- APC InRow RC chilled water 300 mm (ACRC301S / ACRC301H) BACnet IP
In-row precision cooling unit (chilled water computer room air handler) · BACnet points list
APC InRow RC chilled water 300 mm (ACRC301S / ACRC301H) BACnet IP BACnet points list
Updated 12 November 2026
The InRow RC 300 mm chilled water units serve BACnet IP from their network management card. The map has Multi-state Values for on/standby, operating mode, airflow and delta-T setpoint selections and configuration, Binary Values for each alarm (active = alarm), Analog Values for temperatures, flows, demand, power, energy and run hours, and Character String Values for identity.
This page lists 164 BACnet objects for the APC InRow RC chilled water 300 mm (ACRC301S / ACRC301H) BACnet IP — 16 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from APC’s own free documentation, linked below.
- Manufacturer
- APC
- Model
- APC InRow RC chilled water 300 mm (ACRC301S / ACRC301H) BACnet IP
- Equipment
- In-row precision cooling unit (chilled water computer room air handler)
- Equipment type
- Rooftop units, AHUs & DOAS
- BACnet objects
- 164 (16 writable)
- Transport
- BACnet IP
- Firmware
- Application firmware v6.0.0 or later (v2.4.2.1 and later support BACnet IP only)
- Also known as
- ACRC301S, ACRC301H, ACRC3xx, InRow RC 300 mm, InRow CW, Schneider Electric InRow RC, TME27091
Reference only, provided as-is: verify against APC’s current documentation and the live device before use. Not official APC information. Terms of use.
BMS integration notes: APC InRow RC chilled water 300 mm (ACRC301S / ACRC301H) BACnet IP
Enable BACnet on the unit's Network Management Card 2 (see the NMC 2 user guide) and give it a unique device instance. Use MV 0 On or Standby to start and stop the unit and read MV 2 Operating Mode for its state. Map supply and return air temperatures, cool output, fan speed and the alarm Binary Values for monitoring; MV 25 clears active alarms.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| MV 0 | On or Standby | Unit on/standby command (1=Standby, 2=On) | Write |
| MV 25 | Clear Active Alarms | Write 2=Yes to clear active alarms | Write |
| MV 2 | Operating Mode | Standby, on, idle or maintenance | Read |
| AV 10 | Supply Air Temperature | Air leaving the unit | Read |
| AV 11 | Return Air Temperature | Air entering the unit | Read |
| AV 53 | Supply Air Setpoint | Supply air temperature setpoint | Read |
| AV 26 | Cool Output | Cooling delivered by the unit | Read |
| AV 28 | Fan Speed | Current fan speed | Read |
| BV 2 | BN3906 | Cool Fail alarm | Read |
| BV 22 | BN392E | Water Detected Fault alarm | Read |
Enable & remote start
MV 0 On or Standby (writable) switches the unit between standby and on.
Network setup
- BACnet IP only (application firmware v2.4.2.1 and later).
- The map refers to the Network Management Card 2 User Guide for configuring BACnet.
- The map lists one Notification Class object, NC 0 DefaultNotifier.
Watch out for
- The map does not print access or units for the Analog Values; check on the unit before writing setpoints such as AV 53 or AV 52.
- Many Multi-state Values are configuration settings (power source, filter type, configuration type); do not write them cyclically.
APC InRow RC chilled water 300 mm (ACRC301S / ACRC301H) BACnet IP BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AV | 0 | Startup Delay | Read | |||
| AV | 1 | Maximum Chilled Water Flow | Read | |||
| AV | 2 | Number of Rack Inlet Temperature Sensors in Unit | Read | |||
| AV | 3 | Number of Leak Detectors in Unit | Read | |||
| AV | 4 | Rack Inlet Temperature High Threshold | Read | |||
| AV | 5 | Supply Air Temperature High Threshold | Read | |||
| AV | 6 | Return Air Temperature High Threshold | Read | |||
| AV | 7 | Entering Chilled Water Temperature High Threshold | Read | |||
| AV | 8 | Air Filter Service Interval | Read | |||
| AV | 9 | Unit Service Alarm Interval | Read | |||
| AVmin | 10 | Supply Air Temperature | Read | |||
| AVmin | 11 | Return Air Temperature | Read | |||
| AV | 12 | Filter Differential Pressure | Read | |||
| AV | 13 | Entering Chilled Water Temperature | Read | |||
| AV | 14 | Leaving Chilled Water Temperature | Read | |||
| AV | 15 | Chilled Water Valve Position | Read | |||
| AV | 16 | Unit Rack Inlet Temperatures_1 | Read | |||
| AV | 17 | Unit Rack Inlet Temperatures_2 | Read | |||
| AV | 18 | Unit Rack Inlet Temperatures_3 | Read | |||
| AV | 19 | Unit Rack Inlet Temperatures_4 | Read | |||
| AV | 20 | Maximum Rack Inlet Temperature | Read | |||
| AV | 21 | Minimum Rack Inlet Temperature | Read | |||
| AV | 22 | Chilled Water Flow | Read | |||
| AV | 23 | Dew Point Temperature | Read | |||
| AV | 24 | Coil Chilled Water Temperature | Read | |||
| AV | 25 | Cool Demand | Read | |||
| AVmin | 26 | Cool Output | Read | |||
| AV | 27 | Airflow | Read | |||
| AVmin | 28 | Fan Speed | Read | |||
| AV | 29 | Unit Power | Read | |||
| AV | 30 | Unit Energy | Read | |||
| AV | 31 | Circulation Pump Speed | Read | |||
| AV | 32 | Group Cool Demand | Read | |||
| AV | 33 | Group Cool Output | Read | |||
| AV | 34 | Group Airflow | Read | |||
| AV | 35 | Fan run hours_1 | Read | |||
| AV | 36 | Fan run hours_2 | Read | |||
| AV | 37 | Fan run hours_3 | Read | |||
| AV | 38 | Fan run hours_4 | Read | |||
| AV | 39 | Fan run hours_5 | Read | |||
| AV | 40 | Fan run hours_6 | Read | |||
| AV | 41 | Fan run hours_7 | Read | |||
| AV | 42 | Fan run hours_8 | Read | |||
| AV | 43 | Air Filter run hours | Read | |||
| AV | 44 | Fan Power Supply run hours_1 | Read | |||
| AV | 45 | Fan Power Supply run hours_2 | Read | |||
| AV | 46 | Condensate Pump run hours | Read | |||
| AV | 47 | Unit run hours | Read | |||
| AV | 48 | Circulation Pump run hours | Read | |||
| AV | 49 | Percent Glycol | Read | |||
| AV | 50 | Altitude | Read | |||
| AV | 51 | Number of Units in Group | Read | |||
| AV | 52 | Cool Setpoint | Read | |||
| AVmin | 53 | Supply Air Setpoint | Read | |||
| AV | 54 | Maximum Fan Speed | Read | |||
| AV | 55 | Number of Active Flow Controllers | Read | |||
| AV | 56 | Circulation Pump Flow | Read | |||
| AV | 57 | Circulation Pump Power | Read | |||
| BV | 0 | BN3902 | Internal Communication Error | Read | 0=Inactive, 1=Active (alarm) | |
| BV | 1 | BN3904 | Unexpected Number of Units in Group | Read | 0=Inactive, 1=Active (alarm) | |
| BVmin | 2 | BN3906 | Cool Fail | Read | 0=Inactive, 1=Active (alarm) | |
| BV | 3 | BN3908 | Rack Temperature High Violation | Read | 0=Inactive, 1=Active (alarm) | |
| BV | 4 | BN390A | Air Filter Clogged | Read | 0=Inactive, 1=Active (alarm) | |
| BV | 5 | BN390C | Upper Return Air Sensor Fault | Read | 0=Inactive, 1=Active (alarm) | |
| BV | 6 | BN390E | Lower Return Air Sensor Fault | Read | 0=Inactive, 1=Active (alarm) | |
| BV | 7 | BN3910 | Upper Supply Air Sensor Fault | Read | 0=Inactive, 1=Active (alarm) | |
| BV | 8 | BN3912 | Lower Supply Air Sensor Fault | Read | 0=Inactive, 1=Active (alarm) | |
| BV | 9 | BN3914 | Rack Temperature Sensor 1 Fault | Read | 0=Inactive, 1=Active (alarm) | |
| BV | 10 | BN3916 | Rack Temperature Sensor 2 Fault | Read | 0=Inactive, 1=Active (alarm) | |
| BV | 11 | BN3918 | Rack Temperature Sensor 3 Fault | Read | 0=Inactive, 1=Active (alarm) | |
| BV | 12 | BN391A | Rack Temperature Sensor 4 Fault | Read | 0=Inactive, 1=Active (alarm) | |
| BV | 13 | BN391C | Fan 1 Fault | Read | 0=Inactive, 1=Active (alarm) | |
| BV | 14 | BN391E | Fan 2 Fault | Read | 0=Inactive, 1=Active (alarm) | |
| BV | 15 | BN3920 | Fan 3 Fault | Read | 0=Inactive, 1=Active (alarm) | |
| BV | 16 | BN3922 | Fan 4 Fault | Read | 0=Inactive, 1=Active (alarm) | |
| BV | 17 | BN3924 | Fan 5 Fault | Read | 0=Inactive, 1=Active (alarm) | |
| BV | 18 | BN3926 | Fan 6 Fault | Read | 0=Inactive, 1=Active (alarm) | |
| BV | 19 | BN3928 | Fan 7 Fault | Read | 0=Inactive, 1=Active (alarm) | |
| BV | 20 | BN392A | Fan 8 Fault | Read | 0=Inactive, 1=Active (alarm) | |
| BV | 21 | BN392C | Chilled Water Valve Actuator Fault | Read | 0=Inactive, 1=Active (alarm) | |
| BVmin | 22 | BN392E | Water Detected Fault | Read | 0=Inactive, 1=Active (alarm) | |
| BV | 23 | BN3930 | Water Detected Shutdown | Read | 0=Inactive, 1=Active (alarm) | |
| BV | 24 | BN3932 | Check Condensate Management System | Read | 0=Inactive, 1=Active (alarm) | |
| BV | 25 | BN3934 | Chilled Water Flow Meter Fault | Read | 0=Inactive, 1=Active (alarm) | |
| BV | 26 | BN3936 | Entering Chilled Water Temperature High Violation | Read | 0=Inactive, 1=Active (alarm) | |
| BV | 27 | BN3938 | Entering Chilled Water Temperature Sensor Fault | Read | 0=Inactive, 1=Active (alarm) | |
| BV | 28 | BN393A | Leaving Chilled Water Temperature Sensor Fault | Read | 0=Inactive, 1=Active (alarm) | |
| BV | 29 | BN393C | Condensate Pan Full | Read | 0=Inactive, 1=Active (alarm) | |
| BV | 30 | BN393E | Primary Power Source Fail | Read | 0=Inactive, 1=Active (alarm) | |
| BV | 31 | BN3940 | Secondary Power Source Fail | Read | 0=Inactive, 1=Active (alarm) | |
| BV | 32 | BN3942 | Fan Power Supply 1 Fault | Read | 0=Inactive, 1=Active (alarm) | |
| BV | 33 | BN3944 | Fan Power Supply 2 Fault | Read | 0=Inactive, 1=Active (alarm) | |
| BV | 34 | BN3946 | Air Filter Run Hours Violation | Read | 0=Inactive, 1=Active (alarm) | |
| BV | 35 | BN3948 | Supply Air High Temperature Violation | Read | 0=Inactive, 1=Active (alarm) | |
| BV | 36 | BN394A | Return Air High Temperature Violation | Read | 0=Inactive, 1=Active (alarm) | |
| BV | 37 | BN394C | Filter DP Sensor Failure | Read | 0=Inactive, 1=Active (alarm) | |
| BV | 38 | BN394E | Standby Due to Input Contact | Read | 0=Inactive, 1=Active (alarm) | |
| BV | 39 | BN3950 | Chilled Water Valve Control Not Set to Auto | Read | 0=Inactive, 1=Active (alarm) | |
| BV | 40 | BN3952 | EcoAisle Door Open | Read | 0=Inactive, 1=Active (alarm) | |
| BV | 41 | BN3954 | Unexpected Number of Active Flow Controllers | Read | 0=Inactive, 1=Active (alarm) | |
| BV | 42 | BN3956 | Insufficient Airflow | Read | 0=Inactive, 1=Active (alarm) | |
| BV | 43 | BN3958 | Active Flow Controller Sensor Fault | Read | 0=Inactive, 1=Active (alarm) | |
| BV | 44 | BN395A | Unit Service Required | Read | 0=Inactive, 1=Active (alarm) | |
| BV | 45 | BN395C | Humidity Sensor Fault | Read | 0=Inactive, 1=Active (alarm) | |
| BV | 46 | BN395E | Coil Condensation Possible | Read | 0=Inactive, 1=Active (alarm) | |
| BV | 47 | BN3960 | Controller Power Supply 1 Fault | Read | 0=Inactive, 1=Active (alarm) | |
| BV | 48 | BN3962 | Controller Power Supply 2 Fault | Read | 0=Inactive, 1=Active (alarm) | |
| BV | 49 | BN3964 | Coil Chilled Water Temperature Sensor Fault | Read | 0=Inactive, 1=Active (alarm) | |
| BV | 50 | BN3966 | Fan Power Supply 1 Current Sense Fault | Read | 0=Inactive, 1=Active (alarm) | |
| BV | 51 | BN3968 | Fan Power Supply 2 Current Sense Fault | Read | 0=Inactive, 1=Active (alarm) | |
| BV | 52 | BN396A | Factory Configuration Not Completed | Read | 0=Inactive, 1=Active (alarm) | |
| BV | 53 | BN396C | Unit is in Maintenance Mode | Read | 0=Inactive, 1=Active (alarm) | |
| BV | 54 | BN396E | Unexpected Number of Rack Inlet Temperature Sensors | Read | 0=Inactive, 1=Active (alarm) | |
| BV | 55 | BN3970 | Unexpected Number of Leak Detectors | Read | 0=Inactive, 1=Active (alarm) | |
| BV | 56 | BN3972 | Output Relay 1 Active | Read | 0=Inactive, 1=Active (alarm) | |
| BV | 57 | BN3974 | Output Relay 2 Active | Read | 0=Inactive, 1=Active (alarm) | |
| BV | 58 | BN3976 | Output Relay 3 Active | Read | 0=Inactive, 1=Active (alarm) | |
| BV | 59 | BN3978 | Output Relay 4 Active | Read | 0=Inactive, 1=Active (alarm) | |
| BV | 60 | BN397A | Circulation Pump Fault | Read | 0=Inactive, 1=Active (alarm) | |
| BV | 61 | BN397C | Standby Due to User Action | Read | 0=Inactive, 1=Active (alarm) | |
| BV | 62 | BN397E | Circulation Pump Communication Loss | Read | 0=Inactive, 1=Active (alarm) | |
| BV | 63 | BN3980 | Circulation Pump Warning Present | Read | 0=Inactive, 1=Active (alarm) | |
| BV | 64 | BN3982 | Circulation Pump Needs Service | Read | 0=Inactive, 1=Active (alarm) | |
| MVmin | 0 | On or Standby | On / Standby | Write | 1=Standby, 2=On | |
| MV | 1 | Idle on Leak Detect | Write | 1=No, 2=Yes | ||
| MVmin | 2 | Operating Mode | Read | 1=Standby, 2=On, 3=Idle, 4=Maintenance | ||
| MV | 3 | Idle On Cool Fail | Write | 1=No, 2=Yes | ||
| MV | 4 | Power Source | Write | 1=Single, 2=Dual | ||
| MV | 5 | Chilled Water Valve Control | Read | 1=Automatic, 2=Open | ||
| MV | 6 | Bypass Valve Position | Write | 1=Open, 2=Closed | ||
| MV | 7 | Air Filter Type | Write | 1=Standard, 2=Pleated | ||
| MV | 8 | Alarm On Standby | Write | 1=No, 2=Yes | ||
| MV | 9 | Auto Recover Cool Fail | Read | 1=No, 2=Yes | ||
| MV | 10 | Air Filter Service Alarm Enable | Write | 1=Disable, 2=Enable | ||
| MV | 11 | Unit Service Alarm Enable | Read | 1=Disable, 2=Enable | ||
| MV | 12 | Reset Air Filter Service Alarm | Write | 1=No, 2=Yes | ||
| MV | 13 | Standby Input Normal State | Write | 1=Open, 2=Closed | ||
| MV | 14 | Standby Input State | Read | 1=Open, 2=Closed | ||
| MV | 15 | Output State_1 | Output State 1 | Read | 1=Abnormal, 2=Normal | |
| MV | 16 | Output State_2 | Output State 2 | Read | 1=Abnormal, 2=Normal | |
| MV | 17 | Output State_3 | Output State 3 | Read | 1=Abnormal, 2=Normal | |
| MV | 18 | Output State_4 | Output State 4 | Read | 1=Abnormal, 2=Normal | |
| MV | 19 | Leak Detector_1 | Leak Detector 1 | Read | 1=No Leak, 2=Leak Detected | |
| MV | 20 | Leak Detector_2 | Leak Detector 2 | Read | 1=No Leak, 2=Leak Detected | |
| MV | 21 | Leak Detector_3 | Leak Detector 3 | Read | 1=No Leak, 2=Leak Detected | |
| MV | 22 | Leak Detector_4 | Leak Detector 4 | Read | 1=No Leak, 2=Leak Detected | |
| MV | 23 | Active Power Source | Read | 1=Primary, 2=Secondary, 3=No Mains | ||
| MV | 24 | Active Flow Control Status | Read | 1=Under, 2=Okay, 3=Over, 4=N/A | ||
| MVmin | 25 | Clear Active Alarms | Write | 1=No, 2=Yes | ||
| MV | 26 | Reset Unit Energy | Write | 1=No, 2=Yes | ||
| MV | 27 | Configuration Type | Read | 1=RACS, 2=HACS, 3=In-Row, 4=CACS | ||
| MV | 28 | Airflow Control | Write | 1=Automatic, 2=60%, 3=70%, 4=80%, 5=90%, 6=100% | ||
| MV | 29 | Delta-T Setpoint | Write | 1=10F/5.6C, 2=15F/8.3C, 3=20F/11.1C, 4=25F/13.9C, 5=30F/16.7C, 6=35F/19.4C, 7=40F/22.2C | ||
| MV | 30 | Active Flow Control Bias | Read | 1=Positive, 2=Slightly Positive, 3=Zero, 4=Slightly Negative, 5=Negative | ||
| MV | 31 | Active Flow Control Lamp Test | Write | 1=Off, 2=On | ||
| MV | 32 | Circulation Pump Model | Read | 1=None, 2=Stratos, 3=Stratos Maxo | ||
| CSV | 0 | Model Number | Model Number (max 19 chars) | Read | ||
| CSV | 1 | Serial Number | Serial Number (max 19 chars) | Read | ||
| CSV | 2 | Firmware Revision_1 | Firmware Revision (Executing) (max 19 chars) | Read | ||
| CSV | 3 | Firmware Revision_2 | Firmware Revision (Newest) (max 19 chars) | Read | ||
| CSV | 4 | Firmware Revision_3 | Firmware Revision (Oldest) (max 19 chars) | Read | ||
| CSV | 5 | Firmware Revision_4 | Firmware Revision (Bootloader) (max 19 chars) | Read | ||
| CSV | 6 | Hardware Revision | Hardware Revision (max 7 chars) | Read | ||
| NC | 0 | DefaultNotifier | Default Notification Class | Write |
No points match these filters.
Object ID lookup: APC InRow RC ACRC301S / ACRC301H point IDs by name
AV0Startup DelayAV1Maximum Chilled Water FlowAV2Number of Rack Inlet Temperature Sensors in UnitAV3Number of Leak Detectors in UnitAV4Rack Inlet Temperature High ThresholdAV5Supply Air Temperature High ThresholdAV6Return Air Temperature High ThresholdAV7Entering Chilled Water Temperature High ThresholdAV8Air Filter Service IntervalAV9Unit Service Alarm IntervalAV10Supply Air TemperatureAV11Return Air TemperatureAV12Filter Differential PressureAV13Entering Chilled Water TemperatureAV14Leaving Chilled Water TemperatureAV15Chilled Water Valve PositionAV16Unit Rack Inlet Temperatures_1AV17Unit Rack Inlet Temperatures_2AV18Unit Rack Inlet Temperatures_3AV19Unit Rack Inlet Temperatures_4AV20Maximum Rack Inlet TemperatureAV21Minimum Rack Inlet TemperatureAV22Chilled Water FlowAV23Dew Point TemperatureAV24Coil Chilled Water TemperatureAV25Cool DemandAV26Cool OutputAV27AirflowAV28Fan SpeedAV29Unit PowerAV30Unit EnergyAV31Circulation Pump SpeedAV32Group Cool DemandAV33Group Cool OutputAV34Group AirflowAV35Fan run hours_1AV36Fan run hours_2AV37Fan run hours_3AV38Fan run hours_4AV39Fan run hours_5AV40Fan run hours_6AV41Fan run hours_7AV42Fan run hours_8AV43Air Filter run hoursAV44Fan Power Supply run hours_1AV45Fan Power Supply run hours_2AV46Condensate Pump run hoursAV47Unit run hoursAV48Circulation Pump run hoursAV49Percent GlycolAV50AltitudeAV51Number of Units in GroupAV52Cool SetpointAV53Supply Air SetpointAV54Maximum Fan SpeedAV55Number of Active Flow ControllersAV56Circulation Pump FlowAV57Circulation Pump PowerBV0BN3902BV1BN3904BV2BN3906BV3BN3908BV4BN390ABV5BN390CBV6BN390EBV7BN3910BV8BN3912BV9BN3914BV10BN3916BV11BN3918BV12BN391ABV13BN391CBV14BN391EBV15BN3920BV16BN3922BV17BN3924BV18BN3926BV19BN3928BV20BN392ABV21BN392CBV22BN392EBV23BN3930BV24BN3932BV25BN3934BV26BN3936BV27BN3938BV28BN393ABV29BN393CBV30BN393EBV31BN3940BV32BN3942BV33BN3944BV34BN3946BV35BN3948BV36BN394ABV37BN394CBV38BN394EBV39BN3950BV40BN3952BV41BN3954BV42BN3956BV43BN3958BV44BN395ABV45BN395CBV46BN395EBV47BN3960BV48BN3962BV49BN3964BV50BN3966BV51BN3968BV52BN396ABV53BN396CBV54BN396EBV55BN3970BV56BN3972BV57BN3974BV58BN3976BV59BN3978BV60BN397ABV61BN397CBV62BN397EBV63BN3980BV64BN3982MV0On or StandbyMV1Idle on Leak DetectMV2Operating ModeMV3Idle On Cool FailMV4Power SourceMV5Chilled Water Valve ControlMV6Bypass Valve PositionMV7Air Filter TypeMV8Alarm On StandbyMV9Auto Recover Cool FailMV10Air Filter Service Alarm EnableMV11Unit Service Alarm EnableMV12Reset Air Filter Service AlarmMV13Standby Input Normal StateMV14Standby Input StateMV15Output State_1MV16Output State_2MV17Output State_3MV18Output State_4MV19Leak Detector_1MV20Leak Detector_2MV21Leak Detector_3MV22Leak Detector_4MV23Active Power SourceMV24Active Flow Control StatusMV25Clear Active AlarmsMV26Reset Unit EnergyMV27Configuration TypeMV28Airflow ControlMV29Delta-T SetpointMV30Active Flow Control BiasMV31Active Flow Control Lamp TestMV32Circulation Pump ModelCSV0Model NumberCSV1Serial NumberCSV2Firmware Revision_1CSV3Firmware Revision_2CSV4Firmware Revision_3CSV5Firmware Revision_4CSV6Hardware RevisionNC0DefaultNotifier
Integration notes
- The page titled 'Analog Value Objects' actually lists the Multi-state Values (its object IDs are type 19); they are listed here as MV.
- The Analog Value table page is blank in this release (07/2023). The AV names and instances come from the document's index (BACnet Name, Object Type, BACnet Index); units and read/write access are not printed for them, so they are shown as read-only.
- MV 32 Circulation Pump Model is printed between MV 9 and MV 10 in the table; it is listed here in instance order.
- Alarm Binary Values are named by alarm code (BN3902 and so on); the description holds the printed alarm text.
- The ID column is the full object identifier (type x 4194304 + instance) and agrees with the Index column for every row.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the APC InRow RC chilled water 300 mm (ACRC301S / ACRC301H) BACnet IP and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the APC InRow RC chilled water 300 mm (ACRC301S / ACRC301H) BACnet IP
How many BACnet points does the APC InRow RC chilled water 300 mm (ACRC301S / ACRC301H) BACnet IP have?
This list has 164 BACnet objects: 58 analog values, 65 binary values, 1 notification class, 33 multi-state values, 7 characterstring values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which APC InRow RC chilled water 300 mm (ACRC301S / ACRC301H) BACnet IP BACnet points are writable?
16 of the 164 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official APC InRow RC chilled water 300 mm (ACRC301S / ACRC301H) BACnet IP BACnet documentation?
The source is BACnet Application Map - InRow RC Chilled Water Air Conditioners, 300 mm (TME27091), revision 2023-07, published free by APC at https://download.se.com/files?p_Doc_Ref=TME27091.
What are the minimum BACnet points to integrate the APC InRow RC chilled water 300 mm (ACRC301S / ACRC301H) BACnet IP?
Start with MV 0 On or Standby (Unit on/standby command (1=Standby, 2=On)); MV 25 Clear Active Alarms (Write 2=Yes to clear active alarms); MV 2 Operating Mode (Standby, on, idle or maintenance); AV 10 Supply Air Temperature (Air leaving the unit); AV 11 Return Air Temperature (Air entering the unit); AV 53 Supply Air Setpoint (Supply air temperature setpoint); AV 26 Cool Output (Cooling delivered by the unit); AV 28 Fan Speed (Current fan speed); BV 2 BN3906 (Cool Fail alarm); BV 22 BN392E (Water Detected Fault alarm).
How do I enable BMS control of the APC InRow RC chilled water 300 mm (ACRC301S / ACRC301H) BACnet IP?
MV 0 On or Standby (writable) switches the unit between standby and on.
How do I check these points on the real APC InRow RC chilled water 300 mm (ACRC301S / ACRC301H) BACnet IP?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More APC BACnet points lists
- UPS (three-phase) network card
APC Easy UPS 3-Phase with Network Management Card AP9547 (BACnet IP)
APC / Schneider Electric Easy UPS 3-Phase units fitted with the Network Management Card for Easy UPS (AP9547), on BACnet IP.
Also known as: Easy UPS 3-Phase, AP9547, NMC for Easy UPS, Easy UPS 3S, Easy UPS 3M, 990-6445, Schneider Easy UPS BACnet - UPS (uninterruptible power supply) network card
APC Smart-UPS with Network Management Card 2 / 3 (BACnet IP)
APC Smart-UPS units (SMT, SMX, SRT, SURT, SURTD and others) fitted with a Network Management Card 2 (firmware 6.5.6 or later) or Network Management Card 3.
Also known as: APC Smart-UPS BACnet, NMC2 BACnet, NMC3 BACnet, AP9630, AP9631, AP9635, AP9640, AP9641, SMT, SMX, SRT, SURT, 990-5916C, APC UPS BACnet application map - UPS (uninterruptible power supply) network card
APC Symmetra single-phase UPS with Network Management Card 2 (BACnet IP)
APC Symmetra single-phase UPS units fitted with a Network Management Card 2 running the 'sy' application firmware 6.5.6 or later.
Also known as: APC Symmetra BACnet, Symmetra LX, Symmetra RM, NMC2 BACnet, AP9630, AP9631, AP9635, 990-5917B, sy firmware
Source: BACnet Application Map - InRow RC Chilled Water Air Conditioners, 300 mm · TME27091 · rev. 2023-07. Object names, instances and units are reproduced as published; descriptions are our own.