Kitchen hood demand-controlled ventilation controls · BACnet points list

Accurex Vari-Flow Air Management System v2.00 BACnet points list

Updated 7 November 2026

Short answer

Vari-Flow is Accurex's demand-controlled kitchen ventilation controller. It modulates exhaust and supply fans from hood temperatures and can talk BACnet MS/TP or BACnet IP through a communication card. The v2.00 points list covers hood control temperatures, fan speeds and status, temperature settings, hood system on/off commands, remote enable, wash and alarm flags.

This page lists 167 BACnet objects for the Accurex Vari-Flow Air Management System v2.00 — 60 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Accurex’s own free documentation, linked below.

Manufacturer
Accurex
Model
Vari-Flow Air Management System v2.00
Equipment
Kitchen hood demand-controlled ventilation controls
Equipment type
Other equipment
BACnet objects
167 (60 writable)
Transport
BACnet MS/TP, BACnet IP
Firmware
Vari-Flow v2.00
Default device instance
77000
Also known as
Vari-Flow, Vari-Flow 2.00, Accurex demand-controlled kitchen ventilation, Auto Scrubber Control Panel, ASCP v2.00
Source document
Vari-Flow Air Management System - Installation, Operation and Maintenance Manual, BMS Points List (v2.00) · 481515 Rev. 3 · rev. 2019-08
Download CSV 167 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Accurex’s current documentation and the live device before use. Not official Accurex information. Terms of use.

BMS integration notes: Accurex Vari-Flow Air Management System v2.00

Integration in brief

Enable the system with BV 102 Remote Enable and switch hood systems with BV 11-20. Read hood control temperatures (AV 11-20), fan speeds (AV 1011 up) and fan status BVs, and watch BV 10 Global Alarm and BV 101 fire status.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 102Rem_EnRemote enable of the system (1 = on)Write
BV 11Sys1_On_OffHood system 1 on/off (1 = on)Write
AV 11H1_CtempHood 1 control temperatureRead
AV 1011Ef1_SpeedExhaust fan 1 speed, %Read
BV 171Ef1_StatusExhaust fan 1 runningRead
BV 181Sf1_StatusSupply fan 1 runningRead
BV 101Fire_AlmFire system activeRead
BV 10GLOBAL_ALARMAny active alarmRead

Enable & remote start

BV 102 Remote Enable (1 = on) and the per-system On/Off BVs (BV 11-20) let the BMS run the hood systems.

Network setup

Watch out for

Accurex Vari-Flow Air Management System v2.00 BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

167 of 167 shown
Type
AnalogBinary
Access
Show
Accurex Vari-Flow Air Management System v2.00 BACnet Points List
DescriptionStates
AVmin11H1_CtempHood 1 Control Temperature°FRead
AV12H2_CtempHood 2 Control Temperature°FRead
AV13H3_CtempHood 3 Control Temperature°FRead
AV14H4_CtempHood 4 Control Temperature°FRead
AV15H5_CtempHood 5 Control Temperature°FRead
AV16H6_CtempHood 6 Control Temperature°FRead
AV17H7_CtempHood 7 Control Temperature°FRead
AV18H8_CtempHood 8 Control Temperature°FRead
AV19H9_CtempHood 9 Control Temperature°FRead
AV20H10_CtempHood 10 Control Temperature°FRead
AV51Ef1_AmpsExhaust Fan 1 Amps from VFDARead
AV52Ef2_AmpsExhaust Fan 2 Amps from VFDARead
AV53Ef3_AmpsExhaust Fan 3 Amps from VFDARead
AV54Ef4_AmpsExhaust Fan 4 Amps from VFDARead
AV55Ef5_AmpsExhaust Fan 5 Amps from VFDARead
AV56Ef6_AmpsExhaust Fan 6 Amps from VFDARead
AV57Ef7_AmpsExhaust Fan 7 Amps from VFDARead
AV58Ef8_AmpsExhaust Fan 8 Amps from VFDARead
AV59Ef9_AmpsExhaust Fan 9 Amps from VFDARead
AV60Ef10_AmpsExhaust Fan 10 Amps from VFDARead
AV71Sf1_AmpsSupply 1 Amps from VFDARead
AV72Sf2_AmpsSupply 2 Amps from VFDARead
AV73Sf3_AmpsSupply 3 Amps from VFDARead
AV74Sf4_AmpsSupply 4 Amps from VFDARead
AV81Ef1_kWExhaust Fan 1 Power OutputkWRead
AV82Ef2_kWExhaust Fan 2 Power OutputkWRead
AV83Ef3_kWExhaust Fan 3 Power OutputkWRead
AV84Ef4_kWExhaust Fan 4 Power OutputkWRead
AV85Ef5_kWExhaust Fan 5 Power OutputkWRead
AV86Ef6_kWExhaust Fan 6 Power OutputkWRead
AV87Ef7_kWExhaust Fan 7 Power OutputkWRead
AV88Ef8_kWExhaust Fan 8 Power OutputkWRead
AV89Ef9_kWExhaust Fan 9 Power OutputkWRead
AV90Ef10_kWExhaust Fan 10 Power OutputkWRead
AV101Sf1_kWSupply Fan 1 Power OutputkWRead
AV102Sf2_kWSupply Fan 2 Power OutputkWRead
AV103Sf3_kWSupply Fan 3 Power OutputkWRead
AV104Sf4_kWSupply Fan 4 Power OutputkWRead
AV111Ef1_FrReExhaust Fan 1 Frequency ReferenceHzRead
AV112Ef2_FrReExhaust Fan 2 Frequency ReferenceHzRead
AV113Ef3_FrReExhaust Fan 3 Frequency ReferenceHzRead
AV114Ef4_FrReExhaust Fan 4 Frequency ReferenceHzRead
AV115Ef5_FrReExhaust Fan 5 Frequency ReferenceHzRead
AV116Ef6_FrReExhaust Fan 6 Frequency ReferenceHzRead
AV117Ef7_FrReExhaust Fan 7 Frequency ReferenceHzRead
AV118Ef8_FrReExhaust Fan 8 Frequency ReferenceHzRead
AV119Ef9_FrReExhaust Fan 9 Frequency ReferenceHzRead
AV120Ef10_FrReExhaust Fan 10 Frequency ReferenceHzRead
AV131Sf1_FrReSupply Fan 1 Frequency ReferenceHzRead
AV132Sf2_FrReSupply Fan 2 Frequency ReferenceHzRead
AV133Sf3_FrReSupply Fan 3 Frequency ReferenceHzRead
AV134Sf4_FrReSupply Fan 4 Frequency ReferenceHzRead
AV141Ef1_LoTempExhaust Fan 1 Low Temperature Setting°FWrite
AV142Ef2_LoTempExhaust Fan 2 Low Temperature Setting°FWrite
AV143Ef3_LoTempExhaust Fan 3 Low Temperature Setting°FWrite
AV144Ef4_LoTempExhaust Fan 4 Low Temperature Setting°FWrite
AV145EF5_LoTempExhaust Fan 5 Low Temperature Setting°FWrite
AV146EF6_LoTempExhaust Fan 6 Low Temperature Setting°FWrite
AV147EF7_LoTempExhaust Fan 7 Low Temperature Setting°FWrite
AV148EF8_LoTempExhaust Fan 8 Low Temperature Setting°FWrite
AV149EF9_LoTempExhaust Fan 9 Low Temperature Setting°FWrite
AV150EF10_LoTempExhaust Fan 10 Low Temperature Setting°FWrite
AV151Ef1_HiTempExhaust Fan 1 High Temperature Setting°FWrite
AV152Ef2_HiTempExhaust Fan 2 High Temperature Setting°FWrite
AV153Ef3_HiTempExhaust Fan 3 High Temperature Setting°FWrite
AV154Ef4_HiTempExhaust Fan 4 High Temperature Setting°FWrite
AV155Ef5_HiTempExhaust Fan 5 High Temperature Setting°FWrite
AV156Ef6_HiTempExhaust Fan 6 High Temperature Setting°FWrite
AV157Ef7_HiTempExhaust Fan 7 High Temperature Setting°FWrite
AV158Ef8_HiTempExhaust Fan 8 High Temperature Setting°FWrite
AV159Ef9_HiTempExhaust Fan 9 High Temperature Setting°FWrite
AV160Ef10_HiTempExhaust Fan 10 High Temperature Setting°FWrite
AV161Ef1_LoSpeedExhaust Fan 1 Low Speed Setting%Write
AV162Ef2_LoSpeedExhaust Fan 2 Low Speed Setting%Write
AV163Ef3_LoSpeedExhaust Fan 3 Low Speed Setting%Write
AV164Ef4_LoSpeedExhaust Fan 4 Low Speed Setting%Write
AV165Ef5_LoSpeedExhaust Fan 5 Low Speed Setting%Write
AV166Ef6_LoSpeedExhaust Fan 6 Low Speed Setting%Write
AV167Ef7_LoSpeedExhaust Fan 7 Low Speed Setting%Write
AV168Ef8_LoSpeedExhaust Fan 8 Low Speed Setting%Write
AV169Ef9_LoSpeedExhaust Fan 9 Low Speed Setting%Write
AV170Ef10_LoSpeedExhaust Fan 10 Low Speed Setting%Write
AV171Ef1_HiSpeedExhaust Fan 1 High Speed Setting%Write
AV172Ef2_HiSpeedExhaust Fan 2 High Speed Setting%Write
AV173Ef3_HiSpeedExhaust Fan 3 High Speed Setting%Write
AV174Ef4_HiSpeedExhaust Fan 4 High Speed Setting%Write
AV175Ef5_HiSpeedExhaust Fan 5 High Speed Setting%Write
AV176Ef6_HiSpeedExhaust Fan 6 High Speed Setting%Write
AV177Ef7_HiSpeedExhaust Fan 7 High Speed Setting%Write
AV178Ef8_HiSpeedExhaust Fan 8 High Speed Setting%Write
AV179Ef9_HiSpeedExhaust Fan 9 High Speed Setting%Write
AV180Ef10_HiSpeedExhaust Fan 10 High Speed Setting%Write
AV181Sf1_LoSpeedSupply Fan 1 Low Speed Setting%Write
AV182Sf2_LoSpeedSupply Fan 2 Low Speed Setting%Write
AV183Sf3_LoSpeedSupply Fan 3 Low Speed Setting%Write
AV184Sf4_LoSpeedSupply Fan 4 Low Speed Setting%Write
AV191Sf1_HiSpeedSupply Fan 1 High Speed Setting%Write
AV192Sf2_HiSpeedSupply Fan 2 High Speed Setting%Write
AV193Sf3_HiSpeedSupply Fan 3 High Speed Setting%Write
AV194Sf4_HiSpeedSupply Fan 4 High Speed Setting%Write
AVmin1011Ef1_SpeedExhaust Fan 1 Speed Percentage%Read
AV1012Ef2_SpeedExhaust Fan 2 Speed Percentage%Read
AV1013Ef3_SpeedExhaust Fan 3 Speed Percentage%Read
AV1014Ef4_SpeedExhaust Fan 4 Speed Percentage%Read
AV1015Ef5_SpeedExhaust Fan 5 Speed Percentage%Read
AV1016Ef6_SpeedExhaust Fan 6 Speed Percentage%Read
AV1017Ef7_SpeedExhaust Fan 7 Speed Percentage%Read
AV1018Ef8_SpeedExhaust Fan 8 Speed Percentage%Read
AV1019Ef9_SpeedExhaust Fan 9 Speed Percentage%Read
AV1020Ef10_SpeedExhaust Fan 10 Speed Percentage%Read
AV1031Sf1_SpeedSupply Fan 1 Speed Percentage%Read
AV1032Sf2_SpeedSupply Fan 2 Speed Percentage%Read
AV1033Sf3_SpeedSupply Fan 3 Speed Percentage%Read
AV1034Sf4_SpeedSupply Fan 4 Speed Percentage%Read
BVmin10GLOBAL_ALARMGlobal AlarmRead0=Off, 1=Alarm
BVmin11Sys1_On_OffHood System 1 On/OffWrite0=Off, 1=On
BV12Sys2_On_OffHood System 2 On/OffWrite0=Off, 1=On
BV13Sys3_On_OffHood System 3 On/OffWrite0=Off, 1=On
BV14Sys4_On_OffHood System 4 On/OffWrite0=Off, 1=On
BV15Sys5_On_OffHood System 5 On/OffWrite0=Off, 1=On
BV16Sys6_On_OffHood System 6 On/OffWrite0=Off, 1=On
BV17Sys7_On_OffHood System 7 On/OffWrite0=Off, 1=On
BV18Sys8_On_OffHood System 8 On/OffWrite0=Off, 1=On
BV19Sys9_On_OffHood System 9 On/OffWrite0=Off, 1=On
BV20Sys10_On_OffHood System 10 On/OffWrite0=Off, 1=On
BV91T1_AlmTemp Sensor 1 FailureRead0=Off, 1=Alarm
BV92T2_AlmTemp Sensor 2 FailureRead0=Off, 1=Alarm
BV93T3_AlmTemp Sensor 3 FailureRead0=Off, 1=Alarm
BV94T4_AlmTemp Sensor 4 FailureRead0=Off, 1=Alarm
BV95T5_AlmTemp Sensor 5 FailureRead0=Off, 1=Alarm
BV96T6_AlmTemp Sensor 6 FailureRead0=Off, 1=Alarm
BV97T7_AlmTemp Sensor 7 FailureRead0=Off, 1=Alarm
BV98T8_AlmTemp Sensor 8 FailureRead0=Off, 1=Alarm
BV99T9_AlmTemp Sensor 9 FailureRead0=Off, 1=Alarm
BV100T10_AlmTemp Sensor 10 FailureRead0=Off, 1=Alarm
BVmin101Fire_AlmFire System StatusRead0=Ok, 1=Fire
BVmin102Rem_EnRemote EnableWrite0=Off, 1=On
BV103Wash_EnWash EnableWrite0=Off, 1=On
BV104Fill_detDetergent StatusRead0=Ok, 1=Empty
BV105CWM_statusCold Water Mist StatusRead0=Off, 1=On
BV106PCU_filter_1PCU Filter 1 StatusRead0=Ok, 1=Clogged
BV107PCU_filter_2PCU Filter 2 StatusRead0=Ok, 1=Clogged
BV108PCU_filter_3PCU Filter 3 StatusRead0=Ok, 1=Clogged
BV131Sf1_Af_AlmAirflow Alarm Supply Fan 1Read0=Off, 1=Alarm
BV132Sf2_Af_AlmAirflow Alarm Supply Fan 2Read0=Off, 1=Alarm
BV133Sf3_Af_AlmAirflow Alarm Supply Fan 3Read0=Off, 1=Alarm
BV134Sf4_Af_AlmAirflow Alarm Supply Fan 4Read0=Off, 1=Alarm
BV141Sf1_Pres_AlmSupply Fan 1 Pressure AlarmRead0=Off, 1=Alarm
BV160HiTemp_AlmHigh Temperature AlarmRead0=Off, 1=Alarm
BV161Exh_BO_AlmExhaust Starter/VFD FaultRead0=Off, 1=Alarm
BV162Sup_BO_AlmSupply Starter/VFD FaultRead0=Off, 1=Alarm
BV163Exh_VBF_AlmExhaust VFD By Factory FaultRead0=Off, 1=Alarm
BV164Sup_VBF_AlmSupply VFD By Factory FaultRead0=Off, 1=Alarm
BVmin171Ef1_StatusExhaust Fan 1 StatusRead0=Off, 1=On
BV172Ef2_StatusExhaust Fan 2 StatusRead0=Off, 1=On
BV173Ef3_StatusExhaust Fan 3 StatusRead0=Off, 1=On
BV174Ef4_StatusExhaust Fan 4 StatusRead0=Off, 1=On
BV175Ef5_StatusExhaust Fan 5 StatusRead0=Off, 1=On
BV176Ef6_StatusExhaust Fan 6 StatusRead0=Off, 1=On
BV177Ef7_StatusExhaust Fan 7 StatusRead0=Off, 1=On
BV178Ef8_StatusExhaust Fan 8 StatusRead0=Off, 1=On
BV179Ef9_StatusExhaust Fan 9 StatusRead0=Off, 1=On
BV180Ef10_StatusExhaust Fan 10 StatusRead0=Off, 1=On
BVmin181Sf1_StatusSupply Fan 1 StatusRead0=Off, 1=On
BV182Sf2_StatusSupply Fan 2 StatusRead0=Off, 1=On
BV183Sf3_StatusSupply Fan 3 StatusRead0=Off, 1=On
BV184Sf4_StatusSupply Fan 4 StatusRead0=Off, 1=On
Object ID lookup: Accurex Vari-Flow Air Management System v2.00 point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Vari-Flow Air Management System v2.00 and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Accurex Vari-Flow Air Management System v2.00

How many BACnet points does the Accurex Vari-Flow Air Management System v2.00 have?

This list has 167 BACnet objects: 114 analog values, 53 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Accurex Vari-Flow Air Management System v2.00 BACnet points are writable?

60 of the 167 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Accurex Vari-Flow Air Management System v2.00 BACnet documentation?

The source is Vari-Flow Air Management System - Installation, Operation and Maintenance Manual, BMS Points List (v2.00) (481515 Rev. 3), revision 2019-08, published free by Accurex at https://content.accurex.com/accurex-cms-prod/docs/default-source/ioms/vari-flow_management_system_iom.pdf?sfvrsn=ff6579ed_6.

What are the minimum BACnet points to integrate the Accurex Vari-Flow Air Management System v2.00?

Start with BV 102 Rem_En (Remote enable of the system (1 = on)); BV 11 Sys1_On_Off (Hood system 1 on/off (1 = on)); AV 11 H1_Ctemp (Hood 1 control temperature); AV 1011 Ef1_Speed (Exhaust fan 1 speed, %); BV 171 Ef1_Status (Exhaust fan 1 running); BV 181 Sf1_Status (Supply fan 1 running); BV 101 Fire_Alm (Fire system active); BV 10 GLOBAL_ALARM (Any active alarm).

How do I enable BMS control of the Accurex Vari-Flow Air Management System v2.00?

BV 102 Remote Enable (1 = on) and the per-system On/Off BVs (BV 11-20) let the BMS run the hood systems.

How do I check these points on the real Vari-Flow Air Management System v2.00?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Accurex BACnet points lists

Source: Vari-Flow Air Management System - Installation, Operation and Maintenance Manual, BMS Points List (v2.00) · 481515 Rev. 3 · rev. 2019-08. Object names, instances and units are reproduced as published; descriptions are our own.