Pump variable frequency drive BACnet option card · BACnet points list

Bell & Gossett MCA 109 Advanced BACnet Option (FC-102) BACnet points list

Updated 28 October 2026

Short answer

The MCA 109 option card adds a fuller BACnet MS/TP interface to the FC-102 drive used on Bell & Gossett pumps. Besides drive I/O, commands and readings, it exposes three extended PID controllers and individual binary values for every drive warning and alarm, which makes fault reporting to the BAS much more detailed than the embedded interface.

This page lists 297 BACnet objects for the Bell & Gossett MCA 109 Advanced BACnet Option (FC-102) — 81 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Bell & Gossett’s own free documentation, linked below.

Manufacturer
Bell & Gossett
Model
MCA 109 Advanced BACnet Option (FC-102)
Equipment
Pump variable frequency drive BACnet option card
Equipment type
VFDs & pumps
BACnet objects
297 (81 writable)
Transport
BACnet MS/TP
Firmware
3.90 and above
Also known as
MCA109, MCA 109, FC-102 BACnet option, VLT BACnet option
Source document
BacNET Points Firmware 3.90 and above (MCA109 FC-102 Advanced BACnet Option / FC-102 Embedded BACnet) · BGBACNET · rev. December 2019
Download CSV 297 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Bell & Gossett MCA 109 Advanced BACnet Option (FC-102)

Integration in brief

The MCA 109 option card list gives start, coast, direction, jog and reset commands, references and setpoints, three extended PID controllers, and one binary value per drive warning and alarm. A typical integration writes BV 1 and a reference or setpoint, then reads status, speed, power and the warning/alarm bits it cares about.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 1StartStart/stop the drive from the BMSWrite
AV 0ReferenceSpeed reference from the BMS (open-loop control)Write
AV 46Setpoint 1Process setpoint 1 (when the drive runs its own PID)Write
BV 5ResetReset a tripped driveWrite
BV 10Drive ReadyReady to run when given a startRead
BV 16Motor runningRunning statusRead
BV 13Bus controlDrive is under bus controlRead
AV 50FrequencyOutput frequencyRead
AV 15Power [KW]Drive output powerRead
BV 14TripAny active drive faultRead

Enable & remote start

BV 1 Start, BV 2 Coasting, BV 3 CW/CCW and BV 4 Jog are writable commands, and BV 13 shows whether the drive is under bus control. The point list does not explain how bus control is set up on the drive.

Sensors & values from the BMS

AV 2-4 Bus Feedback1-3 and the Ext. 1-3 setpoint/feedback values are writable; the point list does not describe how the drive uses them.

Network setup

Watch out for

Bell & Gossett MCA 109 Advanced BACnet Option (FC-102) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

297 of 297 shown
Type
Multi-state
Access
Show
Bell & Gossett MCA 109 Advanced BACnet Option (FC-102) BACnet Points List
DescriptionStates
AI0Analog Input 53Drive analog input terminal 53 valueRead
AI1Analog Input 54Drive analog input terminal 54 valueRead
AI2Analog Input X30/11Drive analog input terminal X30/11 valueRead
AI3Analog Input X30/12Drive analog input terminal X30/12 valueRead
AI4Analog Input X42/1Drive analog input terminal X42/1 valueRead
AI5Analog Input X42/3Drive analog input terminal X42/3 valueRead
AI6Analog Input X42/5Drive analog input terminal X42/5 valueRead
AO0Terminal 42 Output Bus ControlAnalog or pulse output written over the busWrite
AO1Pulse out #27 Bus ControlAnalog or pulse output written over the busWrite
AO2Pulse out #29 Bus ControlAnalog or pulse output written over the busWrite
AO3Analogue Out X30/8 [mA]Analog or pulse output written over the busWrite
AO4Analogue Out X42/7 [V]Analog or pulse output written over the busWrite
AO5Analogue Out X42/9 [V]Analog or pulse output written over the busWrite
AO6Analogue Out X42/11 [V]Analog or pulse output written over the busWrite
AVmin0ReferenceSpeed / process reference from the busWrite
AV1Speed Act ValueActual speed valueWrite
AV2Bus Feedback1Feedback value 1 written by the BASWrite
AV3Bus Feedback2Feedback value 2 written by the BASWrite
AV4Bus Feedback3Feedback value 3 written by the BASWrite
AV5Motor VoltageMotor voltageRead
AV6Motor CurrentMotor currentRead
AV7Torque [%]Motor torque in percentRead
AV8DC Link VoltageDC link voltageRead
AV9Motor ThermalMotor thermal loadRead
AV10Heatsink Temp.Drive heatsink temperatureRead
AV11Inverter ThermalInverter thermal loadRead
AV12Operating HoursDrive powered-on hoursRead
AV13Running HoursMotor running hoursRead
AV14KWh CounterEnergy counterRead
AVmin15Power [KW]Drive output powerRead
AV16PID Start Speed [Hz]Process PID: Start Speed [Hz]Write
AV17PID Proportional GainProcess PID: Proportional GainWrite
AV18PID Integral TimeProcess PID: Integral TimeWrite
AV19PID Differential TimeProcess PID: Differential TimeWrite
AV20PID Dif. Gain LimitProcess PID: Dif. Gain LimitWrite
AV21On Reference BandwithOn-reference bandwidthWrite
AV22Ext. 1 SetpointExtended PID controller 1: SetpointWrite
AV23Ext. 1 Reference [Unit]Extended PID controller 1: Reference [Unit]Write
AV24Ext. 1 Feedback [Unit]Extended PID controller 1: Feedback [Unit]Write
AV25Ext. 1 Propotional GainExtended PID controller 1: Propotional GainWrite
AV27Ext. 1 Integral TimeExtended PID controller 1: Integral TimeWrite
AV28Ext. 1 Differential TimeExtended PID controller 1: Differential TimeWrite
AV29Ext. 1 Dif. Gain LimitExtended PID controller 1: Dif. Gain LimitWrite
AV31Ext. 2 SetpointExtended PID controller 2: SetpointWrite
AV32Ext. 2 reference [Unit]Extended PID controller 2: reference [Unit]Write
AV33Ext. 2 Feedback [Unit]Extended PID controller 2: Feedback [Unit]Write
AV34Ext. 2 Proportional GainExtended PID controller 2: Proportional GainWrite
AV35Ext. 2 Integral TimeExtended PID controller 2: Integral TimeWrite
AV36Ext. 2 Differential TimeExtended PID controller 2: Differential TimeWrite
AV37Ext. 2 Dif. GainExtended PID controller 2: Dif. GainWrite
AV38Ext. 3 SetpointExtended PID controller 3: SetpointWrite
AV39Ext. 3 Reference [Unit]Extended PID controller 3: Reference [Unit]Write
AV40Ext. 3 Feedback [Unit]Extended PID controller 3: Feedback [Unit]Write
AV41Ext. 3 Proportional GainExtended PID controller 3: Proportional GainWrite
AV42Ext. 3 Integral TimeExtended PID controller 3: Integral TimeWrite
AV43Ext. 3 Differential TimeExtended PID controller 3: Differential TimeWrite
AV44Ext. 3 Dif. Gain LimitExtended PID controller 3: Dif. Gain LimitWrite
AV45Running BypassRunning in bypassRead
AVmin46Setpoint 1Process setpoint 1Write
AV47Setpoint 2Process setpoint 2Write
AV48Setpoint 3Process setpoint 3Write
AVmin50FrequencyOutput frequencyRead
AV51Feedback [Unit]Process feedbackRead
AV58Sensorless ReadoutSensorless pump flow/pressure readoutRead
BI0Digital input 33Drive digital input stateRead
BI1Digital input 32Drive digital input stateRead
BI2Digital input 29Drive digital input stateRead
BI3Digital input 27Drive digital input stateRead
BI4Digital input 19Drive digital input stateRead
BI5Digital input 18Drive digital input stateRead
BI6Digital input 37Drive digital input stateRead
BI7Digital Input X30/2Drive digital input stateRead
BI8Digital Input X30/3Drive digital input stateRead
BI9Digital Input X30/4Drive digital input stateRead
BI10Digital input P1660/10Drive digital input stateRead
BI11Digital input P1660/11Drive digital input stateRead
BI12Digital input P1660/12Drive digital input stateRead
BI13Digital input P1660/13Drive digital input stateRead
BI14Digital input P1660/14Drive digital input stateRead
BI15Digital input P1660/15Drive digital input stateRead
BO0Digital output 27Digital or relay output written over the busWrite
BO1Digital output 29Digital or relay output written over the busWrite
BO2GPIO Output Term X30/6Digital or relay output written over the busWrite
BO3GPIO Output Term X30/7Digital or relay output written over the busWrite
BO4Relay 1 outputDigital or relay output written over the busWrite
BO5Relay 2 outputDigital or relay output written over the busWrite
BO6Option B Relay 1 OutputDigital or relay output written over the busWrite
BO7Option B Relay 2 OutputDigital or relay output written over the busWrite
BO8Option B Relay 3 OutputDigital or relay output written over the busWrite
BO9Reserved output P590/09Reserved digital output (parameter 5-90 bit)Write
BO10Reserved output P590/10Reserved digital output (parameter 5-90 bit)Write
BO11Reserved output P590/11Reserved digital output (parameter 5-90 bit)Write
BO12Reserved output P590/12Reserved digital output (parameter 5-90 bit)Write
BO13Reserved output P590/13Reserved digital output (parameter 5-90 bit)Write
BO14Reserved output P590/14Reserved digital output (parameter 5-90 bit)Write
BO15Reserved output P590/15Reserved digital output (parameter 5-90 bit)Write
BO16Option C Relay 1 OutputDigital or relay output written over the busWrite
BO17Option C Relay 2 OutputDigital or relay output written over the busWrite
BO18Option C Relay 3 OutputDigital or relay output written over the busWrite
BO19Option C Relay 4 OutputDigital or relay output written over the busWrite
BO20Option C Relay 5 OutputDigital or relay output written over the busWrite
BO21Option C Relay 6 OutputDigital or relay output written over the busWrite
BO22Option C Relay 7 OutputDigital or relay output written over the busWrite
BO23Option C Relay 8 OutputDigital or relay output written over the busWrite
BO24Reserved output P590/24Reserved digital output (parameter 5-90 bit)Write
BO25Reserved output P590/25Reserved digital output (parameter 5-90 bit)Write
BO26Reserved output P590/26Reserved digital output (parameter 5-90 bit)Write
BO27Reserved output P590/27Reserved digital output (parameter 5-90 bit)Write
BO28Reserved output P590/28Reserved digital output (parameter 5-90 bit)Write
BO29Reserved output P590/29Reserved digital output (parameter 5-90 bit)Write
BO30Reserved output P590/30Reserved digital output (parameter 5-90 bit)Write
BV0Com. FaultCommunication faultRead
BVmin1StartStart commandWrite
BV2CoastingCoast stop commandWrite
BV3CW/CCWRotation direction commandWrite
BV4JogJog commandWrite
BVmin5ResetReset commandWrite
BV6Reset KwH CounterReset commandWrite
BV7Reset Running Hour CounterReset commandWrite
BVmin10Drive ReadyDrive readyRead
BV12Speed = referenceSpeed equals referenceRead
BVmin13Bus controlDrive under bus controlRead
BVmin14TripDrive trippedRead
BV15Trip LockDrive trip-lockedRead
BVmin16Motor runningMotor runningRead
BV17WarningDrive warning activeRead
BV21ECB Test ModeElectronically controlled bypass: Test ModeRead
BV22ECB DrivemodeElectronically controlled bypass: DrivemodeRead
BV23ECB Aut. Bypass EnableElectronically controlled bypass: Aut. Bypass EnableRead
BV24ECB Bypass ModeElectronically controlled bypass: Bypass ModeRead
BV25ECB StateElectronically controlled bypass: StateRead
BV26ECB Overload TripElectronically controlled bypass: Overload TripRead
BV27M2 FaultBypass motor M2 faultRead
BV28M3 FaultBypass motor M3 faultRead
BV29ECB External InterlockElectronically controlled bypass: External InterlockRead
BV30ECB Manual OverrideElectronically controlled bypass: Manual OverrideRead
BV40A: Brake checkDrive alarm flag: Brake checkRead
BV41A: Pwr. Card TempDrive alarm flag: Pwr. Card TempRead
BV42A: Earth FaultDrive alarm flag: Earth FaultRead
BV43A: Ctrl.Card TempDrive alarm flag: Ctrl.Card TempRead
BV44A: Ctrl. Word TODrive alarm flag: Ctrl. Word TORead
BV45A: Over CurrentDrive alarm flag: Over CurrentRead
BV46A: Torque LimitDrive alarm flag: Torque LimitRead
BV47A: Motor TH OverDrive alarm flag: Motor TH OverRead
BV48A: Motor ETR OverDrive alarm flag: Motor ETR OverRead
BV49A: Inverter Overld.Drive alarm flag: Inverter Overld.Read
BV50A: DC under VoltDrive alarm flag: DC under VoltRead
BV51A: DC over VoltDrive alarm flag: DC over VoltRead
BV52A: Short CircuitDrive alarm flag: Short CircuitRead
BV53A: Inrush FaultDrive alarm flag: Inrush FaultRead
BV54A: Mains FaultDrive alarm flag: Mains FaultRead
BV55A: AMA Not OKDrive alarm flag: AMA Not OKRead
BV56A: Live Zero ErrorDrive alarm flag: Live Zero ErrorRead
BV57A: Internal FaultDrive alarm flag: Internal FaultRead
BV58A: Brake OverloadDrive alarm flag: Brake OverloadRead
BV59A: U Phase LossDrive alarm flag: U Phase LossRead
BV60A: V Phase LossDrive alarm flag: V Phase LossRead
BV61A: W Phase LossDrive alarm flag: W Phase LossRead
BV62A: Fieldbus FaultDrive alarm flag: Fieldbus FaultRead
BV63A: 24 V Supply LowDrive alarm flag: 24 V Supply LowRead
BV64A: Mains faultDrive alarm flag: Mains faultRead
BV65A: 1.8V supply lowDrive alarm flag: 1.8V supply lowRead
BV66A: Brake FailureDrive alarm flag: Brake FailureRead
BV67A: Brake IGBTDrive alarm flag: Brake IGBTRead
BV68A: Option ChangedDrive alarm flag: Option ChangedRead
BV69A: Drive InitialisedDrive alarm flag: Drive InitialisedRead
BV70A: Safe StopDrive alarm flag: Safe StopRead
BV71A: Alarm: Brake lowDrive alarm flag: Alarm: Brake lowRead
BV72A: Service trip 1691/0Drive alarm flag: Service trip 1691/0Read
BV73A: Service trip 1691/1Drive alarm flag: Service trip 1691/1Read
BV74A: Service trip 1691/2Drive alarm flag: Service trip 1691/2Read
BV75A: Service trip 1691/3Drive alarm flag: Service trip 1691/3Read
BV76A: Service trip 1691/4Drive alarm flag: Service trip 1691/4Read
BV77A: No flowDrive alarm flag: No flowRead
BV78A: Dry PumpDrive alarm flag: Dry PumpRead
BV79A: Curve endDrive alarm flag: Curve endRead
BV80A: Broken BeltDrive alarm flag: Broken BeltRead
BV81A: Discharge HighDrive alarm flag: Discharge HighRead
BV82A: Start faultDrive alarm flag: Start faultRead
BV83A: Speed limitDrive alarm flag: Speed limitRead
BV84A: State fault 1691/12Drive alarm flag: State fault 1691/12Read
BV85A: State fault 1691/13Drive alarm flag: State fault 1691/13Read
BV86A: State fault 1691/14Drive alarm flag: State fault 1691/14Read
BV87A: State fault 1691/15Drive alarm flag: State fault 1691/15Read
BV88A: KTY Temparture errorDrive alarm flag: KTY Temparture errorRead
BV89A: Drive Fan errorDrive alarm flag: Drive Fan errorRead
BV90A: ECB errorDrive alarm flag: ECB errorRead
BV91A: Alarm 1691/19Drive alarm flag: Alarm 1691/19Read
BV92A: Alarm 1691/20Drive alarm flag: Alarm 1691/20Read
BV93A: Alarm 1691/21Drive alarm flag: Alarm 1691/21Read
BV94A: Alarm 1691/22Drive alarm flag: Alarm 1691/22Read
BV95A: Alarm 1691/23Drive alarm flag: Alarm 1691/23Read
BV96A: Alarm 1691/24Drive alarm flag: Alarm 1691/24Read
BV97A: Alarm 1691/25Drive alarm flag: Alarm 1691/25Read
BV98A: Alarm 1691/26Drive alarm flag: Alarm 1691/26Read
BV99A: Alarm P1691/27Drive alarm flag: Alarm P1691/27Read
BV100A: Alarm 1691/28Drive alarm flag: Alarm 1691/28Read
BV101A: Alarm 1691/29Drive alarm flag: Alarm 1691/29Read
BV102A: Alarm 1691/30Drive alarm flag: Alarm 1691/30Read
BV103A: Alarm 1691/31Drive alarm flag: Alarm 1691/31Read
BV104W: Brake CheckDrive warning flag: Brake CheckRead
BV105W: Pwr. Card TempDrive warning flag: Pwr. Card TempRead
BV106W: Earth FaultDrive warning flag: Earth FaultRead
BV107W: Ctrl. Card TempDrive warning flag: Ctrl. Card TempRead
BV108W: Crtl. Word TODrive warning flag: Crtl. Word TORead
BV109W: Over CurrentDrive warning flag: Over CurrentRead
BV110W: Torque LimitDrive warning flag: Torque LimitRead
BV111W: Motor Th OverDrive warning flag: Motor Th OverRead
BV112W: Motor ETR OverDrive warning flag: Motor ETR OverRead
BV113W: Inverter overld.Drive warning flag: Inverter overld.Read
BV114W: DC under VoltDrive warning flag: DC under VoltRead
BV115W: DC over VoltDrive warning flag: DC over VoltRead
BV116W: DC Voltage LowDrive warning flag: DC Voltage LowRead
BV117W: DC Voltage highDrive warning flag: DC Voltage highRead
BV118W: Mains Ph. LossDrive warning flag: Mains Ph. LossRead
BV119W: No MotorDrive warning flag: No MotorRead
BV120W: Live Zero ErrorDrive warning flag: Live Zero ErrorRead
BV121W: 10V lowDrive warning flag: 10V lowRead
BV122W: Brake OverloadDrive warning flag: Brake OverloadRead
BV123W: Brake ResistorDrive warning flag: Brake ResistorRead
BV124W: Brake IGBTDrive warning flag: Brake IGBTRead
BV125W: Speed LimitDrive warning flag: Speed LimitRead
BV126W: Fieldbus FaultDrive warning flag: Fieldbus FaultRead
BV127W: 24V Supply LowDrive warning flag: 24V Supply LowRead
BV128W: Mains FailureDrive warning flag: Mains FailureRead
BV129W: Current LimitDrive warning flag: Current LimitRead
BV130W: Low TempDrive warning flag: Low TempRead
BV131W: Voltage LimitDrive warning flag: Voltage LimitRead
BV132W: Encoder lossDrive warning flag: Encoder lossRead
BV133W: Output Freq. limitDrive warning flag: Output Freq. limitRead
BV134W: Safe stopDrive warning flag: Safe stopRead
BV135W: Ext. StatusDrive warning flag: Ext. StatusRead
BV136W: Start delayedDrive warning flag: Start delayedRead
BV137W: Stop delayedDrive warning flag: Stop delayedRead
BV138W: Clock failureDrive warning flag: Clock failureRead
BV139W: Fire mode was activeDrive warning flag: Fire mode was activeRead
BV140W: Reserved - P1693/04Drive warning flag: Reserved - P1693/04Read
BV141W: No FlowDrive warning flag: No FlowRead
BV142W: Dry PumpDrive warning flag: Dry PumpRead
BV143W: End of CurveDrive warning flag: End of CurveRead
BV144W: Belt BrokenDrive warning flag: Belt BrokenRead
BV145W: Discharge HighDrive warning flag: Discharge HighRead
BV146W: Reserved - P1693/10Drive warning flag: Reserved - P1693/10Read
BV147W: Reserved - P1693/11Drive warning flag: Reserved - P1693/11Read
BV148W: Reserved - P1693/12Drive warning flag: Reserved - P1693/12Read
BV149W: Reserved - P1693/13Drive warning flag: Reserved - P1693/13Read
BV150W: Reserved - P1693/14Drive warning flag: Reserved - P1693/14Read
BV151W: Reserved - P1693/15Drive warning flag: Reserved - P1693/15Read
BV152W: Reserved - P1693/16Drive warning flag: Reserved - P1693/16Read
BV153W: KTY TemperatureDrive warning flag: KTY TemperatureRead
BV154W: Drive Fan failureDrive warning flag: Drive Fan failureRead
BV155W: ECB failureDrive warning flag: ECB failureRead
BV156W: Reserved - P1693/20Drive warning flag: Reserved - P1693/20Read
BV157W: Reserved - P1693/21Drive warning flag: Reserved - P1693/21Read
BV158W: Reserved - P1693/22Drive warning flag: Reserved - P1693/22Read
BV159W: Reserved - P1693/23Drive warning flag: Reserved - P1693/23Read
BV160W: Reserved - P1693/24Drive warning flag: Reserved - P1693/24Read
BV161W: Reserved - P1693/25Drive warning flag: Reserved - P1693/25Read
BV162W: Reserved - P1693/26Drive warning flag: Reserved - P1693/26Read
BV163W: Reserved - P1693/27Drive warning flag: Reserved - P1693/27Read
BV164W: Reserved - P1693/28Drive warning flag: Reserved - P1693/28Read
BV165W: Reserved - P1693/29Drive warning flag: Reserved - P1693/29Read
BV166W: PTC TemperatureDrive warning flag: PTC TemperatureRead
BV167W: Reserved - P1693/31Drive warning flag: Reserved - P1693/31Read
BV168Ramping activeDrive status flagRead
BV169AMA RunningDrive status flagRead
BV170Start CW/CCWDrive status flagRead
BV171SlowdownDrive status flagRead
BV172Catch upDrive status flagRead
BV173Feedback HighDrive status flagRead
BV174Feedback LowDrive status flagRead
BV175Output Current HighDrive status flagRead
BV176Output Current LowDrive status flagRead
BV177Output Freq HighDrive status flagRead
BV178Output Freq lowDrive status flagRead
BV179Brake Check OKDrive status flagRead
BV180Brake MaxDrive status flagRead
BV181BrakingDrive status flagRead
BV182Out of Speed rangeDrive status flagRead
BV183OVC ActiveDrive status flagRead
BV184AC BrakeDrive status flagRead
BV185Password TimelockDrive status flagRead
BV186Password statusDrive status flagRead
BV187Reference highDrive status flagRead
BV188Reference lowDrive status flagRead
BV189Reference siteDrive status flagRead
BV190Reserved - P1694/22Reserved status bitRead
BV191Reserved - P1694/23Reserved status bitRead
BV192Reserved - P1694/24Reserved status bitRead
BV193Reserved - P1694/25Reserved status bitRead
BV194Reserved - P1694/26Reserved status bitRead
BV195Reserved - P1694/27Reserved status bitRead
BV196Reserved - P1694/28Reserved status bitRead
BV197Reserved - P1694/29Reserved status bitRead
BV198Reserved - P1694/30Reserved status bitRead
BV199Reserved - P1694/31Reserved status bitRead
MO0Setup commandSelects the active parameter setupWrite

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the MCA 109 Advanced BACnet Option (FC-102) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Bell & Gossett MCA 109 Advanced BACnet Option (FC-102)

How many BACnet points does the Bell & Gossett MCA 109 Advanced BACnet Option (FC-102) have?

This list has 297 BACnet objects: 7 analog inputs, 7 analog outputs, 50 analog values, 16 binary inputs, 31 binary outputs, 185 binary values, 1 multi-state output. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Bell & Gossett MCA 109 Advanced BACnet Option (FC-102) BACnet points are writable?

81 of the 297 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Bell & Gossett MCA 109 Advanced BACnet Option (FC-102) BACnet documentation?

The source is BacNET Points Firmware 3.90 and above (MCA109 FC-102 Advanced BACnet Option / FC-102 Embedded BACnet) (BGBACNET), revision December 2019, published free by Bell & Gossett at https://prod.xylem.com/siteassets/brand/bell-amp-gossett/resources/manual/bgbacnet.pdf.

What are the minimum BACnet points to integrate the Bell & Gossett MCA 109 Advanced BACnet Option (FC-102)?

Start with BV 1 Start (Start/stop the drive from the BMS); AV 0 Reference (Speed reference from the BMS (open-loop control)); AV 46 Setpoint 1 (Process setpoint 1 (when the drive runs its own PID)); BV 5 Reset (Reset a tripped drive); BV 10 Drive Ready (Ready to run when given a start); BV 16 Motor running (Running status); BV 13 Bus control (Drive is under bus control); AV 50 Frequency (Output frequency); AV 15 Power [KW] (Drive output power); BV 14 Trip (Any active drive fault).

How do I enable BMS control of the Bell & Gossett MCA 109 Advanced BACnet Option (FC-102)?

BV 1 Start, BV 2 Coasting, BV 3 CW/CCW and BV 4 Jog are writable commands, and BV 13 shows whether the drive is under bus control. The point list does not explain how bus control is set up on the drive.

Can the BMS supply sensor values to the Bell & Gossett MCA 109 Advanced BACnet Option (FC-102)?

AV 2-4 Bus Feedback1-3 and the Ext. 1-3 setpoint/feedback values are writable; the point list does not describe how the drive uses them.

How do I check these points on the real MCA 109 Advanced BACnet Option (FC-102)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Bell & Gossett BACnet points lists

Source: BacNET Points Firmware 3.90 and above (MCA109 FC-102 Advanced BACnet Option / FC-102 Embedded BACnet) · BGBACNET · rev. December 2019. Object names, instances and units are reproduced as published; descriptions are our own.