Kitchen exhaust pollution control unit (electrostatic precipitator) · BACnet points list
Accurex Grease Trapper ESP Kitchen Exhaust Pollution Control System v1.00 BACnet points list
Updated 7 November 2026
The Grease Trapper ESP is an electrostatic pollution control unit for kitchen exhaust. Its controller offers a short BACnet MS/TP or BACnet IP list: exhaust fan speed, remote enable, fire status, wash enable and status, detergent level, door interlocks, fan fault and the power supply status of each pass.
This page lists 12 BACnet objects for the Accurex Grease Trapper ESP Kitchen Exhaust Pollution Control System v1.00 — 2 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Accurex’s own free documentation, linked below.
- Manufacturer
- Accurex
- Model
- Grease Trapper ESP Kitchen Exhaust Pollution Control System v1.00
- Equipment
- Kitchen exhaust pollution control unit (electrostatic precipitator)
- Equipment type
- Other equipment
- BACnet objects
- 12 (2 writable)
- Transport
- BACnet MS/TP, BACnet IP
- Firmware
- Grease Trapper ESP v1.00
- Default device instance
- 77000
- Also known as
- Grease Trapper ESP, GT-ESP, 482584
Reference only, provided as-is: verify against Accurex’s current documentation and the live device before use. Not official Accurex information. Terms of use.
BMS integration notes: Accurex Grease Trapper ESP Kitchen Exhaust Pollution Control System v1.00
Enable the unit with BV 101 Remote_Enable and start a wash with BV 103. Read BV 130 exhaust fan status, AV 20 fan speed and the pass power supply status, and alarm on BV 105 fan fault, BV 102 fire status and BV 104 low detergent.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 101 | Remote_Enable | Remote fan enable (1 = on) | Write |
| BV 103 | Wash_Enable | Wash enable (1 = on) | Write |
| BV 130 | Exhaust_Active | Exhaust fan running | Read |
| AV 20 | Exhaust_Fan_Speed | Exhaust fan speed, % | Read |
| BV 134 | Wash_Sequence_Active | Wash cycle active | Read |
| BV 102 | Fire_Status | Fire system active | Read |
| BV 105 | Exhaust_Fan_Fault | Exhaust fan fault | Read |
| BV 104 | Detergent_Low | Detergent empty | Read |
Enable & remote start
BV 101 Remote_Enable starts the exhaust fan from the BMS; BV 103 enables the wash.
Network setup
- BACnet MS/TP or BACnet IP needs the matching communication card in the controller serial card port, with BACnet Plugin set to YES.
- Default device instance is 77000; MS/TP MAC, baud and IP settings are adjusted from the controller display (BACnet IP cards ship in DHCP mode).
Watch out for
- Network settings changed on the display only take effect after a Write on the BACnet Read/Write screen and a power cycle.
Accurex Grease Trapper ESP Kitchen Exhaust Pollution Control System v1.00 BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AVmin | 20 | Exhaust_Fan_Speed | Exhaust Fan Speed Percentage | % | Read | |
| BVmin | 101 | Remote_Enable | Remote Fan Enable | Write | 0=Off, 1=On | |
| BVmin | 102 | Fire_Status | Fire System Status | Read | 0=Ok, 1=Fire | |
| BVmin | 103 | Wash_Enable | Wash Enable | Write | 0=Off, 1=On | |
| BVmin | 104 | Detergent_Low | Detergent Status | Read | 0=Ok, 1=Empty | |
| BVmin | 105 | Exhaust_Fan_Fault | Exhaust Fan Fault | Read | 0=Off, 1=On | |
| BV | 106 | Door_Switches | Door Interlock Switches | Read | 1=Ok, 0=Door Open | |
| BVmin | 130 | Exhaust_Active | Exhaust Fan Status | Read | 0=Off, 1=On | |
| BV | 131 | Pass1_Power_Supply | Power Supply Pass 1 Status | Read | 0=Off, 1=On | |
| BV | 132 | Pass2_Power_Supply | Power Supply Pass 2 Status | Read | 0=Off, 1=On | |
| BV | 133 | Pass3_Power_Supply | Power Supply Pass 3 Status | Read | 0=Off, 1=On | |
| BVmin | 134 | Wash_Sequence_Active | Wash Status | Read | 0=Off, 1=Wash Cycle Active |
No points match these filters.
Object ID lookup: Accurex Grease Trapper ESP Kitchen Exhaust Pollution Control System v1.00 point IDs by name
Integration notes
- The points list states the mapping: Analog and Integer variables are Analog Value objects, Digital variables are Binary Value objects.
- BV 106 Door Switches reads 1 when the doors are closed (OK) and 0 when a door is open.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Grease Trapper ESP Kitchen Exhaust Pollution Control System v1.00 and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Accurex Grease Trapper ESP Kitchen Exhaust Pollution Control System v1.00
How many BACnet points does the Accurex Grease Trapper ESP Kitchen Exhaust Pollution Control System v1.00 have?
This list has 12 BACnet objects: 1 analog value, 11 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Accurex Grease Trapper ESP Kitchen Exhaust Pollution Control System v1.00 BACnet points are writable?
2 of the 12 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Accurex Grease Trapper ESP Kitchen Exhaust Pollution Control System v1.00 BACnet documentation?
The source is Grease Trapper ESP Kitchen Exhaust Pollution Control System - Installation, Operation and Maintenance Manual, BMS Points List (v1.00) (482584 Rev. 2), revision 2018-08, published free by Accurex at https://content.accurex.com/accurex-cms-prod/docs/default-source/ioms/482584-grease-trapper-esp-rev-2-august-2018_acx.pdf?sfvrsn=7d55c6a7_8.
What are the minimum BACnet points to integrate the Accurex Grease Trapper ESP Kitchen Exhaust Pollution Control System v1.00?
Start with BV 101 Remote_Enable (Remote fan enable (1 = on)); BV 103 Wash_Enable (Wash enable (1 = on)); BV 130 Exhaust_Active (Exhaust fan running); AV 20 Exhaust_Fan_Speed (Exhaust fan speed, %); BV 134 Wash_Sequence_Active (Wash cycle active); BV 102 Fire_Status (Fire system active); BV 105 Exhaust_Fan_Fault (Exhaust fan fault); BV 104 Detergent_Low (Detergent empty).
How do I enable BMS control of the Accurex Grease Trapper ESP Kitchen Exhaust Pollution Control System v1.00?
BV 101 Remote_Enable starts the exhaust fan from the BMS; BV 103 enables the wash.
How do I check these points on the real Grease Trapper ESP Kitchen Exhaust Pollution Control System v1.00?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Accurex BACnet points lists
- DOAS unit controller (dedicated outdoor air system)
Accurex DOAS microprocessor controller (DOAS_08.000)
Accurex dedicated outdoor air systems with the factory microprocessor controller (program DOAS_08.000) and the BACnet license enabled.
Also known as: Accurex DOAS, Accurex dedicated outdoor air system, DOAS_08.000, 485940, Accurex c.pCO DOAS - Make-up air unit controller
Accurex Make-Up Air (MUA) controller (MUA_01.001)
Accurex make-up air units with the factory microprocessor controller (program MUA_01.001 and later) and the BACnet license enabled.
Also known as: Accurex MUA, Accurex make-up air, MUA_01.001, 485941, Accurex makeup air unit - Kitchen hood demand-controlled ventilation controls
Accurex Vari-Flow Air Management System v2.00
Accurex Vari-Flow demand-controlled kitchen ventilation systems (hood temperature/optic sensing, exhaust and supply fan VFDs) with a Carel-based controller.
Also known as: Vari-Flow, Vari-Flow 2.00, Accurex demand-controlled kitchen ventilation, Auto Scrubber Control Panel, ASCP v2.00 - Kitchen hood demand-controlled ventilation controls
Accurex Vari-Flow Air Management System v3.00
Accurex Vari-Flow demand-controlled kitchen ventilation systems (hood temperature/optic sensing, exhaust and supply fan VFDs) with a Carel-based controller.
Also known as: Vari-Flow, Vari-Flow 3.00, Accurex demand-controlled kitchen ventilation
Source: Grease Trapper ESP Kitchen Exhaust Pollution Control System - Installation, Operation and Maintenance Manual, BMS Points List (v1.00) · 482584 Rev. 2 · rev. 2018-08. Object names, instances and units are reproduced as published; descriptions are our own.