Constant speed pump system controller · BACnet points list

Bell & Gossett Technologic Constant Speed Pump Controller BACnet points list

Updated 28 October 2026

Short answer

The Technologic Constant Speed Pump Controller runs a multi-pump constant speed system and has a BACnet MS/TP interface on RS-485 (B-ASC profile). Its PICS lists 60 objects: pump state codes and process readings as analog inputs, six process commands as analog outputs, failure flags as binary inputs, and start/stop, reset and alternation as binary outputs. Which process readings and commands are used depends on how the controller is set up.

This page lists 60 BACnet objects for the Bell & Gossett Technologic Constant Speed Pump Controller — 9 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Bell & Gossett’s own free documentation, linked below.

Manufacturer
Bell & Gossett
Model
Technologic Constant Speed Pump Controller
Equipment
Constant speed pump system controller
Equipment type
VFDs & pumps
BACnet objects
60 (9 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Also known as
Technologic CS, Technologic constant speed, B&G Technologic, ITT Technologic
Source document
BACnet Protocol Implementation Conformance Statement - Technologic Constant Speed Pump Controller · Technologic Constant Speed Controller MSTP PIC Ver 2.2 · rev. September 20, 2011
Download CSV 60 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Bell & Gossett Technologic Constant Speed Pump Controller

Integration in brief

Write BO 1 to start or stop the system and, if the BMS supplies the setpoint, the AO command that matches the controlled variable. Read BI 1 and BI 2 for run and auto/manual status, the pump state codes and the process readings, and use BI 3 General Alarm with BO 2 to see and reset failures.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BO 1System Start/StopSystem start/stop command (1 = start)Write
AO 2Sys/Sup Press CmdSystem/supply pressure command, 0-65535Write
BO 2System ResetReset/silence on a 0-to-1 changeWrite
BI 1Sys Strt/Stp StatSystem start/stop status (1 = start)Read
BI 2Sys Auto/Man StatAuto/manual status (1 = Auto)Read
AI 1Pump1 StatePump 1 state: 0 disabled, 1 run, 2 ready, 3 failedRead
AI 8Sys/Sup PressSystem/supply pressure, PSIRead
BI 3General AlarmAny active failureRead
BI 4Reset RequiredFailure needs a resetRead

Enable & remote start

BO 1 System Start/Stop starts (1) and stops (0) the system; BI 1 and BI 2 show start/stop and auto/manual status. The PICS does not say what controller setting is needed for BACnet commands to take effect.

Network setup

Watch out for

Bell & Gossett Technologic Constant Speed Pump Controller BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

60 of 60 shown
Type
Access
Show
Bell & Gossett Technologic Constant Speed Pump Controller BACnet Points List
DescriptionStates
AImin1Pump1 StatePump 1 state codeRead0=Disabled, 1=Run, 2=Ready, 3=Failed
AI2Pump2 StatePump 2 state codeRead0=Disabled, 1=Run, 2=Ready, 3=Failed
AI3Pump3 StatePump 3 state codeRead0=Disabled, 1=Run, 2=Ready, 3=Failed
AI4Pump4 StatePump 4 state codeRead0=Disabled, 1=Run, 2=Ready, 3=Failed
AI5Pump5 StatePump 5 state codeRead0=Disabled, 1=Run, 2=Ready, 3=Failed
AI6Pump6 StatePump 6 state codeRead0=Disabled, 1=Run, 2=Ready, 3=Failed
AI7Suc/Ret PressSuction / return pressurePSIRead
AImin8Sys/Sup PressSystem / supply pressurePSIRead
AI9FlowFlowGPMRead
AI10TemperatureProcess temperature°FRead
AI11PressureProcess pressurePSIRead
AI12Diff TempDifferential temperature°FRead
AI13Suc/Ret TempSuction / return temperature°FRead
AI14Sys/Sup TempSystem / supply temperature°FRead
AI15AmpsMotor current, ampsRead
AI16HorsepowerMotor horsepowerRead
AO1Suc/Ret Press CmdSuction / return pressure command, 0-65535PSIWrite
AOmin2Sys/Sup Press CmdSystem / supply pressure command, 0-65535PSIWrite
AO3Flow CommandFlow command, 0-65535PSIWrite
AO4Temp CommandTemperature command, 0-65535PSIWrite
AO5Pressure CommandPressure command, 0-65535PSIWrite
AO6Diff Temp CommandDifferential temperature command, 0-65535PSIWrite
BImin1Sys Strt/Stp StatSystem start/stop statusRead0=Stop, 1=Start
BImin2Sys Auto/Man StatSystem auto/manual statusRead0=Manual, 1=Auto
BImin3General AlarmAny active failureRead0=O.K., 1=Failure
BImin4Reset RequiredA reset is needed to clear a failureRead0=O.K., 1=Reset is Required
BI5AI 1 FailAnalog input 1 failureRead0=O.K., 1=Failure
BI6AI 2 FailAnalog input 2 failureRead0=O.K., 1=Failure
BI7AI 3 FailAnalog input 3 failureRead0=O.K., 1=Failure
BI8AI 4 FailAnalog input 4 failureRead0=O.K., 1=Failure
BI9RTD 1 FailRTD input 1 failureRead0=O.K., 1=Failure
BI10RTD 2 FailRTD input 2 failureRead0=O.K., 1=Failure
BI11Battery FailController battery failureRead0=O.K., 1=Failure
BI12Low Suction AILow suction alarm from the analog inputRead0=O.K., 1=Failure
BI13Low Suction SwLow suction alarm from the switchRead0=O.K., 1=Failure
BI14High SuctionHigh suction alarmRead0=O.K., 1=Failure
BI15Low SystemLow system alarmRead0=O.K., 1=Failure
BI16High SystemHigh system alarmRead0=O.K., 1=Failure
BI17NFSD DTNo-flow shutdown (NFSD DT)Read0=O.K., 1=Failure
BI18NFSD FSNo-flow shutdown (NFSD FS)Read0=O.K., 1=Failure
BI19Low LevelLow level alarmRead0=O.K., 1=Failure
BI20High TempHigh temperature alarmRead0=O.K., 1=Failure
BI21Pump1 DP FailPump 1 differential pressure failureRead0=O.K., 1=Failure
BI22Pump2 DP FailPump 2 differential pressure failureRead0=O.K., 1=Failure
BI23Pump3 DP FailPump 3 differential pressure failureRead0=O.K., 1=Failure
BI24Pump4 DP FailPump 4 differential pressure failureRead0=O.K., 1=Failure
BI25Pump5 DP FailPump 5 differential pressure failureRead0=O.K., 1=Failure
BI26Pump6 DP FailPump 6 differential pressure failureRead0=O.K., 1=Failure
BI27Pump1 OL FailPump 1 overload failureRead0=O.K., 1=Failure
BI28Pump2 OL FailPump 2 overload failureRead0=O.K., 1=Failure
BI29Pump3 OL FailPump 3 overload failureRead0=O.K., 1=Failure
BI30Pump4 OL FailPump 4 overload failureRead0=O.K., 1=Failure
BI31Pump5 OL FailPump 5 overload failureRead0=O.K., 1=Failure
BI32Pump6 OL FailPump 6 overload failureRead0=O.K., 1=Failure
BI33CAN FailCAN bus failureRead0=O.K., 1=Failure
BI34Voltage TolSupply voltage out of toleranceRead0=O.K., 1=Failure
BI35Voltage FailSupply voltage failureRead0=O.K., 1=Failure
BOmin1System Start/StopSystem start/stop commandWrite0=Stop, 1=Start
BOmin2System ResetReset / silence on a positive edgeWrite
BO3Pump AlternationAlternate the lead pump on a positive edgeWrite

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Technologic Constant Speed Pump Controller and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Bell & Gossett Technologic Constant Speed Pump Controller

How many BACnet points does the Bell & Gossett Technologic Constant Speed Pump Controller have?

This list has 60 BACnet objects: 16 analog inputs, 6 analog outputs, 35 binary inputs, 3 binary outputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Bell & Gossett Technologic Constant Speed Pump Controller BACnet points are writable?

9 of the 60 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Bell & Gossett Technologic Constant Speed Pump Controller BACnet documentation?

The source is BACnet Protocol Implementation Conformance Statement - Technologic Constant Speed Pump Controller (Technologic Constant Speed Controller MSTP PIC Ver 2.2), revision September 20, 2011, published free by Bell & Gossett at https://www.bacnetinternational.net/catalog/manu/xylem/Technologic%20Constant%20Speed%20Controller%20BACnet%20MSTP%20Pic.pdf.

What are the minimum BACnet points to integrate the Bell & Gossett Technologic Constant Speed Pump Controller?

Start with BO 1 System Start/Stop (System start/stop command (1 = start)); AO 2 Sys/Sup Press Cmd (System/supply pressure command, 0-65535); BO 2 System Reset (Reset/silence on a 0-to-1 change); BI 1 Sys Strt/Stp Stat (System start/stop status (1 = start)); BI 2 Sys Auto/Man Stat (Auto/manual status (1 = Auto)); AI 1 Pump1 State (Pump 1 state: 0 disabled, 1 run, 2 ready, 3 failed); AI 8 Sys/Sup Press (System/supply pressure, PSI); BI 3 General Alarm (Any active failure); BI 4 Reset Required (Failure needs a reset).

How do I enable BMS control of the Bell & Gossett Technologic Constant Speed Pump Controller?

BO 1 System Start/Stop starts (1) and stops (0) the system; BI 1 and BI 2 show start/stop and auto/manual status. The PICS does not say what controller setting is needed for BACnet commands to take effect.

How do I check these points on the real Technologic Constant Speed Pump Controller?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Bell & Gossett BACnet points lists

Source: BACnet Protocol Implementation Conformance Statement - Technologic Constant Speed Pump Controller · Technologic Constant Speed Controller MSTP PIC Ver 2.2 · rev. September 20, 2011. Object names, instances and units are reproduced as published; descriptions are our own.