Pump variable frequency drive · BACnet points list

Bell & Gossett FC-102 Embedded BACnet (pump drive) BACnet points list

Updated 28 October 2026

Short answer

Bell & Gossett pumps driven by the FC-102 HVAC drive can use the drive's embedded BACnet MS/TP over its RS-485 port. The embedded map covers drive I/O terminals, run/stop and reference commands, setpoints and bus feedback values, drive and motor readings, PID tuning, and bypass (ECB) status. It is shorter than the MCA 109 option map and does not include the individual warning and alarm bits.

This page lists 125 BACnet objects for the Bell & Gossett FC-102 Embedded BACnet (pump drive) — 62 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Bell & Gossett’s own free documentation, linked below.

Manufacturer
Bell & Gossett
Model
FC-102 Embedded BACnet (pump drive)
Equipment
Pump variable frequency drive
Equipment type
VFDs & pumps
BACnet objects
125 (62 writable)
Transport
BACnet MS/TP
Firmware
3.90 and above
Also known as
FC-102, FC102, VLT HVAC Drive FC 102
Source document
BacNET Points Firmware 3.90 and above (MCA109 FC-102 Advanced BACnet Option / FC-102 Embedded BACnet) · BGBACNET · rev. December 2019
Download CSV 125 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Bell & Gossett FC-102 Embedded BACnet (pump drive)

Integration in brief

The embedded FC-102 list gives run/stop, reference select and fault reset commands, writable setpoints and bus feedback values, and read-only drive data. A typical integration writes BV 1 and a setpoint, then reads run/fault status, speed, power and fault codes.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 1RUN/STOP CommandStart/stop the drive from the BMSWrite
AV 1Input Reference 1Speed reference from the BMS (open-loop control)Write
AV 30Setpoint 1Process setpoint 1 (when the drive runs its own PID)Write
BV 3Fault Reset CommandReset a tripped driveWrite
BV 4RUN/STOP MonitorRunning statusRead
BV 32Bus ControlDrive is under bus controlRead
AV 3Output SpeedActual drive output speedRead
AV 6PowerDrive output powerRead
BV 5OK/FAULT MonitorAny active drive faultRead
AV 51Fault CodeActive fault code numberRead

Enable & remote start

BV 1 RUN/STOP Command starts and stops the drive and BV 2 selects reference 1 or 2; BV 32 shows whether the drive is under bus control. The point list does not explain how bus control is set up on the drive.

Sensors & values from the BMS

AV 31, AV 36 and AV 41 Bus Feedback 1-3 and AV 1/AV 2 Input Reference are writable; the point list does not describe how the drive uses them.

Network setup

Watch out for

Bell & Gossett FC-102 Embedded BACnet (pump drive) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

125 of 125 shown
Type
Multi-state
Access
Show
Bell & Gossett FC-102 Embedded BACnet (pump drive) BACnet Points List
DescriptionStates
AI0Analog Input 53Drive analog input terminal 53 valueRead
AI1Analog Input 54Drive analog input terminal 54 valueRead
AI2Analog Input X30/11Drive analog input terminal X30/11 valueRead
AI3Analog Input X30/12Drive analog input terminal X30/12 valueRead
AI4Analog Input X42/1Drive analog input terminal X42/1 valueRead
AI5Analog Input X42/3Drive analog input terminal X42/3 valueRead
AI6Analog Input X42/5Drive analog input terminal X42/5 valueRead
AO0Terminal 42 Output Bus ControlAnalog or pulse output written over the busWrite
AO1Pulse out #27 Bus ControlAnalog or pulse output written over the busWrite
AO2Pulse out #29 Bus ControlAnalog or pulse output written over the busWrite
AO3Analogue Out X30/8 [mA]Analog or pulse output written over the busWrite
AO4Analogue Out X42/7 [V]Analog or pulse output written over the busWrite
AO5Analogue Out X42/9 [V]Analog or pulse output written over the busWrite
AO6Analogue Out X42/11 [V]Analog or pulse output written over the busWrite
AVmin1Input Reference 1Speed / process reference from the busWrite
AV2Input Reference 2Speed / process reference from the busWrite
AVmin3Output SpeedOutput speedRead
AV4PID FeedbackPID feedback valueRead
AV5Motor CurrentMotor currentRead
AVmin6PowerDrive output powerRead
AV15Motor ThermalMotor thermal loadRead
AV21Operating HoursDrive powered-on hoursRead
AV22Running HoursMotor running hoursRead
AV23kWh CounterEnergy counterRead
AV24Motor VoltageMotor voltageRead
AV25FrequencyOutput frequencyRead
AV26TorqueMotor torqueRead
AV27DC Link VoltageDC link voltageRead
AV28Heatsink Temp.Drive heatsink temperatureRead
AV29Inverter ThermalInverter thermal loadRead
AVmin30Setpoint 1Process setpoint 1Write
AV31Bus Feedback 1Feedback value 1 written by the BASWrite
AV35Setpoint 2Process setpoint 2Write
AV36Bus Feedback 2Feedback value 2 written by the BASWrite
AV40Setpoint 3Process setpoint 3Write
AV41Bus Feedback 3Feedback value 3 written by the BASWrite
AV45Running BypassRunning in bypassRead
AV50Last AlarmMost recent alarm codeRead
AVmin51Fault CodeActive fault codeRead
AV52PID Start SpeedProcess PID: Start SpeedWrite
AV53On Reference BandwidthOn-reference bandwidthWrite
AV54PID Proportional GainProcess PID: Proportional GainWrite
AV55PID Integral TimeProcess PID: Integral TimeWrite
AV56PID Differentiation TimeProcess PID: Differentiation TimeWrite
AV57PID Diff. Gain LimitProcess PID: Diff. Gain LimitWrite
AV58Sensorless ReadoutSensorless pump flow/pressure readoutRead
BI0Digital input Term 33Drive digital input stateRead
BI1Digital input Term 32Drive digital input stateRead
BI2Digital input Term 29Drive digital input stateRead
BI3Digital input Term 27Drive digital input stateRead
BI4Digital input Term 19Drive digital input stateRead
BI5Digital input Term 18Drive digital input stateRead
BI6Digital input Term 37Drive digital input stateRead
BI7Digital Input X30/2Drive digital input stateRead
BI8Digital Input X30/3Drive digital input stateRead
BI9Digital Input X30/4Drive digital input stateRead
BI10Digital input P1660/10Drive digital input stateRead
BI11Digital input P1660/11Drive digital input stateRead
BI12Digital input P1660/12Drive digital input stateRead
BI13Digital input P1660/13Drive digital input stateRead
BI14Digital input P1660/14Drive digital input stateRead
BI15Digital input P1660/15Drive digital input stateRead
BO0Digital Output Term 27Digital or relay output written over the busWrite
BO1Digital Output Term 29Digital or relay output written over the busWrite
BO2GPIO Output Term X30/6Digital or relay output written over the busWrite
BO3GPIO Output Term X30/7Digital or relay output written over the busWrite
BO4Relay 1Digital or relay output written over the busWrite
BO5Relay 2Digital or relay output written over the busWrite
BO6Option B Relay 1 OutputDigital or relay output written over the busWrite
BO7Option B Relay 2 OutputDigital or relay output written over the busWrite
BO8Option B Relay 3 OutputDigital or relay output written over the busWrite
BO9Reserved output P590/09Reserved digital output (parameter 5-90 bit)Write
BO10Reserved output P590/10Reserved digital output (parameter 5-90 bit)Write
BO11Reserved output P590/11Reserved digital output (parameter 5-90 bit)Write
BO12Reserved output P590/12Reserved digital output (parameter 5-90 bit)Write
BO13Reserved output P590/13Reserved digital output (parameter 5-90 bit)Write
BO14Reserved output P590/14Reserved digital output (parameter 5-90 bit)Write
BO15Reserved output P590/15Reserved digital output (parameter 5-90 bit)Write
BO16Option C Relay 1 OutputDigital or relay output written over the busWrite
BO17Option C Relay 2 OutputDigital or relay output written over the busWrite
BO18Option C Relay 3 OutputDigital or relay output written over the busWrite
BO19Option C Relay 4 OutputDigital or relay output written over the busWrite
BO20Option C Relay 5 OutputDigital or relay output written over the busWrite
BO21Option C Relay 6 OutputDigital or relay output written over the busWrite
BO22Option C Relay 7 OutputDigital or relay output written over the busWrite
BO23Option C Relay 8 OutputDigital or relay output written over the busWrite
BO24Reserved output P590/24Reserved digital output (parameter 5-90 bit)Write
BO25Reserved output P590/25Reserved digital output (parameter 5-90 bit)Write
BO26Reserved output P590/26Reserved digital output (parameter 5-90 bit)Write
BO27Reserved output P590/27Reserved digital output (parameter 5-90 bit)Write
BO28Reserved output P590/28Reserved digital output (parameter 5-90 bit)Write
BO29Reserved output P590/29Reserved digital output (parameter 5-90 bit)Write
BO30Reserved output P590/30Reserved digital output (parameter 5-90 bit)Write
BVmin1RUN/STOP CommandRun / stop commandWrite
BV2REF 1/REF 2 SelectSelects reference 1 or 2Write
BVmin3Fault Reset CommandFault reset commandWrite
BVmin4RUN/STOP MonitorRun / stop statusRead
BVmin5OK/FAULT MonitorOK / fault statusRead
BV6HAND / AUTO ReferenceHand / auto reference statusRead
BV21WarningDrive warning activeRead
BV22TripDrive trippedRead
BV23TriplockDrive trip-lockedRead
BV24CoastingCoast stop commandWrite
BV25CW/CCWRotation direction commandWrite
BV26JogJog commandWrite
BV27ResetReset commandWrite
BV28Reset KWh CounterReset commandWrite
BV29Reset Running Hours CounterReset commandWrite
BV30ReverseRunning in reverseRead
BV31Speed = referenceSpeed equals referenceRead
BVmin32Bus ControlDrive under bus controlRead
BV33RunningMotor runningRead
BV34Ramp 1/Ramp 2Ramp 1 or 2 in useRead
BV35ECB Test ModeElectronically controlled bypass: Test ModeRead
BV36ECB DrivemodeElectronically controlled bypass: DrivemodeRead
BV37ECB Aut. Bypass EnableElectronically controlled bypass: Aut. Bypass EnableRead
BV38ECB Bypass ModeElectronically controlled bypass: Bypass ModeRead
BV40ECB StateElectronically controlled bypass: StateRead
BV41ECB Overload TripElectronically controlled bypass: Overload TripRead
BV42M2 FaultBypass motor M2 faultRead
BV43M3 FaultBypass motor M3 faultRead
BV44ECB External InterlockElectronically controlled bypass: External InterlockRead
BV45ECB Manual OverrideElectronically controlled bypass: Manual OverrideRead
MO0Smart Logic Controller StateSmart logic controller stateRead
MO1Active SetupActive parameter setupWrite

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the FC-102 Embedded BACnet (pump drive) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Bell & Gossett FC-102 Embedded BACnet (pump drive)

How many BACnet points does the Bell & Gossett FC-102 Embedded BACnet (pump drive) have?

This list has 125 BACnet objects: 7 analog inputs, 7 analog outputs, 32 analog values, 16 binary inputs, 31 binary outputs, 30 binary values, 2 multi-state outputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Bell & Gossett FC-102 Embedded BACnet (pump drive) BACnet points are writable?

62 of the 125 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Bell & Gossett FC-102 Embedded BACnet (pump drive) BACnet documentation?

The source is BacNET Points Firmware 3.90 and above (MCA109 FC-102 Advanced BACnet Option / FC-102 Embedded BACnet) (BGBACNET), revision December 2019, published free by Bell & Gossett at https://prod.xylem.com/siteassets/brand/bell-amp-gossett/resources/manual/bgbacnet.pdf.

What are the minimum BACnet points to integrate the Bell & Gossett FC-102 Embedded BACnet (pump drive)?

Start with BV 1 RUN/STOP Command (Start/stop the drive from the BMS); AV 1 Input Reference 1 (Speed reference from the BMS (open-loop control)); AV 30 Setpoint 1 (Process setpoint 1 (when the drive runs its own PID)); BV 3 Fault Reset Command (Reset a tripped drive); BV 4 RUN/STOP Monitor (Running status); BV 32 Bus Control (Drive is under bus control); AV 3 Output Speed (Actual drive output speed); AV 6 Power (Drive output power); BV 5 OK/FAULT Monitor (Any active drive fault); AV 51 Fault Code (Active fault code number).

How do I enable BMS control of the Bell & Gossett FC-102 Embedded BACnet (pump drive)?

BV 1 RUN/STOP Command starts and stops the drive and BV 2 selects reference 1 or 2; BV 32 shows whether the drive is under bus control. The point list does not explain how bus control is set up on the drive.

Can the BMS supply sensor values to the Bell & Gossett FC-102 Embedded BACnet (pump drive)?

AV 31, AV 36 and AV 41 Bus Feedback 1-3 and AV 1/AV 2 Input Reference are writable; the point list does not describe how the drive uses them.

How do I check these points on the real FC-102 Embedded BACnet (pump drive)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Bell & Gossett BACnet points lists

Source: BacNET Points Firmware 3.90 and above (MCA109 FC-102 Advanced BACnet Option / FC-102 Embedded BACnet) · BGBACNET · rev. December 2019. Object names, instances and units are reproduced as published; descriptions are our own.