APC Easy UPS 3-Phase with Network Management Card AP9547 (BACnet IP) BACnet points list

Updated 6 November 2026

Short answer

The AP9547 network card puts an Easy UPS 3-Phase on BACnet IP. It exposes 60 read-only Analog Values (runtime, battery, input, bypass and output voltages, currents, power, load percent, maintenance and running-time counters), 60 alarm Binary Values that also send event notifications, five text values (model, serial, firmware) and three Multi-State Values (UPS state, last transfer cause, last battery test).

This page lists 128 BACnet objects for the APC Easy UPS 3-Phase with Network Management Card AP9547 (BACnet IP) — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from APC’s own free documentation, linked below.

Manufacturer
APC
Model
Easy UPS 3-Phase with Network Management Card AP9547 (BACnet IP)
Equipment
UPS (three-phase) network card
Equipment type
Other equipment
BACnet objects
128 (0 writable)
Transport
BACnet IP
Firmware
Not stated
Also known as
Easy UPS 3-Phase, AP9547, NMC for Easy UPS, Easy UPS 3S, Easy UPS 3M, 990-6445, Schneider Easy UPS BACnet
Source document
BACnet Application Map for Network Management Card for Easy UPS, 3-Phase · 990-6445B · rev. 2024-04
Download CSV 128 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against APC’s current documentation and the live device before use. Not official APC information. Terms of use.

BMS integration notes: APC Easy UPS 3-Phase with Network Management Card AP9547 (BACnet IP)

Integration in brief

Enable BACnet on the NMC (see the NMC for Easy UPS user guide), give it a device instance, then read UPS state, runtime, battery charge, load and the key alarm BVs. Use the notification class for alarm events if the BMS supports them.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 1UPSStateUPS status: online, on battery, bypass, fault...Read
AV 0RuntimeBattery runtime left at present load, sRead
AV 31BatteryStateOfChargeBattery charge, %Read
AV 16OutputVAPercentagePhase1Phase 1 load, % of rated VARead
AV 2UtilityInputVoltage1Phase 1 input voltage, VRead
BV 31OnBattery2UPS on battery after an input problemRead
BV 3LowBatteryBattery too low to keep supporting the loadRead
BV 0LostUPSCommCard lost communication with the UPSRead

Enable & remote start

BACnet is enabled and configured on the network management card (web interface); there is no BMS enable point.

Network setup

Watch out for

APC Easy UPS 3-Phase with Network Management Card AP9547 (BACnet IP) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

128 of 128 shown
Type
AnalogBinaryMulti-stateOther
Show
APC Easy UPS 3-Phase with Network Management Card AP9547 (BACnet IP) BACnet Points List
DescriptionStates
AVmin0RuntimeHow long the UPS can support its present load while running on battery powersRead
AV1BatteryTemperatureTemperature as reported by the sensor in the battery compartment, in Degrees C°CRead
AVmin2UtilityInputVoltage1The AC voltage (VAC) being received by the UPSVRead
AV3UtilityInputVoltage2The AC voltage (VAC) being received by the UPSVRead
AV4UtilityInputVoltage3The AC voltage (VAC) being received by the UPSVRead
AV5UtilityInputVoltage12The AC voltage (VAC) phase to phase being received by the UPSVRead
AV6UtilityInputVoltage23The AC voltage (VAC) phase to phase being received by the UPSVRead
AV7UtilityInputVoltage31The AC voltage (VAC) phase to phase being received by the UPSVRead
AV8UtilityInputCurrent1The current, in Amps, being received by the UPSARead
AV9UtilityInputCurrent2The current, in Amps, being received by the UPSARead
AV10UtilityInputCurrent3The current, in Amps, being received by the UPSARead
AV11UtilityInputFrequencyThe frequency in Hertz (Hz) of the voltage being received by the UPSHzRead
AV12OutputFrequencyThe frequency in Hertz (Hz) of the output voltageHzRead
AV13OutputVoltage1The AC voltage (VAC) that the UPS is supplying to its loadVRead
AV14OutputVoltage2The AC voltage (VAC) that the UPS is supplying to its loadVRead
AV15OutputVoltage3The AC voltage (VAC) that the UPS is supplying to its loadVRead
AVmin16OutputVAPercentagePhase1The UPS load as a percentage of available VA%Read
AV17OutputVAPercentagePhase2The UPS load as a percentage of available VA%Read
AV18OutputVAPercentagePhase3The UPS load as a percentage of available VA%Read
AV19OutputLoadCurrent1The current, in Amps, supplied to the loadARead
AV20OutputLoadCurrent2The current, in Amps, supplied to the loadARead
AV21OutputLoadCurrent3The current, in Amps, supplied to the loadARead
AV22OutputWattsPercentagePhase1The UPS load as a percentage of available Watts%Read
AV23OutputWattsPercentagePhase2The UPS load as a percentage of available Watts%Read
AV24OutputWattsPercentagePhase3The UPS load as a percentage of available Watts%Read
AV25BypassInputFrequencyMeasured frequency on the bypass input for separate bypass feedHzRead
AV26BypassInputVoltage12Bypass phase-to-phase voltage (not on all UPS)VRead
AV27BypassInputVoltage23Bypass phase-to-phase voltage (not on all UPS)VRead
AV28BypassInputVoltage31Bypass phase-to-phase voltage (not on all UPS)VRead
AV29PositiveBatteryVoltageMeasured battery voltage, positive busVRead
AV30NegativeBatteryVoltageMeasured battery voltage - negative battery busVRead
AVmin31BatteryStateOfChargeThe percentage of the UPS battery capacity that is available to support the attached equipment%Read
AV32PositiveBatteryCurrentThe current being battery positiveARead
AV33NegativeBatteryCurrentThe current being battery negativeARead
AV34OutputActivePowerL1Measure the active power on the phase 1kWRead
AV35OutputActivePowerL2Measure the active power on the phase 2kWRead
AV36OutputActivePowerL3Measure the active power on the phase 3kWRead
AV37OutputApparantPowerL1Measure the apparent power on the phase 1kVARead
AV38OutputApparantPowerL2Measure the apparent power on the phase 2kVARead
AV39OutputApparantPowerL3Measure the apparent power on the phase 3kVARead
AV40UPSapparentpowerratingThe rated apparent full powerkVARead
AV41DCcapacitorMaintenanceCycleMeasure DC capacitor maintainance cycle perioddaysRead
AV42ACcapacitorMaintenanceCycleMeasure AC capacitor maintainance cycle perioddaysRead
AV43AuxPowerSupplyMaintenanceCycleMeasure the Aux PowerSupply Maintenance Cycle perioddaysRead
AV44AirFilterMaintenanceCycleMeasure the Air filter maintenance cycle perioddaysRead
AV45BatteryMaintenanceCycleMeasure the battery maintenance cycle perioddaysRead
AV46WarrantyCycleMeasure the Warranty Cycle timeperioddaysRead
AV47DCcapacitorRunningTimeMeasure the DC capacitor running timedaysRead
AV48ACcapacitorRunningTimeMeasure the AC capacitor running timedaysRead
AV49BatteryRunningTimeMeasure the Air filter running time perioddaysRead
AV50AmbientTemperatureMeasure the Ambient temperature°CRead
AV51BypassInputVoltage1The AC voltage (VAC) being received from Bypass SupplyVRead
AV52BypassInputVoltage2The AC voltage (VAC) being received from Bypass SupplyVRead
AV53BypassInputVoltage3The AC voltage (VAC) being received from Bypass SupplyVRead
AV54OutputVoltage12The Phase12 AC voltage (VAC) that the UPS is supplying to its loadVRead
AV55OutputVoltage23The Phase23 AC voltage (VAC) that the UPS is supplying to its loadVRead
AV56OutputVoltage31The Phase31 AC voltage (VAC) that the UPS is supplying to its loadVRead
AV57AuxPowerSupplyRunningTimeMeasure the Aux PowerSupply running timemonthsRead
AV58AirFilterRunningTimeMeasure the Aux PowerSupply running timemonthsRead
AV59WarrantyElapsedTimeMeasure Warranty elapsed timemonthsRead
BVmin0LostUPSCommNMC lost comm with UPS (alarm)Read0=Inactive, 1=Active
BV1OverloadThe load exceeds 100% of rated capacity (alarm)Read0=Inactive, 1=Active
BV2SelfTestInProgressUPS self-test in progress (alarm)Read0=Inactive, 1=Active
BVmin3LowBatteryBattery too low to support the load (alarm)Read0=Inactive, 1=Active
BV4LowBatteryOnBatteryOn battery (alarm)Read0=Inactive, 1=Active
BV5InBypassBypassSwitchIn bypass in response to the bypass switch at the UPS (alarm)Read0=Inactive, 1=Active
BV6FanProblemSystem level fan fault exists (alarm)Read0=Inactive, 1=Active
BV7BatteryChargerInoperableA battery charger is not fully functional (alarm)Read0=Inactive, 1=Active
BV8BatteryDisconnectedThe battery is not installed properly (alarm)Read0=Inactive, 1=Active
BV9LostUPSCommOnBatLost the management interface-to-UPS communication while the UPS was on battery (alarm)Read0=Inactive, 1=Active
BV10UPSTempCriticalRectifier over temperature (alarm)Read0=Inactive, 1=Active
BV11OutputShortCircuitThe output has a short-circuit (alarm)Read0=Inactive, 1=Active
BV12InverterInoperableInverter module is inoperable (alarm)Read0=Inactive, 1=Active
BV13BatteryNearEndOfLifeBattery near end of life (alarm)Read0=Inactive, 1=Active
BV14EPOActiveEPO activated (alarm)Read0=Inactive, 1=Active
BV15WeakBatteryWeak battery exists (alarm)Read0=Inactive, 1=Active
BV16PowerSavingModeHigh Efficiency Mode is no longer disabled from an input relay (alarm)Read0=Inactive, 1=Active
BV17InverterShutdownOverloadInverter overload shutdown (alarm)Read0=Inactive, 1=Active
BV18OverloadOnInstallationOverload On Installation (alarm)Read0=Inactive, 1=Active
BV19RectifierFailurePFC Rectifier is InOperable (alarm)Read0=Inactive, 1=Active
BV20InverterFaultInverter Module InOperable (alarm)Read0=Inactive, 1=Active
BV21AuxPowerFaultAuxiliary Power supply Fault (alarm)Read0=Inactive, 1=Active
BV22InverterOverTemperatureInverter Temperature Overload Exist (alarm)Read0=Inactive, 1=Active
BV23InverterOverLoadInverter Over Load (alarm)Read0=Inactive, 1=Active
BV24UPSOverLoadUPS Over load (alarm)Read0=Inactive, 1=Active
BV25InverterFailureInverter Module is inoperable (alarm)Read0=Inactive, 1=Active
BV26InputFailureUPS: Mains input is not available due to inoperable condition (alarm)Read0=Inactive, 1=Active
BV27RectifierFaultPFC rectifier is inoperable (alarm)Read0=Inactive, 1=Active
BV28LoadNotPoweredThe output power is turned off (alarm)Read0=Inactive, 1=Active
BV29BreakerQ2UOBOpenBreaker Q2 UOB Open (alarm)Read0=Inactive, 1=Active
BV30BypassOverTemperatureBypass Over Temperature (alarm)Read0=Inactive, 1=Active
BVmin31OnBattery2On battery power in response to an input power problem (alarm)Read0=Inactive, 1=Active
BV32LoadkVAAlarmViolationA load (kVA) alarm threshold violation exists (alarm)Read0=Inactive, 1=Active
BV33ManualBypassIn bypass in response to the bypass switch at the UPS, typically for maintenance (alarm)Read0=Inactive, 1=Active
BV34MainsFrequencyFailureMains input frequency is out of tolerance (alarm)Read0=Inactive, 1=Active
BV35MainsVoltageFailureMains input voltage is out of range (alarm)Read0=Inactive, 1=Active
BV36BypassVoltageErrorLowVoltageBypass voltage error, low voltage (alarm)Read0=Inactive, 1=Active
BV37BypassVoltageErrorHighVoltageBypass voltage error, high voltage (alarm)Read0=Inactive, 1=Active
BV38BypassFrequencyFailureBypass input frequency is out of tolerance (alarm)Read0=Inactive, 1=Active
BV39OutputVoltageErrorLowVoltageOutput voltage low (alarm)Read0=Inactive, 1=Active
BV40OutputVoltageErrorHighVoltageOutput voltage high (alarm)Read0=Inactive, 1=Active
BV41OverlaodOnBypassStaticSwitchOverload on bypass static switch (alarm)Read0=Inactive, 1=Active
BV42AmbientTempratureOutOfRangeAmbient temperature out of range (alarm)Read0=Inactive, 1=Active
BV43BypassInputVoltageErrorLowVoltageBypass input voltage is out of tolerance (alarm)Read0=Inactive, 1=Active
BV44BatteriesAreDischargingBatteries are discharging (alarm)Read0=Inactive, 1=Active
BV45BateryCondtionIsWeakBattery capacity is between 50% to 75% (alarm)Read0=Inactive, 1=Active
BV46BateryCondtionIsPoorBattery capacity is lower than 50% (alarm)Read0=Inactive, 1=Active
BV47BatteryVoltErrorVoltageAboveShutdownLevelBattery voltage error - voltage above shutdown level (alarm)Read0=Inactive, 1=Active
BV48OutputVoltageErrorThe output voltage is out of tolerance (alarm)Read0=Inactive, 1=Active
BV49LoadOnUpsIsAboveWarningLevelLoad on UPS is above warning level (alarm)Read0=Inactive, 1=Active
BV50BatteryVoltErrorVoltageBelowShutdownLevelBattery voltage error - voltage below shutdown level (alarm)Read0=Inactive, 1=Active
BV51BatteryBreakerOpenBattery breaker open (alarm)Read0=Inactive, 1=Active
BV52InternalBatterytemperatureExceedsThresholdThe internal battery temperature exceeds the critical threshold (alarm)Read0=Inactive, 1=Active
BV53OperationModeStaticBypassStandbyThe UPS is ready to enter static bypass but awaits permission from the system (alarm)Read0=Inactive, 1=Active
BV54OperationModeInverterStandbyThe UPS is ready to enter battery operation but awaits permission from the system (alarm)Read0=Inactive, 1=Active
BV55TechnicalCheckRequiredTechnical check recommended (alarm)Read0=Inactive, 1=Active
BV56WarrantyExpiringSoonWarranty expiring soon (alarm)Read0=Inactive, 1=Active
BV57BatteriesCheckRequiredThe batteries need to be checked as preventive maintenance is recommended (alarm)Read0=Inactive, 1=Active
BV58AirFilterTechnicalCheckRecommendedThe air filters need to be checked as preventive maintenance is recommended (alarm)Read0=Inactive, 1=Active
BV59FansCheckRecommendedThe fans need to be checked as preventive maintenance is recommended (alarm)Read0=Inactive, 1=Active
CSV0UPSmodelThe UPS model name, up to 24 charactersRead
CSV1UPSserialnumberThe UPS serial number, up to 16 charactersRead
CSV2UPSFirmwareRevisionThe revision number of the UPS firmware, up to 16 charactersRead
CSV3UPSModelFullNameUPS product name, up to 24 charactersRead
CSV4UPSDateOfManufactureUPS date of manufacture, up to 11 charactersRead
MV0LastbatterytransferThe cause of the last switch to battery operationReadNone, Input Failure, UPS Battery Test
MVmin1UPSStateUPS status summaryReadUnknown, Online, Online green, On battery, Self-test, Low battery, Shutdown, Bypass, Fault
MV2LastBatteryTestResultProvide the last battery last resultReadPass, Fail
Object ID lookup: APC Easy UPS 3-Phase with Network Management Card AP9547 point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Easy UPS 3-Phase with Network Management Card AP9547 (BACnet IP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the APC Easy UPS 3-Phase with Network Management Card AP9547 (BACnet IP)

How many BACnet points does the APC Easy UPS 3-Phase with Network Management Card AP9547 (BACnet IP) have?

This list has 128 BACnet objects: 60 analog values, 60 binary values, 3 multi-state values, 5 characterstring values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which APC Easy UPS 3-Phase with Network Management Card AP9547 (BACnet IP) BACnet points are writable?

None of the listed objects are marked writable in the source documentation.

Where is the official APC Easy UPS 3-Phase with Network Management Card AP9547 (BACnet IP) BACnet documentation?

The source is BACnet Application Map for Network Management Card for Easy UPS, 3-Phase (990-6445B), revision 2024-04, published free by APC at https://download.se.com/files?p_Doc_Ref=SPD_CDIG-NMCBAC47_EN.

What are the minimum BACnet points to integrate the APC Easy UPS 3-Phase with Network Management Card AP9547 (BACnet IP)?

Start with MV 1 UPSState (UPS status: online, on battery, bypass, fault); AV 0 Runtime (Battery runtime left at present load, s); AV 31 BatteryStateOfCharge (Battery charge, %); AV 16 OutputVAPercentagePhase1 (Phase 1 load, % of rated VA); AV 2 UtilityInputVoltage1 (Phase 1 input voltage, V); BV 31 OnBattery2 (UPS on battery after an input problem); BV 3 LowBattery (Battery too low to keep supporting the load); BV 0 LostUPSComm (Card lost communication with the UPS).

How do I enable BMS control of the APC Easy UPS 3-Phase with Network Management Card AP9547 (BACnet IP)?

BACnet is enabled and configured on the network management card (web interface); there is no BMS enable point.

How do I check these points on the real Easy UPS 3-Phase with Network Management Card AP9547 (BACnet IP)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.