Boiler cascade controller gateway · BACnet points list

Bosch Buderus Cascade SSB 255 / 399 / 512 (ProtoAir FPA-W44, C_Platform) BACnet points list

Updated 6 November 2026

Short answer

Bosch's ProtoAir FPA-W44 start-up guide maps the C_Platform (Buderus SSB 255/399/512 cascade) to 154 objects: unit selection and control register, state, status, error code, pump states, temperatures, firing rate, flame current, ignition and burn-hour counters, 16-deep lockout and blocking history, state/error/firing rate of up to 15 dependent boilers, and read and write copies of the CH/DHW mode, setpoints, reset curve, warm weather shutdown and night setback.

This page lists 154 BACnet objects for the Bosch Buderus Cascade SSB 255 / 399 / 512 (ProtoAir FPA-W44, C_Platform) — 14 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Bosch’s own free documentation, linked below.

Manufacturer
Bosch
Model
Buderus Cascade SSB 255 / 399 / 512 (ProtoAir FPA-W44, C_Platform)
Equipment
Boiler cascade controller gateway
Equipment type
Boilers & water heaters
BACnet objects
154 (14 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Also known as
SSB 255, SSB 399, SSB 512, Buderus SSB, C_Platform, ProtoAir FPA-W44, Bosch cascade
Source document
ProtoAir FPA-W44 Start-up Guide for Bosch, Appendix C.1 C_Platform Modbus RTU Mappings to BACnet · Document Revision 5.D · rev. 2020-03
Download CSV 154 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Bosch’s current documentation and the live device before use. Not official Bosch information. Terms of use.

BMS integration notes: Bosch Buderus Cascade SSB 255 / 399 / 512 (ProtoAir FPA-W44, C_Platform)

Integration in brief

Map the CH mode and setpoint AVs for control and read State, Status, supply and return temperatures, firing rate, the error code and the dependent boilers' state. The guide does not explain the Control Register or the mode codes, so check the boiler's Modbus documentation before writing.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AV 144CH ModeCentral heating mode commandWrite
AV 146CH SetpointCentral heating setpointWrite
AV 2Control RegisterControl register; see the boiler Modbus manualWrite
AI 3StateBoiler state codeRead
AI 4StatusBoiler status codeRead
AI 9Supply TemperatureSupply water temperatureRead
AI 15Firing RateFiring rateRead
AI 87Dependent 01 StateDependent 01 state (repeat for 02-15)Read
AI 5Error CodeActive error codeRead

Enable & remote start

AV 144-155 are the writable mode, setpoint, reset-curve and night setback values (their read-back copies are AI 132-143). AV 2 Control Register is writable too; the guide does not say how it is used.

Network setup

Watch out for

Bosch Buderus Cascade SSB 255 / 399 / 512 (ProtoAir FPA-W44, C_Platform) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

154 of 154 shown
Type
Access
Show
Bosch Buderus Cascade SSB 255 / 399 / 512 (ProtoAir FPA-W44, C_Platform) BACnet Points List
DescriptionStates
AV1Unit SelectionWrite
AVmin2Control RegisterControl word for writes (meaning not given in the guide)Write
AImin3StateRead
AImin4StatusRead
AImin5Error CodeRead
AI6CH PumpRead
AI7DHW PumpRead
AI8General PumpRead
AImin9Supply TemperatureRead
AI10Return TemperatureRead
AI11DHW TemperatureRead
AI12Flue Gas TemperatureRead
AI13System (Heat Exchanger) TemperatureRead
AI14Outside TemperatureRead
AImin15Firing RateRead
AI16Flame (Ionization) CurrentRead
AI18Successful Ignition CounterRead
AI19Failed Ignition CounterRead
AI20Flame Failure CounterRead
AI21Burn Hours CHRead
AI22Burn Hours DHWRead
AI231st Lockout In HistoryRead
AI242nd Lockout In HistoryRead
AI253rd Lockout In HistoryRead
AI264th Lockout In HistoryRead
AI275th Lockout In HistoryRead
AI286th Lockout In HistoryRead
AI297th Lockout In HistoryRead
AI308th Lockout In HistoryRead
AI319th Lockout In HistoryRead
AI3210th Lockout In HistoryRead
AI3311th Lockout In HistoryRead
AI3412th Lockout In HistoryRead
AI3513th Lockout In HistoryRead
AI3614th Lockout In HistoryRead
AI3715th Lockout In HistoryRead
AI3816th Lockout In HistoryRead
AI39Time After 1st LockoutRead
AI40Time After 2nd LockoutRead
AI41Time After 3rd LockoutRead
AI42Time After 4th LockoutRead
AI43Time After 5th LockoutRead
AI44Time After 6th LockoutRead
AI45Time After 7th LockoutRead
AI46Time After 8th LockoutRead
AI47Time After 9th LockoutRead
AI48Time After 10th LockoutRead
AI49Time After 11th LockoutRead
AI50Time After 12th LockoutRead
AI51Time After 13th LockoutRead
AI52Time After 14th LockoutRead
AI53Time After 15th LockoutRead
AI54Time After 16th LockoutRead
AI551st Blocking In HistoryRead
AI562nd Blocking In HistoryRead
AI573rd Blocking In HistoryRead
AI584th Blocking In HistoryRead
AI595th Blocking In HistoryRead
AI606th Blocking In HistoryRead
AI617th Blocking In HistoryRead
AI628th Blocking In HistoryRead
AI639th Blocking In HistoryRead
AI6410th Blocking In HistoryRead
AI6511th Blocking In HistoryRead
AI6612th Blocking In HistoryRead
AI6713th Blocking In HistoryRead
AI6814th Blocking In HistoryRead
AI6915th Blocking In HistoryRead
AI7016th Blocking In HistoryRead
AI71Time After 1st BlockingRead
AI72Time After 2nd BlockingRead
AI73Time After 3rd BlockingRead
AI74Time After 4th BlockingRead
AI75Time After 5th BlockingRead
AI76Time After 6th BlockingRead
AI77Time After 7th BlockingRead
AI78Time After 8th BlockingRead
AI79Time After 9th BlockingRead
AI80Time After 10th BlockingRead
AI81Time After 11th BlockingRead
AI82Time After 12th BlockingRead
AI83Time After 13th BlockingRead
AI84Time After 14th BlockingRead
AI85Time After 15th BlockingRead
AI86Time After 16th BlockingRead
AImin87Dependent 01 StateRead
AI88Dependent 01 Error CodeRead
AI89Dependent 01 Firing RateRead
AI90Dependent 02 StateRead
AI91Dependent 02 Error CodeRead
AI92Dependent 02 Firing RateRead
AI93Dependent 03 StateRead
AI94Dependent 03 Error CodeRead
AI95Dependent 03 Firing RateRead
AI96Dependent 04 StateRead
AI97Dependent 04 Error CodeRead
AI98Dependent 04 Firing RateRead
AI99Dependent 05 StateRead
AI100Dependent 05 Error CodeRead
AI101Dependent 05 Firing RateRead
AI102Dependent 06 StateRead
AI103Dependent 06 Error CodeRead
AI104Dependent 06 Firing RateRead
AI105Dependent 07 StateRead
AI106Dependent 07 Error CodeRead
AI107Dependent 07 Firing RateRead
AI108Dependent 08 StateRead
AI109Dependent 08 Error CodeRead
AI110Dependent 08 Firing RateRead
AI111Dependent 09 StateRead
AI112Dependent 09 Error CodeRead
AI113Dependent 09 Firing RateRead
AI114Dependent 10 StateRead
AI115Dependent 10 Error CodeRead
AI116Dependent 10 Firing RateRead
AI117Dependent 11 StateRead
AI118Dependent 11 Error CodeRead
AI119Dependent 11 Firing RateRead
AI120Dependent 12 StateRead
AI121Dependent 12 Error CodeRead
AI122Dependent 12 Firing RateRead
AI123Dependent 13 StateRead
AI124Dependent 13 Error CodeRead
AI125Dependent 13 Firing RateRead
AI126Dependent 14 StateRead
AI127Dependent 14 Error CodeRead
AI128Dependent 14 Firing RateRead
AI129Dependent 15 StateRead
AI130Dependent 15 Error CodeRead
AI131Dependent 15 Firing RateRead
AI132CH ModeRead
AI133DHW ModeRead
AI134CH SetpointRead
AI135DHW SetpointRead
AI136Reset Curve Boiler DesignRead
AI137Reset Curve Boiler Mild WeatherRead
AI138Reset Curve Outdoor Mild WeatherRead
AI139Reset Curve Outdoor DesignRead
AI140Warm Weather ShutdownRead
AI141Reset Curve Boiler MaximumRead
AI142Reset Curve Boiler MinimumRead
AI143Night SetbackRead
AVmin144CH ModeWrite
AV145DHW ModeWrite
AVmin146CH SetpointWrite
AV147DHW SetpointWrite
AV148Reset Curve Boiler DesignWrite
AV149Reset Curve Boiler Mild WeatherWrite
AV140Reset Curve Outdoor Mild WeatherPrinted as AV 140 between AV 149 and AV 151 (likely 150)Write
AV151Reset Curve Outdoor DesignWrite
AV152Warm Weather ShutdownWrite
AV153Reset Curve Boiler MaximumWrite
AV154Reset Curve Boiler MinimumWrite
AV155Night SetbackWrite
Object ID lookup: Bosch Buderus Cascade SSB 255 / 399 / 512 point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Buderus Cascade SSB 255 / 399 / 512 (ProtoAir FPA-W44, C_Platform) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Bosch Buderus Cascade SSB 255 / 399 / 512 (ProtoAir FPA-W44, C_Platform)

How many BACnet points does the Bosch Buderus Cascade SSB 255 / 399 / 512 (ProtoAir FPA-W44, C_Platform) have?

This list has 154 BACnet objects: 140 analog inputs, 14 analog values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Bosch Buderus Cascade SSB 255 / 399 / 512 (ProtoAir FPA-W44, C_Platform) BACnet points are writable?

14 of the 154 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Bosch Buderus Cascade SSB 255 / 399 / 512 (ProtoAir FPA-W44, C_Platform) BACnet documentation?

The source is ProtoAir FPA-W44 Start-up Guide for Bosch, Appendix C.1 C_Platform Modbus RTU Mappings to BACnet (Document Revision 5.D), revision 2020-03, published free by Bosch at https://www.bosch-homecomfort.com/us/media/country_pool/service/technical_guides/protoair_fpa-w44_start-up_guide_03.2020.pdf.

What are the minimum BACnet points to integrate the Bosch Buderus Cascade SSB 255 / 399 / 512 (ProtoAir FPA-W44, C_Platform)?

Start with AV 144 CH Mode (Central heating mode command); AV 146 CH Setpoint (Central heating setpoint); AV 2 Control Register (Control register; see the boiler Modbus manual); AI 3 State (Boiler state code); AI 4 Status (Boiler status code); AI 9 Supply Temperature (Supply water temperature); AI 15 Firing Rate (Firing rate); AI 87 Dependent 01 State (Dependent 01 state (repeat for 02-15)); AI 5 Error Code (Active error code).

How do I enable BMS control of the Bosch Buderus Cascade SSB 255 / 399 / 512 (ProtoAir FPA-W44, C_Platform)?

AV 144-155 are the writable mode, setpoint, reset-curve and night setback values (their read-back copies are AI 132-143). AV 2 Control Register is writable too; the guide does not say how it is used.

How do I check these points on the real Buderus Cascade SSB 255 / 399 / 512 (ProtoAir FPA-W44, C_Platform)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Bosch BACnet points lists

Source: ProtoAir FPA-W44 Start-up Guide for Bosch, Appendix C.1 C_Platform Modbus RTU Mappings to BACnet · Document Revision 5.D · rev. 2020-03. Object names, instances and units are reproduced as published; descriptions are our own.