UPS (uninterruptible power supply) network card · BACnet points list

APC Smart-UPS with Network Management Card 2 / 3 (BACnet IP) BACnet points list

Updated 4 November 2026

Short answer

The APC Network Management Card in a Smart-UPS serves BACnet IP. The object list is fixed by the card firmware: Analog Values for runtime, battery, input, output and load readings plus outlet-group and shutdown settings; Binary Values for outlet states, test commands, option enables and about 170 UPS alarm flags; Character String Values for identity text; and Multi-state Values for UPS state, UPS control and outlet-group control. Each object is only present on the UPS families marked in the table.

This page lists 390 BACnet objects for the APC Smart-UPS with Network Management Card 2 / 3 (BACnet IP) — 151 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from APC’s own free documentation, linked below.

Manufacturer
APC
Model
Smart-UPS with Network Management Card 2 / 3 (BACnet IP)
Equipment
UPS (uninterruptible power supply) network card
Equipment type
Other equipment
BACnet objects
390 (151 writable)
Transport
BACnet IP
Firmware
NMC2 application firmware 6.5.6 or later (sumx); NMC3 below 3.0 (su). See notes for NMC3 3.1.
Also known as
APC Smart-UPS BACnet, NMC2 BACnet, NMC3 BACnet, AP9630, AP9631, AP9635, AP9640, AP9641, SMT, SMX, SRT, SURT, 990-5916C, APC UPS BACnet application map
Source document
BACnet Application Map for Network Management Card 2 and 3 (Smart-UPS) · 990-5916C · rev. 2024-04
Download CSV 390 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against APC’s current documentation and the live device before use. Not official APC information. Terms of use.

BMS integration notes: APC Smart-UPS with Network Management Card 2 / 3 (BACnet IP)

Integration in brief

Enable BACnet on the Network Management Card (sumx/su firmware) and give the card a unique device instance. Read UPS state (MV 5), runtime remaining (AV 0), battery charge (AV 66), load (AV 19) and the alarm flags such as OnBattery, LowBattery and Overload. UPS Control (MV 6) and the outlet-group control MVs switch the UPS or its outlets, so restrict who can write them.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 6UPS ControlUPS on/off/reboot/sleep/bypass commandWrite
MV 5UPS stateOnline, on battery, bypass, fault and so onRead
AV 0Runtime remainingBattery runtime left, sRead
AV 66Battery state of chargeBattery charge, %Read
AV 19Output watts phase 1Load as % of the watt ratingRead
AV 10Output voltage 1Output voltage, VRead
BV 73OnBatteryUPS is running on batteryRead
BV 72LowBatteryBattery low alarmRead
BV 70OverloadOutput overload alarmRead
BV 69LostUPSCommCard lost communication with the UPSRead

Enable & remote start

BACnet IP is part of the NMC2 'sumx' and NMC3 'su' application firmware and is turned on in the card's configuration. No BMS enable point is needed; UPS Control (MV 6) acts directly on the UPS.

Network setup

Watch out for

APC Smart-UPS with Network Management Card 2 / 3 (BACnet IP) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

390 of 390 shown
Type
AnalogBinaryMulti-state
Access
Show
APC Smart-UPS with Network Management Card 2 / 3 (BACnet IP) BACnet Points List
DescriptionStates
AVmin0Runtime remainingBattery runtime left at the present load [SMT/SMX/SRT, SURT, SURTD, other models]sRead
AV1Battery TemperatureBattery compartment temperature [SMT/SMX/SRT, SURT, SURTD, other models]°CRead
AV2Utility voltage 1Input voltage, phase 1 [SURTD, other models]VRead
AV3Utility voltage 2Input voltage, phase 2 [SURTD, other models]VRead
AV4Utility voltage 3Input voltage, phase 3 [other models]VRead
AV5Utility current 1Input current, phase 1 [other models]ARead
AV6Utility current 2Input current, phase 2 [other models]ARead
AV7Utility current 3Input current, phase 3 [other models]ARead
AV8Utility Input frequencyInput frequency [SURT]HzRead
AV9Output frequencyOutput frequency [SURT]HzRead
AVmin10Output voltage 1Output voltage, phase 1 [SMT/SMX/SRT, SURT, SURTD, other models]VRead
AV11Output voltage 2Output voltage, phase 2 [SMT/SMX/SRT, SURT, SURTD, other models]VRead
AV12Output voltage 3Output voltage, phase 3 [other models]VRead
AV13Output VA phase 1Load as % of VA rating, phase 1 [SURTD, other models]%Read
AV14Output VA phase 2Load as % of VA rating, phase 2 [SURTD, other models]%Read
AV15Output VA phase 3Load as % of VA rating, phase 3 [other models]%Read
AV16Output load current 1Output current, phase 1 [SMT/SMX/SRT, SURT, SURTD, other models]ARead
AV17Output load current 2Output current, phase 2 [SURTD, other models]ARead
AV18Output load current 3Output current, phase 3 [other models]ARead
AVmin19Output watts phase 1Load as % of watt rating, phase 1 [SMT/SMX/SRT, SURT, SURTD, other models]%Read
AV20Output watts phase 2Load as % of watt rating, phase 2 [SURTD, other models]%Read
AV21Output watts phase 3Load as % of watt rating, phase 3 [other models]%Read
AV22Output efficiencyShare of input power delivered to the load [SMT/SMX/SRT, SURT]%Read
AV23Output energy usageLoad energy since last reset to defaults [SMT/SMX/SRT, SURT]kWhRead
AV24Outlet group main power off delayDelay before the outlet group turns off [SMT/SMX/SRT, SURT]sWrite
AV25Outlet group switched 1 power off delayDelay before the outlet group turns off [SMT/SMX/SRT, SURT]sWrite
AV26Outlet group switched 2 power off delayDelay before the outlet group turns off [SMT/SMX/SRT, SURT]sWrite
AV27Outlet group switched 3 power off delayDelay before the outlet group turns off [SMT/SMX/SRT, SURT]sWrite
AV28Outlet group main reboot durationOff time during an outlet group reboot [SMT/SMX/SRT, SURT]sWrite
AV29Outlet group switched 1 reboot durationOff time during an outlet group reboot [SMT/SMX/SRT, SURT]sWrite
AV30Outlet group switched 2 reboot durationOff time during an outlet group reboot [SMT/SMX/SRT, SURT]sWrite
AV31Outlet group switched 3 reboot durationOff time during an outlet group reboot [SMT/SMX/SRT, SURT]sWrite
AV32Outlet group main power on delayDelay before the outlet group turns on [SMT/SMX/SRT, SURT]sWrite
AV33Outlet group switched 1 power on delayDelay before the outlet group turns on [SMT/SMX/SRT, SURT]sWrite
AV34Outlet group switched 2 power on delayDelay before the outlet group turns on [SMT/SMX/SRT, SURT]sWrite
AV35Outlet group switched 3 power on delayDelay before the outlet group turns on [SMT/SMX/SRT, SURT]sWrite
AV36Outlet group main minimum return runtimeRuntime needed before the group turns back on [SMT/SMX/SRT, SURT]sWrite
AV37Outlet group switched 1 minimum return runtimeRuntime needed before the group turns back on [SMT/SMX/SRT, SURT]sWrite
AV38Outlet group switched 2 minimum return runtimeRuntime needed before the group turns back on [SMT/SMX/SRT, SURT]sWrite
AV39Outlet group switched 3 minimum return runtimeRuntime needed before the group turns back on [SMT/SMX/SRT, SURT]sWrite
AV40Outlet group main load shed runtime remainingGroup turns off when runtime falls to this [SMT/SMX/SRT, SURT]sWrite
AV41Outlet group switched 1 load shed runtime remainingGroup turns off when runtime falls to this [SMT/SMX/SRT, SURT]sWrite
AV42Outlet group switched 2 load shed runtime remainingGroup turns off when runtime falls to this [SMT/SMX/SRT, SURT]sWrite
AV43Outlet group switched 3load shed runtime remainingGroup turns off when runtime falls to this [SMT/SMX/SRT, SURT]sWrite
AV44Outlet group main load shed time on batteryGroup turns off after this time on battery [SMT/SMX/SRT, SURT]sWrite
AV45Outlet group switched 1 load shed time on batteryGroup turns off after this time on battery [SMT/SMX/SRT, SURT]sWrite
AV46Outlet group switched 2 load shed time on batteryGroup turns off after this time on battery [SMT/SMX/SRT, SURT]sWrite
AV47Outlet group switched 3 load shed time on batteryGroup turns off after this time on battery [SMT/SMX/SRT, SURT]sWrite
AV48Output upper limitUpper transfer voltage [SMT/SMX/SRT, SURT, SURTD, other models]VWrite
AV49Output lower limitLower transfer voltage [SMT/SMX/SRT, SURT, SURTD, other models]VWrite
AV50Bypass upper limitUpper bypass voltage limit [SURT, SURTD, other models]VWrite
AV51Bypass lower limitLower bypass voltage limit [SURT, SURTD, other models]VWrite
AV52Low Battery durationRuntime left that raises the low-battery alarm [SMT/SMX/SRT, SURT, SURTD, other models]sWrite
AV53Basic low battery durationBasic low-battery warning time [SMT/SMX/SRT, SURT, SURTD, other models]sWrite
AV54Sleep timeSleep duration for a sleep command [SMT/SMX/SRT, SURT, SURTD, other models]hWrite
AV55Shutdown DelayDelay before the UPS shuts down [other models]sWrite
AV56Minimum return capacityBattery charge needed before restart [other models]%Write
AV57Return DelayDelay before restart after power returns [other models]sWrite
AV58Maximum required delayLongest shutdown delay needed by clients [other models]minRead
AV59Bypass input frequencyBypass input frequency [SURT, SURTD, other models]HzRead
AV60Bypass input voltage 1Bypass input voltage, phase 1 [other models]VRead
AV61Bypass input voltage 2Bypass input voltage, phase 2 [other models]VRead
AV62Bypass input voltage 3Bypass input voltage, phase 3 [other models]VRead
AV63Positive battery voltageBattery voltage (positive bus) [SMT/SMX/SRT, SURT, SURTD, other models]VRead
AV64Negative battery voltageBattery voltage (negative bus) [SURT]VRead
AV65Nominal battery voltageNominal battery voltage [other models]VRead
AVmin66Battery state of chargeBattery charge level [SMT/SMX/SRT, SURT, SURTD, other models]%Read
AV67Battery currentBattery current [other models]ARead
AV68Number of external batteriesCount of external battery packs [other models]Read
AV69Controlled Early Shutdown Time On BatteryEarly shutdown threshold (time on battery) [other models]minWrite
AV70Controlled Early Shutdown Runtime RemainingEarly shutdown threshold (runtime remaining) [other models]minWrite
AV71Controlled Early Shutdown Battery CapacityEarly shutdown threshold (battery capacity) [other models]minWrite
AV72Controlled Early Shutdown Load PercentageEarly shutdown threshold (load percentage) [other models]minWrite
AV73UIO probe 1 temperatureUniversal I/O probe reading [SMT/SMX/SRT with AP9631/AP9635 NMC]°CRead
AV74UIO probe 1 humidityUniversal I/O probe reading [SMT/SMX/SRT with AP9631/AP9635 NMC]%Read
AV75UIO probe 1 temperature maximumProbe alarm threshold [SMT/SMX/SRT with AP9631/AP9635 NMC]°CWrite
AV76UIO probe 1 temperature highProbe alarm threshold [SMT/SMX/SRT with AP9631/AP9635 NMC]°CWrite
AV77UIO probe 1 temperature lowProbe alarm threshold [SMT/SMX/SRT with AP9631/AP9635 NMC]°CWrite
AV78UIO probe 1 temperature minimumProbe alarm threshold [SMT/SMX/SRT with AP9631/AP9635 NMC]°CWrite
AV79UIO probe 1 temperature hysteresisProbe alarm hysteresis [SMT/SMX/SRT with AP9631/AP9635 NMC]°CWrite
AV80UIO probe 1 humidity maximumProbe alarm threshold [SMT/SMX/SRT with AP9631/AP9635 NMC]%Write
AV81UIO probe 1 humidity highProbe alarm threshold [SMT/SMX/SRT with AP9631/AP9635 NMC]%Write
AV82UIO probe 1 humidity lowProbe alarm threshold [SMT/SMX/SRT with AP9631/AP9635 NMC]%Write
AV83UIO probe 1 humidity minimumProbe alarm threshold [SMT/SMX/SRT with AP9631/AP9635 NMC]%Write
AV84UIO probe 1 humidity hysteresisProbe alarm hysteresis [SMT/SMX/SRT with AP9631/AP9635 NMC]%Write
AV85UIO probe 1 output relay 1 delayTime a condition must last before the relay acts [SMT/SMX/SRT with AP9631/AP9635 NMC]sWrite
AV86UIO probe 1 output relay 1 holdMinimum relay hold time after an alarm [SMT/SMX/SRT with AP9631/AP9635 NMC]sWrite
AV87UIO probe 2 temperatureUniversal I/O probe reading [SMT/SMX/SRT with AP9631 NMC]°CRead
AV88UIO probe 2 humidityUniversal I/O probe reading [SMT/SMX/SRT with AP9631 NMC]%Read
AV89UIO probe 2 temperature maximumProbe alarm threshold [SMT/SMX/SRT with AP9631 NMC]°CWrite
AV90UIO probe 2 temperature highProbe alarm threshold [SMT/SMX/SRT with AP9631 NMC]°CWrite
AV91UIO probe 2 temperature lowProbe alarm threshold [SMT/SMX/SRT with AP9631 NMC]°CWrite
AV92UIO probe 2 temperature minimumProbe alarm threshold [SMT/SMX/SRT with AP9631 NMC]°CWrite
AV93UIO probe 2 temperature hysteresisProbe alarm hysteresis [SMT/SMX/SRT with AP9631 NMC]°CWrite
AV94UIO probe 2 humidity maximumProbe alarm threshold [SMT/SMX/SRT with AP9631 NMC]%Write
AV95UIO probe 2 humidity highProbe alarm threshold [SMT/SMX/SRT with AP9631 NMC]%Write
AV96UIO probe 2 humidity lowProbe alarm threshold [SMT/SMX/SRT with AP9631 NMC]%Write
AV97UIO probe 2 humidity minimumProbe alarm threshold [SMT/SMX/SRT with AP9631 NMC]%Write
AV98UIO probe 2 humidity hysteresisProbe alarm hysteresis [SMT/SMX/SRT with AP9631 NMC]%Write
AV99UIO probe 2 output relay 1 delayTime a condition must last before the relay acts [SMT/SMX/SRT with AP9631 NMC]sWrite
AV100UIO probe 2 output relay 1 holdMinimum relay hold time after an alarm [SMT/SMX/SRT with AP9631 NMC]sWrite
BV0Outlet group main stateOutlet group on/off state [SMT/SMX/SRT, SURT]Read
BV1Outlet group switched 1 stateOutlet group on/off state [SMT/SMX/SRT, SURT]Read
BV2Outlet group switched 2 stateOutlet group on/off state [SMT/SMX/SRT, SURT]Read
BV3Outlet group switched 3 stateOutlet group on/off state [SMT/SMX/SRT, SURT]Read
BV4Outlet group main load shed runtime remaining enableEnables the matching threshold or action [SMT/SMX/SRT, SURT]Write
BV5Outlet group switched 1 load shed runtime remaining enableEnables the matching threshold or action [SMT/SMX/SRT, SURT]Write
BV6Outlet group switched 2 load shed runtime remaining enableEnables the matching threshold or action [SMT/SMX/SRT, SURT]Write
BV7Outlet group switched 3 load shed runtime remaining enableEnables the matching threshold or action [SMT/SMX/SRT, SURT]Write
BV8Outlet group main load shed time on battery enableEnables the matching threshold or action [SMT/SMX/SRT, SURT]Write
BV9Outlet group switched 1 load shed time on battery enableEnables the matching threshold or action [SMT/SMX/SRT, SURT]Write
BV10Outlet group switched 2 load shed time on battery enableEnables the matching threshold or action [SMT/SMX/SRT, SURT]Write
BV11Outlet group switched 3 load shed time on battery enableEnables the matching threshold or action [SMT/SMX/SRT, SURT]Write
BV12Outlet group main load shed skip off delayLoad shed option for the outlet group [SMT/SMX/SRT, SURT]Write
BV13Outlet group switched 1 load shed skip off delayLoad shed option for the outlet group [SMT/SMX/SRT, SURT]Write
BV14Outlet group switched 2 load shed skip off delayLoad shed option for the outlet group [SMT/SMX/SRT, SURT]Write
BV15Outlet group switched 3 load shed skip off delayLoad shed option for the outlet group [SMT/SMX/SRT, SURT]Write
BV16Outlet group main load shed stay off after power returnsLoad shed option for the outlet group [SMT/SMX/SRT, SURT]Write
BV17Outlet group switched 1 load shed stay off after power returnsLoad shed option for the outlet group [SMT/SMX/SRT, SURT]Write
BV18Outlet group switched 2 load shed stay off after power returnsLoad shed option for the outlet group [SMT/SMX/SRT, SURT]Write
BV19Outlet group switched 3 load shed stay off after power returnsLoad shed option for the outlet group [SMT/SMX/SRT, SURT]Write
BV20Outlet group switched 1 load shed overloadLoad shed option for the outlet group [SMT/SMX/SRT, SURT]Write
BV21Outlet group switched 2 load shed overloadLoad shed option for the outlet group [SMT/SMX/SRT, SURT]Write
BV22Outlet group switched 3 load shed overloadLoad shed option for the outlet group [SMT/SMX/SRT, SURT]Write
BV23Run UPS self testCommand: run ups self test [SMT/SMX/SRT, SURT, SURTD, other models]Write
BV24Run UPS alarm testCommand: run ups alarm test [SMT/SMX/SRT, SURT, SURTD, other models]Write
BV25Run UPS alarm test continuousCommand: run ups alarm test continuous [SMT/SMX/SRT, SURT]Write
BV26Run UPS runtime calibrationCommand: run ups runtime calibration [SMT/SMX/SRT, SURT, SURTD, other models]Write
BV27Cancel TestCommand: cancel test [SMT/SMX/SRT, SURT]Write
BV28Controlled Early Shutdown Time On Battery EnableEnables the matching threshold or action [SMT/SMX/SRT, SURT, SURTD, other models]Write
BV29Controlled Early Shutdown Runtime Remaining EnableEnables the matching threshold or action [SMT/SMX/SRT, SURT, SURTD, other models]Write
BV30Controlled Early Shutdown Battery Capacity EnableEnables the matching threshold or action [SMT/SMX/SRT, SURT, SURTD, other models]Write
BV31Controlled Early Shutdown Load Percentage EnableEnables the matching threshold or action [SMT/SMX/SRT, SURT, SURTD, other models]Write
BV32Controlled Early Shutdown Stay Off After Power Return EnableEnables the matching threshold or action [SMT/SMX/SRT, SURT, SURTD, other models]Write
BV33UIO probe 1 temperature maximum enableEnables the matching threshold or action [SMT/SMX/SRT with AP9631/AP9635 NMC]Write
BV34UIO probe 1 temperature high enableEnables the matching threshold or action [SMT/SMX/SRT with AP9631/AP9635 NMC]Write
BV35UIO probe 1 temperature low enableEnables the matching threshold or action [SMT/SMX/SRT with AP9631/AP9635 NMC]Write
BV36UIO probe 1 temperature minimum enableEnables the matching threshold or action [SMT/SMX/SRT with AP9631/AP9635 NMC]Write
BV37UIO probe 1 humidity maximum enableEnables the matching threshold or action [SMT/SMX/SRT with AP9631/AP9635 NMC]Write
BV38UIO probe 1 humidity high enableEnables the matching threshold or action [SMT/SMX/SRT with AP9631/AP9635 NMC]Write
BV39UIO probe 1 humidity low enableEnables the matching threshold or action [SMT/SMX/SRT with AP9631/AP9635 NMC]Write
BV40UIO probe 1 humidity minimum enableEnables the matching threshold or action [SMT/SMX/SRT with AP9631/AP9635 NMC]Write
BV41UIO probe 1 contact 1enableEnables the matching threshold or action [SMT/SMX/SRT with AP9631/AP9635 NMC]Write
BV42UIO probe 1 contact 2 enableEnables the matching threshold or action [SMT/SMX/SRT with AP9631/AP9635 NMC]Write
BV43UIO probe 1 input contact 1 stateInput contact state [SMT/SMX/SRT with AP9631/AP9635 NMC]Read
BV44UIO probe 1 input contact 2Input contact state [SMT/SMX/SRT with AP9631/AP9635 NMC]Read
BV45UIO probe 1 input contact 1 normal stateSets the contact/relay normal state [SMT/SMX/SRT with AP9631/AP9635 NMC]Write
BV46UIO probe 1 input contact 2 normal stateSets the contact/relay normal state [SMT/SMX/SRT with AP9631/AP9635 NMC]Write
BV47UIO probe 1 contact 1 severityAlarm severity for the contact [SMT/SMX/SRT with AP9631/AP9635 NMC]Write
BV48UIO probe 1 contact 2 severityAlarm severity for the contact [SMT/SMX/SRT with AP9631/AP9635 NMC]Write
BV49UIO probe 1 output relay 1 stateOutput relay state [SMT/SMX/SRT with AP9631/AP9635 NMC]Read
BV50UIO probe 1 output relay 1 normal stateSets the contact/relay normal state [SMT/SMX/SRT with AP9631/AP9635 NMC]Write
BV51UIO probe 2 temperature maximum enableEnables the matching threshold or action [SMT/SMX/SRT with AP9631 NMC]Write
BV52UIO probe 2 temperature high enableEnables the matching threshold or action [SMT/SMX/SRT with AP9631 NMC]Write
BV53UIO probe 2 temperature low enableEnables the matching threshold or action [SMT/SMX/SRT with AP9631 NMC]Write
BV54UIO probe 2 temperature minimum enableEnables the matching threshold or action [SMT/SMX/SRT with AP9631 NMC]Write
BV55UIO probe 2 humidity maximum enableEnables the matching threshold or action [SMT/SMX/SRT with AP9631 NMC]Write
BV56UIO probe 2 humidity high enableEnables the matching threshold or action [SMT/SMX/SRT with AP9631 NMC]Write
BV57UIO probe 2 humidity low enableEnables the matching threshold or action [SMT/SMX/SRT with AP9631 NMC]Write
BV58UIO probe 2 humidity minimum enableEnables the matching threshold or action [SMT/SMX/SRT with AP9631 NMC]Write
BV59UIO probe 2 contact 1enableEnables the matching threshold or action [SMT/SMX/SRT with AP9631 NMC]Write
BV60UIO probe 2 contact 2 enableEnables the matching threshold or action [SMT/SMX/SRT with AP9631 NMC]Write
BV61UIO probe 2 input contact 1 stateInput contact state [SMT/SMX/SRT with AP9631 NMC]Read
BV62UIO probe 2 input contact 2 stateInput contact state [SMT/SMX/SRT with AP9631 NMC]Read
BV63UIO probe 2 input contact 1 normal stateSets the contact/relay normal state [SMT/SMX/SRT with AP9631 NMC]Write
BV64UIO probe 2 input contact 2 normal stateSets the contact/relay normal state [SMT/SMX/SRT with AP9631 NMC]Write
BV65UIO probe 2 contact 1 severityAlarm severity for the contact [SMT/SMX/SRT with AP9631 NMC]Write
BV66UIO probe 2 contact 2 severityAlarm severity for the contact [SMT/SMX/SRT with AP9631 NMC]Write
BV67UIO probe 2 output relay 1 stateOutput relay state [SMT/SMX/SRT with AP9631 NMC]Read
BV68UIO probe 2 output relay 1 normal stateSets the contact/relay normal state [SMT/SMX/SRT with AP9631 NMC]Write
BVmin69LostUPSCommUPS alarm/event flagRead
BVmin70OverloadUPS alarm/event flagRead
BV71SelfTestFailedUPS alarm/event flagRead
BVmin72LowBatteryUPS alarm/event flagRead
BVmin73OnBatteryUPS alarm/event flagRead
BV74LowInputVoltageUPS alarm/event flagRead
BV75HighInputVoltageUPS alarm/event flagRead
BV76MainInputBadUPS alarm/event flagRead
BV77LowBattery2UPS alarm/event flagRead
BV78OutputOffUPS alarm/event flagRead
BV79ShutdownWaitingForPowerReturnUPS alarm/event flagRead
BV80BadBatteryUPS alarm/event flagRead
BV81InBypassInternalHardwareConditionUPS alarm/event flagRead
BV82InBypassFrontPanelSoftwareUPS alarm/event flagRead
BV83InBypassBypassSwitchUPS alarm/event flagRead
BV84BypassPowerSupplyProblemUPS alarm/event flagRead
BV85FanProblemUPS alarm/event flagRead
BV86LostBattCommUPS alarm/event flagRead
BV87RuntimeCalStartedUPS alarm/event flagRead
BV88GracefulShutdownInProgressUPS alarm/event flagRead
BV89AvrRelayInoperableUPS alarm/event flagRead
BV90AbnormaOutputVoltageUPS alarm/event flagRead
BV91BatteryChargerInoperableUPS alarm/event flagRead
BV92InternalBattTempHighUPS alarm/event flagRead
BV93BatteryDisconnectedUPS alarm/event flagRead
BV94OutletGroupOffUPS alarm/event flagRead
BV95DcImbalanceUPS alarm/event flagRead
BV96MainRelayInoperableUPS alarm/event flagRead
BV97BypassRelayInoperableUPS alarm/event flagRead
BV98LostUPSCommOnBatUPS alarm/event flagRead
BV99PFCInputRelayInoperableUPS alarm/event flagRead
BV100UPSTempCriticalUPS alarm/event flagRead
BV101BattVoltageHighUPS alarm/event flagRead
BV102EepromInoperableUPS alarm/event flagRead
BV103BattTempSensorIssueUPS alarm/event flagRead
BV104BattBusSoftStartInoperableUPS alarm/event flagRead
BV105BattVoltageSenseIssueUPS alarm/event flagRead
BV106OutputShortCircuitUPS alarm/event flagRead
BV107OutputRelayInoperableUPS alarm/event flagRead
BV108PfcInoperableUPS alarm/event flagRead
BV109DcBusOvervoltageUPS alarm/event flagRead
BV110InverterInoperableUPS alarm/event flagRead
BV111OvercurrentTripUPS alarm/event flagRead
BV112BypassPfcRelayInoperableUPS alarm/event flagRead
BV113DcBusSoftStartInoperableUPS alarm/event flagRead
BV114GreenRelayConditionUPS alarm/event flagRead
BV115DcOutputConditionUPS alarm/event flagRead
BV116DcBusConditionUPS alarm/event flagRead
BV117PowerSystemSensorConditionUPS alarm/event flagRead
BV118AdConverterInoperableUPS alarm/event flagRead
BV119LogicPowerSupplyInoperableUPS alarm/event flagRead
BV120BackfeedRelayInoperableUPS alarm/event flagRead
BV121UpsInternalCommErrorUPS alarm/event flagRead
BV122FirmwareTransferToUpsDidNotSucceedUPS alarm/event flagRead
BV123UpsInvalidFirmwareUPS alarm/event flagRead
BV124WarrantyExpiringSoonUPS alarm/event flagRead
BV125TechnicalCheckRecommendedUPS alarm/event flagRead
BV126BatteryNearEndOfLifeUPS alarm/event flagRead
BV127BatteryMeasureLifeNearEndUPS alarm/event flagRead
BV128BatteryLifeExceededUPS alarm/event flagRead
BV129BatteryTempWarningUPS alarm/event flagRead
BV130BatteryGeneralConditionUPS alarm/event flagRead
BV131BatteryCommLostUPS alarm/event flagRead
BV132BatteryPackDisconnectedUPS alarm/event flagRead
BV133BatteryFirmwareMismatchUPS alarm/event flagRead
BV134BatteryTempSensorNotOperatingUPS alarm/event flagRead
BV135LocalDisplayButtonIssueUPS alarm/event flagRead
BV136UpsNeedsFactorySetupUPS alarm/event flagRead
BV137EpoActiveUPS alarm/event flagRead
BV138FirmwareMismatchUPS alarm/event flagRead
BV139OscillatorInoperableUPS alarm/event flagRead
BV140MeasureMismatchUPS alarm/event flagRead
BV141GeneralSubsystemConditionUPS alarm/event flagRead
BV142LogicPowerSuppyRelayConditionUPS alarm/event flagRead
BV143PowerSystemConditionUPS alarm/event flagRead
BV144MaintenanceModeForFanUPS alarm/event flagRead
BV145ServiceBypassInBypassUPS alarm/event flagRead
BV146ServiceBypassDisconnectedUPS alarm/event flagRead
BV147ServiceBypassOutputConditionUPS alarm/event flagRead
BV148ServiceBypassInternalConditionUPS alarm/event flagRead
BV149InTemporaryBypassUPS alarm/event flagRead
BV150PowerModuleInoperableUPS alarm/event flagRead
BV151BatteryInoperableUPS alarm/event flagRead
BV152LoadKvaAlarmViolationUPS alarm/event flagRead
BV153InputVoltageFreqPreventsBypassUPS alarm/event flagRead
BV154BypassDueToInternalHardwareConditionUPS alarm/event flagRead
BV155BypassDueToOverloadUPS alarm/event flagRead
BV156BypassDueToMaintenanceUPS alarm/event flagRead
BV157SystemFanInoperableUPS alarm/event flagRead
BV158RuntimeAlarmViolationUPS alarm/event flagRead
BV159ExtendedRunFrameInoperableUPS alarm/event flagRead
BV160OutputVoltageOutsideLimitsUPS alarm/event flagRead
BV161PhaseSyncConditionUPS alarm/event flagRead
BV162BatteryNotInstalledProperlyUPS alarm/event flagRead
BV163BatteryVoltageExceedsNominalUPS alarm/event flagRead
BV164SiteWiringFaultUPS alarm/event flagRead
BV165NumBatteriesIncreasedUPS alarm/event flagRead
BV166NumBatteryDecreasedUPS alarm/event flagRead
BV167ExtendedRunFramesIncreasedUPS alarm/event flagRead
BV168ExtendedRunFramesDecreasedUPS alarm/event flagRead
BV169ExternalSwitchQ001ClosedUPS alarm/event flagRead
BV170ExternalSwitchQ002ClosedUPS alarm/event flagRead
BV171ExternalSwitchQ003ClosedUPS alarm/event flagRead
BV172ExternalSwitchQ004ClosedUPS alarm/event flagRead
BV173ExternalSwitchQ005ClosedUPS alarm/event flagRead
BV174ExternalSwitchQ006ClosedUPS alarm/event flagRead
BV175ExternalSwitchQ007ClosedUPS alarm/event flagRead
BV176ExternalSwitchQ008ClosedUPS alarm/event flagRead
BV177ExternalSwitchQ009ClosedUPS alarm/event flagRead
BV178ExternalSwitchQ0010ClosedUPS alarm/event flagRead
BV179EpoActive2UPS alarm/event flagRead
BV180StaticBypassSwitchInoperableUPS alarm/event flagRead
BV181SystemStartupConfigProblemUPS alarm/event flagRead
BV182PsuInoperableUPS alarm/event flagRead
BV183WeakBatteryUPS alarm/event flagRead
BV184HighBatteryTemperatureUPS alarm/event flagRead
BV185InternalMechanicalBypassUPS alarm/event flagRead
BV186LostParallelRedundancyUPS alarm/event flagRead
BV187ParallelCommCondition1UPS alarm/event flagRead
BV188ParalletlCommCondition2UPS alarm/event flagRead
BV189AuxCommConditionUPS alarm/event flagRead
BV190ParallelTerminationCondition1UPS alarm/event flagRead
BV191ParallelTerminationCondition2UPS alarm/event flagRead
BV192AuxTerminationConditionUPS alarm/event flagRead
BV193NoMasterPresentUPS alarm/event flagRead
BV194ParallelOverloadUPS alarm/event flagRead
BV195ParallelConfigConditionUPS alarm/event flagRead
BV196ChangeDustFilterSoonUPS alarm/event flagRead
BV197ChangeDustFilterNowUPS alarm/event flagRead
BV198UioInputContact1Critical1UPS alarm/event flagRead
BV199UioInputContact1Critical2UPS alarm/event flagRead
BV200UioInputContact2Critical1UPS alarm/event flagRead
BV201UioInputContact2Critical2UPS alarm/event flagRead
BV202UioTempMinThresholdViolation1UPS alarm/event flagRead
BV203UioTempMinThresholdViolation2UPS alarm/event flagRead
BV204UioTempLowThresholdViolation1UPS alarm/event flagRead
BV205UioTempLowThresholdViolation2UPS alarm/event flagRead
BV206UioTempHighThresholdViolation1UPS alarm/event flagRead
BV207UioTempHighThresholdViolation2UPS alarm/event flagRead
BV208UioTempMaxThresholdViolation1UPS alarm/event flagRead
BV209UioTempMaxThresholdViolation2UPS alarm/event flagRead
BV210UioHumidMinThresholdViolation1UPS alarm/event flagRead
BV211UioHumidMinThresholdViolation2UPS alarm/event flagRead
BV212UioHumidLowThresholdViolation1UPS alarm/event flagRead
BV213UioHumidLowThresholdViolation2UPS alarm/event flagRead
BV214UioHumidHighThresholdViolation1UPS alarm/event flagRead
BV215UioHumidHighThresholdViolation2UPS alarm/event flagRead
BV216UioHumidMaxThresholdViolation1UPS alarm/event flagRead
BV217UioHumidMaxThresholdViolation2UPS alarm/event flagRead
BV218UioLostComm1UPS alarm/event flagRead
BV219UioLostComm2UPS alarm/event flagRead
BV220UioCriticalFaultUPS alarm/event flagRead
BV221UioOutputRelayAbnormalState1UPS alarm/event flagRead
BV222UioOutputRelayAbnormalState2UPS alarm/event flagRead
BV223UioInputContact1Warning1UPS alarm/event flagRead
BV224UioInputContact1Warning2UPS alarm/event flagRead
BV225UioInputContact2Warning1UPS alarm/event flagRead
BV226UioInputContact2Warning2UPS alarm/event flagRead
BV227InputContactOutputRelayFaultUPS alarm/event flagRead
BV228AirFilterWarningUPS alarm/event flagRead
BV229BatteryPackIncompatibleUPS alarm/event flagRead
BV230UpsInputContact1AbnormalStateUPS alarm/event flagRead
BV231UpsInputContact2AbnormalStateUPS alarm/event flagRead
BV232UpsOutputRelay1AbnormalStateUPS alarm/event flagRead
BV233UpsOutputRelay2AbnormalStateUPS alarm/event flagRead
BV234UpsOutputRelay3AbnormalStateUPS alarm/event flagRead
BV235UpsOutputRelay4AbnormalStateUPS alarm/event flagRead
BV236UpsOutputRelay5AbnormalStateUPS alarm/event flagRead
BV237UpsOutputRelay6AbnormalStateUPS alarm/event flagRead
CSV0UPS modelText, up to 24 characters [SMT/SMX/SRT, SURT, SURTD, other models]Read
CSV1UPS serial numberText, up to 16 characters [SMT/SMX/SRT, SURT, SURTD, other models]Read
CSV2UPS manufacture dateText, up to 16 characters [SMT/SMX/SRT, SURT, SURTD, other models]Read
CSV3User-specified battery replacement dateText, up to 16 characters [SMT/SMX/SRT, SURT, SURTD, other models]Read
CSV4UPS apparent power ratingText, up to 16 characters [SMT/SMX/SRT, SURT]Read
CSV5UPS real power ratingText, up to 16 characters [SMT/SMX/SRT, SURT]Read
CSV6UPS external battery SKUText, up to 16 characters [SMT/SMX/SRT, SURT]Read
CSV7UPS SKUText, up to 16 characters [SMT/SMX/SRT, SURT]Read
CSV8UPS Firmware RevisionText, up to 16 characters [SMT/SMX/SRT, SURT, SURTD, other models]Read
CSV9UPS Internal Battery SKUText, up to 16 characters [SMT/SMX/SRT, SURT]Read
CSV10Outlet group main nameText, up to 16 characters [SMT/SMX/SRT, SURT, SURTD, other models]Write
CSV11Outlet group switched 1 nameText, up to 16 characters [SMT/SMX/SRT, SURT, SURTD, other models]Write
CSV12Outlet group switched 2 nameText, up to 16 characters [SMT/SMX/SRT, SURT, SURTD, other models]Write
CSV13Outlet group switched 3 nameText, up to 16 characters [SMT/SMX/SRT, SURT, SURTD, other models]Write
CSV14Output frequency settingOutput frequency setting as text [SURT]Read
CSV15UPS nameText, up to 24 characters [SMT/SMX/SRT, SURT, SURTD, other models]Write
CSV16Next battery replacement dateText, up to 16 characters [SMT/SMX/SRT, SURT]Read
CSV17Self test resultText, up to 100 characters [SMT/SMX/SRT, SURT, SURTD, other models]Read
CSV18Runtime calibration resultText, up to 100 characters [SMT/SMX/SRT, SURT, SURTD, other models]Read
CSV19UIO probe 1 temperature and humidity nameText, up to 20 characters [SMT/SMX/SRT with AP9631/AP9635 NMC]Write
CSV20UIO probe 1 temperature and humidity locationText, up to 20 characters [SMT/SMX/SRT with AP9631/AP9635 NMC]Write
CSV21UIO probe 1 contact 1 nameText, up to 20 characters [SMT/SMX/SRT with AP9631/AP9635 NMC]Write
CSV22UIO probe 1 contact 2 nameText, up to 20 characters [SMT/SMX/SRT with AP9631/AP9635 NMC]Write
CSV23UIO probe 1 contact 1 locationText, up to 20 characters [SMT/SMX/SRT with AP9631/AP9635 NMC]Write
CSV24UIO probe 1 contact 2 locationText, up to 20 characters [SMT/SMX/SRT with AP9631/AP9635 NMC]Write
CSV25UIO probe 1 output relay 1 nameText, up to 20 characters [SMT/SMX/SRT with AP9631/AP9635 NMC]Write
CSV26UIO probe 1 output relay 1 locationText, up to 20 characters [SMT/SMX/SRT with AP9631/AP9635 NMC]Write
CSV27UIO probe 2 temperature and humidity nameText, up to 20 characters [SMT/SMX/SRT with AP9631 NMC]Write
CSV28UIO probe 2 temperature and humidity locationText, up to 20 characters [SMT/SMX/SRT with AP9631 NMC]Write
CSV29UIO probe 2 contact 1 nameText, up to 20 characters [SMT/SMX/SRT with AP9631 NMC]Write
CSV30UIO probe 2 contact 2 nameText, up to 20 characters [SMT/SMX/SRT with AP9631 NMC]Write
CSV31UIO probe 2 contact 1 locationText, up to 20 characters [SMT/SMX/SRT with AP9631 NMC]Write
CSV32UIO probe 2 contact 2 locationText, up to 20 characters [SMT/SMX/SRT with AP9631 NMC]Write
CSV33UIO probe 2 output relay 1 nameText, up to 20 characters [SMT/SMX/SRT with AP9631 NMC]Write
CSV34UIO probe 2 output relay 1 locationText, up to 20 characters [SMT/SMX/SRT with AP9631 NMC]Write
MV0Last battery transferCause of the last transfer to battery [SMT/SMX/SRT, SURT, SURTD, other models]ReadOptions in printed order: none, unknown, high input voltage, low input voltage, distorted input, rapid change input voltage, high input frequency, low input frequency, freq and/or phase difference, test, general error, power system error, battery system error, distorted inverter output, epo interface, graceful shutdown
MV1Rated Output voltage settingRated output voltage setting [SMT/SMX/SRT, SURT, SURTD, other models]ReadOptions in printed order: 100, 120, 200, 208, 220, 230, 240, 380, 400, 415, 480, 110, 127, Auto_120, 120/208, 120/240, 100/200, 225, 115
MV2SensitivityInput power sensitivity [SMT/SMX/SRT, SURT, SURTD, other models]WriteOptions in printed order: normal, reduced, low
MV3Audible AlarmWhen the UPS beeper sounds [SMT/SMX/SRT, SURT, SURTD, other models]WriteOptions in printed order: at power outage, at low battery, mute, never
MV4Self test scheduleAutomatic self-test schedule [SMT/SMX/SRT, SURT, SURTD, other models]WriteOptions in printed order: never, startup, every 7, every 14, startup and every 7 since test, startup and every 14 since test
MVmin5UPS statePresent UPS operating state [SMT/SMX/SRT, SURT, SURTD, other models]ReadOptions in printed order: unknown, online, online green, on battery, sleep, shutdown, fault, self test, calibration, bypass, low battery
MVmin6UPS ControlCommand to switch the UPS on, off, bypass, reboot or sleep [all models]WriteOptions in printed order: do nothing, on immediately, on delayed, off immediately, off delayed, bypass, return from bypass, reboot immediately, reboot delayed, sleep immediately, sleep delayed
MV7Main Outlet Group controlCommand for the main outlet group [SMT/SMX/SRT, SURT]WriteOptions in printed order: do nothing, cancel, on immediately, on delayed, off immediately, off delayed, reboot immediately, reboot delayed, shutdown immediately with ac restart, shutdown delayed with ac restart
MV8Switched Outlet group 1 controlCommand for switched outlet group 1 [SMT/SMX/SRT, SURT]WriteOptions in printed order: do nothing, cancel, on immediately, on delayed, off immediately, off delayed, reboot immediately, reboot delayed, shutdown immediately with ac restart, shutdown delayed with ac restart
MV9Switched Outlet group 2 controlCommand for switched outlet group 2 [SMT/SMX/SRT, SURT]WriteOptions in printed order: do nothing, cancel, on immediately, on delayed, off immediately, off delayed, reboot immediately, reboot delayed, shutdown immediately with ac restart, shutdown delayed with ac restart
MV10Switched Outlet group 3 controlCommand for switched outlet group 3 [SMT/SMX/SRT, SURT]WriteOptions in printed order: do nothing, cancel, on immediately, on delayed, off immediately, off delayed, reboot immediately, reboot delayed, shutdown immediately with ac restart, shutdown delayed with ac restart
MV11UIO probe 1 temperature and humidity statusProbe status [SMT/SMX/SRT with AP9631/AP9635 NMC]ReadOptions in printed order: not present, ok, warning, critical
MV12UIO probe 1 contact statusProbe status [SMT/SMX/SRT with AP9631/AP9635 NMC]ReadOptions in printed order: not present, ok, warning, critical
MV13UIO probe 2 temperature and humidity statusProbe status [SMT/SMX/SRT with AP9631 NMC]ReadOptions in printed order: not present, ok, warning, critical
MV14UIO probe 2 contact statusProbe status [SMT/SMX/SRT with AP9631 NMC]ReadOptions in printed order: not present, ok, warning, critical
NC0DefaultNotifierDefault notification class for UPS alarm BVsWrite
Object ID lookup: APC Smart-UPS with Network Management Card 2 / 3 point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Smart-UPS with Network Management Card 2 / 3 (BACnet IP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the APC Smart-UPS with Network Management Card 2 / 3 (BACnet IP)

How many BACnet points does the APC Smart-UPS with Network Management Card 2 / 3 (BACnet IP) have?

This list has 390 BACnet objects: 101 analog values, 238 binary values, 1 notification class, 15 multi-state values, 35 characterstring values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which APC Smart-UPS with Network Management Card 2 / 3 (BACnet IP) BACnet points are writable?

151 of the 390 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official APC Smart-UPS with Network Management Card 2 / 3 (BACnet IP) BACnet documentation?

The source is BACnet Application Map for Network Management Card 2 and 3 (Smart-UPS) (990-5916C), revision 2024-04, published free by APC at https://download.se.com/files?p_Doc_Ref=SPD_CCON-AUTEZG_EN.

What are the minimum BACnet points to integrate the APC Smart-UPS with Network Management Card 2 / 3 (BACnet IP)?

Start with MV 6 UPS Control (UPS on/off/reboot/sleep/bypass command); MV 5 UPS state (Online, on battery, bypass, fault and so on); AV 0 Runtime remaining (Battery runtime left, s); AV 66 Battery state of charge (Battery charge, %); AV 19 Output watts phase 1 (Load as % of the watt rating); AV 10 Output voltage 1 (Output voltage, V); BV 73 OnBattery (UPS is running on battery); BV 72 LowBattery (Battery low alarm); BV 70 Overload (Output overload alarm); BV 69 LostUPSComm (Card lost communication with the UPS).

How do I enable BMS control of the APC Smart-UPS with Network Management Card 2 / 3 (BACnet IP)?

BACnet IP is part of the NMC2 'sumx' and NMC3 'su' application firmware and is turned on in the card's configuration. No BMS enable point is needed; UPS Control (MV 6) acts directly on the UPS.

How do I check these points on the real Smart-UPS with Network Management Card 2 / 3 (BACnet IP)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More APC BACnet points lists

Source: BACnet Application Map for Network Management Card 2 and 3 (Smart-UPS) · 990-5916C · rev. 2024-04. Object names, instances and units are reproduced as published; descriptions are our own.