- Home
- BACnet points lists
- APC
- Easy UPS 3-Phase with Network Management Card AP9547 (BACnet IP)
UPS (three-phase) network card · BACnet points list
APC Easy UPS 3-Phase with Network Management Card AP9547 (BACnet IP) BACnet points list
Updated 6 November 2026
The AP9547 network card puts an Easy UPS 3-Phase on BACnet IP. It exposes 60 read-only Analog Values (runtime, battery, input, bypass and output voltages, currents, power, load percent, maintenance and running-time counters), 60 alarm Binary Values that also send event notifications, five text values (model, serial, firmware) and three Multi-State Values (UPS state, last transfer cause, last battery test).
This page lists 128 BACnet objects for the APC Easy UPS 3-Phase with Network Management Card AP9547 (BACnet IP) — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from APC’s own free documentation, linked below.
- Manufacturer
- APC
- Model
- Easy UPS 3-Phase with Network Management Card AP9547 (BACnet IP)
- Equipment
- UPS (three-phase) network card
- Equipment type
- Other equipment
- BACnet objects
- 128 (0 writable)
- Transport
- BACnet IP
- Firmware
- Not stated
- Also known as
- Easy UPS 3-Phase, AP9547, NMC for Easy UPS, Easy UPS 3S, Easy UPS 3M, 990-6445, Schneider Easy UPS BACnet
Reference only, provided as-is: verify against APC’s current documentation and the live device before use. Not official APC information. Terms of use.
BMS integration notes: APC Easy UPS 3-Phase with Network Management Card AP9547 (BACnet IP)
Enable BACnet on the NMC (see the NMC for Easy UPS user guide), give it a device instance, then read UPS state, runtime, battery charge, load and the key alarm BVs. Use the notification class for alarm events if the BMS supports them.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| MV 1 | UPSState | UPS status: online, on battery, bypass, fault... | Read |
| AV 0 | Runtime | Battery runtime left at present load, s | Read |
| AV 31 | BatteryStateOfCharge | Battery charge, % | Read |
| AV 16 | OutputVAPercentagePhase1 | Phase 1 load, % of rated VA | Read |
| AV 2 | UtilityInputVoltage1 | Phase 1 input voltage, V | Read |
| BV 31 | OnBattery2 | UPS on battery after an input problem | Read |
| BV 3 | LowBattery | Battery too low to keep supporting the load | Read |
| BV 0 | LostUPSComm | Card lost communication with the UPS | Read |
Enable & remote start
BACnet is enabled and configured on the network management card (web interface); there is no BMS enable point.
Network setup
- AP9547 supports BACnet IP only.
- BACnet settings (enable, device instance, port, BBMD) are on the NMC; see the NMC for Easy UPS user guide.
Watch out for
- Map is read-only; UPS control is not available over BACnet.
- Check BV 0 LostUPSComm before trusting other values.
APC Easy UPS 3-Phase with Network Management Card AP9547 (BACnet IP) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AVmin | 0 | Runtime | How long the UPS can support its present load while running on battery power | s | Read | |
| AV | 1 | BatteryTemperature | Temperature as reported by the sensor in the battery compartment, in Degrees C | °C | Read | |
| AVmin | 2 | UtilityInputVoltage1 | The AC voltage (VAC) being received by the UPS | V | Read | |
| AV | 3 | UtilityInputVoltage2 | The AC voltage (VAC) being received by the UPS | V | Read | |
| AV | 4 | UtilityInputVoltage3 | The AC voltage (VAC) being received by the UPS | V | Read | |
| AV | 5 | UtilityInputVoltage12 | The AC voltage (VAC) phase to phase being received by the UPS | V | Read | |
| AV | 6 | UtilityInputVoltage23 | The AC voltage (VAC) phase to phase being received by the UPS | V | Read | |
| AV | 7 | UtilityInputVoltage31 | The AC voltage (VAC) phase to phase being received by the UPS | V | Read | |
| AV | 8 | UtilityInputCurrent1 | The current, in Amps, being received by the UPS | A | Read | |
| AV | 9 | UtilityInputCurrent2 | The current, in Amps, being received by the UPS | A | Read | |
| AV | 10 | UtilityInputCurrent3 | The current, in Amps, being received by the UPS | A | Read | |
| AV | 11 | UtilityInputFrequency | The frequency in Hertz (Hz) of the voltage being received by the UPS | Hz | Read | |
| AV | 12 | OutputFrequency | The frequency in Hertz (Hz) of the output voltage | Hz | Read | |
| AV | 13 | OutputVoltage1 | The AC voltage (VAC) that the UPS is supplying to its load | V | Read | |
| AV | 14 | OutputVoltage2 | The AC voltage (VAC) that the UPS is supplying to its load | V | Read | |
| AV | 15 | OutputVoltage3 | The AC voltage (VAC) that the UPS is supplying to its load | V | Read | |
| AVmin | 16 | OutputVAPercentagePhase1 | The UPS load as a percentage of available VA | % | Read | |
| AV | 17 | OutputVAPercentagePhase2 | The UPS load as a percentage of available VA | % | Read | |
| AV | 18 | OutputVAPercentagePhase3 | The UPS load as a percentage of available VA | % | Read | |
| AV | 19 | OutputLoadCurrent1 | The current, in Amps, supplied to the load | A | Read | |
| AV | 20 | OutputLoadCurrent2 | The current, in Amps, supplied to the load | A | Read | |
| AV | 21 | OutputLoadCurrent3 | The current, in Amps, supplied to the load | A | Read | |
| AV | 22 | OutputWattsPercentagePhase1 | The UPS load as a percentage of available Watts | % | Read | |
| AV | 23 | OutputWattsPercentagePhase2 | The UPS load as a percentage of available Watts | % | Read | |
| AV | 24 | OutputWattsPercentagePhase3 | The UPS load as a percentage of available Watts | % | Read | |
| AV | 25 | BypassInputFrequency | Measured frequency on the bypass input for separate bypass feed | Hz | Read | |
| AV | 26 | BypassInputVoltage12 | Bypass phase-to-phase voltage (not on all UPS) | V | Read | |
| AV | 27 | BypassInputVoltage23 | Bypass phase-to-phase voltage (not on all UPS) | V | Read | |
| AV | 28 | BypassInputVoltage31 | Bypass phase-to-phase voltage (not on all UPS) | V | Read | |
| AV | 29 | PositiveBatteryVoltage | Measured battery voltage, positive bus | V | Read | |
| AV | 30 | NegativeBatteryVoltage | Measured battery voltage - negative battery bus | V | Read | |
| AVmin | 31 | BatteryStateOfCharge | The percentage of the UPS battery capacity that is available to support the attached equipment | % | Read | |
| AV | 32 | PositiveBatteryCurrent | The current being battery positive | A | Read | |
| AV | 33 | NegativeBatteryCurrent | The current being battery negative | A | Read | |
| AV | 34 | OutputActivePowerL1 | Measure the active power on the phase 1 | kW | Read | |
| AV | 35 | OutputActivePowerL2 | Measure the active power on the phase 2 | kW | Read | |
| AV | 36 | OutputActivePowerL3 | Measure the active power on the phase 3 | kW | Read | |
| AV | 37 | OutputApparantPowerL1 | Measure the apparent power on the phase 1 | kVA | Read | |
| AV | 38 | OutputApparantPowerL2 | Measure the apparent power on the phase 2 | kVA | Read | |
| AV | 39 | OutputApparantPowerL3 | Measure the apparent power on the phase 3 | kVA | Read | |
| AV | 40 | UPSapparentpowerrating | The rated apparent full power | kVA | Read | |
| AV | 41 | DCcapacitorMaintenanceCycle | Measure DC capacitor maintainance cycle period | days | Read | |
| AV | 42 | ACcapacitorMaintenanceCycle | Measure AC capacitor maintainance cycle period | days | Read | |
| AV | 43 | AuxPowerSupplyMaintenanceCycle | Measure the Aux PowerSupply Maintenance Cycle period | days | Read | |
| AV | 44 | AirFilterMaintenanceCycle | Measure the Air filter maintenance cycle period | days | Read | |
| AV | 45 | BatteryMaintenanceCycle | Measure the battery maintenance cycle period | days | Read | |
| AV | 46 | WarrantyCycle | Measure the Warranty Cycle timeperiod | days | Read | |
| AV | 47 | DCcapacitorRunningTime | Measure the DC capacitor running time | days | Read | |
| AV | 48 | ACcapacitorRunningTime | Measure the AC capacitor running time | days | Read | |
| AV | 49 | BatteryRunningTime | Measure the Air filter running time period | days | Read | |
| AV | 50 | AmbientTemperature | Measure the Ambient temperature | °C | Read | |
| AV | 51 | BypassInputVoltage1 | The AC voltage (VAC) being received from Bypass Supply | V | Read | |
| AV | 52 | BypassInputVoltage2 | The AC voltage (VAC) being received from Bypass Supply | V | Read | |
| AV | 53 | BypassInputVoltage3 | The AC voltage (VAC) being received from Bypass Supply | V | Read | |
| AV | 54 | OutputVoltage12 | The Phase12 AC voltage (VAC) that the UPS is supplying to its load | V | Read | |
| AV | 55 | OutputVoltage23 | The Phase23 AC voltage (VAC) that the UPS is supplying to its load | V | Read | |
| AV | 56 | OutputVoltage31 | The Phase31 AC voltage (VAC) that the UPS is supplying to its load | V | Read | |
| AV | 57 | AuxPowerSupplyRunningTime | Measure the Aux PowerSupply running time | months | Read | |
| AV | 58 | AirFilterRunningTime | Measure the Aux PowerSupply running time | months | Read | |
| AV | 59 | WarrantyElapsedTime | Measure Warranty elapsed time | months | Read | |
| BVmin | 0 | LostUPSComm | NMC lost comm with UPS (alarm) | Read | 0=Inactive, 1=Active | |
| BV | 1 | Overload | The load exceeds 100% of rated capacity (alarm) | Read | 0=Inactive, 1=Active | |
| BV | 2 | SelfTestInProgress | UPS self-test in progress (alarm) | Read | 0=Inactive, 1=Active | |
| BVmin | 3 | LowBattery | Battery too low to support the load (alarm) | Read | 0=Inactive, 1=Active | |
| BV | 4 | LowBatteryOnBattery | On battery (alarm) | Read | 0=Inactive, 1=Active | |
| BV | 5 | InBypassBypassSwitch | In bypass in response to the bypass switch at the UPS (alarm) | Read | 0=Inactive, 1=Active | |
| BV | 6 | FanProblem | System level fan fault exists (alarm) | Read | 0=Inactive, 1=Active | |
| BV | 7 | BatteryChargerInoperable | A battery charger is not fully functional (alarm) | Read | 0=Inactive, 1=Active | |
| BV | 8 | BatteryDisconnected | The battery is not installed properly (alarm) | Read | 0=Inactive, 1=Active | |
| BV | 9 | LostUPSCommOnBat | Lost the management interface-to-UPS communication while the UPS was on battery (alarm) | Read | 0=Inactive, 1=Active | |
| BV | 10 | UPSTempCritical | Rectifier over temperature (alarm) | Read | 0=Inactive, 1=Active | |
| BV | 11 | OutputShortCircuit | The output has a short-circuit (alarm) | Read | 0=Inactive, 1=Active | |
| BV | 12 | InverterInoperable | Inverter module is inoperable (alarm) | Read | 0=Inactive, 1=Active | |
| BV | 13 | BatteryNearEndOfLife | Battery near end of life (alarm) | Read | 0=Inactive, 1=Active | |
| BV | 14 | EPOActive | EPO activated (alarm) | Read | 0=Inactive, 1=Active | |
| BV | 15 | WeakBattery | Weak battery exists (alarm) | Read | 0=Inactive, 1=Active | |
| BV | 16 | PowerSavingMode | High Efficiency Mode is no longer disabled from an input relay (alarm) | Read | 0=Inactive, 1=Active | |
| BV | 17 | InverterShutdownOverload | Inverter overload shutdown (alarm) | Read | 0=Inactive, 1=Active | |
| BV | 18 | OverloadOnInstallation | Overload On Installation (alarm) | Read | 0=Inactive, 1=Active | |
| BV | 19 | RectifierFailure | PFC Rectifier is InOperable (alarm) | Read | 0=Inactive, 1=Active | |
| BV | 20 | InverterFault | Inverter Module InOperable (alarm) | Read | 0=Inactive, 1=Active | |
| BV | 21 | AuxPowerFault | Auxiliary Power supply Fault (alarm) | Read | 0=Inactive, 1=Active | |
| BV | 22 | InverterOverTemperature | Inverter Temperature Overload Exist (alarm) | Read | 0=Inactive, 1=Active | |
| BV | 23 | InverterOverLoad | Inverter Over Load (alarm) | Read | 0=Inactive, 1=Active | |
| BV | 24 | UPSOverLoad | UPS Over load (alarm) | Read | 0=Inactive, 1=Active | |
| BV | 25 | InverterFailure | Inverter Module is inoperable (alarm) | Read | 0=Inactive, 1=Active | |
| BV | 26 | InputFailure | UPS: Mains input is not available due to inoperable condition (alarm) | Read | 0=Inactive, 1=Active | |
| BV | 27 | RectifierFault | PFC rectifier is inoperable (alarm) | Read | 0=Inactive, 1=Active | |
| BV | 28 | LoadNotPowered | The output power is turned off (alarm) | Read | 0=Inactive, 1=Active | |
| BV | 29 | BreakerQ2UOBOpen | Breaker Q2 UOB Open (alarm) | Read | 0=Inactive, 1=Active | |
| BV | 30 | BypassOverTemperature | Bypass Over Temperature (alarm) | Read | 0=Inactive, 1=Active | |
| BVmin | 31 | OnBattery2 | On battery power in response to an input power problem (alarm) | Read | 0=Inactive, 1=Active | |
| BV | 32 | LoadkVAAlarmViolation | A load (kVA) alarm threshold violation exists (alarm) | Read | 0=Inactive, 1=Active | |
| BV | 33 | ManualBypass | In bypass in response to the bypass switch at the UPS, typically for maintenance (alarm) | Read | 0=Inactive, 1=Active | |
| BV | 34 | MainsFrequencyFailure | Mains input frequency is out of tolerance (alarm) | Read | 0=Inactive, 1=Active | |
| BV | 35 | MainsVoltageFailure | Mains input voltage is out of range (alarm) | Read | 0=Inactive, 1=Active | |
| BV | 36 | BypassVoltageErrorLowVoltage | Bypass voltage error, low voltage (alarm) | Read | 0=Inactive, 1=Active | |
| BV | 37 | BypassVoltageErrorHighVoltage | Bypass voltage error, high voltage (alarm) | Read | 0=Inactive, 1=Active | |
| BV | 38 | BypassFrequencyFailure | Bypass input frequency is out of tolerance (alarm) | Read | 0=Inactive, 1=Active | |
| BV | 39 | OutputVoltageErrorLowVoltage | Output voltage low (alarm) | Read | 0=Inactive, 1=Active | |
| BV | 40 | OutputVoltageErrorHighVoltage | Output voltage high (alarm) | Read | 0=Inactive, 1=Active | |
| BV | 41 | OverlaodOnBypassStaticSwitch | Overload on bypass static switch (alarm) | Read | 0=Inactive, 1=Active | |
| BV | 42 | AmbientTempratureOutOfRange | Ambient temperature out of range (alarm) | Read | 0=Inactive, 1=Active | |
| BV | 43 | BypassInputVoltageErrorLowVoltage | Bypass input voltage is out of tolerance (alarm) | Read | 0=Inactive, 1=Active | |
| BV | 44 | BatteriesAreDischarging | Batteries are discharging (alarm) | Read | 0=Inactive, 1=Active | |
| BV | 45 | BateryCondtionIsWeak | Battery capacity is between 50% to 75% (alarm) | Read | 0=Inactive, 1=Active | |
| BV | 46 | BateryCondtionIsPoor | Battery capacity is lower than 50% (alarm) | Read | 0=Inactive, 1=Active | |
| BV | 47 | BatteryVoltErrorVoltageAboveShutdownLevel | Battery voltage error - voltage above shutdown level (alarm) | Read | 0=Inactive, 1=Active | |
| BV | 48 | OutputVoltageError | The output voltage is out of tolerance (alarm) | Read | 0=Inactive, 1=Active | |
| BV | 49 | LoadOnUpsIsAboveWarningLevel | Load on UPS is above warning level (alarm) | Read | 0=Inactive, 1=Active | |
| BV | 50 | BatteryVoltErrorVoltageBelowShutdownLevel | Battery voltage error - voltage below shutdown level (alarm) | Read | 0=Inactive, 1=Active | |
| BV | 51 | BatteryBreakerOpen | Battery breaker open (alarm) | Read | 0=Inactive, 1=Active | |
| BV | 52 | InternalBatterytemperatureExceedsThreshold | The internal battery temperature exceeds the critical threshold (alarm) | Read | 0=Inactive, 1=Active | |
| BV | 53 | OperationModeStaticBypassStandby | The UPS is ready to enter static bypass but awaits permission from the system (alarm) | Read | 0=Inactive, 1=Active | |
| BV | 54 | OperationModeInverterStandby | The UPS is ready to enter battery operation but awaits permission from the system (alarm) | Read | 0=Inactive, 1=Active | |
| BV | 55 | TechnicalCheckRequired | Technical check recommended (alarm) | Read | 0=Inactive, 1=Active | |
| BV | 56 | WarrantyExpiringSoon | Warranty expiring soon (alarm) | Read | 0=Inactive, 1=Active | |
| BV | 57 | BatteriesCheckRequired | The batteries need to be checked as preventive maintenance is recommended (alarm) | Read | 0=Inactive, 1=Active | |
| BV | 58 | AirFilterTechnicalCheckRecommended | The air filters need to be checked as preventive maintenance is recommended (alarm) | Read | 0=Inactive, 1=Active | |
| BV | 59 | FansCheckRecommended | The fans need to be checked as preventive maintenance is recommended (alarm) | Read | 0=Inactive, 1=Active | |
| CSV | 0 | UPSmodel | The UPS model name, up to 24 characters | Read | ||
| CSV | 1 | UPSserialnumber | The UPS serial number, up to 16 characters | Read | ||
| CSV | 2 | UPSFirmwareRevision | The revision number of the UPS firmware, up to 16 characters | Read | ||
| CSV | 3 | UPSModelFullName | UPS product name, up to 24 characters | Read | ||
| CSV | 4 | UPSDateOfManufacture | UPS date of manufacture, up to 11 characters | Read | ||
| MV | 0 | Lastbatterytransfer | The cause of the last switch to battery operation | Read | None, Input Failure, UPS Battery Test | |
| MVmin | 1 | UPSState | UPS status summary | Read | Unknown, Online, Online green, On battery, Self-test, Low battery, Shutdown, Bypass, Fault | |
| MV | 2 | LastBatteryTestResult | Provide the last battery last result | Read | Pass, Fail |
No points match these filters.
Object ID lookup: APC Easy UPS 3-Phase with Network Management Card AP9547 point IDs by name
AV0RuntimeAV1BatteryTemperatureAV2UtilityInputVoltage1AV3UtilityInputVoltage2AV4UtilityInputVoltage3AV5UtilityInputVoltage12AV6UtilityInputVoltage23AV7UtilityInputVoltage31AV8UtilityInputCurrent1AV9UtilityInputCurrent2AV10UtilityInputCurrent3AV11UtilityInputFrequencyAV12OutputFrequencyAV13OutputVoltage1AV14OutputVoltage2AV15OutputVoltage3AV16OutputVAPercentagePhase1AV17OutputVAPercentagePhase2AV18OutputVAPercentagePhase3AV19OutputLoadCurrent1AV20OutputLoadCurrent2AV21OutputLoadCurrent3AV22OutputWattsPercentagePhase1AV23OutputWattsPercentagePhase2AV24OutputWattsPercentagePhase3AV25BypassInputFrequencyAV26BypassInputVoltage12AV27BypassInputVoltage23AV28BypassInputVoltage31AV29PositiveBatteryVoltageAV30NegativeBatteryVoltageAV31BatteryStateOfChargeAV32PositiveBatteryCurrentAV33NegativeBatteryCurrentAV34OutputActivePowerL1AV35OutputActivePowerL2AV36OutputActivePowerL3AV37OutputApparantPowerL1AV38OutputApparantPowerL2AV39OutputApparantPowerL3AV40UPSapparentpowerratingAV41DCcapacitorMaintenanceCycleAV42ACcapacitorMaintenanceCycleAV43AuxPowerSupplyMaintenanceCycleAV44AirFilterMaintenanceCycleAV45BatteryMaintenanceCycleAV46WarrantyCycleAV47DCcapacitorRunningTimeAV48ACcapacitorRunningTimeAV49BatteryRunningTimeAV50AmbientTemperatureAV51BypassInputVoltage1AV52BypassInputVoltage2AV53BypassInputVoltage3AV54OutputVoltage12AV55OutputVoltage23AV56OutputVoltage31AV57AuxPowerSupplyRunningTimeAV58AirFilterRunningTimeAV59WarrantyElapsedTimeBV0LostUPSCommBV1OverloadBV2SelfTestInProgressBV3LowBatteryBV4LowBatteryOnBatteryBV5InBypassBypassSwitchBV6FanProblemBV7BatteryChargerInoperableBV8BatteryDisconnectedBV9LostUPSCommOnBatBV10UPSTempCriticalBV11OutputShortCircuitBV12InverterInoperableBV13BatteryNearEndOfLifeBV14EPOActiveBV15WeakBatteryBV16PowerSavingModeBV17InverterShutdownOverloadBV18OverloadOnInstallationBV19RectifierFailureBV20InverterFaultBV21AuxPowerFaultBV22InverterOverTemperatureBV23InverterOverLoadBV24UPSOverLoadBV25InverterFailureBV26InputFailureBV27RectifierFaultBV28LoadNotPoweredBV29BreakerQ2UOBOpenBV30BypassOverTemperatureBV31OnBattery2BV32LoadkVAAlarmViolationBV33ManualBypassBV34MainsFrequencyFailureBV35MainsVoltageFailureBV36BypassVoltageErrorLowVoltageBV37BypassVoltageErrorHighVoltageBV38BypassFrequencyFailureBV39OutputVoltageErrorLowVoltageBV40OutputVoltageErrorHighVoltageBV41OverlaodOnBypassStaticSwitchBV42AmbientTempratureOutOfRangeBV43BypassInputVoltageErrorLowVoltageBV44BatteriesAreDischargingBV45BateryCondtionIsWeakBV46BateryCondtionIsPoorBV47BatteryVoltErrorVoltageAboveShutdownLevelBV48OutputVoltageErrorBV49LoadOnUpsIsAboveWarningLevelBV50BatteryVoltErrorVoltageBelowShutdownLevelBV51BatteryBreakerOpenBV52InternalBatterytemperatureExceedsThresholdBV53OperationModeStaticBypassStandbyBV54OperationModeInverterStandbyBV55TechnicalCheckRequiredBV56WarrantyExpiringSoonBV57BatteriesCheckRequiredBV58AirFilterTechnicalCheckRecommendedBV59FansCheckRecommendedCSV0UPSmodelCSV1UPSserialnumberCSV2UPSFirmwareRevisionCSV3UPSModelFullNameCSV4UPSDateOfManufactureMV0LastbatterytransferMV1UPSStateMV2LastBatteryTestResult
Integration notes
- All objects are read-only in this map; there are no BACnet commands.
- Alarm BVs send notifications to the recipients in the Notification Class object (NC 0) set up on the card.
- Some bypass objects are not available on every UPS model.
- Several names are printed with typos (e.g. OutputApparantPowerL1, OverlaodOnBypassStaticSwitch, BateryCondtionIsWeak); they are kept as printed.
- AV 49 BatteryRunningTime and AV 58 AirFilterRunningTime carry copied descriptions in the map (air filter / aux power supply).
- Source: BACnet Application Map for Network Management Card for Easy UPS, 3-Phase, 990-6445B (04/2024).
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Easy UPS 3-Phase with Network Management Card AP9547 (BACnet IP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the APC Easy UPS 3-Phase with Network Management Card AP9547 (BACnet IP)
How many BACnet points does the APC Easy UPS 3-Phase with Network Management Card AP9547 (BACnet IP) have?
This list has 128 BACnet objects: 60 analog values, 60 binary values, 3 multi-state values, 5 characterstring values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which APC Easy UPS 3-Phase with Network Management Card AP9547 (BACnet IP) BACnet points are writable?
None of the listed objects are marked writable in the source documentation.
Where is the official APC Easy UPS 3-Phase with Network Management Card AP9547 (BACnet IP) BACnet documentation?
The source is BACnet Application Map for Network Management Card for Easy UPS, 3-Phase (990-6445B), revision 2024-04, published free by APC at https://download.se.com/files?p_Doc_Ref=SPD_CDIG-NMCBAC47_EN.
What are the minimum BACnet points to integrate the APC Easy UPS 3-Phase with Network Management Card AP9547 (BACnet IP)?
Start with MV 1 UPSState (UPS status: online, on battery, bypass, fault); AV 0 Runtime (Battery runtime left at present load, s); AV 31 BatteryStateOfCharge (Battery charge, %); AV 16 OutputVAPercentagePhase1 (Phase 1 load, % of rated VA); AV 2 UtilityInputVoltage1 (Phase 1 input voltage, V); BV 31 OnBattery2 (UPS on battery after an input problem); BV 3 LowBattery (Battery too low to keep supporting the load); BV 0 LostUPSComm (Card lost communication with the UPS).
How do I enable BMS control of the APC Easy UPS 3-Phase with Network Management Card AP9547 (BACnet IP)?
BACnet is enabled and configured on the network management card (web interface); there is no BMS enable point.
How do I check these points on the real Easy UPS 3-Phase with Network Management Card AP9547 (BACnet IP)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More APC BACnet points lists
- In-row precision cooling unit (chilled water computer room air handler)
APC InRow RC chilled water 300 mm (ACRC301S / ACRC301H) BACnet IP
APC / Schneider Electric InRow RC 300 mm chilled water in-row coolers ACRC301S and ACRC301H with application firmware v6.0.0 or later.
Also known as: ACRC301S, ACRC301H, ACRC3xx, InRow RC 300 mm, InRow CW, Schneider Electric InRow RC, TME27091 - UPS (uninterruptible power supply) network card
APC Smart-UPS with Network Management Card 2 / 3 (BACnet IP)
APC Smart-UPS units (SMT, SMX, SRT, SURT, SURTD and others) fitted with a Network Management Card 2 (firmware 6.5.6 or later) or Network Management Card 3.
Also known as: APC Smart-UPS BACnet, NMC2 BACnet, NMC3 BACnet, AP9630, AP9631, AP9635, AP9640, AP9641, SMT, SMX, SRT, SURT, 990-5916C, APC UPS BACnet application map - UPS (uninterruptible power supply) network card
APC Symmetra single-phase UPS with Network Management Card 2 (BACnet IP)
APC Symmetra single-phase UPS units fitted with a Network Management Card 2 running the 'sy' application firmware 6.5.6 or later.
Also known as: APC Symmetra BACnet, Symmetra LX, Symmetra RM, NMC2 BACnet, AP9630, AP9631, AP9635, 990-5917B, sy firmware
Source: BACnet Application Map for Network Management Card for Easy UPS, 3-Phase · 990-6445B · rev. 2024-04. Object names, instances and units are reproduced as published; descriptions are our own.