Booster pump controller · BACnet points list
Bell & Gossett TechnoForce e-MTV booster pump controller BACnet points list
Updated 12 November 2026
The TechnoForce e-MTV controller runs a variable-speed water booster set and has a small BACnet object list: Binary Values for drive not-ready and trip alarms, pump enable, pump run status, general and sensor alarms, auto/manual status, system start/stop, manual alternation and alarm reset, and Analog Inputs for discharge pressure, flow, setpoint, speed and pump run hours.
This page lists 28 BACnet objects for the Bell & Gossett TechnoForce e-MTV booster pump controller — 6 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Bell & Gossett’s own free documentation, linked below.
- Manufacturer
- Bell & Gossett
- Model
- TechnoForce e-MTV booster pump controller
- Equipment
- Booster pump controller
- Equipment type
- VFDs & pumps
- BACnet objects
- 28 (6 writable)
- Transport
- BACnet IP, BACnet MS/TP
- Firmware
- e-MTV application 1.0 or above, FW 596.13 or above
- Also known as
- TechnoForce e-MTV, e-MTV, B&G TechnoForce, TechnoForce Pump Controller, IM361
- Source document
- TechnoForce e-MTV Instruction Manual · IM361 R1
Reference only, provided as-is: verify against Bell & Gossett’s current documentation and the live device before use. Not official Bell & Gossett information. Terms of use.
BMS integration notes: Bell & Gossett TechnoForce e-MTV booster pump controller
Start and stop the booster with BV 18 and enable pumps with BV 6-8. Read discharge pressure, setpoint, flow and speed (AI 0-3), pump run status (BV 9-11) and the general alarm (BV 12); BV 20 resets alarms.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 18 | Start_Stop | System start/stop (1 = on) | Write |
| BV 6 | Pump1EnableDisable | Pump 1 enable | Write |
| BV 20 | AlarmReset | Alarm reset | Write |
| AI 0 | DischargePressure | Discharge pressure | Read |
| AI 2 | Setpoint | Pressure setpoint in use | Read |
| AI 3 | Speed | System speed, % | Read |
| BV 9 | Pump1RunStatus | Pump 1 running | Read |
| BV 17 | AutoManualStatus | Auto/manual status (1 = auto) | Read |
| BV 12 | GeneralAlarm | General alarm | Read |
Enable & remote start
BV 18 Start_Stop starts and stops the system; BV 17 shows whether the controller is in auto.
Watch out for
- Units for pressure and flow depend on the controller unit setting.
Bell & Gossett TechnoForce e-MTV booster pump controller BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| BV | 0 | VFD1NotReady | Read | 0=O.K., 1=Failure | ||
| BV | 1 | VFD1Trip | Read | 0=O.K., 1=Failure | ||
| BV | 2 | VFD2NotReady | Read | 0=O.K., 1=Failure | ||
| BV | 3 | VFD2Trip | Read | 0=O.K., 1=Alarm | ||
| BV | 4 | VFD3NotReady | Read | 0=O.K., 1=Failure | ||
| BV | 5 | VFD3Trip | Read | 0=O.K., 1=Failure | ||
| BVmin | 6 | Pump1EnableDisable | Write | 0=Disable, 1=Enable | ||
| BV | 7 | Pump2EnableDisable | Write | 0=Disable, 1=Enable | ||
| BV | 8 | Pump3EnableDisable | Write | 0=Disable, 1=Enable | ||
| BVmin | 9 | Pump1RunStatus | Read | 0=Not Running, 1=Running | ||
| BV | 10 | Pump2RunStatus | Read | 0=Not Running, 1=Running | ||
| BV | 11 | Pump3RunStatus | Read | 0=Not Running, 1=Running | ||
| BVmin | 12 | GeneralAlarm | Read | 0=O.K., 1=Failure | ||
| BV | 13 | AL_FTFault | Read | 0=O.K., 1=Failure | ||
| BV | 14 | AL_PTFault | Read | 0=O.K., 1=Failure | ||
| BV | 15 | AL_PT1Fault | Read | 0=O.K., 1=Failure | ||
| BV | 16 | AL_PT2Fault | Read | 0=O.K., 1=Failure | ||
| BVmin | 17 | AutoManualStatus | Read | 0=Manual, 1=Auto | ||
| BVmin | 18 | Start_Stop | Write | 0=OFFF, 1=ON | ||
| BV | 19 | ManualAlteration | Write | 0=Off, 1=On | ||
| BVmin | 20 | AlarmReset | Write | 0=O.K., 1=Failure | ||
| AImin | 0 | DischargePressure | Range 0 to Span | PSI or BAR | Read | |
| AI | 1 | DischargeFlow | Range 0 to Span | GPM or M3/h | Read | |
| AImin | 2 | Setpoint | Range 0 to Span | PSI or BAR | Read | |
| AImin | 3 | Speed | Range 0 to 100 | % | Read | |
| AI | 4 | Pump1RunHour | Range 0 to Max Value | h | Read | |
| AI | 5 | Pump2RunHour | Range 0 to Max Value | h | Read | |
| AI | 6 | Pump3RunHour | Range 0 to Max Value | h | Read |
No points match these filters.
Object ID lookup: Bell & Gossett TechnoForce e-MTV booster pump controller point IDs by name
BV0VFD1NotReadyBV1VFD1TripBV2VFD2NotReadyBV3VFD2TripBV4VFD3NotReadyBV5VFD3TripBV6Pump1EnableDisableBV7Pump2EnableDisableBV8Pump3EnableDisableBV9Pump1RunStatusBV10Pump2RunStatusBV11Pump3RunStatusBV12GeneralAlarmBV13AL_FTFaultBV14AL_PTFaultBV15AL_PT1FaultBV16AL_PT2FaultBV17AutoManualStatusBV18Start_StopBV19ManualAlterationBV20AlarmResetAI0DischargePressureAI1DischargeFlowAI2SetpointAI3SpeedAI4Pump1RunHourAI5Pump2RunHourAI6Pump3RunHour
Integration notes
- Pressure and flow units follow the controller setting (PSI or bar, GPM or m3/h).
- BV 20 AlarmReset prints the alarm state texts (1 = Failure, 0 = O.K.); write 1 to reset.
- BV 18 Start_Stop states are printed "1=ON 0= OFFF".
- The PICS describes communication over RS-485 or IP; the manual also has a Modbus RTU / IP point table.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the TechnoForce e-MTV booster pump controller and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Bell & Gossett TechnoForce e-MTV booster pump controller
How many BACnet points does the Bell & Gossett TechnoForce e-MTV booster pump controller have?
This list has 28 BACnet objects: 7 analog inputs, 21 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Bell & Gossett TechnoForce e-MTV booster pump controller BACnet points are writable?
6 of the 28 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Bell & Gossett TechnoForce e-MTV booster pump controller BACnet documentation?
The source is TechnoForce e-MTV Instruction Manual (IM361 R1), published free by Bell & Gossett at https://www.xylem.com/siteassets/brand/bell-amp-gossett/resources/manual/technoforce-e-mtv-iom-im361-r1.pdf.
What are the minimum BACnet points to integrate the Bell & Gossett TechnoForce e-MTV booster pump controller?
Start with BV 18 Start_Stop (System start/stop (1 = on)); BV 6 Pump1EnableDisable (Pump 1 enable); BV 20 AlarmReset (Alarm reset); AI 0 DischargePressure (Discharge pressure); AI 2 Setpoint (Pressure setpoint in use); AI 3 Speed (System speed, %); BV 9 Pump1RunStatus (Pump 1 running); BV 17 AutoManualStatus (Auto/manual status (1 = auto)); BV 12 GeneralAlarm (General alarm).
How do I enable BMS control of the Bell & Gossett TechnoForce e-MTV booster pump controller?
BV 18 Start_Stop starts and stops the system; BV 17 shows whether the controller is in auto.
How do I check these points on the real TechnoForce e-MTV booster pump controller?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Bell & Gossett BACnet points lists
- Pump variable frequency drive
Bell & Gossett FC-102 Embedded BACnet (pump drive)
Bell & Gossett pump packages that use the FC-102 HVAC drive with its built-in BACnet MS/TP (firmware 3.90 and above).
Also known as: FC-102, FC102, VLT HVAC Drive FC 102 - Pump variable frequency drive BACnet option card
Bell & Gossett MCA 109 Advanced BACnet Option (FC-102)
Bell & Gossett pump packages with an FC-102 drive fitted with the MCA 109 Advanced BACnet option card (firmware 3.90 and above).
Also known as: MCA109, MCA 109, FC-102 BACnet option, VLT BACnet option - Constant speed pump system controller
Bell & Gossett Technologic Constant Speed Pump Controller
Bell & Gossett Technologic constant speed pumping systems for up to six pumps, with the BACnet MS/TP interface.
Also known as: Technologic CS, Technologic constant speed, B&G Technologic, ITT Technologic
Source: TechnoForce e-MTV Instruction Manual · IM361 R1. Object names, instances and units are reproduced as published; descriptions are our own.