 "manufacturer": "APC",
 "manufacturer_slug": "apc",
 "model": "APC InRow RC chilled water 300 mm (ACRC301S / ACRC301H) BACnet IP",
 "model_slug": "inrow-rc-acrc301-chilled-water",
 "short_model": "InRow RC ACRC301S / ACRC301H",
 "aliases": [
  "ACRC301S",
  "ACRC301H",
  "ACRC3xx",
  "InRow RC 300 mm",
  "InRow CW",
  "Schneider Electric InRow RC",
  "TME27091"
 ],
 "equipment_type": "In-row precision cooling unit (chilled water computer room air handler)",
 "applies_to": "APC / Schneider Electric InRow RC 300 mm chilled water in-row coolers ACRC301S and ACRC301H with application firmware v6.0.0 or later.",
 "summary": "The InRow RC 300 mm chilled water units serve BACnet IP from their network management card. The map has Multi-state Values for on/standby, operating mode, airflow and delta-T setpoint selections and configuration, Binary Values for each alarm (active = alarm), Analog Values for temperatures, flows, demand, power, energy and run hours, and Character String Values for identity.",
 "bacnet_transport": [
  "BACnet IP"
 ],
 "firmware": "Application firmware v6.0.0 or later (v2.4.2.1 and later support BACnet IP only)",
 "default_device_instance": null,
 "access_inferred": false,
 "notes": [
  "The page titled 'Analog Value Objects' actually lists the Multi-state Values (its object IDs are type 19); they are listed here as MV.",
  "The Analog Value table page is blank in this release (07/2023). The AV names and instances come from the document's index (BACnet Name, Object Type, BACnet Index); units and read/write access are not printed for them, so they are shown as read-only.",
  "MV 32 Circulation Pump Model is printed between MV 9 and MV 10 in the table; it is listed here in instance order.",
  "Alarm Binary Values are named by alarm code (BN3902 and so on); the description holds the printed alarm text.",
  "The ID column is the full object identifier (type x 4194304 + instance) and agrees with the Index column for every row."
 ],
 "source": {
  "title": "BACnet Application Map - InRow RC Chilled Water Air Conditioners, 300 mm",
  "doc_number": "TME27091",
  "revision_date": "2023-07",
  "url": "https://download.se.com/files?p_Doc_Ref=TME27091"
 },
 "integration": {
  "summary": "Enable BACnet on the unit's Network Management Card 2 (see the NMC 2 user guide) and give it a unique device instance. Use MV 0 On or Standby to start and stop the unit and read MV 2 Operating Mode for its state. Map supply and return air temperatures, cool output, fan speed and the alarm Binary Values for monitoring; MV 25 clears active alarms.",
  "minimum_points": [
   {
    "ref": "MV 0",
    "name": "On or Standby",
    "why": "Unit on/standby command (1=Standby, 2=On)"
   },
   {
    "ref": "MV 25",
    "name": "Clear Active Alarms",
    "why": "Write 2=Yes to clear active alarms"
   },
   {
    "ref": "MV 2",
    "name": "Operating Mode",
    "why": "Standby, on, idle or maintenance"
   },
   {
    "ref": "AV 10",
    "name": "Supply Air Temperature",
    "why": "Air leaving the unit"
   },
   {
    "ref": "AV 11",
    "name": "Return Air Temperature",
    "why": "Air entering the unit"
   },
   {
    "ref": "AV 53",
    "name": "Supply Air Setpoint",
    "why": "Supply air temperature setpoint"
   },
   {
    "ref": "AV 26",
    "name": "Cool Output",
    "why": "Cooling delivered by the unit"
   },
   {
    "ref": "AV 28",
    "name": "Fan Speed",
    "why": "Current fan speed"
   },
   {
    "ref": "BV 2",
    "name": "BN3906",
    "why": "Cool Fail alarm"
   },
   {
    "ref": "BV 22",
    "name": "BN392E",
    "why": "Water Detected Fault alarm"
   }
  ],
  "enable": "MV 0 On or Standby (writable) switches the unit between standby and on.",
  "heartbeat": null,
  "remote_sensors": null,
  "setup": [
   "BACnet IP only (application firmware v2.4.2.1 and later).",
   "The map refers to the Network Management Card 2 User Guide for configuring BACnet.",
   "The map lists one Notification Class object, NC 0 DefaultNotifier."
  ],
  "gotchas": [
   "The map does not print access or units for the Analog Values; check on the unit before writing setpoints such as AV 53 or AV 52.",
   "Many Multi-state Values are configuration settings (power source, filter type, configuration type); do not write them cyclically."
  ]
 },
 "points": [
  {
   "type": "AV",
   "instance": 0,
   "name": "Startup Delay",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1,
   "name": "Maximum Chilled Water Flow",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2,
   "name": "Number of Rack Inlet Temperature Sensors in Unit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3,
   "name": "Number of Leak Detectors in Unit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 4,
   "name": "Rack Inlet Temperature High Threshold",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 5,
   "name": "Supply Air Temperature High Threshold",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 6,
   "name": "Return Air Temperature High Threshold",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 7,
   "name": "Entering Chilled Water Temperature High Threshold",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 8,
   "name": "Air Filter Service Interval",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 9,
   "name": "Unit Service Alarm Interval",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10,
   "name": "Supply Air Temperature",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 11,
   "name": "Return Air Temperature",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 12,
   "name": "Filter Differential Pressure",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 13,
   "name": "Entering Chilled Water Temperature",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 14,
   "name": "Leaving Chilled Water Temperature",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 15,
   "name": "Chilled Water Valve Position",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 16,
   "name": "Unit Rack Inlet Temperatures_1",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 17,
   "name": "Unit Rack Inlet Temperatures_2",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 18,
   "name": "Unit Rack Inlet Temperatures_3",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 19,
   "name": "Unit Rack Inlet Temperatures_4",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 20,
   "name": "Maximum Rack Inlet Temperature",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 21,
   "name": "Minimum Rack Inlet Temperature",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 22,
   "name": "Chilled Water Flow",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 23,
   "name": "Dew Point Temperature",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 24,
   "name": "Coil Chilled Water Temperature",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 25,
   "name": "Cool Demand",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 26,
   "name": "Cool Output",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 27,
   "name": "Airflow",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 28,
   "name": "Fan Speed",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 29,
   "name": "Unit Power",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 30,
   "name": "Unit Energy",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 31,
   "name": "Circulation Pump Speed",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 32,
   "name": "Group Cool Demand",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 33,
   "name": "Group Cool Output",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 34,
   "name": "Group Airflow",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 35,
   "name": "Fan run hours_1",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 36,
   "name": "Fan run hours_2",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 37,
   "name": "Fan run hours_3",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 38,
   "name": "Fan run hours_4",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 39,
   "name": "Fan run hours_5",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 40,
   "name": "Fan run hours_6",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 41,
   "name": "Fan run hours_7",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 42,
   "name": "Fan run hours_8",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 43,
   "name": "Air Filter run hours",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 44,
   "name": "Fan Power Supply run hours_1",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 45,
   "name": "Fan Power Supply run hours_2",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 46,
   "name": "Condensate Pump run hours",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 47,
   "name": "Unit run hours",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 48,
   "name": "Circulation Pump run hours",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 49,
   "name": "Percent Glycol",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 50,
   "name": "Altitude",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 51,
   "name": "Number of Units in Group",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 52,
   "name": "Cool Setpoint",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 53,
   "name": "Supply Air Setpoint",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 54,
   "name": "Maximum Fan Speed",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 55,
   "name": "Number of Active Flow Controllers",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 56,
   "name": "Circulation Pump Flow",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 57,
   "name": "Circulation Pump Power",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 0,
   "name": "BN3902",
   "description": "Internal Communication Error",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active (alarm)"
  },
  {
   "type": "BV",
   "instance": 1,
   "name": "BN3904",
   "description": "Unexpected Number of Units in Group",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active (alarm)"
  },
  {
   "type": "BV",
   "instance": 2,
   "name": "BN3906",
   "description": "Cool Fail",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active (alarm)"
  },
  {
   "type": "BV",
   "instance": 3,
   "name": "BN3908",
   "description": "Rack Temperature High Violation",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active (alarm)"
  },
  {
   "type": "BV",
   "instance": 4,
   "name": "BN390A",
   "description": "Air Filter Clogged",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active (alarm)"
  },
  {
   "type": "BV",
   "instance": 5,
   "name": "BN390C",
   "description": "Upper Return Air Sensor Fault",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active (alarm)"
  },
  {
   "type": "BV",
   "instance": 6,
   "name": "BN390E",
   "description": "Lower Return Air Sensor Fault",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active (alarm)"
  },
  {
   "type": "BV",
   "instance": 7,
   "name": "BN3910",
   "description": "Upper Supply Air Sensor Fault",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active (alarm)"
  },
  {
   "type": "BV",
   "instance": 8,
   "name": "BN3912",
   "description": "Lower Supply Air Sensor Fault",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active (alarm)"
  },
  {
   "type": "BV",
   "instance": 9,
   "name": "BN3914",
   "description": "Rack Temperature Sensor 1 Fault",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active (alarm)"
  },
  {
   "type": "BV",
   "instance": 10,
   "name": "BN3916",
   "description": "Rack Temperature Sensor 2 Fault",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active (alarm)"
  },
  {
   "type": "BV",
   "instance": 11,
   "name": "BN3918",
   "description": "Rack Temperature Sensor 3 Fault",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active (alarm)"
  },
  {
   "type": "BV",
   "instance": 12,
   "name": "BN391A",
   "description": "Rack Temperature Sensor 4 Fault",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active (alarm)"
  },
  {
   "type": "BV",
   "instance": 13,
   "name": "BN391C",
   "description": "Fan 1 Fault",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active (alarm)"
  },
  {
   "type": "BV",
   "instance": 14,
   "name": "BN391E",
   "description": "Fan 2 Fault",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active (alarm)"
  },
  {
   "type": "BV",
   "instance": 15,
   "name": "BN3920",
   "description": "Fan 3 Fault",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active (alarm)"
  },
  {
   "type": "BV",
   "instance": 16,
   "name": "BN3922",
   "description": "Fan 4 Fault",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active (alarm)"
  },
  {
   "type": "BV",
   "instance": 17,
   "name": "BN3924",
   "description": "Fan 5 Fault",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active (alarm)"
  },
  {
   "type": "BV",
   "instance": 18,
   "name": "BN3926",
   "description": "Fan 6 Fault",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active (alarm)"
  },
  {
   "type": "BV",
   "instance": 19,
   "name": "BN3928",
   "description": "Fan 7 Fault",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active (alarm)"
  },
  {
   "type": "BV",
   "instance": 20,
   "name": "BN392A",
   "description": "Fan 8 Fault",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active (alarm)"
  },
  {
   "type": "BV",
   "instance": 21,
   "name": "BN392C",
   "description": "Chilled Water Valve Actuator Fault",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active (alarm)"
  },
  {
   "type": "BV",
   "instance": 22,
   "name": "BN392E",
   "description": "Water Detected Fault",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active (alarm)"
  },
  {
   "type": "BV",
   "instance": 23,
   "name": "BN3930",
   "description": "Water Detected Shutdown",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active (alarm)"
  },
  {
   "type": "BV",
   "instance": 24,
   "name": "BN3932",
   "description": "Check Condensate Management System",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active (alarm)"
  },
  {
   "type": "BV",
   "instance": 25,
   "name": "BN3934",
   "description": "Chilled Water Flow Meter Fault",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active (alarm)"
  },
  {
   "type": "BV",
   "instance": 26,
   "name": "BN3936",
   "description": "Entering Chilled Water Temperature High Violation",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active (alarm)"
  },
  {
   "type": "BV",
   "instance": 27,
   "name": "BN3938",
   "description": "Entering Chilled Water Temperature Sensor Fault",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active (alarm)"
  },
  {
   "type": "BV",
   "instance": 28,
   "name": "BN393A",
   "description": "Leaving Chilled Water Temperature Sensor Fault",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active (alarm)"
  },
  {
   "type": "BV",
   "instance": 29,
   "name": "BN393C",
   "description": "Condensate Pan Full",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active (alarm)"
  },
  {
   "type": "BV",
   "instance": 30,
   "name": "BN393E",
   "description": "Primary Power Source Fail",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active (alarm)"
  },
  {
   "type": "BV",
   "instance": 31,
   "name": "BN3940",
   "description": "Secondary Power Source Fail",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active (alarm)"
  },
  {
   "type": "BV",
   "instance": 32,
   "name": "BN3942",
   "description": "Fan Power Supply 1 Fault",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active (alarm)"
  },
  {
   "type": "BV",
   "instance": 33,
   "name": "BN3944",
   "description": "Fan Power Supply 2 Fault",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active (alarm)"
  },
  {
   "type": "BV",
   "instance": 34,
   "name": "BN3946",
   "description": "Air Filter Run Hours Violation",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active (alarm)"
  },
  {
   "type": "BV",
   "instance": 35,
   "name": "BN3948",
   "description": "Supply Air High Temperature Violation",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active (alarm)"
  },
  {
   "type": "BV",
   "instance": 36,
   "name": "BN394A",
   "description": "Return Air High Temperature Violation",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active (alarm)"
  },
  {
   "type": "BV",
   "instance": 37,
   "name": "BN394C",
   "description": "Filter DP Sensor Failure",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active (alarm)"
  },
  {
   "type": "BV",
   "instance": 38,
   "name": "BN394E",
   "description": "Standby Due to Input Contact",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active (alarm)"
  },
  {
   "type": "BV",
   "instance": 39,
   "name": "BN3950",
   "description": "Chilled Water Valve Control Not Set to Auto",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active (alarm)"
  },
  {
   "type": "BV",
   "instance": 40,
   "name": "BN3952",
   "description": "EcoAisle Door Open",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active (alarm)"
  },
  {
   "type": "BV",
   "instance": 41,
   "name": "BN3954",
   "description": "Unexpected Number of Active Flow Controllers",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active (alarm)"
  },
  {
   "type": "BV",
   "instance": 42,
   "name": "BN3956",
   "description": "Insufficient Airflow",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active (alarm)"
  },
  {
   "type": "BV",
   "instance": 43,
   "name": "BN3958",
   "description": "Active Flow Controller Sensor Fault",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active (alarm)"
  },
  {
   "type": "BV",
   "instance": 44,
   "name": "BN395A",
   "description": "Unit Service Required",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active (alarm)"
  },
  {
   "type": "BV",
   "instance": 45,
   "name": "BN395C",
   "description": "Humidity Sensor Fault",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active (alarm)"
  },
  {
   "type": "BV",
   "instance": 46,
   "name": "BN395E",
   "description": "Coil Condensation Possible",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active (alarm)"
  },
  {
   "type": "BV",
   "instance": 47,
   "name": "BN3960",
   "description": "Controller Power Supply 1 Fault",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active (alarm)"
  },
  {
   "type": "BV",
   "instance": 48,
   "name": "BN3962",
   "description": "Controller Power Supply 2 Fault",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active (alarm)"
  },
  {
   "type": "BV",
   "instance": 49,
   "name": "BN3964",
   "description": "Coil Chilled Water Temperature Sensor Fault",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active (alarm)"
  },
  {
   "type": "BV",
   "instance": 50,
   "name": "BN3966",
   "description": "Fan Power Supply 1 Current Sense Fault",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active (alarm)"
  },
  {
   "type": "BV",
   "instance": 51,
   "name": "BN3968",
   "description": "Fan Power Supply 2 Current Sense Fault",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active (alarm)"
  },
  {
   "type": "BV",
   "instance": 52,
   "name": "BN396A",
   "description": "Factory Configuration Not Completed",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active (alarm)"
  },
  {
   "type": "BV",
   "instance": 53,
   "name": "BN396C",
   "description": "Unit is in Maintenance Mode",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active (alarm)"
  },
  {
   "type": "BV",
   "instance": 54,
   "name": "BN396E",
   "description": "Unexpected Number of Rack Inlet Temperature Sensors",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active (alarm)"
  },
  {
   "type": "BV",
   "instance": 55,
   "name": "BN3970",
   "description": "Unexpected Number of Leak Detectors",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active (alarm)"
  },
  {
   "type": "BV",
   "instance": 56,
   "name": "BN3972",
   "description": "Output Relay 1 Active",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active (alarm)"
  },
  {
   "type": "BV",
   "instance": 57,
   "name": "BN3974",
   "description": "Output Relay 2 Active",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active (alarm)"
  },
  {
   "type": "BV",
   "instance": 58,
   "name": "BN3976",
   "description": "Output Relay 3 Active",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active (alarm)"
  },
  {
   "type": "BV",
   "instance": 59,
   "name": "BN3978",
   "description": "Output Relay 4 Active",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active (alarm)"
  },
  {
   "type": "BV",
   "instance": 60,
   "name": "BN397A",
   "description": "Circulation Pump Fault",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active (alarm)"
  },
  {
   "type": "BV",
   "instance": 61,
   "name": "BN397C",
   "description": "Standby Due to User Action",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active (alarm)"
  },
  {
   "type": "BV",
   "instance": 62,
   "name": "BN397E",
   "description": "Circulation Pump Communication Loss",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active (alarm)"
  },
  {
   "type": "BV",
   "instance": 63,
   "name": "BN3980",
   "description": "Circulation Pump Warning Present",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active (alarm)"
  },
  {
   "type": "BV",
   "instance": 64,
   "name": "BN3982",
   "description": "Circulation Pump Needs Service",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active (alarm)"
  },
  {
   "type": "MV",
   "instance": 0,
   "name": "On or Standby",
   "description": "On / Standby",
   "units": "",
   "access": "W",
   "states": "1=Standby, 2=On"
  },
  {
   "type": "MV",
   "instance": 1,
   "name": "Idle on Leak Detect",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=No, 2=Yes"
  },
  {
   "type": "MV",
   "instance": 2,
   "name": "Operating Mode",
   "description": "",
   "units": "",
   "access": "R",
   "states": "1=Standby, 2=On, 3=Idle, 4=Maintenance"
  },
  {
   "type": "MV",
   "instance": 3,
   "name": "Idle On Cool Fail",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=No, 2=Yes"
  },
  {
   "type": "MV",
   "instance": 4,
   "name": "Power Source",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Single, 2=Dual"
  },
  {
   "type": "MV",
   "instance": 5,
   "name": "Chilled Water Valve Control",
   "description": "",
   "units": "",
   "access": "R",
   "states": "1=Automatic, 2=Open"
  },
  {
   "type": "MV",
   "instance": 6,
   "name": "Bypass Valve Position",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Open, 2=Closed"
  },
  {
   "type": "MV",
   "instance": 7,
   "name": "Air Filter Type",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Standard, 2=Pleated"
  },
  {
   "type": "MV",
   "instance": 8,
   "name": "Alarm On Standby",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=No, 2=Yes"
  },
  {
   "type": "MV",
   "instance": 9,
   "name": "Auto Recover Cool Fail",
   "description": "",
   "units": "",
   "access": "R",
   "states": "1=No, 2=Yes"
  },
  {
   "type": "MV",
   "instance": 10,
   "name": "Air Filter Service Alarm Enable",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Disable, 2=Enable"
  },
  {
   "type": "MV",
   "instance": 11,
   "name": "Unit Service Alarm Enable",
   "description": "",
   "units": "",
   "access": "R",
   "states": "1=Disable, 2=Enable"
  },
  {
   "type": "MV",
   "instance": 12,
   "name": "Reset Air Filter Service Alarm",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=No, 2=Yes"
  },
  {
   "type": "MV",
   "instance": 13,
   "name": "Standby Input Normal State",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Open, 2=Closed"
  },
  {
   "type": "MV",
   "instance": 14,
   "name": "Standby Input State",
   "description": "",
   "units": "",
   "access": "R",
   "states": "1=Open, 2=Closed"
  },
  {
   "type": "MV",
   "instance": 15,
   "name": "Output State_1",
   "description": "Output State 1",
   "units": "",
   "access": "R",
   "states": "1=Abnormal, 2=Normal"
  },
  {
   "type": "MV",
   "instance": 16,
   "name": "Output State_2",
   "description": "Output State 2",
   "units": "",
   "access": "R",
   "states": "1=Abnormal, 2=Normal"
  },
  {
   "type": "MV",
   "instance": 17,
   "name": "Output State_3",
   "description": "Output State 3",
   "units": "",
   "access": "R",
   "states": "1=Abnormal, 2=Normal"
  },
  {
   "type": "MV",
   "instance": 18,
   "name": "Output State_4",
   "description": "Output State 4",
   "units": "",
   "access": "R",
   "states": "1=Abnormal, 2=Normal"
  },
  {
   "type": "MV",
   "instance": 19,
   "name": "Leak Detector_1",
   "description": "Leak Detector 1",
   "units": "",
   "access": "R",
   "states": "1=No Leak, 2=Leak Detected"
  },
  {
   "type": "MV",
   "instance": 20,
   "name": "Leak Detector_2",
   "description": "Leak Detector 2",
   "units": "",
   "access": "R",
   "states": "1=No Leak, 2=Leak Detected"
  },
  {
   "type": "MV",
   "instance": 21,
   "name": "Leak Detector_3",
   "description": "Leak Detector 3",
   "units": "",
   "access": "R",
   "states": "1=No Leak, 2=Leak Detected"
  },
  {
   "type": "MV",
   "instance": 22,
   "name": "Leak Detector_4",
   "description": "Leak Detector 4",
   "units": "",
   "access": "R",
   "states": "1=No Leak, 2=Leak Detected"
  },
  {
   "type": "MV",
   "instance": 23,
   "name": "Active Power Source",
   "description": "",
   "units": "",
   "access": "R",
   "states": "1=Primary, 2=Secondary, 3=No Mains"
  },
  {
   "type": "MV",
   "instance": 24,
   "name": "Active Flow Control Status",
   "description": "",
   "units": "",
   "access": "R",
   "states": "1=Under, 2=Okay, 3=Over, 4=N/A"
  },
  {
   "type": "MV",
   "instance": 25,
   "name": "Clear Active Alarms",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=No, 2=Yes"
  },
  {
   "type": "MV",
   "instance": 26,
   "name": "Reset Unit Energy",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=No, 2=Yes"
  },
  {
   "type": "MV",
   "instance": 27,
   "name": "Configuration Type",
   "description": "",
   "units": "",
   "access": "R",
   "states": "1=RACS, 2=HACS, 3=In-Row, 4=CACS"
  },
  {
   "type": "MV",
   "instance": 28,
   "name": "Airflow Control",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Automatic, 2=60%, 3=70%, 4=80%, 5=90%, 6=100%"
  },
  {
   "type": "MV",
   "instance": 29,
   "name": "Delta-T Setpoint",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=10F/5.6C, 2=15F/8.3C, 3=20F/11.1C, 4=25F/13.9C, 5=30F/16.7C, 6=35F/19.4C, 7=40F/22.2C"
  },
  {
   "type": "MV",
   "instance": 30,
   "name": "Active Flow Control Bias",
   "description": "",
   "units": "",
   "access": "R",
   "states": "1=Positive, 2=Slightly Positive, 3=Zero, 4=Slightly Negative, 5=Negative"
  },
  {
   "type": "MV",
   "instance": 31,
   "name": "Active Flow Control Lamp Test",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Off, 2=On"
  },
  {
   "type": "MV",
   "instance": 32,
   "name": "Circulation Pump Model",
   "description": "",
   "units": "",
   "access": "R",
   "states": "1=None, 2=Stratos, 3=Stratos Maxo"
  },
  {
   "type": "CSV",
   "instance": 0,
   "name": "Model Number",
   "description": "Model Number (max 19 chars)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "CSV",
   "instance": 1,
   "name": "Serial Number",
   "description": "Serial Number (max 19 chars)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "CSV",
   "instance": 2,
   "name": "Firmware Revision_1",
   "description": "Firmware Revision (Executing) (max 19 chars)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "CSV",
   "instance": 3,
   "name": "Firmware Revision_2",
   "description": "Firmware Revision (Newest) (max 19 chars)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "CSV",
   "instance": 4,
   "name": "Firmware Revision_3",
   "description": "Firmware Revision (Oldest) (max 19 chars)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "CSV",
   "instance": 5,
   "name": "Firmware Revision_4",
   "description": "Firmware Revision (Bootloader) (max 19 chars)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "CSV",
   "instance": 6,
   "name": "Hardware Revision",
   "description": "Hardware Revision (max 7 chars)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "NC",
   "instance": 0,
   "name": "DefaultNotifier",
   "description": "Default Notification Class",
   "units": "",
   "access": "W",
   "states": ""
  }
 ],
 "page": "https://easybacnet.com/bacnet-points-lists/apc/inrow-rc-acrc301-chilled-water",
 "note": "Provided as-is. Point availability varies by firmware and options; verify against the live device.",
 "disclaimer": "DISCLAIMER: reference only, provided AS IS with no warranty. May contain errors or be out of date. You must verify every point against the manufacturer's current documentation and the live device before use. easybacnet.com accepts no liability for its use and is not affiliated with the manufacturer. Terms: https://easybacnet.com/terms#content"
}