering Water Temp Sensor - Economizer/Boilerless 2 = Differential Pressure Switch 3 = Secondary Condensate Pan 4 = Fan Status Switch 5 = Valve End Switch 6 = Damper End Switch 7 = Smoke Detector Switch 8 = Pump Status Switch 9 = MIxed Air Temp Sensor - Mixed Air Control 10 = Input Expansion Module (IEM) 11 = Not Used (Default)
BV7lckout_resp_1Fan Response for Comp LockoutWrite0 = Do not lock fan upon compressor lockout (Default) 1 = Lock fan upon compressor lockout
AV41zs_sensor_en_1ZS Sensor EnableWrite0 = No ZS Sensors 1 = ZS Sensors Enabled (Default)
AV1904eq_rh_1Equipment Touch RHWrite
AV1902eq_temp_1Equipment Touch TempWrite
AV40zs_sen_combo_sel_1ZS Sensor Combo SelectorWrite0 = Temp Only 1 = RH Only 2 = CO2 Only 3 = Temp + RH 4 = Temp + CO2 5 = RH + CO2 6 = Temp + RH + CO2 (Default) 7 = No ZS Sensor
AV42stpt_adj_lim_1ZS Sensor Setpoint Adjustment Limit°FWrite
BV95enable_push_button_1Sensor Override Enable/DisableWrite0 = ZS Sensor Override NOT Allowed 1 = ZS Sensor Override Allowed (Default)
BV94override_status_1Override StatusRead0 = Normal 1 = ZS Sensor in Override Mode
AV115tlo_rem_1Override Time RemainingRead
AVmin4occ_clg_stpt_1Setpoint°FWrite
AVmin2occ_htg_stpt_1Setpoint°FWrite
AV1unocc_clg_stpt_1Setpoint°FWrite
AV3unocc_htg_stpt_1Setpoint°FWrite
AV5eff_clg_stpt_1Effective Cooling Setpoint°FRead
AV6eff_htg_stpt_1Effective Heating Setpoint°FRead
AVmin7eff_zone_temp_1Zone Temperature°FRead
BV22nsb_status_1Night Setback (NSB) StatusRead0 = Night Setback disabled 1 = Night Setback enabled
BV26ztmp_hi_1High ZS Zone Sensor Temperature AlarmRead0 = Normal 1 = High Zone Temperature(Default: 10 °F Above Setpoint)
BV27ztmp_lo_1Low ZS Zone Sensor Temperature AlarmRead0 = Normal 1 = Low Zone Temperature(Default: 10 °F Below Setpoint)
BV28zone_sen_1ZS Zone Sensor Hardware Failure AlarmRead0 = Normal 1 = Sensor Failure (Check: ZS Sensor Hardware)
AV9eff_remzone_temp_1Effect Zone Remote TemperatureRead
AV31zone_rem_sen_val_1Remote Temp or Return Air Temp ValueRead
AVmin16sys_status_1System StatusRead0 = Unoccupied 1 = Occupied 2 = Fan Only 3 = Heating 4 = Cooling 5 = Transition to Cool 6 = Transition to Heat 7 = Air Economizer 8 = Unit Locked 9 = Aux Heat 10 = Re-Heat 11 = Manual Re-Heat 12 = Transition to Re-Heat 13 = Free Cooling 14 = Transition to Free Cooling 15 = Water-Side Economizer
AV13clg_pct_1Cooling Demand PercentageRead
AV12htg_pct_1Heating Demand Percentage%Read
AV11eff_lwt_1Leaving Water Temperature (LWT)°FRead
AV10eff_dat_1Effect Disch Air Temp°FRead
AV75eff_oat_1Outdoor Air Temperature (OAT)°FRead
AV30dat_stpt_1Discharged Air Temperature Setpoint°FWrite
AV8rst_temp_source_1Temperature Reset SourceWrite0 = Outside Air Temperature Reset (Default) 1 = Mixed Air (or Return Air) Temperature Reset
AV78oat_sel_sta_1Outside Air Temperature Sensor Source StatusRead1 = BAS OAT Sensor 2 = Hard-Wired OAT Sensor (Default)
AV71oat_rst_mode_1Temperature Reset ModeWrite0 = Single 1 = Multiple (Default)
AV69oat_reset1_1Single Reset/Free Cooling Reset Temperature°FWrite
AV72oat_reset2_1Part Cool Reset Temperature°FWrite
AV74oat_reset3_1Full Cool Reset Temperature°FWrite
AV92oat_reset_ht_1Heating Reset Temperature°FWrite
AV73oat_sel_1Outside Air Temperature SensorWrite1 = BAS OAT Sensor 2 = Hard-Wired OAT Sensor (Default)
BV87oat_sen_1Outside Air Temperature Sensor FailureRead0 = Normal 1 = Sensor Failure (Check Sensor Hardware
AV28eff_hgr_mod_vlv1_1Hot Gas Reheat Modulating Valve StatusRead
AV68enabled_clstages_1Compressor Enabled StagesRead0 = No Stages Enabled 1 = 1 Stage Enabled 2 = 2 Stages Enabled
AV58dat_stpt_diff_1Supply Air Setpoint Differential°FWrite
AV63sat_hi_trip_1Supply Air High Differential Trip°FWrite
AV77sat_lo_trip_1Supply Air Low Differential Trip°FWrite
BV86csat_hi_1High Cooling Supply Air Temperature in DACRead0 = Normal 1 = Alarm Active
BV149hsat_lo_1Low Heating Supply Air Temperature in DACRead0 = Normal 1 = Active (Default: <80 °F)
AV67eff_dat_stpt_1Effective Discharge Air Temperature Setpoint°FRead
AV116zt_reset_1Effective ZS Sensor TemperatureRead
BV21occ_status_1Occupancy StatusRead0 = Unoccupied 1 = Occupied
BV17fan_cmd_1Fan Output CmdRead0 = Fan Output Off 1 = Fan Output On
BV15rev_vlv_cmd_1Reversing Valve Output StatusRead0 = Reversing Valve De-energized 1 = Reversing Valve Energized
BV11cmp_stg1_cmd_1Comp Stage1 Output CmdRead0 = Compressor 1 Off 1 = Compressor 1 On
BV12cmp_stg2_cmd_1Comp Stage2 Output CmdRead0 = Compressor 2 Off 1 = Compressor 2 On
AV14cmp_stgs_1Compressor StagesRead1 = 1 Compressor 1 Stage 2 = 2 Compressor 2 Stages 5 = 1 Compressor 2 Stages
AV120comp_state_1Compressor StatusRead0 = Normal/Off 1 = Compressor Locked 2 = Compressor Overriden "ON" 3 = Compressor Shutdown/Alarm
BVmin24alm_status_1Alarm StatusRead0 = System Normal 1 = System in Alarm
AVmin17current_alarm_1Current Alarm Condition StatusRead0 = No Alarm, 1-10 = UPM Fault Code (See UPM Alarms below) 20 = Output Overridden via Keypad 30 = Sensor Failure 40 = Leaving Water Temp Alarm 50 = Zone Temp Alarm 60 = Discharge Air Temperature Alarm 70 = Filter Alarm/Compressors 1 & 2 Runtime 80 = Zone Humidity Alarm 90 = High CO2 Level Alarm 100 = Differential Pressure Switch (DPS) Alarm
BV32lvg_hi_1High Leaving Water TemperatureRead0 = Normal 1 = Alarm (Default: >135 °F)
BV33lvg_lo_1Low Leaving Water TemperatureRead0 = Normal 1 = Alarm (Default: <40 °F)
BV29dat_hi_1High Discharge Air TemperatureRead0 = Normal 1 = Alarm (Default: >70 °F)
BV30dat_lo_1Discharge Air Temperature AlarmRead0 = Normal 1 = Low DAT Alarm (Default: <75 °F)
BV5hp1_2st_1UPM Safety - High Pressure AlarmRead0 = Normal 1 = High Pressure Alarm (UPM-I code = 1; UPM-II codes = 1,3)
BV4lp1_2st_1UPM Safety - Low Pressure AlarmRead0 = Normal 1 = Low Pressure Alarm (UPM-I code = 2; UPM-II codes = 2,4)
BV8frz_2st_1UPM Safety - Condenser Coil Freeze AlarmRead0 = Normal 1 = Condenser Freeze Alarm(UPM-I code = 3; UPM-II codes = 5,9)
BV9con_2st_1UPM Safety - High Condensate AlarmRead0 = Normal 1 = Condensate Overflow Alarm(UPM-I code = 4; UPM-II code = 6)
BV10brn_2st_1UPM Safety - Brownout AlarmRead0 = Normal 1 = Brownout Alarm (UPM-I code = 5; UPM-II code = 7)
BV90frz_evap_2st_1UPM Safety - Evaporator Coil Freeze AlarmRead0 = Normal 1 = Evaporator Freeze Alarm (UPM-I code = 6; UPM-II codes = 8,10)
BV104a2l_2st_1UPM Safety - A2L AlarmWrite0 = Normal 1 = A2L Alarm (UPM-I code = 7; UPM-II codes = 11)
BV106comm_2st_1UPM Safety - Communication AlarmWrite0 = Normal 1 = Communication Alarm (UPM-II codes = 12)
BV25upm_rst_1UPM ResetWrite0 = Reset Off (Default) 1 = Reset On
BV39upm_input_1UPM Input AlarmRead0 = UPM Connected 1 = UPM Connection Failure(Check Alarm Hardware Configuration)
BV34lvg_sen_1Leaving Water Temperature Sensor FailureRead0 = Normal 1 = Sensor Failure (Check Sensor Hardware
BV31da_sen_1Discharge Air Temperature SensorRead0 = Sensor Normal 1 = Sensor Failure Alarm (Check Sensor Hardware Configuration)
BV37do_lock_1Digital Override Lock AlarmRead0 = Normal 1 = Digital Override Enabled Alarm
BV38input_lock_1Inputs Override StatusRead0 = Normal 1 = Software Lock Enabled
BV2dup_in12_1Duplicate Input 1&2 AlarmRead0 = Normal 1 = Alarm (Check input configuration for conflicts)
BV35comp1_rntm_1Compressor 1 RuntimeRead1 = Auto (cycle with compressor) 4 = On (Default)
BV36comp2_rntm_1Compressor 2 RuntimeRead0 = Normal 1 = Timer Has Expired (Default: >8760 Hours)
BV13cmp1_rntm_rst_1Compressor 1 Runtime ResetWrite0 = Reset Off (Default) 1 = Reset On
BV14cmp2_rntm_rst_1Compressor 2 Runtime ResetWrite0 = Reset Off (Default) 1 = Reset On
BV41zrem_hi_1High Remote Temperature AlarmRead0 = Normal 1 = High Zone Temperature(Default: 10 °F Above Setpoint)
BV42zrem_lo_1Low Remote Temperature AlarmRead0 = Normal 1 = Low Zone Temperature(Default: 10 °F Below Setpoint)
BV43zrem_sen_1Remote Temperature Sensor Hardware Failure AlarmRead0 = Normal 1 = Sensor Failure (Check Remote Sensor Hardware)
BV80ewt_sen_1Entering Water Temperature Sensor AlarmRead0 = Normal 1 = Sensor Failure Alarm (Check Hardware)
BV6aecon_status_1Air Economizer StatusRead0 = Inactive 1 = Active
AV100oat_hi_lim_aecon_1OAT high limit for Air Econ°FWrite
AV117oat_lo_lim_aecon_1OAT low limit for Air Econ°FWrite
AV118rh_hi_lim_aecon_1Outdoor RH high limit for Air Econ%Write
AV119rh_lo_lim_aecon_1Outdoor RH low limit for Air Econ%Write
BV91htg_econ_1Boilerless StatusRead0 = Off 1 = On (Electric Heating)
BV92clg_econ_1Economizer Cooling CommandRead0 = On 1 = Off
AV62eff_ewt_1Entering Water Temperature°FRead
BV79cwv_cmd_1Condenser Water Valve OutputRead0 = Closed 1 = Open
BV68ves_status_1Valve End Switch StatusRead0 = Off 1 = Valve End Switch Detected
BV150ves_hand_1Valve Switch HandRead
BV151ves_fail_1Valve End Switch AlarmRead0 = Normal 1 = Active
BV77dps_alarm_1Differential Pressure Switch (DPS) AlarmRead0 = Normal 1 = Alarm
BV20aux_htg_cmd_1Aux Heat Output CmdRead0 = Aux Heat Off 1 = Aux Heat On
AV175pre_htg_ovrde_1Pre-Heat Output OverrideWrite0 = Do not allow override (Default) 1 = allow override
AV121mat_pid_1SCR Electric Heat Output%Read
BV40filter_1Filter Service AlarmRead0 = Off 1 = Service Filter Alarm
BV19fan_rntm_rst_1Reset Fan RuntimeWrite0 = Reset Off (Default) 1 = Reset On
MV2fan_mode_1Set Fan ModeWrite1 = Auto (Cycel with Compressor) 4 = On (Default)
MV1fan_mode_stat_1Fan Mode StatusRead1 = Auto (Cycel with Compressor) 4 = On (Default)
BV66fan_status_1Fan Running StatusRead0 = Off 1 = On - Fan Running
BV83saf_hand_1Fan Hand Mode AlarmRead
BV82saf_switch_fail_1Supply Air Fan Switch FailureRead0 = Normal 1 = Alarm (Check Fan Hardware)
AV20eff_zone_humid_1Zone Humidity%Read
AV21occ_zhumid_stpt_1Occupied Zone Humidity Setpoint%Write
AV22zhumid_stpt_diff_1Zone Humidity Setpoint Differential%Write
BV44eff_hgrv_cmd_1Hot Gas ReHeat Valve StatusRead0 = Valve Off 1 = Valve On
BV45zhumid_hi_1High Humidity AlarmRead0 = Normal 1 = High Humidity (Default: 10% above Setpoint)
BV46zhumid_lo_1Low Humidity AlarmRead0 = Normal 1 = Low Humidity (Default: 30% below Setpoint)
BV47zhumid_sen_1Humidity Sensor Hardware Failure AlarmRead0 = Normal 1 = Sensor Failure (Check RH Sensor Hardware Configuration)
AV50iem_mode_1Input Expansion Module ModeWrite0 = Dirty Filter Switch, Fan Status Switch, Valve End Switch (Default) 1 = Smoke Detector Switch, Fan Status Switch, Valve End Switch 2 = Dirty Filter Switch, Fan Status Switch, Differential Pressure Switch 3 = Smoke Detector Switch, Fan Status Switch, Dirty Filter Switch 4 = Dirty Filter Switch, Fan Status Switch, Damper End Switch 5 = Smoke Detector Switch, Fan Status Switch, Secondary Drain Pan 6 = Dirty Filter Switch, Fan Status Switch, Pump Status
BV67allow_fan_alrm_1Enable/Disable Fan Status Switch in IEMWrite0 = FSS on IEM disabled (Default)
BV69allow_ves_alrm_1Enable/Disable Valve Switch in IEMWrite0 = VES on IEM disabled (Default)
BV71smoke_alrm_enable_1Smoke Alarm Enable/DisableWrite0 = SDS on IEM disabled (Default) 1 = SDS on IEM Enabled
AV87eff_mat_1Mixed Air Temperature (MAT)°FRead
AV84mat_sel_status_1Mix Air Temperature Source StatusRead0 = BAS MAT 1 = Wired MAT
AV85mat_sel_1Mixed Air Temperature SensorWrite0 = BAS MAT Sensor 1 = Hard-Wired MAT Sensor (Default)
AV90mat_stpt_1Mixed Air Temperature Setpoint°FWrite
AV61ma_preheat_1Electric Preheat OutputRead
BV89mat_low_1Low Mixed Air TemperatureRead0 = Normal 1 = Alarm (Default: <38 °F)
BV88mat_sen_1Mix Air Temperature Sensor FailureRead0 = Normal 1 = Sensor Failure (Check Sensor Hardware
BV3pump_cmd_1Circulation Pump Output CommandRead0 = Pump Running 1 = Pump Off
BV56pss_fail_1Circulation Pump Switch Failure AlarmRead0 = Normal 1 = Active
BV57pump_status_1Pump Switch StatusRead0 = Off 1 = Pump Switch Detected
BV58pss_hand_1Circulation Pump Switch In Hand AlarmRead
BV50conpump_1Secondary Condensate Pump AlarmRead0 = Normal 1 = Alarm Active
BV81smoke_1Smoke Event Alarm NotificationRead0 = Normal 1 = Alarm
BV70smoke_status_1Smoke Event StatusRead0 = Normal 1 = Smoke Detector Active
AV25eff_zn_co2_lev_1Zone CO2 LevelppmRead
AV27zn_co2_hi_trip_1Zone CO2 High TripppmWrite
BV51zn_co2_fail_1CO2 Hardware Failure AlarmRead0 = Normal 1 = Sensor Failure (Check CO2 Hardware Configuration)
BV48zn_co2_hi_1High CO2 AlarmRead0 = Normal 1 = High CO2 Level (Default: >1200 PPM)
AV107dmp_opt_sel_1Damper Option SelectionWrite0 = Damper Opens when Fan Runs (Default) 1 = Damper Opens when Occupied 2 = Damper Opens for Free Cooling (Air Economizer)
BV49damper_cmd_1Damper CommandRead0 = Closed 1 = Open
BV93des_status_1Damper End SwitchRead0 = Damper Closed 1 = Damper Open
AV81eff_dpr_pos_screen_1Modulating Damper Position%Read
AV79min_mdpr_pos_1Minimum Damper PositionWrite
AV97mdpr_occ_sel_1Damper Occupancy SelectionWrite0 = Disabled 1 = Occupied (Default) 2 = Unoccupied 3 = Any Occupancy
AV55eff_sa_fan_speed_1Static Air Fan Speed%Read
AV53eff_sa_sta_press_1Supply Air Duct Static Pressurein. W.C.Read
AV52sta_press_stpt_1Static Press Setpointin. W.C.Write
AV59saf_min_speed_1Supply Air Fan Minimum SpeedWrite
AV54sa_sta_hi_trip_1Supply Air Static Pressure High Tripin. W.C.Write
BV65sas_sen_1Static Air Pressure Sensor Hardware AlarmRead0 = Normal 1 = Sensor Failure (Check Static Pressure Hardware Configuration)
BV64sas_hi_1High Static Pressure AlarmRead0 = Normal 1 = High Static Pressure (Default: > 2.75" H20)
AV23unit_mode_1Unit ModeWrite0 = Cooling only 2 = Heat Pump (Default)
AV114stages_1Compressor Stages SelectionWrite1 = 1 Compressor 1 Stage (UPM-I Alarm Codes Used) 2 = 2 Compressor 2 Stages (UPM-II Alarm Codes Used) 5 = 1 Compressor 2 Stages (UPM-I Alarm Codes Used) (Default)
AV94coil_cfg_1Evaporator Coil Configuration SelectionWrite0 = Parallel (Default) 1 = Series
BV23loop_enabled_1BAS Loop Enable/DisableWrite0 = Disable Heat/Cool 1 = Allow Heat/Cool Operation (Default)
AV51rh_bas_sel_1BAS Relative Humidity Enable/DisableWrite0 = BAS RH Sensor 1 = Hard-Wired RH Sensor (Default)
AV106co2_bas_ena_1CO2 BAS Enable/DisableWrite0 = BAS CO2 Sensor 1 = Hard-Wired CO2 Sensor (Default)
AV49bas_co2_val_1BAS CO2 Sensor ValueppmWrite
AV86bas_mat_1BAS Mixed Air Temp°FWrite
AV29effective_oat_1BAS Outside Air Temperature°FWrite
AV56bas_rh_sen_val_1BAS RH Sensor Value%Write
AV19bas_sen_val_1BAS Temperature Sensor Value°FWrite

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Control Air 5600 - Water to Air (WAZ software) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Bosch Control Air 5600 - Water to Air (WAZ software)

How many BACnet points does the Bosch Control Air 5600 - Water to Air (WAZ software) have?

This list has 174 BACnet objects: 88 analog values, 82 binary values, 4 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Bosch Control Air 5600 - Water to Air (WAZ software) BACnet points are writable?

73 of the 174 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Bosch Control Air 5600 - Water to Air (WAZ software) BACnet documentation?

The source is Bosch TT - Water to Air Network Integration Points List (WAZ.1.03), published free by Bosch at https://www.bosch-homecomfort.com/us/media/country_pool/service/technical_guides/ipl_waz_1_03.pdf.

What are the minimum BACnet points to integrate the Bosch Control Air 5600 - Water to Air (WAZ software)?

Start with BV 1 occupancy_cmd_1 (BAS occupied command; 1 enables unit operation); AV 15 ctrl_source_1 (Occupancy source; 2 = BAS occupancy command (default)); MV 3 zone_mode_1 (Auto / heat / cool / off); AV 4 occ_clg_stpt_1 (Occupied cooling setpoint); AV 2 occ_htg_stpt_1 (Occupied heating setpoint); AV 16 sys_status_1 (Unoccupied / occupied / fan only / heating / cooling state); AV 7 eff_zone_temp_1 (Zone temperature in use); AV 17 current_alarm_1 (Active alarm code); BV 24 alm_status_1 (Alarm present flag).

How do I enable BMS control of the Bosch Control Air 5600 - Water to Air (WAZ software)?

Set ctrl_source_1 (AV 15) to 2 = BAS Occupancy Command (factory default) and write occupancy_cmd_1 (BV 1) = 1 to occupy the unit. Other sources are a digital input enable, keypad schedule or manual on. The BAS loop enable point (loop_enabled_1, BV 23) must be 1 to allow heating/cooling; it defaults to 1.

Does the Bosch Control Air 5600 - Water to Air (WAZ software) need a BACnet heartbeat or have a communication timeout?

No communication timeout is described. If the BAS temperature source is used and nothing is ever written, the zone temperature defaults to 74 °F; after that the last written value is used indefinitely.

Can the BMS supply sensor values to the Bosch Control Air 5600 - Water to Air (WAZ software)?

Set the compressor control mode (comp_mode_1, AV 64) to 2 = Zone Control - BAS Sensor and write the zone temperature to bas_sen_val_1 (AV 19). BAS humidity goes to bas_rh_sen_val_1 (AV 56) with rh_bas_sel_1 (AV 51); BAS CO2 to bas_co2_val_1 (AV 49) with co2_bas_ena_1 (AV 106); mixed air to bas_mat_1 (AV 86); outdoor air to effective_oat_1 (AV 29).

How do I check these points on the real Control Air 5600 - Water to Air (WAZ software)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Bosch BACnet points lists