- Smart-UPS with Network Management Card 2 / 3 (BACnet IP)
UPS (uninterruptible power supply) network card · BACnet points list
APC Smart-UPS with Network Management Card 2 / 3 (BACnet IP) BACnet points list
Updated 4 November 2026
The APC Network Management Card in a Smart-UPS serves BACnet IP. The object list is fixed by the card firmware: Analog Values for runtime, battery, input, output and load readings plus outlet-group and shutdown settings; Binary Values for outlet states, test commands, option enables and about 170 UPS alarm flags; Character String Values for identity text; and Multi-state Values for UPS state, UPS control and outlet-group control. Each object is only present on the UPS families marked in the table.
This page lists 390 BACnet objects for the APC Smart-UPS with Network Management Card 2 / 3 (BACnet IP) — 151 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from APC’s own free documentation, linked below.
- Manufacturer
- APC
- Model
- Smart-UPS with Network Management Card 2 / 3 (BACnet IP)
- Equipment
- UPS (uninterruptible power supply) network card
- Equipment type
- Other equipment
- BACnet objects
- 390 (151 writable)
- Transport
- BACnet IP
- Firmware
- NMC2 application firmware 6.5.6 or later (sumx); NMC3 below 3.0 (su). See notes for NMC3 3.1.
- Also known as
- APC Smart-UPS BACnet, NMC2 BACnet, NMC3 BACnet, AP9630, AP9631, AP9635, AP9640, AP9641, SMT, SMX, SRT, SURT, 990-5916C, APC UPS BACnet application map
Reference only, provided as-is: verify against APC’s current documentation and the live device before use. Not official APC information. Terms of use.
BMS integration notes: APC Smart-UPS with Network Management Card 2 / 3 (BACnet IP)
Enable BACnet on the Network Management Card (sumx/su firmware) and give the card a unique device instance. Read UPS state (MV 5), runtime remaining (AV 0), battery charge (AV 66), load (AV 19) and the alarm flags such as OnBattery, LowBattery and Overload. UPS Control (MV 6) and the outlet-group control MVs switch the UPS or its outlets, so restrict who can write them.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| MV 6 | UPS Control | UPS on/off/reboot/sleep/bypass command | Write |
| MV 5 | UPS state | Online, on battery, bypass, fault and so on | Read |
| AV 0 | Runtime remaining | Battery runtime left, s | Read |
| AV 66 | Battery state of charge | Battery charge, % | Read |
| AV 19 | Output watts phase 1 | Load as % of the watt rating | Read |
| AV 10 | Output voltage 1 | Output voltage, V | Read |
| BV 73 | OnBattery | UPS is running on battery | Read |
| BV 72 | LowBattery | Battery low alarm | Read |
| BV 70 | Overload | Output overload alarm | Read |
| BV 69 | LostUPSComm | Card lost communication with the UPS | Read |
Enable & remote start
BACnet IP is part of the NMC2 'sumx' and NMC3 'su' application firmware and is turned on in the card's configuration. No BMS enable point is needed; UPS Control (MV 6) acts directly on the UPS.
Network setup
- BACnet IP only; BACnet is configured on the Network Management Card (device instance and related settings are covered in the NMC User Guide).
- Check the UPS model prefix on the UPS label (SMT/SMX/SRT, SURT, SURTD) to know which objects it will have.
- On NMC3 firmware 3.1, read the object list again: several BV, MV and CSV instances shift (see notes).
- Alarm BVs can send event notifications; add the BMS as a recipient of NC 0 DefaultNotifier.
Watch out for
- Writing UPS Control or an outlet-group control MV can switch off the protected load.
- BV 23-26 start real UPS tests (self test, alarm tests, runtime calibration); BV 27 cancels a running test.
- Universal I/O probe objects exist only with an AP9631/AP9635 card and a probe fitted.
- Instances differ between NMC2/NMC3 below 3.0 and NMC3 3.1 for alarm flags; remap after a card firmware upgrade.
APC Smart-UPS with Network Management Card 2 / 3 (BACnet IP) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AVmin | 0 | Runtime remaining | Battery runtime left at the present load [SMT/SMX/SRT, SURT, SURTD, other models] | s | Read | |
| AV | 1 | Battery Temperature | Battery compartment temperature [SMT/SMX/SRT, SURT, SURTD, other models] | °C | Read | |
| AV | 2 | Utility voltage 1 | Input voltage, phase 1 [SURTD, other models] | V | Read | |
| AV | 3 | Utility voltage 2 | Input voltage, phase 2 [SURTD, other models] | V | Read | |
| AV | 4 | Utility voltage 3 | Input voltage, phase 3 [other models] | V | Read | |
| AV | 5 | Utility current 1 | Input current, phase 1 [other models] | A | Read | |
| AV | 6 | Utility current 2 | Input current, phase 2 [other models] | A | Read | |
| AV | 7 | Utility current 3 | Input current, phase 3 [other models] | A | Read | |
| AV | 8 | Utility Input frequency | Input frequency [SURT] | Hz | Read | |
| AV | 9 | Output frequency | Output frequency [SURT] | Hz | Read | |
| AVmin | 10 | Output voltage 1 | Output voltage, phase 1 [SMT/SMX/SRT, SURT, SURTD, other models] | V | Read | |
| AV | 11 | Output voltage 2 | Output voltage, phase 2 [SMT/SMX/SRT, SURT, SURTD, other models] | V | Read | |
| AV | 12 | Output voltage 3 | Output voltage, phase 3 [other models] | V | Read | |
| AV | 13 | Output VA phase 1 | Load as % of VA rating, phase 1 [SURTD, other models] | % | Read | |
| AV | 14 | Output VA phase 2 | Load as % of VA rating, phase 2 [SURTD, other models] | % | Read | |
| AV | 15 | Output VA phase 3 | Load as % of VA rating, phase 3 [other models] | % | Read | |
| AV | 16 | Output load current 1 | Output current, phase 1 [SMT/SMX/SRT, SURT, SURTD, other models] | A | Read | |
| AV | 17 | Output load current 2 | Output current, phase 2 [SURTD, other models] | A | Read | |
| AV | 18 | Output load current 3 | Output current, phase 3 [other models] | A | Read | |
| AVmin | 19 | Output watts phase 1 | Load as % of watt rating, phase 1 [SMT/SMX/SRT, SURT, SURTD, other models] | % | Read | |
| AV | 20 | Output watts phase 2 | Load as % of watt rating, phase 2 [SURTD, other models] | % | Read | |
| AV | 21 | Output watts phase 3 | Load as % of watt rating, phase 3 [other models] | % | Read | |
| AV | 22 | Output efficiency | Share of input power delivered to the load [SMT/SMX/SRT, SURT] | % | Read | |
| AV | 23 | Output energy usage | Load energy since last reset to defaults [SMT/SMX/SRT, SURT] | kWh | Read | |
| AV | 24 | Outlet group main power off delay | Delay before the outlet group turns off [SMT/SMX/SRT, SURT] | s | Write | |
| AV | 25 | Outlet group switched 1 power off delay | Delay before the outlet group turns off [SMT/SMX/SRT, SURT] | s | Write | |
| AV | 26 | Outlet group switched 2 power off delay | Delay before the outlet group turns off [SMT/SMX/SRT, SURT] | s | Write | |
| AV | 27 | Outlet group switched 3 power off delay | Delay before the outlet group turns off [SMT/SMX/SRT, SURT] | s | Write | |
| AV | 28 | Outlet group main reboot duration | Off time during an outlet group reboot [SMT/SMX/SRT, SURT] | s | Write | |
| AV | 29 | Outlet group switched 1 reboot duration | Off time during an outlet group reboot [SMT/SMX/SRT, SURT] | s | Write | |
| AV | 30 | Outlet group switched 2 reboot duration | Off time during an outlet group reboot [SMT/SMX/SRT, SURT] | s | Write | |
| AV | 31 | Outlet group switched 3 reboot duration | Off time during an outlet group reboot [SMT/SMX/SRT, SURT] | s | Write | |
| AV | 32 | Outlet group main power on delay | Delay before the outlet group turns on [SMT/SMX/SRT, SURT] | s | Write | |
| AV | 33 | Outlet group switched 1 power on delay | Delay before the outlet group turns on [SMT/SMX/SRT, SURT] | s | Write | |
| AV | 34 | Outlet group switched 2 power on delay | Delay before the outlet group turns on [SMT/SMX/SRT, SURT] | s | Write | |
| AV | 35 | Outlet group switched 3 power on delay | Delay before the outlet group turns on [SMT/SMX/SRT, SURT] | s | Write | |
| AV | 36 | Outlet group main minimum return runtime | Runtime needed before the group turns back on [SMT/SMX/SRT, SURT] | s | Write | |
| AV | 37 | Outlet group switched 1 minimum return runtime | Runtime needed before the group turns back on [SMT/SMX/SRT, SURT] | s | Write | |
| AV | 38 | Outlet group switched 2 minimum return runtime | Runtime needed before the group turns back on [SMT/SMX/SRT, SURT] | s | Write | |
| AV | 39 | Outlet group switched 3 minimum return runtime | Runtime needed before the group turns back on [SMT/SMX/SRT, SURT] | s | Write | |
| AV | 40 | Outlet group main load shed runtime remaining | Group turns off when runtime falls to this [SMT/SMX/SRT, SURT] | s | Write | |
| AV | 41 | Outlet group switched 1 load shed runtime remaining | Group turns off when runtime falls to this [SMT/SMX/SRT, SURT] | s | Write | |
| AV | 42 | Outlet group switched 2 load shed runtime remaining | Group turns off when runtime falls to this [SMT/SMX/SRT, SURT] | s | Write | |
| AV | 43 | Outlet group switched 3load shed runtime remaining | Group turns off when runtime falls to this [SMT/SMX/SRT, SURT] | s | Write | |
| AV | 44 | Outlet group main load shed time on battery | Group turns off after this time on battery [SMT/SMX/SRT, SURT] | s | Write | |
| AV | 45 | Outlet group switched 1 load shed time on battery | Group turns off after this time on battery [SMT/SMX/SRT, SURT] | s | Write | |
| AV | 46 | Outlet group switched 2 load shed time on battery | Group turns off after this time on battery [SMT/SMX/SRT, SURT] | s | Write | |
| AV | 47 | Outlet group switched 3 load shed time on battery | Group turns off after this time on battery [SMT/SMX/SRT, SURT] | s | Write | |
| AV | 48 | Output upper limit | Upper transfer voltage [SMT/SMX/SRT, SURT, SURTD, other models] | V | Write | |
| AV | 49 | Output lower limit | Lower transfer voltage [SMT/SMX/SRT, SURT, SURTD, other models] | V | Write | |
| AV | 50 | Bypass upper limit | Upper bypass voltage limit [SURT, SURTD, other models] | V | Write | |
| AV | 51 | Bypass lower limit | Lower bypass voltage limit [SURT, SURTD, other models] | V | Write | |
| AV | 52 | Low Battery duration | Runtime left that raises the low-battery alarm [SMT/SMX/SRT, SURT, SURTD, other models] | s | Write | |
| AV | 53 | Basic low battery duration | Basic low-battery warning time [SMT/SMX/SRT, SURT, SURTD, other models] | s | Write | |
| AV | 54 | Sleep time | Sleep duration for a sleep command [SMT/SMX/SRT, SURT, SURTD, other models] | h | Write | |
| AV | 55 | Shutdown Delay | Delay before the UPS shuts down [other models] | s | Write | |
| AV | 56 | Minimum return capacity | Battery charge needed before restart [other models] | % | Write | |
| AV | 57 | Return Delay | Delay before restart after power returns [other models] | s | Write | |
| AV | 58 | Maximum required delay | Longest shutdown delay needed by clients [other models] | min | Read | |
| AV | 59 | Bypass input frequency | Bypass input frequency [SURT, SURTD, other models] | Hz | Read | |
| AV | 60 | Bypass input voltage 1 | Bypass input voltage, phase 1 [other models] | V | Read | |
| AV | 61 | Bypass input voltage 2 | Bypass input voltage, phase 2 [other models] | V | Read | |
| AV | 62 | Bypass input voltage 3 | Bypass input voltage, phase 3 [other models] | V | Read | |
| AV | 63 | Positive battery voltage | Battery voltage (positive bus) [SMT/SMX/SRT, SURT, SURTD, other models] | V | Read | |
| AV | 64 | Negative battery voltage | Battery voltage (negative bus) [SURT] | V | Read | |
| AV | 65 | Nominal battery voltage | Nominal battery voltage [other models] | V | Read | |
| AVmin | 66 | Battery state of charge | Battery charge level [SMT/SMX/SRT, SURT, SURTD, other models] | % | Read | |
| AV | 67 | Battery current | Battery current [other models] | A | Read | |
| AV | 68 | Number of external batteries | Count of external battery packs [other models] | Read | ||
| AV | 69 | Controlled Early Shutdown Time On Battery | Early shutdown threshold (time on battery) [other models] | min | Write | |
| AV | 70 | Controlled Early Shutdown Runtime Remaining | Early shutdown threshold (runtime remaining) [other models] | min | Write | |
| AV | 71 | Controlled Early Shutdown Battery Capacity | Early shutdown threshold (battery capacity) [other models] | min | Write | |
| AV | 72 | Controlled Early Shutdown Load Percentage | Early shutdown threshold (load percentage) [other models] | min | Write | |
| AV | 73 | UIO probe 1 temperature | Universal I/O probe reading [SMT/SMX/SRT with AP9631/AP9635 NMC] | °C | Read | |
| AV | 74 | UIO probe 1 humidity | Universal I/O probe reading [SMT/SMX/SRT with AP9631/AP9635 NMC] | % | Read | |
| AV | 75 | UIO probe 1 temperature maximum | Probe alarm threshold [SMT/SMX/SRT with AP9631/AP9635 NMC] | °C | Write | |
| AV | 76 | UIO probe 1 temperature high | Probe alarm threshold [SMT/SMX/SRT with AP9631/AP9635 NMC] | °C | Write | |
| AV | 77 | UIO probe 1 temperature low | Probe alarm threshold [SMT/SMX/SRT with AP9631/AP9635 NMC] | °C | Write | |
| AV | 78 | UIO probe 1 temperature minimum | Probe alarm threshold [SMT/SMX/SRT with AP9631/AP9635 NMC] | °C | Write | |
| AV | 79 | UIO probe 1 temperature hysteresis | Probe alarm hysteresis [SMT/SMX/SRT with AP9631/AP9635 NMC] | °C | Write | |
| AV | 80 | UIO probe 1 humidity maximum | Probe alarm threshold [SMT/SMX/SRT with AP9631/AP9635 NMC] | % | Write | |
| AV | 81 | UIO probe 1 humidity high | Probe alarm threshold [SMT/SMX/SRT with AP9631/AP9635 NMC] | % | Write | |
| AV | 82 | UIO probe 1 humidity low | Probe alarm threshold [SMT/SMX/SRT with AP9631/AP9635 NMC] | % | Write | |
| AV | 83 | UIO probe 1 humidity minimum | Probe alarm threshold [SMT/SMX/SRT with AP9631/AP9635 NMC] | % | Write | |
| AV | 84 | UIO probe 1 humidity hysteresis | Probe alarm hysteresis [SMT/SMX/SRT with AP9631/AP9635 NMC] | % | Write | |
| AV | 85 | UIO probe 1 output relay 1 delay | Time a condition must last before the relay acts [SMT/SMX/SRT with AP9631/AP9635 NMC] | s | Write | |
| AV | 86 | UIO probe 1 output relay 1 hold | Minimum relay hold time after an alarm [SMT/SMX/SRT with AP9631/AP9635 NMC] | s | Write | |
| AV | 87 | UIO probe 2 temperature | Universal I/O probe reading [SMT/SMX/SRT with AP9631 NMC] | °C | Read | |
| AV | 88 | UIO probe 2 humidity | Universal I/O probe reading [SMT/SMX/SRT with AP9631 NMC] | % | Read | |
| AV | 89 | UIO probe 2 temperature maximum | Probe alarm threshold [SMT/SMX/SRT with AP9631 NMC] | °C | Write | |
| AV | 90 | UIO probe 2 temperature high | Probe alarm threshold [SMT/SMX/SRT with AP9631 NMC] | °C | Write | |
| AV | 91 | UIO probe 2 temperature low | Probe alarm threshold [SMT/SMX/SRT with AP9631 NMC] | °C | Write | |
| AV | 92 | UIO probe 2 temperature minimum | Probe alarm threshold [SMT/SMX/SRT with AP9631 NMC] | °C | Write | |
| AV | 93 | UIO probe 2 temperature hysteresis | Probe alarm hysteresis [SMT/SMX/SRT with AP9631 NMC] | °C | Write | |
| AV | 94 | UIO probe 2 humidity maximum | Probe alarm threshold [SMT/SMX/SRT with AP9631 NMC] | % | Write | |
| AV | 95 | UIO probe 2 humidity high | Probe alarm threshold [SMT/SMX/SRT with AP9631 NMC] | % | Write | |
| AV | 96 | UIO probe 2 humidity low | Probe alarm threshold [SMT/SMX/SRT with AP9631 NMC] | % | Write | |
| AV | 97 | UIO probe 2 humidity minimum | Probe alarm threshold [SMT/SMX/SRT with AP9631 NMC] | % | Write | |
| AV | 98 | UIO probe 2 humidity hysteresis | Probe alarm hysteresis [SMT/SMX/SRT with AP9631 NMC] | % | Write | |
| AV | 99 | UIO probe 2 output relay 1 delay | Time a condition must last before the relay acts [SMT/SMX/SRT with AP9631 NMC] | s | Write | |
| AV | 100 | UIO probe 2 output relay 1 hold | Minimum relay hold time after an alarm [SMT/SMX/SRT with AP9631 NMC] | s | Write | |
| BV | 0 | Outlet group main state | Outlet group on/off state [SMT/SMX/SRT, SURT] | Read | ||
| BV | 1 | Outlet group switched 1 state | Outlet group on/off state [SMT/SMX/SRT, SURT] | Read | ||
| BV | 2 | Outlet group switched 2 state | Outlet group on/off state [SMT/SMX/SRT, SURT] | Read | ||
| BV | 3 | Outlet group switched 3 state | Outlet group on/off state [SMT/SMX/SRT, SURT] | Read | ||
| BV | 4 | Outlet group main load shed runtime remaining enable | Enables the matching threshold or action [SMT/SMX/SRT, SURT] | Write | ||
| BV | 5 | Outlet group switched 1 load shed runtime remaining enable | Enables the matching threshold or action [SMT/SMX/SRT, SURT] | Write | ||
| BV | 6 | Outlet group switched 2 load shed runtime remaining enable | Enables the matching threshold or action [SMT/SMX/SRT, SURT] | Write | ||
| BV | 7 | Outlet group switched 3 load shed runtime remaining enable | Enables the matching threshold or action [SMT/SMX/SRT, SURT] | Write | ||
| BV | 8 | Outlet group main load shed time on battery enable | Enables the matching threshold or action [SMT/SMX/SRT, SURT] | Write | ||
| BV | 9 | Outlet group switched 1 load shed time on battery enable | Enables the matching threshold or action [SMT/SMX/SRT, SURT] | Write | ||
| BV | 10 | Outlet group switched 2 load shed time on battery enable | Enables the matching threshold or action [SMT/SMX/SRT, SURT] | Write | ||
| BV | 11 | Outlet group switched 3 load shed time on battery enable | Enables the matching threshold or action [SMT/SMX/SRT, SURT] | Write | ||
| BV | 12 | Outlet group main load shed skip off delay | Load shed option for the outlet group [SMT/SMX/SRT, SURT] | Write | ||
| BV | 13 | Outlet group switched 1 load shed skip off delay | Load shed option for the outlet group [SMT/SMX/SRT, SURT] | Write | ||
| BV | 14 | Outlet group switched 2 load shed skip off delay | Load shed option for the outlet group [SMT/SMX/SRT, SURT] | Write | ||
| BV | 15 | Outlet group switched 3 load shed skip off delay | Load shed option for the outlet group [SMT/SMX/SRT, SURT] | Write | ||
| BV | 16 | Outlet group main load shed stay off after power returns | Load shed option for the outlet group [SMT/SMX/SRT, SURT] | Write | ||
| BV | 17 | Outlet group switched 1 load shed stay off after power returns | Load shed option for the outlet group [SMT/SMX/SRT, SURT] | Write | ||
| BV | 18 | Outlet group switched 2 load shed stay off after power returns | Load shed option for the outlet group [SMT/SMX/SRT, SURT] | Write | ||
| BV | 19 | Outlet group switched 3 load shed stay off after power returns | Load shed option for the outlet group [SMT/SMX/SRT, SURT] | Write | ||
| BV | 20 | Outlet group switched 1 load shed overload | Load shed option for the outlet group [SMT/SMX/SRT, SURT] | Write | ||
| BV | 21 | Outlet group switched 2 load shed overload | Load shed option for the outlet group [SMT/SMX/SRT, SURT] | Write | ||
| BV | 22 | Outlet group switched 3 load shed overload | Load shed option for the outlet group [SMT/SMX/SRT, SURT] | Write | ||
| BV | 23 | Run UPS self test | Command: run ups self test [SMT/SMX/SRT, SURT, SURTD, other models] | Write | ||
| BV | 24 | Run UPS alarm test | Command: run ups alarm test [SMT/SMX/SRT, SURT, SURTD, other models] | Write | ||
| BV | 25 | Run UPS alarm test continuous | Command: run ups alarm test continuous [SMT/SMX/SRT, SURT] | Write | ||
| BV | 26 | Run UPS runtime calibration | Command: run ups runtime calibration [SMT/SMX/SRT, SURT, SURTD, other models] | Write | ||
| BV | 27 | Cancel Test | Command: cancel test [SMT/SMX/SRT, SURT] | Write | ||
| BV | 28 | Controlled Early Shutdown Time On Battery Enable | Enables the matching threshold or action [SMT/SMX/SRT, SURT, SURTD, other models] | Write | ||
| BV | 29 | Controlled Early Shutdown Runtime Remaining Enable | Enables the matching threshold or action [SMT/SMX/SRT, SURT, SURTD, other models] | Write | ||
| BV | 30 | Controlled Early Shutdown Battery Capacity Enable | Enables the matching threshold or action [SMT/SMX/SRT, SURT, SURTD, other models] | Write | ||
| BV | 31 | Controlled Early Shutdown Load Percentage Enable | Enables the matching threshold or action [SMT/SMX/SRT, SURT, SURTD, other models] | Write | ||
| BV | 32 | Controlled Early Shutdown Stay Off After Power Return Enable | Enables the matching threshold or action [SMT/SMX/SRT, SURT, SURTD, other models] | Write | ||
| BV | 33 | UIO probe 1 temperature maximum enable | Enables the matching threshold or action [SMT/SMX/SRT with AP9631/AP9635 NMC] | Write | ||
| BV | 34 | UIO probe 1 temperature high enable | Enables the matching threshold or action [SMT/SMX/SRT with AP9631/AP9635 NMC] | Write | ||
| BV | 35 | UIO probe 1 temperature low enable | Enables the matching threshold or action [SMT/SMX/SRT with AP9631/AP9635 NMC] | Write | ||
| BV | 36 | UIO probe 1 temperature minimum enable | Enables the matching threshold or action [SMT/SMX/SRT with AP9631/AP9635 NMC] | Write | ||
| BV | 37 | UIO probe 1 humidity maximum enable | Enables the matching threshold or action [SMT/SMX/SRT with AP9631/AP9635 NMC] | Write | ||
| BV | 38 | UIO probe 1 humidity high enable | Enables the matching threshold or action [SMT/SMX/SRT with AP9631/AP9635 NMC] | Write | ||
| BV | 39 | UIO probe 1 humidity low enable | Enables the matching threshold or action [SMT/SMX/SRT with AP9631/AP9635 NMC] | Write | ||
| BV | 40 | UIO probe 1 humidity minimum enable | Enables the matching threshold or action [SMT/SMX/SRT with AP9631/AP9635 NMC] | Write | ||
| BV | 41 | UIO probe 1 contact 1enable | Enables the matching threshold or action [SMT/SMX/SRT with AP9631/AP9635 NMC] | Write | ||
| BV | 42 | UIO probe 1 contact 2 enable | Enables the matching threshold or action [SMT/SMX/SRT with AP9631/AP9635 NMC] | Write | ||
| BV | 43 | UIO probe 1 input contact 1 state | Input contact state [SMT/SMX/SRT with AP9631/AP9635 NMC] | Read | ||
| BV | 44 | UIO probe 1 input contact 2 | Input contact state [SMT/SMX/SRT with AP9631/AP9635 NMC] | Read | ||
| BV | 45 | UIO probe 1 input contact 1 normal state | Sets the contact/relay normal state [SMT/SMX/SRT with AP9631/AP9635 NMC] | Write | ||
| BV | 46 | UIO probe 1 input contact 2 normal state | Sets the contact/relay normal state [SMT/SMX/SRT with AP9631/AP9635 NMC] | Write | ||
| BV | 47 | UIO probe 1 contact 1 severity | Alarm severity for the contact [SMT/SMX/SRT with AP9631/AP9635 NMC] | Write | ||
| BV | 48 | UIO probe 1 contact 2 severity | Alarm severity for the contact [SMT/SMX/SRT with AP9631/AP9635 NMC] | Write | ||
| BV | 49 | UIO probe 1 output relay 1 state | Output relay state [SMT/SMX/SRT with AP9631/AP9635 NMC] | Read | ||
| BV | 50 | UIO probe 1 output relay 1 normal state | Sets the contact/relay normal state [SMT/SMX/SRT with AP9631/AP9635 NMC] | Write | ||
| BV | 51 | UIO probe 2 temperature maximum enable | Enables the matching threshold or action [SMT/SMX/SRT with AP9631 NMC] | Write | ||
| BV | 52 | UIO probe 2 temperature high enable | Enables the matching threshold or action [SMT/SMX/SRT with AP9631 NMC] | Write | ||
| BV | 53 | UIO probe 2 temperature low enable | Enables the matching threshold or action [SMT/SMX/SRT with AP9631 NMC] | Write | ||
| BV | 54 | UIO probe 2 temperature minimum enable | Enables the matching threshold or action [SMT/SMX/SRT with AP9631 NMC] | Write | ||
| BV | 55 | UIO probe 2 humidity maximum enable | Enables the matching threshold or action [SMT/SMX/SRT with AP9631 NMC] | Write | ||
| BV | 56 | UIO probe 2 humidity high enable | Enables the matching threshold or action [SMT/SMX/SRT with AP9631 NMC] | Write | ||
| BV | 57 | UIO probe 2 humidity low enable | Enables the matching threshold or action [SMT/SMX/SRT with AP9631 NMC] | Write | ||
| BV | 58 | UIO probe 2 humidity minimum enable | Enables the matching threshold or action [SMT/SMX/SRT with AP9631 NMC] | Write | ||
| BV | 59 | UIO probe 2 contact 1enable | Enables the matching threshold or action [SMT/SMX/SRT with AP9631 NMC] | Write | ||
| BV | 60 | UIO probe 2 contact 2 enable | Enables the matching threshold or action [SMT/SMX/SRT with AP9631 NMC] | Write | ||
| BV | 61 | UIO probe 2 input contact 1 state | Input contact state [SMT/SMX/SRT with AP9631 NMC] | Read | ||
| BV | 62 | UIO probe 2 input contact 2 state | Input contact state [SMT/SMX/SRT with AP9631 NMC] | Read | ||
| BV | 63 | UIO probe 2 input contact 1 normal state | Sets the contact/relay normal state [SMT/SMX/SRT with AP9631 NMC] | Write | ||
| BV | 64 | UIO probe 2 input contact 2 normal state | Sets the contact/relay normal state [SMT/SMX/SRT with AP9631 NMC] | Write | ||
| BV | 65 | UIO probe 2 contact 1 severity | Alarm severity for the contact [SMT/SMX/SRT with AP9631 NMC] | Write | ||
| BV | 66 | UIO probe 2 contact 2 severity | Alarm severity for the contact [SMT/SMX/SRT with AP9631 NMC] | Write | ||
| BV | 67 | UIO probe 2 output relay 1 state | Output relay state [SMT/SMX/SRT with AP9631 NMC] | Read | ||
| BV | 68 | UIO probe 2 output relay 1 normal state | Sets the contact/relay normal state [SMT/SMX/SRT with AP9631 NMC] | Write | ||
| BVmin | 69 | LostUPSComm | UPS alarm/event flag | Read | ||
| BVmin | 70 | Overload | UPS alarm/event flag | Read | ||
| BV | 71 | SelfTestFailed | UPS alarm/event flag | Read | ||
| BVmin | 72 | LowBattery | UPS alarm/event flag | Read | ||
| BVmin | 73 | OnBattery | UPS alarm/event flag | Read | ||
| BV | 74 | LowInputVoltage | UPS alarm/event flag | Read | ||
| BV | 75 | HighInputVoltage | UPS alarm/event flag | Read | ||
| BV | 76 | MainInputBad | UPS alarm/event flag | Read | ||
| BV | 77 | LowBattery2 | UPS alarm/event flag | Read | ||
| BV | 78 | OutputOff | UPS alarm/event flag | Read | ||
| BV | 79 | ShutdownWaitingForPowerReturn | UPS alarm/event flag | Read | ||
| BV | 80 | BadBattery | UPS alarm/event flag | Read | ||
| BV | 81 | InBypassInternalHardwareCondition | UPS alarm/event flag | Read | ||
| BV | 82 | InBypassFrontPanelSoftware | UPS alarm/event flag | Read | ||
| BV | 83 | InBypassBypassSwitch | UPS alarm/event flag | Read | ||
| BV | 84 | BypassPowerSupplyProblem | UPS alarm/event flag | Read | ||
| BV | 85 | FanProblem | UPS alarm/event flag | Read | ||
| BV | 86 | LostBattComm | UPS alarm/event flag | Read | ||
| BV | 87 | RuntimeCalStarted | UPS alarm/event flag | Read | ||
| BV | 88 | GracefulShutdownInProgress | UPS alarm/event flag | Read | ||
| BV | 89 | AvrRelayInoperable | UPS alarm/event flag | Read | ||
| BV | 90 | AbnormaOutputVoltage | UPS alarm/event flag | Read | ||
| BV | 91 | BatteryChargerInoperable | UPS alarm/event flag | Read | ||
| BV | 92 | InternalBattTempHigh | UPS alarm/event flag | Read | ||
| BV | 93 | BatteryDisconnected | UPS alarm/event flag | Read | ||
| BV | 94 | OutletGroupOff | UPS alarm/event flag | Read | ||
| BV | 95 | DcImbalance | UPS alarm/event flag | Read | ||
| BV | 96 | MainRelayInoperable | UPS alarm/event flag | Read | ||
| BV | 97 | BypassRelayInoperable | UPS alarm/event flag | Read | ||
| BV | 98 | LostUPSCommOnBat | UPS alarm/event flag | Read | ||
| BV | 99 | PFCInputRelayInoperable | UPS alarm/event flag | Read | ||
| BV | 100 | UPSTempCritical | UPS alarm/event flag | Read | ||
| BV | 101 | BattVoltageHigh | UPS alarm/event flag | Read | ||
| BV | 102 | EepromInoperable | UPS alarm/event flag | Read | ||
| BV | 103 | BattTempSensorIssue | UPS alarm/event flag | Read | ||
| BV | 104 | BattBusSoftStartInoperable | UPS alarm/event flag | Read | ||
| BV | 105 | BattVoltageSenseIssue | UPS alarm/event flag | Read | ||
| BV | 106 | OutputShortCircuit | UPS alarm/event flag | Read | ||
| BV | 107 | OutputRelayInoperable | UPS alarm/event flag | Read | ||
| BV | 108 | PfcInoperable | UPS alarm/event flag | Read | ||
| BV | 109 | DcBusOvervoltage | UPS alarm/event flag | Read | ||
| BV | 110 | InverterInoperable | UPS alarm/event flag | Read | ||
| BV | 111 | OvercurrentTrip | UPS alarm/event flag | Read | ||
| BV | 112 | BypassPfcRelayInoperable | UPS alarm/event flag | Read | ||
| BV | 113 | DcBusSoftStartInoperable | UPS alarm/event flag | Read | ||
| BV | 114 | GreenRelayCondition | UPS alarm/event flag | Read | ||
| BV | 115 | DcOutputCondition | UPS alarm/event flag | Read | ||
| BV | 116 | DcBusCondition | UPS alarm/event flag | Read | ||
| BV | 117 | PowerSystemSensorCondition | UPS alarm/event flag | Read | ||
| BV | 118 | AdConverterInoperable | UPS alarm/event flag | Read | ||
| BV | 119 | LogicPowerSupplyInoperable | UPS alarm/event flag | Read | ||
| BV | 120 | BackfeedRelayInoperable | UPS alarm/event flag | Read | ||
| BV | 121 | UpsInternalCommError | UPS alarm/event flag | Read | ||
| BV | 122 | FirmwareTransferToUpsDidNotSucceed | UPS alarm/event flag | Read | ||
| BV | 123 | UpsInvalidFirmware | UPS alarm/event flag | Read | ||
| BV | 124 | WarrantyExpiringSoon | UPS alarm/event flag | Read | ||
| BV | 125 | TechnicalCheckRecommended | UPS alarm/event flag | Read | ||
| BV | 126 | BatteryNearEndOfLife | UPS alarm/event flag | Read | ||
| BV | 127 | BatteryMeasureLifeNearEnd | UPS alarm/event flag | Read | ||
| BV | 128 | BatteryLifeExceeded | UPS alarm/event flag | Read | ||
| BV | 129 | BatteryTempWarning | UPS alarm/event flag | Read | ||
| BV | 130 | BatteryGeneralCondition | UPS alarm/event flag | Read | ||
| BV | 131 | BatteryCommLost | UPS alarm/event flag | Read | ||
| BV | 132 | BatteryPackDisconnected | UPS alarm/event flag | Read | ||
| BV | 133 | BatteryFirmwareMismatch | UPS alarm/event flag | Read | ||
| BV | 134 | BatteryTempSensorNotOperating | UPS alarm/event flag | Read | ||
| BV | 135 | LocalDisplayButtonIssue | UPS alarm/event flag | Read | ||
| BV | 136 | UpsNeedsFactorySetup | UPS alarm/event flag | Read | ||
| BV | 137 | EpoActive | UPS alarm/event flag | Read | ||
| BV | 138 | FirmwareMismatch | UPS alarm/event flag | Read | ||
| BV | 139 | OscillatorInoperable | UPS alarm/event flag | Read | ||
| BV | 140 | MeasureMismatch | UPS alarm/event flag | Read | ||
| BV | 141 | GeneralSubsystemCondition | UPS alarm/event flag | Read | ||
| BV | 142 | LogicPowerSuppyRelayCondition | UPS alarm/event flag | Read | ||
| BV | 143 | PowerSystemCondition | UPS alarm/event flag | Read | ||
| BV | 144 | MaintenanceModeForFan | UPS alarm/event flag | Read | ||
| BV | 145 | ServiceBypassInBypass | UPS alarm/event flag | Read | ||
| BV | 146 | ServiceBypassDisconnected | UPS alarm/event flag | Read | ||
| BV | 147 | ServiceBypassOutputCondition | UPS alarm/event flag | Read | ||
| BV | 148 | ServiceBypassInternalCondition | UPS alarm/event flag | Read | ||
| BV | 149 | InTemporaryBypass | UPS alarm/event flag | Read | ||
| BV | 150 | PowerModuleInoperable | UPS alarm/event flag | Read | ||
| BV | 151 | BatteryInoperable | UPS alarm/event flag | Read | ||
| BV | 152 | LoadKvaAlarmViolation | UPS alarm/event flag | Read | ||
| BV | 153 | InputVoltageFreqPreventsBypass | UPS alarm/event flag | Read | ||
| BV | 154 | BypassDueToInternalHardwareCondition | UPS alarm/event flag | Read | ||
| BV | 155 | BypassDueToOverload | UPS alarm/event flag | Read | ||
| BV | 156 | BypassDueToMaintenance | UPS alarm/event flag | Read | ||
| BV | 157 | SystemFanInoperable | UPS alarm/event flag | Read | ||
| BV | 158 | RuntimeAlarmViolation | UPS alarm/event flag | Read | ||
| BV | 159 | ExtendedRunFrameInoperable | UPS alarm/event flag | Read | ||
| BV | 160 | OutputVoltageOutsideLimits | UPS alarm/event flag | Read | ||
| BV | 161 | PhaseSyncCondition | UPS alarm/event flag | Read | ||
| BV | 162 | BatteryNotInstalledProperly | UPS alarm/event flag | Read | ||
| BV | 163 | BatteryVoltageExceedsNominal | UPS alarm/event flag | Read | ||
| BV | 164 | SiteWiringFault | UPS alarm/event flag | Read | ||
| BV | 165 | NumBatteriesIncreased | UPS alarm/event flag | Read | ||
| BV | 166 | NumBatteryDecreased | UPS alarm/event flag | Read | ||
| BV | 167 | ExtendedRunFramesIncreased | UPS alarm/event flag | Read | ||
| BV | 168 | ExtendedRunFramesDecreased | UPS alarm/event flag | Read | ||
| BV | 169 | ExternalSwitchQ001Closed | UPS alarm/event flag | Read | ||
| BV | 170 | ExternalSwitchQ002Closed | UPS alarm/event flag | Read | ||
| BV | 171 | ExternalSwitchQ003Closed | UPS alarm/event flag | Read | ||
| BV | 172 | ExternalSwitchQ004Closed | UPS alarm/event flag | Read | ||
| BV | 173 | ExternalSwitchQ005Closed | UPS alarm/event flag | Read | ||
| BV | 174 | ExternalSwitchQ006Closed | UPS alarm/event flag | Read | ||
| BV | 175 | ExternalSwitchQ007Closed | UPS alarm/event flag | Read | ||
| BV | 176 | ExternalSwitchQ008Closed | UPS alarm/event flag | Read | ||
| BV | 177 | ExternalSwitchQ009Closed | UPS alarm/event flag | Read | ||
| BV | 178 | ExternalSwitchQ0010Closed | UPS alarm/event flag | Read | ||
| BV | 179 | EpoActive2 | UPS alarm/event flag | Read | ||
| BV | 180 | StaticBypassSwitchInoperable | UPS alarm/event flag | Read | ||
| BV | 181 | SystemStartupConfigProblem | UPS alarm/event flag | Read | ||
| BV | 182 | PsuInoperable | UPS alarm/event flag | Read | ||
| BV | 183 | WeakBattery | UPS alarm/event flag | Read | ||
| BV | 184 | HighBatteryTemperature | UPS alarm/event flag | Read | ||
| BV | 185 | InternalMechanicalBypass | UPS alarm/event flag | Read | ||
| BV | 186 | LostParallelRedundancy | UPS alarm/event flag | Read | ||
| BV | 187 | ParallelCommCondition1 | UPS alarm/event flag | Read | ||
| BV | 188 | ParalletlCommCondition2 | UPS alarm/event flag | Read | ||
| BV | 189 | AuxCommCondition | UPS alarm/event flag | Read | ||
| BV | 190 | ParallelTerminationCondition1 | UPS alarm/event flag | Read | ||
| BV | 191 | ParallelTerminationCondition2 | UPS alarm/event flag | Read | ||
| BV | 192 | AuxTerminationCondition | UPS alarm/event flag | Read | ||
| BV | 193 | NoMasterPresent | UPS alarm/event flag | Read | ||
| BV | 194 | ParallelOverload | UPS alarm/event flag | Read | ||
| BV | 195 | ParallelConfigCondition | UPS alarm/event flag | Read | ||
| BV | 196 | ChangeDustFilterSoon | UPS alarm/event flag | Read | ||
| BV | 197 | ChangeDustFilterNow | UPS alarm/event flag | Read | ||
| BV | 198 | UioInputContact1Critical1 | UPS alarm/event flag | Read | ||
| BV | 199 | UioInputContact1Critical2 | UPS alarm/event flag | Read | ||
| BV | 200 | UioInputContact2Critical1 | UPS alarm/event flag | Read | ||
| BV | 201 | UioInputContact2Critical2 | UPS alarm/event flag | Read | ||
| BV | 202 | UioTempMinThresholdViolation1 | UPS alarm/event flag | Read | ||
| BV | 203 | UioTempMinThresholdViolation2 | UPS alarm/event flag | Read | ||
| BV | 204 | UioTempLowThresholdViolation1 | UPS alarm/event flag | Read | ||
| BV | 205 | UioTempLowThresholdViolation2 | UPS alarm/event flag | Read | ||
| BV | 206 | UioTempHighThresholdViolation1 | UPS alarm/event flag | Read | ||
| BV | 207 | UioTempHighThresholdViolation2 | UPS alarm/event flag | Read | ||
| BV | 208 | UioTempMaxThresholdViolation1 | UPS alarm/event flag | Read | ||
| BV | 209 | UioTempMaxThresholdViolation2 | UPS alarm/event flag | Read | ||
| BV | 210 | UioHumidMinThresholdViolation1 | UPS alarm/event flag | Read | ||
| BV | 211 | UioHumidMinThresholdViolation2 | UPS alarm/event flag | Read | ||
| BV | 212 | UioHumidLowThresholdViolation1 | UPS alarm/event flag | Read | ||
| BV | 213 | UioHumidLowThresholdViolation2 | UPS alarm/event flag | Read | ||
| BV | 214 | UioHumidHighThresholdViolation1 | UPS alarm/event flag | Read | ||
| BV | 215 | UioHumidHighThresholdViolation2 | UPS alarm/event flag | Read | ||
| BV | 216 | UioHumidMaxThresholdViolation1 | UPS alarm/event flag | Read | ||
| BV | 217 | UioHumidMaxThresholdViolation2 | UPS alarm/event flag | Read | ||
| BV | 218 | UioLostComm1 | UPS alarm/event flag | Read | ||
| BV | 219 | UioLostComm2 | UPS alarm/event flag | Read | ||
| BV | 220 | UioCriticalFault | UPS alarm/event flag | Read | ||
| BV | 221 | UioOutputRelayAbnormalState1 | UPS alarm/event flag | Read | ||
| BV | 222 | UioOutputRelayAbnormalState2 | UPS alarm/event flag | Read | ||
| BV | 223 | UioInputContact1Warning1 | UPS alarm/event flag | Read | ||
| BV | 224 | UioInputContact1Warning2 | UPS alarm/event flag | Read | ||
| BV | 225 | UioInputContact2Warning1 | UPS alarm/event flag | Read | ||
| BV | 226 | UioInputContact2Warning2 | UPS alarm/event flag | Read | ||
| BV | 227 | InputContactOutputRelayFault | UPS alarm/event flag | Read | ||
| BV | 228 | AirFilterWarning | UPS alarm/event flag | Read | ||
| BV | 229 | BatteryPackIncompatible | UPS alarm/event flag | Read | ||
| BV | 230 | UpsInputContact1AbnormalState | UPS alarm/event flag | Read | ||
| BV | 231 | UpsInputContact2AbnormalState | UPS alarm/event flag | Read | ||
| BV | 232 | UpsOutputRelay1AbnormalState | UPS alarm/event flag | Read | ||
| BV | 233 | UpsOutputRelay2AbnormalState | UPS alarm/event flag | Read | ||
| BV | 234 | UpsOutputRelay3AbnormalState | UPS alarm/event flag | Read | ||
| BV | 235 | UpsOutputRelay4AbnormalState | UPS alarm/event flag | Read | ||
| BV | 236 | UpsOutputRelay5AbnormalState | UPS alarm/event flag | Read | ||
| BV | 237 | UpsOutputRelay6AbnormalState | UPS alarm/event flag | Read | ||
| CSV | 0 | UPS model | Text, up to 24 characters [SMT/SMX/SRT, SURT, SURTD, other models] | Read | ||
| CSV | 1 | UPS serial number | Text, up to 16 characters [SMT/SMX/SRT, SURT, SURTD, other models] | Read | ||
| CSV | 2 | UPS manufacture date | Text, up to 16 characters [SMT/SMX/SRT, SURT, SURTD, other models] | Read | ||
| CSV | 3 | User-specified battery replacement date | Text, up to 16 characters [SMT/SMX/SRT, SURT, SURTD, other models] | Read | ||
| CSV | 4 | UPS apparent power rating | Text, up to 16 characters [SMT/SMX/SRT, SURT] | Read | ||
| CSV | 5 | UPS real power rating | Text, up to 16 characters [SMT/SMX/SRT, SURT] | Read | ||
| CSV | 6 | UPS external battery SKU | Text, up to 16 characters [SMT/SMX/SRT, SURT] | Read | ||
| CSV | 7 | UPS SKU | Text, up to 16 characters [SMT/SMX/SRT, SURT] | Read | ||
| CSV | 8 | UPS Firmware Revision | Text, up to 16 characters [SMT/SMX/SRT, SURT, SURTD, other models] | Read | ||
| CSV | 9 | UPS Internal Battery SKU | Text, up to 16 characters [SMT/SMX/SRT, SURT] | Read | ||
| CSV | 10 | Outlet group main name | Text, up to 16 characters [SMT/SMX/SRT, SURT, SURTD, other models] | Write | ||
| CSV | 11 | Outlet group switched 1 name | Text, up to 16 characters [SMT/SMX/SRT, SURT, SURTD, other models] | Write | ||
| CSV | 12 | Outlet group switched 2 name | Text, up to 16 characters [SMT/SMX/SRT, SURT, SURTD, other models] | Write | ||
| CSV | 13 | Outlet group switched 3 name | Text, up to 16 characters [SMT/SMX/SRT, SURT, SURTD, other models] | Write | ||
| CSV | 14 | Output frequency setting | Output frequency setting as text [SURT] | Read | ||
| CSV | 15 | UPS name | Text, up to 24 characters [SMT/SMX/SRT, SURT, SURTD, other models] | Write | ||
| CSV | 16 | Next battery replacement date | Text, up to 16 characters [SMT/SMX/SRT, SURT] | Read | ||
| CSV | 17 | Self test result | Text, up to 100 characters [SMT/SMX/SRT, SURT, SURTD, other models] | Read | ||
| CSV | 18 | Runtime calibration result | Text, up to 100 characters [SMT/SMX/SRT, SURT, SURTD, other models] | Read | ||
| CSV | 19 | UIO probe 1 temperature and humidity name | Text, up to 20 characters [SMT/SMX/SRT with AP9631/AP9635 NMC] | Write | ||
| CSV | 20 | UIO probe 1 temperature and humidity location | Text, up to 20 characters [SMT/SMX/SRT with AP9631/AP9635 NMC] | Write | ||
| CSV | 21 | UIO probe 1 contact 1 name | Text, up to 20 characters [SMT/SMX/SRT with AP9631/AP9635 NMC] | Write | ||
| CSV | 22 | UIO probe 1 contact 2 name | Text, up to 20 characters [SMT/SMX/SRT with AP9631/AP9635 NMC] | Write | ||
| CSV | 23 | UIO probe 1 contact 1 location | Text, up to 20 characters [SMT/SMX/SRT with AP9631/AP9635 NMC] | Write | ||
| CSV | 24 | UIO probe 1 contact 2 location | Text, up to 20 characters [SMT/SMX/SRT with AP9631/AP9635 NMC] | Write | ||
| CSV | 25 | UIO probe 1 output relay 1 name | Text, up to 20 characters [SMT/SMX/SRT with AP9631/AP9635 NMC] | Write | ||
| CSV | 26 | UIO probe 1 output relay 1 location | Text, up to 20 characters [SMT/SMX/SRT with AP9631/AP9635 NMC] | Write | ||
| CSV | 27 | UIO probe 2 temperature and humidity name | Text, up to 20 characters [SMT/SMX/SRT with AP9631 NMC] | Write | ||
| CSV | 28 | UIO probe 2 temperature and humidity location | Text, up to 20 characters [SMT/SMX/SRT with AP9631 NMC] | Write | ||
| CSV | 29 | UIO probe 2 contact 1 name | Text, up to 20 characters [SMT/SMX/SRT with AP9631 NMC] | Write | ||
| CSV | 30 | UIO probe 2 contact 2 name | Text, up to 20 characters [SMT/SMX/SRT with AP9631 NMC] | Write | ||
| CSV | 31 | UIO probe 2 contact 1 location | Text, up to 20 characters [SMT/SMX/SRT with AP9631 NMC] | Write | ||
| CSV | 32 | UIO probe 2 contact 2 location | Text, up to 20 characters [SMT/SMX/SRT with AP9631 NMC] | Write | ||
| CSV | 33 | UIO probe 2 output relay 1 name | Text, up to 20 characters [SMT/SMX/SRT with AP9631 NMC] | Write | ||
| CSV | 34 | UIO probe 2 output relay 1 location | Text, up to 20 characters [SMT/SMX/SRT with AP9631 NMC] | Write | ||
| MV | 0 | Last battery transfer | Cause of the last transfer to battery [SMT/SMX/SRT, SURT, SURTD, other models] | Read | Options in printed order: none, unknown, high input voltage, low input voltage, distorted input, rapid change input voltage, high input frequency, low input frequency, freq and/or phase difference, test, general error, power system error, battery system error, distorted inverter output, epo interface, graceful shutdown | |
| MV | 1 | Rated Output voltage setting | Rated output voltage setting [SMT/SMX/SRT, SURT, SURTD, other models] | Read | Options in printed order: 100, 120, 200, 208, 220, 230, 240, 380, 400, 415, 480, 110, 127, Auto_120, 120/208, 120/240, 100/200, 225, 115 | |
| MV | 2 | Sensitivity | Input power sensitivity [SMT/SMX/SRT, SURT, SURTD, other models] | Write | Options in printed order: normal, reduced, low | |
| MV | 3 | Audible Alarm | When the UPS beeper sounds [SMT/SMX/SRT, SURT, SURTD, other models] | Write | Options in printed order: at power outage, at low battery, mute, never | |
| MV | 4 | Self test schedule | Automatic self-test schedule [SMT/SMX/SRT, SURT, SURTD, other models] | Write | Options in printed order: never, startup, every 7, every 14, startup and every 7 since test, startup and every 14 since test | |
| MVmin | 5 | UPS state | Present UPS operating state [SMT/SMX/SRT, SURT, SURTD, other models] | Read | Options in printed order: unknown, online, online green, on battery, sleep, shutdown, fault, self test, calibration, bypass, low battery | |
| MVmin | 6 | UPS Control | Command to switch the UPS on, off, bypass, reboot or sleep [all models] | Write | Options in printed order: do nothing, on immediately, on delayed, off immediately, off delayed, bypass, return from bypass, reboot immediately, reboot delayed, sleep immediately, sleep delayed | |
| MV | 7 | Main Outlet Group control | Command for the main outlet group [SMT/SMX/SRT, SURT] | Write | Options in printed order: do nothing, cancel, on immediately, on delayed, off immediately, off delayed, reboot immediately, reboot delayed, shutdown immediately with ac restart, shutdown delayed with ac restart | |
| MV | 8 | Switched Outlet group 1 control | Command for switched outlet group 1 [SMT/SMX/SRT, SURT] | Write | Options in printed order: do nothing, cancel, on immediately, on delayed, off immediately, off delayed, reboot immediately, reboot delayed, shutdown immediately with ac restart, shutdown delayed with ac restart | |
| MV | 9 | Switched Outlet group 2 control | Command for switched outlet group 2 [SMT/SMX/SRT, SURT] | Write | Options in printed order: do nothing, cancel, on immediately, on delayed, off immediately, off delayed, reboot immediately, reboot delayed, shutdown immediately with ac restart, shutdown delayed with ac restart | |
| MV | 10 | Switched Outlet group 3 control | Command for switched outlet group 3 [SMT/SMX/SRT, SURT] | Write | Options in printed order: do nothing, cancel, on immediately, on delayed, off immediately, off delayed, reboot immediately, reboot delayed, shutdown immediately with ac restart, shutdown delayed with ac restart | |
| MV | 11 | UIO probe 1 temperature and humidity status | Probe status [SMT/SMX/SRT with AP9631/AP9635 NMC] | Read | Options in printed order: not present, ok, warning, critical | |
| MV | 12 | UIO probe 1 contact status | Probe status [SMT/SMX/SRT with AP9631/AP9635 NMC] | Read | Options in printed order: not present, ok, warning, critical | |
| MV | 13 | UIO probe 2 temperature and humidity status | Probe status [SMT/SMX/SRT with AP9631 NMC] | Read | Options in printed order: not present, ok, warning, critical | |
| MV | 14 | UIO probe 2 contact status | Probe status [SMT/SMX/SRT with AP9631 NMC] | Read | Options in printed order: not present, ok, warning, critical | |
| NC | 0 | DefaultNotifier | Default notification class for UPS alarm BVs | Write |
No points match these filters.
Object ID lookup: APC Smart-UPS with Network Management Card 2 / 3 point IDs by name
AV0Runtime remainingAV1Battery TemperatureAV2Utility voltage 1AV3Utility voltage 2AV4Utility voltage 3AV5Utility current 1AV6Utility current 2AV7Utility current 3AV8Utility Input frequencyAV9Output frequencyAV10Output voltage 1AV11Output voltage 2AV12Output voltage 3AV13Output VA phase 1AV14Output VA phase 2AV15Output VA phase 3AV16Output load current 1AV17Output load current 2AV18Output load current 3AV19Output watts phase 1AV20Output watts phase 2AV21Output watts phase 3AV22Output efficiencyAV23Output energy usageAV24Outlet group main power off delayAV25Outlet group switched 1 power off delayAV26Outlet group switched 2 power off delayAV27Outlet group switched 3 power off delayAV28Outlet group main reboot durationAV29Outlet group switched 1 reboot durationAV30Outlet group switched 2 reboot durationAV31Outlet group switched 3 reboot durationAV32Outlet group main power on delayAV33Outlet group switched 1 power on delayAV34Outlet group switched 2 power on delayAV35Outlet group switched 3 power on delayAV36Outlet group main minimum return runtimeAV37Outlet group switched 1 minimum return runtimeAV38Outlet group switched 2 minimum return runtimeAV39Outlet group switched 3 minimum return runtimeAV40Outlet group main load shed runtime remainingAV41Outlet group switched 1 load shed runtime remainingAV42Outlet group switched 2 load shed runtime remainingAV43Outlet group switched 3load shed runtime remainingAV44Outlet group main load shed time on batteryAV45Outlet group switched 1 load shed time on batteryAV46Outlet group switched 2 load shed time on batteryAV47Outlet group switched 3 load shed time on batteryAV48Output upper limitAV49Output lower limitAV50Bypass upper limitAV51Bypass lower limitAV52Low Battery durationAV53Basic low battery durationAV54Sleep timeAV55Shutdown DelayAV56Minimum return capacityAV57Return DelayAV58Maximum required delayAV59Bypass input frequencyAV60Bypass input voltage 1AV61Bypass input voltage 2AV62Bypass input voltage 3AV63Positive battery voltageAV64Negative battery voltageAV65Nominal battery voltageAV66Battery state of chargeAV67Battery currentAV68Number of external batteriesAV69Controlled Early Shutdown Time On BatteryAV70Controlled Early Shutdown Runtime RemainingAV71Controlled Early Shutdown Battery CapacityAV72Controlled Early Shutdown Load PercentageAV73UIO probe 1 temperatureAV74UIO probe 1 humidityAV75UIO probe 1 temperature maximumAV76UIO probe 1 temperature highAV77UIO probe 1 temperature lowAV78UIO probe 1 temperature minimumAV79UIO probe 1 temperature hysteresisAV80UIO probe 1 humidity maximumAV81UIO probe 1 humidity highAV82UIO probe 1 humidity lowAV83UIO probe 1 humidity minimumAV84UIO probe 1 humidity hysteresisAV85UIO probe 1 output relay 1 delayAV86UIO probe 1 output relay 1 holdAV87UIO probe 2 temperatureAV88UIO probe 2 humidityAV89UIO probe 2 temperature maximumAV90UIO probe 2 temperature highAV91UIO probe 2 temperature lowAV92UIO probe 2 temperature minimumAV93UIO probe 2 temperature hysteresisAV94UIO probe 2 humidity maximumAV95UIO probe 2 humidity highAV96UIO probe 2 humidity lowAV97UIO probe 2 humidity minimumAV98UIO probe 2 humidity hysteresisAV99UIO probe 2 output relay 1 delayAV100UIO probe 2 output relay 1 holdBV0Outlet group main stateBV1Outlet group switched 1 stateBV2Outlet group switched 2 stateBV3Outlet group switched 3 stateBV4Outlet group main load shed runtime remaining enableBV5Outlet group switched 1 load shed runtime remaining enableBV6Outlet group switched 2 load shed runtime remaining enableBV7Outlet group switched 3 load shed runtime remaining enableBV8Outlet group main load shed time on battery enableBV9Outlet group switched 1 load shed time on battery enableBV10Outlet group switched 2 load shed time on battery enableBV11Outlet group switched 3 load shed time on battery enableBV12Outlet group main load shed skip off delayBV13Outlet group switched 1 load shed skip off delayBV14Outlet group switched 2 load shed skip off delayBV15Outlet group switched 3 load shed skip off delayBV16Outlet group main load shed stay off after power returnsBV17Outlet group switched 1 load shed stay off after power returnsBV18Outlet group switched 2 load shed stay off after power returnsBV19Outlet group switched 3 load shed stay off after power returnsBV20Outlet group switched 1 load shed overloadBV21Outlet group switched 2 load shed overloadBV22Outlet group switched 3 load shed overloadBV23Run UPS self testBV24Run UPS alarm testBV25Run UPS alarm test continuousBV26Run UPS runtime calibrationBV27Cancel TestBV28Controlled Early Shutdown Time On Battery EnableBV29Controlled Early Shutdown Runtime Remaining EnableBV30Controlled Early Shutdown Battery Capacity EnableBV31Controlled Early Shutdown Load Percentage EnableBV32Controlled Early Shutdown Stay Off After Power Return EnableBV33UIO probe 1 temperature maximum enableBV34UIO probe 1 temperature high enableBV35UIO probe 1 temperature low enableBV36UIO probe 1 temperature minimum enableBV37UIO probe 1 humidity maximum enableBV38UIO probe 1 humidity high enableBV39UIO probe 1 humidity low enableBV40UIO probe 1 humidity minimum enableBV41UIO probe 1 contact 1enableBV42UIO probe 1 contact 2 enableBV43UIO probe 1 input contact 1 stateBV44UIO probe 1 input contact 2BV45UIO probe 1 input contact 1 normal stateBV46UIO probe 1 input contact 2 normal stateBV47UIO probe 1 contact 1 severityBV48UIO probe 1 contact 2 severityBV49UIO probe 1 output relay 1 stateBV50UIO probe 1 output relay 1 normal stateBV51UIO probe 2 temperature maximum enableBV52UIO probe 2 temperature high enableBV53UIO probe 2 temperature low enableBV54UIO probe 2 temperature minimum enableBV55UIO probe 2 humidity maximum enableBV56UIO probe 2 humidity high enableBV57UIO probe 2 humidity low enableBV58UIO probe 2 humidity minimum enableBV59UIO probe 2 contact 1enableBV60UIO probe 2 contact 2 enableBV61UIO probe 2 input contact 1 stateBV62UIO probe 2 input contact 2 stateBV63UIO probe 2 input contact 1 normal stateBV64UIO probe 2 input contact 2 normal stateBV65UIO probe 2 contact 1 severityBV66UIO probe 2 contact 2 severityBV67UIO probe 2 output relay 1 stateBV68UIO probe 2 output relay 1 normal stateBV69LostUPSCommBV70OverloadBV71SelfTestFailedBV72LowBatteryBV73OnBatteryBV74LowInputVoltageBV75HighInputVoltageBV76MainInputBadBV77LowBattery2BV78OutputOffBV79ShutdownWaitingForPowerReturnBV80BadBatteryBV81InBypassInternalHardwareConditionBV82InBypassFrontPanelSoftwareBV83InBypassBypassSwitchBV84BypassPowerSupplyProblemBV85FanProblemBV86LostBattCommBV87RuntimeCalStartedBV88GracefulShutdownInProgressBV89AvrRelayInoperableBV90AbnormaOutputVoltageBV91BatteryChargerInoperableBV92InternalBattTempHighBV93BatteryDisconnectedBV94OutletGroupOffBV95DcImbalanceBV96MainRelayInoperableBV97BypassRelayInoperableBV98LostUPSCommOnBatBV99PFCInputRelayInoperableBV100UPSTempCriticalBV101BattVoltageHighBV102EepromInoperableBV103BattTempSensorIssueBV104BattBusSoftStartInoperableBV105BattVoltageSenseIssueBV106OutputShortCircuitBV107OutputRelayInoperableBV108PfcInoperableBV109DcBusOvervoltageBV110InverterInoperableBV111OvercurrentTripBV112BypassPfcRelayInoperableBV113DcBusSoftStartInoperableBV114GreenRelayConditionBV115DcOutputConditionBV116DcBusConditionBV117PowerSystemSensorConditionBV118AdConverterInoperableBV119LogicPowerSupplyInoperableBV120BackfeedRelayInoperableBV121UpsInternalCommErrorBV122FirmwareTransferToUpsDidNotSucceedBV123UpsInvalidFirmwareBV124WarrantyExpiringSoonBV125TechnicalCheckRecommendedBV126BatteryNearEndOfLifeBV127BatteryMeasureLifeNearEndBV128BatteryLifeExceededBV129BatteryTempWarningBV130BatteryGeneralConditionBV131BatteryCommLostBV132BatteryPackDisconnectedBV133BatteryFirmwareMismatchBV134BatteryTempSensorNotOperatingBV135LocalDisplayButtonIssueBV136UpsNeedsFactorySetupBV137EpoActiveBV138FirmwareMismatchBV139OscillatorInoperableBV140MeasureMismatchBV141GeneralSubsystemConditionBV142LogicPowerSuppyRelayConditionBV143PowerSystemConditionBV144MaintenanceModeForFanBV145ServiceBypassInBypassBV146ServiceBypassDisconnectedBV147ServiceBypassOutputConditionBV148ServiceBypassInternalConditionBV149InTemporaryBypassBV150PowerModuleInoperableBV151BatteryInoperableBV152LoadKvaAlarmViolationBV153InputVoltageFreqPreventsBypassBV154BypassDueToInternalHardwareConditionBV155BypassDueToOverloadBV156BypassDueToMaintenanceBV157SystemFanInoperableBV158RuntimeAlarmViolationBV159ExtendedRunFrameInoperableBV160OutputVoltageOutsideLimitsBV161PhaseSyncConditionBV162BatteryNotInstalledProperlyBV163BatteryVoltageExceedsNominalBV164SiteWiringFaultBV165NumBatteriesIncreasedBV166NumBatteryDecreasedBV167ExtendedRunFramesIncreasedBV168ExtendedRunFramesDecreasedBV169ExternalSwitchQ001ClosedBV170ExternalSwitchQ002ClosedBV171ExternalSwitchQ003ClosedBV172ExternalSwitchQ004ClosedBV173ExternalSwitchQ005ClosedBV174ExternalSwitchQ006ClosedBV175ExternalSwitchQ007ClosedBV176ExternalSwitchQ008ClosedBV177ExternalSwitchQ009ClosedBV178ExternalSwitchQ0010ClosedBV179EpoActive2BV180StaticBypassSwitchInoperableBV181SystemStartupConfigProblemBV182PsuInoperableBV183WeakBatteryBV184HighBatteryTemperatureBV185InternalMechanicalBypassBV186LostParallelRedundancyBV187ParallelCommCondition1BV188ParalletlCommCondition2BV189AuxCommConditionBV190ParallelTerminationCondition1BV191ParallelTerminationCondition2BV192AuxTerminationConditionBV193NoMasterPresentBV194ParallelOverloadBV195ParallelConfigConditionBV196ChangeDustFilterSoonBV197ChangeDustFilterNowBV198UioInputContact1Critical1BV199UioInputContact1Critical2BV200UioInputContact2Critical1BV201UioInputContact2Critical2BV202UioTempMinThresholdViolation1BV203UioTempMinThresholdViolation2BV204UioTempLowThresholdViolation1BV205UioTempLowThresholdViolation2BV206UioTempHighThresholdViolation1BV207UioTempHighThresholdViolation2BV208UioTempMaxThresholdViolation1BV209UioTempMaxThresholdViolation2BV210UioHumidMinThresholdViolation1BV211UioHumidMinThresholdViolation2BV212UioHumidLowThresholdViolation1BV213UioHumidLowThresholdViolation2BV214UioHumidHighThresholdViolation1BV215UioHumidHighThresholdViolation2BV216UioHumidMaxThresholdViolation1BV217UioHumidMaxThresholdViolation2BV218UioLostComm1BV219UioLostComm2BV220UioCriticalFaultBV221UioOutputRelayAbnormalState1BV222UioOutputRelayAbnormalState2BV223UioInputContact1Warning1BV224UioInputContact1Warning2BV225UioInputContact2Warning1BV226UioInputContact2Warning2BV227InputContactOutputRelayFaultBV228AirFilterWarningBV229BatteryPackIncompatibleBV230UpsInputContact1AbnormalStateBV231UpsInputContact2AbnormalStateBV232UpsOutputRelay1AbnormalStateBV233UpsOutputRelay2AbnormalStateBV234UpsOutputRelay3AbnormalStateBV235UpsOutputRelay4AbnormalStateBV236UpsOutputRelay5AbnormalStateBV237UpsOutputRelay6AbnormalStateCSV0UPS modelCSV1UPS serial numberCSV2UPS manufacture dateCSV3User-specified battery replacement dateCSV4UPS apparent power ratingCSV5UPS real power ratingCSV6UPS external battery SKUCSV7UPS SKUCSV8UPS Firmware RevisionCSV9UPS Internal Battery SKUCSV10Outlet group main nameCSV11Outlet group switched 1 nameCSV12Outlet group switched 2 nameCSV13Outlet group switched 3 nameCSV14Output frequency settingCSV15UPS nameCSV16Next battery replacement dateCSV17Self test resultCSV18Runtime calibration resultCSV19UIO probe 1 temperature and humidity nameCSV20UIO probe 1 temperature and humidity locationCSV21UIO probe 1 contact 1 nameCSV22UIO probe 1 contact 2 nameCSV23UIO probe 1 contact 1 locationCSV24UIO probe 1 contact 2 locationCSV25UIO probe 1 output relay 1 nameCSV26UIO probe 1 output relay 1 locationCSV27UIO probe 2 temperature and humidity nameCSV28UIO probe 2 temperature and humidity locationCSV29UIO probe 2 contact 1 nameCSV30UIO probe 2 contact 2 nameCSV31UIO probe 2 contact 1 locationCSV32UIO probe 2 contact 2 locationCSV33UIO probe 2 output relay 1 nameCSV34UIO probe 2 output relay 1 locationMV0Last battery transferMV1Rated Output voltage settingMV2SensitivityMV3Audible AlarmMV4Self test scheduleMV5UPS stateMV6UPS ControlMV7Main Outlet Group controlMV8Switched Outlet group 1 controlMV9Switched Outlet group 2 controlMV10Switched Outlet group 3 controlMV11UIO probe 1 temperature and humidity statusMV12UIO probe 1 contact statusMV13UIO probe 2 temperature and humidity statusMV14UIO probe 2 contact statusNC0DefaultNotifier
Integration notes
- Instances are the NMC2 / NMC3 (< v3.0) index column. NMC3 firmware 3.1 renumbers some objects: BV 51-68 move up by 1 and BV 69-237 (alarm flags) move up by 2; MV 13-14 move up by 1; CSV 27-34 move up by 2. Index 47 'UIO probe 1 contact 1 severity' prints as 48 in the v3.1 column.
- NMC3 v3.1 also adds objects that have no index on older cards: spot fluid sensor enables, alarms (BV 240-241 in v3.1), name/location text values and status MVs. They are not listed here.
- Bracketed text in a description names the UPS families that support the object; objects marked for an AP9631/AP9635 card need the Universal I/O probe port. Alarm flags (BV 69-237) carry no model column in the document.
- Multi-state option lists are given in the printed order; the document does not print state numbers.
- Alarm flag BVs send event notifications to the recipients in the Default Notification Class (NC 0).
- Some names are printed with typos (e.g. 'AbnormaOutputVoltage', 'ParalletlCommCondition2', 'Outlet group switched 3load shed runtime remaining'); they are kept as printed.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Smart-UPS with Network Management Card 2 / 3 (BACnet IP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the APC Smart-UPS with Network Management Card 2 / 3 (BACnet IP)
How many BACnet points does the APC Smart-UPS with Network Management Card 2 / 3 (BACnet IP) have?
This list has 390 BACnet objects: 101 analog values, 238 binary values, 1 notification class, 15 multi-state values, 35 characterstring values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which APC Smart-UPS with Network Management Card 2 / 3 (BACnet IP) BACnet points are writable?
151 of the 390 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official APC Smart-UPS with Network Management Card 2 / 3 (BACnet IP) BACnet documentation?
The source is BACnet Application Map for Network Management Card 2 and 3 (Smart-UPS) (990-5916C), revision 2024-04, published free by APC at https://download.se.com/files?p_Doc_Ref=SPD_CCON-AUTEZG_EN.
What are the minimum BACnet points to integrate the APC Smart-UPS with Network Management Card 2 / 3 (BACnet IP)?
Start with MV 6 UPS Control (UPS on/off/reboot/sleep/bypass command); MV 5 UPS state (Online, on battery, bypass, fault and so on); AV 0 Runtime remaining (Battery runtime left, s); AV 66 Battery state of charge (Battery charge, %); AV 19 Output watts phase 1 (Load as % of the watt rating); AV 10 Output voltage 1 (Output voltage, V); BV 73 OnBattery (UPS is running on battery); BV 72 LowBattery (Battery low alarm); BV 70 Overload (Output overload alarm); BV 69 LostUPSComm (Card lost communication with the UPS).
How do I enable BMS control of the APC Smart-UPS with Network Management Card 2 / 3 (BACnet IP)?
BACnet IP is part of the NMC2 'sumx' and NMC3 'su' application firmware and is turned on in the card's configuration. No BMS enable point is needed; UPS Control (MV 6) acts directly on the UPS.
How do I check these points on the real Smart-UPS with Network Management Card 2 / 3 (BACnet IP)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More APC BACnet points lists
- In-row precision cooling unit (chilled water computer room air handler)
APC InRow RC chilled water 300 mm (ACRC301S / ACRC301H) BACnet IP
APC / Schneider Electric InRow RC 300 mm chilled water in-row coolers ACRC301S and ACRC301H with application firmware v6.0.0 or later.
Also known as: ACRC301S, ACRC301H, ACRC3xx, InRow RC 300 mm, InRow CW, Schneider Electric InRow RC, TME27091 - UPS (three-phase) network card
APC Easy UPS 3-Phase with Network Management Card AP9547 (BACnet IP)
APC / Schneider Electric Easy UPS 3-Phase units fitted with the Network Management Card for Easy UPS (AP9547), on BACnet IP.
Also known as: Easy UPS 3-Phase, AP9547, NMC for Easy UPS, Easy UPS 3S, Easy UPS 3M, 990-6445, Schneider Easy UPS BACnet - UPS (uninterruptible power supply) network card
APC Symmetra single-phase UPS with Network Management Card 2 (BACnet IP)
APC Symmetra single-phase UPS units fitted with a Network Management Card 2 running the 'sy' application firmware 6.5.6 or later.
Also known as: APC Symmetra BACnet, Symmetra LX, Symmetra RM, NMC2 BACnet, AP9630, AP9631, AP9635, 990-5917B, sy firmware
Source: BACnet Application Map for Network Management Card 2 and 3 (Smart-UPS) · 990-5916C · rev. 2024-04. Object names, instances and units are reproduced as published; descriptions are our own.