Booster pump controller · BACnet points list

Bell & Gossett TechnoForce e-MTV booster pump controller BACnet points list

Updated 12 November 2026

Short answer

The TechnoForce e-MTV controller runs a variable-speed water booster set and has a small BACnet object list: Binary Values for drive not-ready and trip alarms, pump enable, pump run status, general and sensor alarms, auto/manual status, system start/stop, manual alternation and alarm reset, and Analog Inputs for discharge pressure, flow, setpoint, speed and pump run hours.

This page lists 28 BACnet objects for the Bell & Gossett TechnoForce e-MTV booster pump controller — 6 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Bell & Gossett’s own free documentation, linked below.

Manufacturer
Bell & Gossett
Model
TechnoForce e-MTV booster pump controller
Equipment
Booster pump controller
Equipment type
VFDs & pumps
BACnet objects
28 (6 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
e-MTV application 1.0 or above, FW 596.13 or above
Also known as
TechnoForce e-MTV, e-MTV, B&G TechnoForce, TechnoForce Pump Controller, IM361
Source document
TechnoForce e-MTV Instruction Manual · IM361 R1
Download CSV 28 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Bell & Gossett’s current documentation and the live device before use. Not official Bell & Gossett information. Terms of use.

BMS integration notes: Bell & Gossett TechnoForce e-MTV booster pump controller

Integration in brief

Start and stop the booster with BV 18 and enable pumps with BV 6-8. Read discharge pressure, setpoint, flow and speed (AI 0-3), pump run status (BV 9-11) and the general alarm (BV 12); BV 20 resets alarms.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 18Start_StopSystem start/stop (1 = on)Write
BV 6Pump1EnableDisablePump 1 enableWrite
BV 20AlarmResetAlarm resetWrite
AI 0DischargePressureDischarge pressureRead
AI 2SetpointPressure setpoint in useRead
AI 3SpeedSystem speed, %Read
BV 9Pump1RunStatusPump 1 runningRead
BV 17AutoManualStatusAuto/manual status (1 = auto)Read
BV 12GeneralAlarmGeneral alarmRead

Enable & remote start

BV 18 Start_Stop starts and stops the system; BV 17 shows whether the controller is in auto.

Watch out for

Bell & Gossett TechnoForce e-MTV booster pump controller BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

28 of 28 shown
Type
AnalogBinary
Access
Show
Bell & Gossett TechnoForce e-MTV booster pump controller BACnet Points List
DescriptionStates
BV0VFD1NotReadyRead0=O.K., 1=Failure
BV1VFD1TripRead0=O.K., 1=Failure
BV2VFD2NotReadyRead0=O.K., 1=Failure
BV3VFD2TripRead0=O.K., 1=Alarm
BV4VFD3NotReadyRead0=O.K., 1=Failure
BV5VFD3TripRead0=O.K., 1=Failure
BVmin6Pump1EnableDisableWrite0=Disable, 1=Enable
BV7Pump2EnableDisableWrite0=Disable, 1=Enable
BV8Pump3EnableDisableWrite0=Disable, 1=Enable
BVmin9Pump1RunStatusRead0=Not Running, 1=Running
BV10Pump2RunStatusRead0=Not Running, 1=Running
BV11Pump3RunStatusRead0=Not Running, 1=Running
BVmin12GeneralAlarmRead0=O.K., 1=Failure
BV13AL_FTFaultRead0=O.K., 1=Failure
BV14AL_PTFaultRead0=O.K., 1=Failure
BV15AL_PT1FaultRead0=O.K., 1=Failure
BV16AL_PT2FaultRead0=O.K., 1=Failure
BVmin17AutoManualStatusRead0=Manual, 1=Auto
BVmin18Start_StopWrite0=OFFF, 1=ON
BV19ManualAlterationWrite0=Off, 1=On
BVmin20AlarmResetWrite0=O.K., 1=Failure
AImin0DischargePressureRange 0 to SpanPSI or BARRead
AI1DischargeFlowRange 0 to SpanGPM or M3/hRead
AImin2SetpointRange 0 to SpanPSI or BARRead
AImin3SpeedRange 0 to 100%Read
AI4Pump1RunHourRange 0 to Max ValuehRead
AI5Pump2RunHourRange 0 to Max ValuehRead
AI6Pump3RunHourRange 0 to Max ValuehRead
Object ID lookup: Bell & Gossett TechnoForce e-MTV booster pump controller point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the TechnoForce e-MTV booster pump controller and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Bell & Gossett TechnoForce e-MTV booster pump controller

How many BACnet points does the Bell & Gossett TechnoForce e-MTV booster pump controller have?

This list has 28 BACnet objects: 7 analog inputs, 21 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Bell & Gossett TechnoForce e-MTV booster pump controller BACnet points are writable?

6 of the 28 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Bell & Gossett TechnoForce e-MTV booster pump controller BACnet documentation?

The source is TechnoForce e-MTV Instruction Manual (IM361 R1), published free by Bell & Gossett at https://www.xylem.com/siteassets/brand/bell-amp-gossett/resources/manual/technoforce-e-mtv-iom-im361-r1.pdf.

What are the minimum BACnet points to integrate the Bell & Gossett TechnoForce e-MTV booster pump controller?

Start with BV 18 Start_Stop (System start/stop (1 = on)); BV 6 Pump1EnableDisable (Pump 1 enable); BV 20 AlarmReset (Alarm reset); AI 0 DischargePressure (Discharge pressure); AI 2 Setpoint (Pressure setpoint in use); AI 3 Speed (System speed, %); BV 9 Pump1RunStatus (Pump 1 running); BV 17 AutoManualStatus (Auto/manual status (1 = auto)); BV 12 GeneralAlarm (General alarm).

How do I enable BMS control of the Bell & Gossett TechnoForce e-MTV booster pump controller?

BV 18 Start_Stop starts and stops the system; BV 17 shows whether the controller is in auto.

How do I check these points on the real TechnoForce e-MTV booster pump controller?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Bell & Gossett BACnet points lists

Source: TechnoForce e-MTV Instruction Manual · IM361 R1. Object names, instances and units are reproduced as published; descriptions are our own.