Water-source heat pump controller · BACnet points list
Bosch Control Air 5600 - Water to Air (WAZ software) BACnet points list
Updated 28 October 2026
The Control Air 5600 is Bosch's factory-mounted DDC controller for water-source heat pumps. It speaks BACnet MS/TP (or BACnet over ARC156, Modbus, N2 and Lon) and exposes occupancy, mode, setpoint, sensor, configuration and alarm points as AV/BV/MSV objects. The same point list also documents Modbus registers and N2/LON equivalents.
This page lists 174 BACnet objects for the Bosch Control Air 5600 - Water to Air (WAZ software) — 73 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Bosch’s own free documentation, linked below.
- Manufacturer
- Bosch
- Model
- Control Air 5600 - Water to Air (WAZ software)
- Equipment
- Water-source heat pump controller
- Equipment type
- Heat pumps
- BACnet objects
- 174 (73 writable)
- Transport
- BACnet MS/TP, BACnet ARC156
- Firmware
- WAZ.1.03
- Also known as
- Control Air 5600, WAZ 1.03, Bosch WSHP DDC, Bosch water source heat pump BACnet, Bosch TT Water to Air
BMS integration notes: Bosch Control Air 5600 - Water to Air (WAZ software)
Leave Control Source at its default (BAS Occupancy Command), then command occupied/unoccupied with occupancy_cmd_1 and set the occupied cooling/heating setpoints. Choose the zone temperature source (ZS sensor, remote sensor or BAS value) and, if the BMS supplies the temperature, write bas_sen_val_1. Monitor current_alarm_1, alm_status_1 and the effective zone temperature.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 1 | occupancy_cmd_1 | BAS occupied command; 1 enables unit operation | Write |
| AV 15 | ctrl_source_1 | Occupancy source; 2 = BAS occupancy command (default) | Write |
| MV 3 | zone_mode_1 | Auto / heat / cool / off | Write |
| AV 4 | occ_clg_stpt_1 | Occupied cooling setpoint | Write |
| AV 2 | occ_htg_stpt_1 | Occupied heating setpoint | Write |
| AV 16 | sys_status_1 | Unoccupied / occupied / fan only / heating / cooling state | Read |
| AV 7 | eff_zone_temp_1 | Zone temperature in use | Read |
| AV 17 | current_alarm_1 | Active alarm code | Read |
| BV 24 | alm_status_1 | Alarm present flag | Read |
Enable & remote start
Set ctrl_source_1 (AV 15) to 2 = BAS Occupancy Command (factory default) and write occupancy_cmd_1 (BV 1) = 1 to occupy the unit. Other sources are a digital input enable, keypad schedule or manual on. The BAS loop enable point (loop_enabled_1, BV 23) must be 1 to allow heating/cooling; it defaults to 1.
Heartbeat & communication loss
No communication timeout is described. If the BAS temperature source is used and nothing is ever written, the zone temperature defaults to 74 °F; after that the last written value is used indefinitely.
Sensors & values from the BMS
Set the compressor control mode (comp_mode_1, AV 64) to 2 = Zone Control - BAS Sensor and write the zone temperature to bas_sen_val_1 (AV 19). BAS humidity goes to bas_rh_sen_val_1 (AV 56) with rh_bas_sel_1 (AV 51); BAS CO2 to bas_co2_val_1 (AV 49) with co2_bas_ena_1 (AV 106); mixed air to bas_mat_1 (AV 86); outdoor air to effective_oat_1 (AV 29).
Network setup
- BACnet MS/TP runs on the EIA-485 port; the BAS Port Settings DIP switches select the protocol (BACnet MS/TP, N2, Modbus) and baud rate (9.6 to 76.8 kbps), the same for every controller on the trunk.
- The two rotary dials set the MAC address (tens and ones); the controller only reads them at power-up, so change them with power off.
- A Communication jumper selects EIA-485 (MS/TP, N2, Modbus, Lon) or BACnet over ARC156 at 156 kbps.
- Setpoints and configuration can also be changed locally with a BACview terminal or Virtual BACview.
Watch out for
- With a ZS or remote sensor selected, the controller looks for it during the first 30 s after power-up; if missing, the unit stays unoccupied, alarms and shows -60 °F.
- Writing bas_smoke_1 = 1 shuts the supply fan, compressors and reheat valve off.
- The input/output configuration AVs (in1/in2/ao/bo cfg) change how hardware I/O is used; treat them as commissioning settings, not operating points.
- There is a 1-minute delay when the unit changes between heating and cooling.
Bosch Control Air 5600 - Water to Air (WAZ software) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AVmin | 15 | ctrl_source_1 | Control Source | Write | 0 = Digital Input Enable (e.g. Room Occupancy Sensor) 1 = Keypad Schedule 2 = BAS Occupancy Command (Default) 3 = Factory Use Only 4 = Manual On-Continuous | |
| BVmin | 1 | occupancy_cmd_1 | Occupancy Command (BAS) | Write | 0 = Unoccupied (Default) 1 = Occupied (Enables Unit Operation) | |
| BV | 75 | bas_smoke_1 | BAS Smoke Input / Emergency Shutdown | Write | 0 = Normal (Default) | |
| MV | 4 | zone_mode_stat_1 | Zone Mode Status | Read | 1 = Auto (Default) 2 = Heat 3 = Cool 5 = Off | |
| AV | 24 | mode_status_1 | Unit Mode Status | Read | 0 = Straight Cool 2 = Heat pump (Default) | |
| MVmin | 3 | zone_mode_1 | Set Zone Mode | Write | 1 = Auto (Default) 2 = Heat 3 = Cool 5 = Off | |
| AV | 64 | comp_mode_1 | Compressor Control Mode | Write | 0 = Zone Control - ZS (Default) 1 = Discharge Air Control 2 = Zone Control - BAS Sensor 3 = Zone Control - Remote Sensor | |
| AV | 108 | ao3_cfg_sel_1 | Analog Output 3 Options Configuration | Write | 0 = Not Used (Default) 1 = Modulating Outdoor Air Damper Control | |
| AV | 83 | ao2_cfg_sel_1 | Analog Output 2 Options Configuration | Write | 0 = Not Used (Default) 1 = Modulating Hot Gas Reheat Valve Control | |
| AV | 82 | ao1_cfg_sel_1 | Analog Output 1 Options Configuration | Write | 0 = Not Used (Default) 1 =Variable Frequence Drive Signal Control 2 =Mixed Air SCR Preheat Control 3 =SCR Controlled Aux Electric Heat | |
| AV | 113 | bo5_cfg_sel_1 | Output 5 Options Configuration | Write | 0 = Not Used (Default) 1 = Hot Gas Reheat for Humidity Control 2 = Auxiliary Electric Heat Control 3 = Fresh Air Damper Control 4 = Condenser Water Valve (Loop Valve) Control 6 = Water-Side Economizer Control 7 = Boilerless Electric Heat Control | |
| AV | 112 | bo4_cfg_sel_1 | Output 4 Options Configuration | Write | 155 = "1" 0 = Not Used (Default) 1 = Economizer Valve 2 = Boilerless Control 3 = Fresh Air Damper Control | |
| AV | 110 | in1_cfg_sel_1 | Input 1 Configuration | Write | 0 = Not Used (Default) 2 = Digital Input Enable (e.g. Room Occupancy Sensor) 3 = RH Probe Sensor | |
| AV | 111 | in2_cfg_sel_1 | Input 2 Configuration | Write | 0 = Not Used 1 = Zone Remote Sensor 2 = Outdoor Air Temperature Sensor 3 = Entering Water Temperature Sensor (Default) 4 = Mixed Air Temperature Sensor 5 = Relative Humidity Sensor (Probe) 6 = Digital Enable (e.g. Room Occupancy Sensor) 7 = Return Air Temperature Sensor | |
| AV | 60 | di5_mode_1 | DI5 Mode (Digital Input 5) | Write | 0 = Dirty Filter Switch 1 = Entering Water Temp Sensor - Economizer/Boilerless 2 = Differential Pressure Switch 3 = Secondary Condensate Pan 4 = Fan Status Switch 5 = Valve End Switch 6 = Damper End Switch 7 = Smoke Detector Switch 8 = Pump Status Switch 9 = MIxed Air Temp Sensor - Mixed Air Control 10 = Input Expansion Module (IEM) 11 = Not Used (Default) | |
| BV | 7 | lckout_resp_1 | Fan Response for Comp Lockout | Write | 0 = Do not lock fan upon compressor lockout (Default) 1 = Lock fan upon compressor lockout | |
| AV | 41 | zs_sensor_en_1 | ZS Sensor Enable | Write | 0 = No ZS Sensors 1 = ZS Sensors Enabled (Default) | |
| AV | 1904 | eq_rh_1 | Equipment Touch RH | Write | ||
| AV | 1902 | eq_temp_1 | Equipment Touch Temp | Write | ||
| AV | 40 | zs_sen_combo_sel_1 | ZS Sensor Combo Selector | Write | 0 = Temp Only 1 = RH Only 2 = CO2 Only 3 = Temp + RH 4 = Temp + CO2 5 = RH + CO2 6 = Temp + RH + CO2 (Default) 7 = No ZS Sensor | |
| AV | 42 | stpt_adj_lim_1 | ZS Sensor Setpoint Adjustment Limit | °F | Write | |
| BV | 95 | enable_push_button_1 | Sensor Override Enable/Disable | Write | 0 = ZS Sensor Override NOT Allowed 1 = ZS Sensor Override Allowed (Default) | |
| BV | 94 | override_status_1 | Override Status | Read | 0 = Normal 1 = ZS Sensor in Override Mode | |
| AV | 115 | tlo_rem_1 | Override Time Remaining | Read | ||
| AVmin | 4 | occ_clg_stpt_1 | Setpoint | °F | Write | |
| AVmin | 2 | occ_htg_stpt_1 | Setpoint | °F | Write | |
| AV | 1 | unocc_clg_stpt_1 | Setpoint | °F | Write | |
| AV | 3 | unocc_htg_stpt_1 | Setpoint | °F | Write | |
| AV | 5 | eff_clg_stpt_1 | Effective Cooling Setpoint | °F | Read | |
| AV | 6 | eff_htg_stpt_1 | Effective Heating Setpoint | °F | Read | |
| AVmin | 7 | eff_zone_temp_1 | Zone Temperature | °F | Read | |
| BV | 22 | nsb_status_1 | Night Setback (NSB) Status | Read | 0 = Night Setback disabled 1 = Night Setback enabled | |
| BV | 26 | ztmp_hi_1 | High ZS Zone Sensor Temperature Alarm | Read | 0 = Normal 1 = High Zone Temperature(Default: 10 °F Above Setpoint) | |
| BV | 27 | ztmp_lo_1 | Low ZS Zone Sensor Temperature Alarm | Read | 0 = Normal 1 = Low Zone Temperature(Default: 10 °F Below Setpoint) | |
| BV | 28 | zone_sen_1 | ZS Zone Sensor Hardware Failure Alarm | Read | 0 = Normal 1 = Sensor Failure (Check: ZS Sensor Hardware) | |
| AV | 9 | eff_remzone_temp_1 | Effect Zone Remote Temperature | Read | ||
| AV | 31 | zone_rem_sen_val_1 | Remote Temp or Return Air Temp Value | Read | ||
| AVmin | 16 | sys_status_1 | System Status | Read | 0 = Unoccupied 1 = Occupied 2 = Fan Only 3 = Heating 4 = Cooling 5 = Transition to Cool 6 = Transition to Heat 7 = Air Economizer 8 = Unit Locked 9 = Aux Heat 10 = Re-Heat 11 = Manual Re-Heat 12 = Transition to Re-Heat 13 = Free Cooling 14 = Transition to Free Cooling 15 = Water-Side Economizer | |
| AV | 13 | clg_pct_1 | Cooling Demand Percentage | Read | ||
| AV | 12 | htg_pct_1 | Heating Demand Percentage | % | Read | |
| AV | 11 | eff_lwt_1 | Leaving Water Temperature (LWT) | °F | Read | |
| AV | 10 | eff_dat_1 | Effect Disch Air Temp | °F | Read | |
| AV | 75 | eff_oat_1 | Outdoor Air Temperature (OAT) | °F | Read | |
| AV | 30 | dat_stpt_1 | Discharged Air Temperature Setpoint | °F | Write | |
| AV | 8 | rst_temp_source_1 | Temperature Reset Source | Write | 0 = Outside Air Temperature Reset (Default) 1 = Mixed Air (or Return Air) Temperature Reset | |
| AV | 78 | oat_sel_sta_1 | Outside Air Temperature Sensor Source Status | Read | 1 = BAS OAT Sensor 2 = Hard-Wired OAT Sensor (Default) | |
| AV | 71 | oat_rst_mode_1 | Temperature Reset Mode | Write | 0 = Single 1 = Multiple (Default) | |
| AV | 69 | oat_reset1_1 | Single Reset/Free Cooling Reset Temperature | °F | Write | |
| AV | 72 | oat_reset2_1 | Part Cool Reset Temperature | °F | Write | |
| AV | 74 | oat_reset3_1 | Full Cool Reset Temperature | °F | Write | |
| AV | 92 | oat_reset_ht_1 | Heating Reset Temperature | °F | Write | |
| AV | 73 | oat_sel_1 | Outside Air Temperature Sensor | Write | 1 = BAS OAT Sensor 2 = Hard-Wired OAT Sensor (Default) | |
| BV | 87 | oat_sen_1 | Outside Air Temperature Sensor Failure | Read | 0 = Normal 1 = Sensor Failure (Check Sensor Hardware | |
| AV | 28 | eff_hgr_mod_vlv1_1 | Hot Gas Reheat Modulating Valve Status | Read | ||
| AV | 68 | enabled_clstages_1 | Compressor Enabled Stages | Read | 0 = No Stages Enabled 1 = 1 Stage Enabled 2 = 2 Stages Enabled | |
| AV | 58 | dat_stpt_diff_1 | Supply Air Setpoint Differential | °F | Write | |
| AV | 63 | sat_hi_trip_1 | Supply Air High Differential Trip | °F | Write | |
| AV | 77 | sat_lo_trip_1 | Supply Air Low Differential Trip | °F | Write | |
| BV | 86 | csat_hi_1 | High Cooling Supply Air Temperature in DAC | Read | 0 = Normal 1 = Alarm Active | |
| BV | 149 | hsat_lo_1 | Low Heating Supply Air Temperature in DAC | Read | 0 = Normal 1 = Active (Default: <80 °F) | |
| AV | 67 | eff_dat_stpt_1 | Effective Discharge Air Temperature Setpoint | °F | Read | |
| AV | 116 | zt_reset_1 | Effective ZS Sensor Temperature | Read | ||
| BV | 21 | occ_status_1 | Occupancy Status | Read | 0 = Unoccupied 1 = Occupied | |
| BV | 17 | fan_cmd_1 | Fan Output Cmd | Read | 0 = Fan Output Off 1 = Fan Output On | |
| BV | 15 | rev_vlv_cmd_1 | Reversing Valve Output Status | Read | 0 = Reversing Valve De-energized 1 = Reversing Valve Energized | |
| BV | 11 | cmp_stg1_cmd_1 | Comp Stage1 Output Cmd | Read | 0 = Compressor 1 Off 1 = Compressor 1 On | |
| BV | 12 | cmp_stg2_cmd_1 | Comp Stage2 Output Cmd | Read | 0 = Compressor 2 Off 1 = Compressor 2 On | |
| AV | 14 | cmp_stgs_1 | Compressor Stages | Read | 1 = 1 Compressor 1 Stage 2 = 2 Compressor 2 Stages 5 = 1 Compressor 2 Stages | |
| AV | 120 | comp_state_1 | Compressor Status | Read | 0 = Normal/Off 1 = Compressor Locked 2 = Compressor Overriden "ON" 3 = Compressor Shutdown/Alarm | |
| BVmin | 24 | alm_status_1 | Alarm Status | Read | 0 = System Normal 1 = System in Alarm | |
| AVmin | 17 | current_alarm_1 | Current Alarm Condition Status | Read | 0 = No Alarm, 1-10 = UPM Fault Code (See UPM Alarms below) 20 = Output Overridden via Keypad 30 = Sensor Failure 40 = Leaving Water Temp Alarm 50 = Zone Temp Alarm 60 = Discharge Air Temperature Alarm 70 = Filter Alarm/Compressors 1 & 2 Runtime 80 = Zone Humidity Alarm 90 = High CO2 Level Alarm 100 = Differential Pressure Switch (DPS) Alarm | |
| BV | 32 | lvg_hi_1 | High Leaving Water Temperature | Read | 0 = Normal 1 = Alarm (Default: >135 °F) | |
| BV | 33 | lvg_lo_1 | Low Leaving Water Temperature | Read | 0 = Normal 1 = Alarm (Default: <40 °F) | |
| BV | 29 | dat_hi_1 | High Discharge Air Temperature | Read | 0 = Normal 1 = Alarm (Default: >70 °F) | |
| BV | 30 | dat_lo_1 | Discharge Air Temperature Alarm | Read | 0 = Normal 1 = Low DAT Alarm (Default: <75 °F) | |
| BV | 5 | hp1_2st_1 | UPM Safety - High Pressure Alarm | Read | 0 = Normal 1 = High Pressure Alarm (UPM-I code = 1; UPM-II codes = 1,3) | |
| BV | 4 | lp1_2st_1 | UPM Safety - Low Pressure Alarm | Read | 0 = Normal 1 = Low Pressure Alarm (UPM-I code = 2; UPM-II codes = 2,4) | |
| BV | 8 | frz_2st_1 | UPM Safety - Condenser Coil Freeze Alarm | Read | 0 = Normal 1 = Condenser Freeze Alarm(UPM-I code = 3; UPM-II codes = 5,9) | |
| BV | 9 | con_2st_1 | UPM Safety - High Condensate Alarm | Read | 0 = Normal 1 = Condensate Overflow Alarm(UPM-I code = 4; UPM-II code = 6) | |
| BV | 10 | brn_2st_1 | UPM Safety - Brownout Alarm | Read | 0 = Normal 1 = Brownout Alarm (UPM-I code = 5; UPM-II code = 7) | |
| BV | 90 | frz_evap_2st_1 | UPM Safety - Evaporator Coil Freeze Alarm | Read | 0 = Normal 1 = Evaporator Freeze Alarm (UPM-I code = 6; UPM-II codes = 8,10) | |
| BV | 104 | a2l_2st_1 | UPM Safety - A2L Alarm | Write | 0 = Normal 1 = A2L Alarm (UPM-I code = 7; UPM-II codes = 11) | |
| BV | 106 | comm_2st_1 | UPM Safety - Communication Alarm | Write | 0 = Normal 1 = Communication Alarm (UPM-II codes = 12) | |
| BV | 25 | upm_rst_1 | UPM Reset | Write | 0 = Reset Off (Default) 1 = Reset On | |
| BV | 39 | upm_input_1 | UPM Input Alarm | Read | 0 = UPM Connected 1 = UPM Connection Failure(Check Alarm Hardware Configuration) | |
| BV | 34 | lvg_sen_1 | Leaving Water Temperature Sensor Failure | Read | 0 = Normal 1 = Sensor Failure (Check Sensor Hardware | |
| BV | 31 | da_sen_1 | Discharge Air Temperature Sensor | Read | 0 = Sensor Normal 1 = Sensor Failure Alarm (Check Sensor Hardware Configuration) | |
| BV | 37 | do_lock_1 | Digital Override Lock Alarm | Read | 0 = Normal 1 = Digital Override Enabled Alarm | |
| BV | 38 | input_lock_1 | Inputs Override Status | Read | 0 = Normal 1 = Software Lock Enabled | |
| BV | 2 | dup_in12_1 | Duplicate Input 1&2 Alarm | Read | 0 = Normal 1 = Alarm (Check input configuration for conflicts) | |
| BV | 35 | comp1_rntm_1 | Compressor 1 Runtime | Read | 1 = Auto (cycle with compressor) 4 = On (Default) | |
| BV | 36 | comp2_rntm_1 | Compressor 2 Runtime | Read | 0 = Normal 1 = Timer Has Expired (Default: >8760 Hours) | |
| BV | 13 | cmp1_rntm_rst_1 | Compressor 1 Runtime Reset | Write | 0 = Reset Off (Default) 1 = Reset On | |
| BV | 14 | cmp2_rntm_rst_1 | Compressor 2 Runtime Reset | Write | 0 = Reset Off (Default) 1 = Reset On | |
| BV | 41 | zrem_hi_1 | High Remote Temperature Alarm | Read | 0 = Normal 1 = High Zone Temperature(Default: 10 °F Above Setpoint) | |
| BV | 42 | zrem_lo_1 | Low Remote Temperature Alarm | Read | 0 = Normal 1 = Low Zone Temperature(Default: 10 °F Below Setpoint) | |
| BV | 43 | zrem_sen_1 | Remote Temperature Sensor Hardware Failure Alarm | Read | 0 = Normal 1 = Sensor Failure (Check Remote Sensor Hardware) | |
| BV | 80 | ewt_sen_1 | Entering Water Temperature Sensor Alarm | Read | 0 = Normal 1 = Sensor Failure Alarm (Check Hardware) | |
| BV | 6 | aecon_status_1 | Air Economizer Status | Read | 0 = Inactive 1 = Active | |
| AV | 100 | oat_hi_lim_aecon_1 | OAT high limit for Air Econ | °F | Write | |
| AV | 117 | oat_lo_lim_aecon_1 | OAT low limit for Air Econ | °F | Write | |
| AV | 118 | rh_hi_lim_aecon_1 | Outdoor RH high limit for Air Econ | % | Write | |
| AV | 119 | rh_lo_lim_aecon_1 | Outdoor RH low limit for Air Econ | % | Write | |
| BV | 91 | htg_econ_1 | Boilerless Status | Read | 0 = Off 1 = On (Electric Heating) | |
| BV | 92 | clg_econ_1 | Economizer Cooling Command | Read | 0 = On 1 = Off | |
| AV | 62 | eff_ewt_1 | Entering Water Temperature | °F | Read | |
| BV | 79 | cwv_cmd_1 | Condenser Water Valve Output | Read | 0 = Closed 1 = Open | |
| BV | 68 | ves_status_1 | Valve End Switch Status | Read | 0 = Off 1 = Valve End Switch Detected | |
| BV | 150 | ves_hand_1 | Valve Switch Hand | Read | ||
| BV | 151 | ves_fail_1 | Valve End Switch Alarm | Read | 0 = Normal 1 = Active | |
| BV | 77 | dps_alarm_1 | Differential Pressure Switch (DPS) Alarm | Read | 0 = Normal 1 = Alarm | |
| BV | 20 | aux_htg_cmd_1 | Aux Heat Output Cmd | Read | 0 = Aux Heat Off 1 = Aux Heat On | |
| AV | 175 | pre_htg_ovrde_1 | Pre-Heat Output Override | Write | 0 = Do not allow override (Default) 1 = allow override | |
| AV | 121 | mat_pid_1 | SCR Electric Heat Output | % | Read | |
| BV | 40 | filter_1 | Filter Service Alarm | Read | 0 = Off 1 = Service Filter Alarm | |
| BV | 19 | fan_rntm_rst_1 | Reset Fan Runtime | Write | 0 = Reset Off (Default) 1 = Reset On | |
| MV | 2 | fan_mode_1 | Set Fan Mode | Write | 1 = Auto (Cycel with Compressor) 4 = On (Default) | |
| MV | 1 | fan_mode_stat_1 | Fan Mode Status | Read | 1 = Auto (Cycel with Compressor) 4 = On (Default) | |
| BV | 66 | fan_status_1 | Fan Running Status | Read | 0 = Off 1 = On - Fan Running | |
| BV | 83 | saf_hand_1 | Fan Hand Mode Alarm | Read | ||
| BV | 82 | saf_switch_fail_1 | Supply Air Fan Switch Failure | Read | 0 = Normal 1 = Alarm (Check Fan Hardware) | |
| AV | 20 | eff_zone_humid_1 | Zone Humidity | % | Read | |
| AV | 21 | occ_zhumid_stpt_1 | Occupied Zone Humidity Setpoint | % | Write | |
| AV | 22 | zhumid_stpt_diff_1 | Zone Humidity Setpoint Differential | % | Write | |
| BV | 44 | eff_hgrv_cmd_1 | Hot Gas ReHeat Valve Status | Read | 0 = Valve Off 1 = Valve On | |
| BV | 45 | zhumid_hi_1 | High Humidity Alarm | Read | 0 = Normal 1 = High Humidity (Default: 10% above Setpoint) | |
| BV | 46 | zhumid_lo_1 | Low Humidity Alarm | Read | 0 = Normal 1 = Low Humidity (Default: 30% below Setpoint) | |
| BV | 47 | zhumid_sen_1 | Humidity Sensor Hardware Failure Alarm | Read | 0 = Normal 1 = Sensor Failure (Check RH Sensor Hardware Configuration) | |
| AV | 50 | iem_mode_1 | Input Expansion Module Mode | Write | 0 = Dirty Filter Switch, Fan Status Switch, Valve End Switch (Default) 1 = Smoke Detector Switch, Fan Status Switch, Valve End Switch 2 = Dirty Filter Switch, Fan Status Switch, Differential Pressure Switch 3 = Smoke Detector Switch, Fan Status Switch, Dirty Filter Switch 4 = Dirty Filter Switch, Fan Status Switch, Damper End Switch 5 = Smoke Detector Switch, Fan Status Switch, Secondary Drain Pan 6 = Dirty Filter Switch, Fan Status Switch, Pump Status | |
| BV | 67 | allow_fan_alrm_1 | Enable/Disable Fan Status Switch in IEM | Write | 0 = FSS on IEM disabled (Default) | |
| BV | 69 | allow_ves_alrm_1 | Enable/Disable Valve Switch in IEM | Write | 0 = VES on IEM disabled (Default) | |
| BV | 71 | smoke_alrm_enable_1 | Smoke Alarm Enable/Disable | Write | 0 = SDS on IEM disabled (Default) 1 = SDS on IEM Enabled | |
| AV | 87 | eff_mat_1 | Mixed Air Temperature (MAT) | °F | Read | |
| AV | 84 | mat_sel_status_1 | Mix Air Temperature Source Status | Read | 0 = BAS MAT 1 = Wired MAT | |
| AV | 85 | mat_sel_1 | Mixed Air Temperature Sensor | Write | 0 = BAS MAT Sensor 1 = Hard-Wired MAT Sensor (Default) | |
| AV | 90 | mat_stpt_1 | Mixed Air Temperature Setpoint | °F | Write | |
| AV | 61 | ma_preheat_1 | Electric Preheat Output | Read | ||
| BV | 89 | mat_low_1 | Low Mixed Air Temperature | Read | 0 = Normal 1 = Alarm (Default: <38 °F) | |
| BV | 88 | mat_sen_1 | Mix Air Temperature Sensor Failure | Read | 0 = Normal 1 = Sensor Failure (Check Sensor Hardware | |
| BV | 3 | pump_cmd_1 | Circulation Pump Output Command | Read | 0 = Pump Running 1 = Pump Off | |
| BV | 56 | pss_fail_1 | Circulation Pump Switch Failure Alarm | Read | 0 = Normal 1 = Active | |
| BV | 57 | pump_status_1 | Pump Switch Status | Read | 0 = Off 1 = Pump Switch Detected | |
| BV | 58 | pss_hand_1 | Circulation Pump Switch In Hand Alarm | Read | ||
| BV | 50 | conpump_1 | Secondary Condensate Pump Alarm | Read | 0 = Normal 1 = Alarm Active | |
| BV | 81 | smoke_1 | Smoke Event Alarm Notification | Read | 0 = Normal 1 = Alarm | |
| BV | 70 | smoke_status_1 | Smoke Event Status | Read | 0 = Normal 1 = Smoke Detector Active | |
| AV | 25 | eff_zn_co2_lev_1 | Zone CO2 Level | ppm | Read | |
| AV | 27 | zn_co2_hi_trip_1 | Zone CO2 High Trip | ppm | Write | |
| BV | 51 | zn_co2_fail_1 | CO2 Hardware Failure Alarm | Read | 0 = Normal 1 = Sensor Failure (Check CO2 Hardware Configuration) | |
| BV | 48 | zn_co2_hi_1 | High CO2 Alarm | Read | 0 = Normal 1 = High CO2 Level (Default: >1200 PPM) | |
| AV | 107 | dmp_opt_sel_1 | Damper Option Selection | Write | 0 = Damper Opens when Fan Runs (Default) 1 = Damper Opens when Occupied 2 = Damper Opens for Free Cooling (Air Economizer) | |
| BV | 49 | damper_cmd_1 | Damper Command | Read | 0 = Closed 1 = Open | |
| BV | 93 | des_status_1 | Damper End Switch | Read | 0 = Damper Closed 1 = Damper Open | |
| AV | 81 | eff_dpr_pos_screen_1 | Modulating Damper Position | % | Read | |
| AV | 79 | min_mdpr_pos_1 | Minimum Damper Position | Write | ||
| AV | 97 | mdpr_occ_sel_1 | Damper Occupancy Selection | Write | 0 = Disabled 1 = Occupied (Default) 2 = Unoccupied 3 = Any Occupancy | |
| AV | 55 | eff_sa_fan_speed_1 | Static Air Fan Speed | % | Read | |
| AV | 53 | eff_sa_sta_press_1 | Supply Air Duct Static Pressure | in. W.C. | Read | |
| AV | 52 | sta_press_stpt_1 | Static Press Setpoint | in. W.C. | Write | |
| AV | 59 | saf_min_speed_1 | Supply Air Fan Minimum Speed | Write | ||
| AV | 54 | sa_sta_hi_trip_1 | Supply Air Static Pressure High Trip | in. W.C. | Write | |
| BV | 65 | sas_sen_1 | Static Air Pressure Sensor Hardware Alarm | Read | 0 = Normal 1 = Sensor Failure (Check Static Pressure Hardware Configuration) | |
| BV | 64 | sas_hi_1 | High Static Pressure Alarm | Read | 0 = Normal 1 = High Static Pressure (Default: > 2.75" H20) | |
| AV | 23 | unit_mode_1 | Unit Mode | Write | 0 = Cooling only 2 = Heat Pump (Default) | |
| AV | 114 | stages_1 | Compressor Stages Selection | Write | 1 = 1 Compressor 1 Stage (UPM-I Alarm Codes Used) 2 = 2 Compressor 2 Stages (UPM-II Alarm Codes Used) 5 = 1 Compressor 2 Stages (UPM-I Alarm Codes Used) (Default) | |
| AV | 94 | coil_cfg_1 | Evaporator Coil Configuration Selection | Write | 0 = Parallel (Default) 1 = Series | |
| BV | 23 | loop_enabled_1 | BAS Loop Enable/Disable | Write | 0 = Disable Heat/Cool 1 = Allow Heat/Cool Operation (Default) | |
| AV | 51 | rh_bas_sel_1 | BAS Relative Humidity Enable/Disable | Write | 0 = BAS RH Sensor 1 = Hard-Wired RH Sensor (Default) | |
| AV | 106 | co2_bas_ena_1 | CO2 BAS Enable/Disable | Write | 0 = BAS CO2 Sensor 1 = Hard-Wired CO2 Sensor (Default) | |
| AV | 49 | bas_co2_val_1 | BAS CO2 Sensor Value | ppm | Write | |
| AV | 86 | bas_mat_1 | BAS Mixed Air Temp | °F | Write | |
| AV | 29 | effective_oat_1 | BAS Outside Air Temperature | °F | Write | |
| AV | 56 | bas_rh_sen_val_1 | BAS RH Sensor Value | % | Write | |
| AV | 19 | bas_sen_val_1 | BAS Temperature Sensor Value | °F | Write |
No points match these filters.
Integration notes
- Object names end in _1 as printed in the points list.
- Two names were split across lines in the PDF and were re-joined here: eq_temp_1 (AV 1902) and zs_sen_combo_sel_1 (AV 40).
- Many AV points are configuration selectors (input/output assignments); several only matter when that option (economizer, hot gas reheat, VFD, CO2, damper) is installed.
- Writable points are those not marked read-only in the list.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Control Air 5600 - Water to Air (WAZ software) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Bosch Control Air 5600 - Water to Air (WAZ software)
How many BACnet points does the Bosch Control Air 5600 - Water to Air (WAZ software) have?
This list has 174 BACnet objects: 88 analog values, 82 binary values, 4 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Bosch Control Air 5600 - Water to Air (WAZ software) BACnet points are writable?
73 of the 174 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Bosch Control Air 5600 - Water to Air (WAZ software) BACnet documentation?
The source is Bosch TT - Water to Air Network Integration Points List (WAZ.1.03), published free by Bosch at https://www.bosch-homecomfort.com/us/media/country_pool/service/technical_guides/ipl_waz_1_03.pdf.
What are the minimum BACnet points to integrate the Bosch Control Air 5600 - Water to Air (WAZ software)?
Start with BV 1 occupancy_cmd_1 (BAS occupied command; 1 enables unit operation); AV 15 ctrl_source_1 (Occupancy source; 2 = BAS occupancy command (default)); MV 3 zone_mode_1 (Auto / heat / cool / off); AV 4 occ_clg_stpt_1 (Occupied cooling setpoint); AV 2 occ_htg_stpt_1 (Occupied heating setpoint); AV 16 sys_status_1 (Unoccupied / occupied / fan only / heating / cooling state); AV 7 eff_zone_temp_1 (Zone temperature in use); AV 17 current_alarm_1 (Active alarm code); BV 24 alm_status_1 (Alarm present flag).
How do I enable BMS control of the Bosch Control Air 5600 - Water to Air (WAZ software)?
Set ctrl_source_1 (AV 15) to 2 = BAS Occupancy Command (factory default) and write occupancy_cmd_1 (BV 1) = 1 to occupy the unit. Other sources are a digital input enable, keypad schedule or manual on. The BAS loop enable point (loop_enabled_1, BV 23) must be 1 to allow heating/cooling; it defaults to 1.
Does the Bosch Control Air 5600 - Water to Air (WAZ software) need a BACnet heartbeat or have a communication timeout?
No communication timeout is described. If the BAS temperature source is used and nothing is ever written, the zone temperature defaults to 74 °F; after that the last written value is used indefinitely.
Can the BMS supply sensor values to the Bosch Control Air 5600 - Water to Air (WAZ software)?
Set the compressor control mode (comp_mode_1, AV 64) to 2 = Zone Control - BAS Sensor and write the zone temperature to bas_sen_val_1 (AV 19). BAS humidity goes to bas_rh_sen_val_1 (AV 56) with rh_bas_sel_1 (AV 51); BAS CO2 to bas_co2_val_1 (AV 49) with co2_bas_ena_1 (AV 106); mixed air to bas_mat_1 (AV 86); outdoor air to effective_oat_1 (AV 29).
How do I check these points on the real Control Air 5600 - Water to Air (WAZ software)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Bosch BACnet points lists
- Condensing boiler gateway
Bosch Buderus SSB800 / SSB1000 / SSB1000TL boiler (ProtoNode FPC-N38)
Bosch Buderus SSB800, SSB1000 and SSB1000TL condensing boilers (D_Platform control) connected through a ProtoNode FPC-N38 gateway.
Also known as: SSB800, SSB1000, SSB1000TL, Buderus SSB, Bosch SSB, ProtoNode FPC-N38, D_Platform - Water-to-water heat pump controller
Bosch Control Air 5600 - Water to Water (WWZ software)
Bosch water-to-water heat pumps fitted with the Control Air 5600 DDC controller running WWZ software.
Also known as: Control Air 5600, WWZ 1.03, Bosch water to water heat pump BACnet, Bosch TT Water to Water - Commercial water-source heat pump controller
Bosch Control Air 6120 - Water to Air (WAF software)
Bosch commercial water-to-air heat pumps (up to 4 compressor stages) with the Control Air 6120 DDC controller and WAF software.
Also known as: Control Air 6120, WAF 1.01, Bosch commercial WSHP DDC, Bosch TT Water to Air
Source: Bosch TT - Water to Air Network Integration Points List · WAZ.1.03. Object names, instances and units are reproduced as published; descriptions are our own.