Easy BACnet
  1. Home
  2. BACnet points lists
  3. Accurex
  4. Make-Up Air (MUA) controller (MUA_01.001)

Make-up air unit controller · BACnet points list

Accurex Make-Up Air (MUA) controller (MUA_01.001) BACnet points list

Updated 4 November 2026

Short answer

Accurex make-up air units use the same controller family and layout as the Accurex DOAS, with BACnet once the BACnet license is installed (the guide covers BACnet IP settings such as BBMD). The fixed points list covers enable, occupancy, reset modes and setpoints, BMS-written sensors and fan/damper overrides behind a watchdog, plus bit-packed status and alarm words.

This page lists 58 BACnet objects for the Accurex Make-Up Air (MUA) controller (MUA_01.001) — 28 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Accurex’s own free documentation, linked below.

Manufacturer
Accurex
Model
Make-Up Air (MUA) controller (MUA_01.001)
Equipment
Make-up air unit controller
Equipment type
Rooftop units, AHUs & DOAS
BACnet objects
58 (28 writable)
Transport
BACnet IP
Firmware
MUA_01.001 and later
Also known as
Accurex MUA, Accurex make-up air, MUA_01.001, 485941, Accurex makeup air unit
Source document
BACnet Integration Guide for Makeup Air Systems · 485941 (MUA_01.001) · rev. 10/2022
Download CSV 58 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Accurex’s current documentation and the live device before use. Not official Accurex information. Terms of use.

BMS integration notes: Accurex Make-Up Air (MUA) controller (MUA_01.001)

Integration in brief

With the BACnet license installed, set the BACnet network settings at the controller. Write BV 2 to enable the unit and BV 3 for occupancy, and adjust setpoints such as AV 1. To command the supply fan, damper or sensor values, set the matching BMS-source BV and write BV 1 watchdog repeatedly.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 2System_EnableUnit enable (1 = enabled)Write
BV 3BMS_Occupancy_CommandOccupancy: 0 = occupied, 1 = unoccupiedWrite
AV 1Temperature_SetpointOccupied temperature setpoint, °FWrite
BV 1BMS_WatchdogWatchdog; write 1 regularly when BMS commandsWrite
BV 4Reset_All_AlarmsResets alarmsWrite
AV 41Unit_Status_ModeUnit mode number (status mode table)Read
AI 2Supply_Temp_Analog_InputSupply air temperature, °FRead
BI 2Supply_Fan_1_Status_Digital_InputSupply fan runningRead
BV 19Global_AlarmAny active alarmRead
IV 9LatestAlmLatest alarm code; 0 = noneRead

Enable & remote start

BV 2 System_Enable enables or disables the unit, and BV 3 BMS_Occupancy_Command sets occupancy (default occupancy mode expects the BMS command; schedule, digital input or fixed modes can be chosen at the controller).

Heartbeat & communication loss

BV 1 BMS_Watchdog must be written True regularly whenever the BMS commands the fan, damper or sensor values. If it stays False longer than the timeout (default 15 min, adjustable), an alarm is raised (alarm 19) and the controller goes back to local control and sensors. With Enable Relinquish Default on, commandable points are cleared 5 minutes after the watchdog drops.

Sensors & values from the BMS

Set the source BV to BMS (BV 6, 9, 10, 12, 13) and write the value to AV 30 outside temperature, AV 33 space CO2, AV 34 return CO2, AV 36 space static or AV 37 space temperature. Keep the watchdog alive or the controller falls back to its local sensor.

Network setup

Watch out for

Accurex Make-Up Air (MUA) controller (MUA_01.001) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

58 of 58 shown
Type
Other
Access
Show
Accurex Make-Up Air (MUA) controller (MUA_01.001) BACnet Points List
DescriptionStates
BVmin1BMS_WatchdogBMS watchdog; write 1 regularlyWriteActive/Inactive
BVmin2System_EnableMaster system enable/disableWriteEnabled/Disabled
BVmin3BMS_Occupancy_CommandBuilding occupancy commandWriteUnoccupied/Occupied
BVmin4Reset_All_AlarmsAlarm reset commandWriteReset/Normal
BV6Outside_Temp_Source_BMSUse outside temp from BMS (AV 30)WriteBMS/Local
BV9Space_1_CO2_Source_BMSUse space 1 CO2 from BMS (AV 33)WriteBMS/Local
BV10Return_CO2_Source_BMSUse return CO2 from BMS (AV 34)WriteBMS/Local
BV12Space_Static_Source_BMSUse space static from BMS (AV 36)WriteBMS/Local
BV13Space_Temp_Source_BMSUse space temp from BMS (AV 37)WriteBMS/Local
BV14SF_Control_Source_BMSBMS controls supply fan speed (AV 38)WriteBMS/Local
BV15OAD_Control_Source_BMSBMS controls outside air damper (AV 39)WriteBMS/Local
BVmin19Global_AlarmAny alarm activeReadAlarm/Normal
BV20BMS_Watchdog_ActiveWatchdog statusReadActive/Inactive
BI1Exhaust_Fan_1_Status_Digital_InputExhaust fan 1 statusReadActive/Inactive
BImin2Supply_Fan_1_Status_Digital_InputSupply fan 1 statusReadActive/Inactive
IV1Temperature_Reset_ModeOccupied supply temperature reset modeWrite1=No Reset, 2=Space Reset, 3=Return Reset, 4=Outside Reset
IV2Temperature_Reset_Mode_UnoccupiedUnoccupied reset modeWrite1=No Reset, 2=Space Reset, 3=Return Reset, 4=Outside Reset
IVmin9LatestAlmMost recent active alarm code (alarm table), 0 = noneRead
IV10Digital_Output_WordBit-packed digital output enablesReadBit 0=Supply Fan Start, 1=Exhaust Fan Start, 2=Exhaust Relief Enable, 3=Compressor 1 Start, 4=Compressor 2 Start, 5=Condenser Fan Start, 7=Furnace 1 Start, 8=Furnace 1 Stage 2 Start, 9=Furnace 2 Start, 10=Furnace 2 Stage 2 Start, 11=Furnace 3 Start, 13=Damper Actuator Power Enable, 14=Direct Gas Start, 15=Electric Heat Start, 16=Evaporative Cooling Valve Enable, 17=Evaporative Cooling Pump Enable
IV11Cooling_Alarm_WordBit-packed cooling alarmsReadBit 0=Circuit A High Low Pressure Switch Alarm, 1=Circuit B High Low Pressure Switch Alarm
IV12Device_Offline_WordBit-packed device communication alarmsReadBit 0=Space TStat 1 Offline, 1=Space TStat 2 Offline, 2=Space TStat 3 Offline, 3=Space TStat 4 Offline, 4=IG Furnace Controller 1 Offline, 5=IG Furnace Controller 2 Offline, 6=Cooling Controller Offline, 7=GreenTrol Outside Air Offline, 8=BMS Offline Alarm, 9=Permanent Memory - Too Many Writes
IV13Device_Alarm_WordBit-packed device alarmsReadBit 0=Supply Fan Alarm, 1=Exhaust Fan Alarm, 2=Drain Pan Alarm, 3=Filter Alarm, 4=GreenTrol OAD AFMS Alarm, 5=Outside Air Temp Sensor Alarm, 6=Space CO2 Sensor Alarm, 7=Supply Air Temp Sensor Alarm, 8=Space Temperature Sensor Alarm, 9=Supply Temp Low Limit Alarm, 10=Supply Temp High Limit Alarm, 11=Supply High Duct Static Alarm, 12=Supply Duct Static Sensor Alarm, 13=Space Static Pressure Sensor Alarm, 14=Space High Static Alarm, 15=Return CO2 Sensor Alarm, 17=Shutdown Input Alarm
IV14Heating_Alarm_WordBit-packed heating alarmsReadBit 0=DG Flame Safeguard General Reference, 1=DG Flame Safeguard Manual Reset at FSG, 2=DG Pilot Flame Alarm Did Not Prove, 3=DG Heating Safety Check Circuit, 4=DG Flame Safeguard Check Functionality, 5=DG Burner Differential Check Pressure, 6=General IG Furnace Alarm, 7=IG Furnace 1 No flame Alarm After 3 Tries, 8=IG Furnace 1 Large No Flame After 3 Tries, 9=IG Furnace 1 Combust Fan High Pressure Sw, 10=IG Furnace 1 Ignition Controller Alarm, 11=IG Furnace 1 Pressure Switch Fault Alarm, 12=IG Furnace 1 Combust Fan Proving Alarm, 13=IG Furnace 1 Max Retries, 14=IG Furnace 1 High Limit Trip, 15=IG Furnace 1 IC fault Check Furnace Wiring, 16=IG Furnace 1 Combustion Fan Alarm, 17=IG Furnace 2-No Flame Alarm After 3 Tries, 18=IG Furnace 2 Max Retries, 19=IG Furnace 2 Ignition Controller Alarm, 20=IG Furnace 3-No Flame Alarm After 3 Tries, 21=IG Furnace 3 Max Retries, 22=IG Furnace 3 Ignition Controller Alarm
IV15Unit_Status_WordBit-packed unit status wordReadBit 0=Off/Standby, 1=Unoccupied Start, 2=Occupied Start, 3=Opening Dampers, 4=Dampers Open, 5=Fan Start Delay, 6=Exhaust Fan On, 7=Supply Fan On, 8=System On, 9=Soft Shutdown, 10=System Disabled, 11=Remote Off, 12=System Shutdown Alarm, 13=Supply Fan Only, 14=Exhaust Fan Only, 15=Purge Mode (Supply and Exhaust Only), 16=Case Heat Active, 17=Fans Only, 18=Economizing, 19=Energy Recovery Active, 20=Cooling, 21=Heating, 22=Dehumidifying, 23=Hot Gas Reheat Active, 24=HGRH Purging, 25=Dehum w/Heat, 26=Energy Recovery Defrost Active, 27=Heat Pump Defrost Active, 28=Morning Warm Up/Cool Down Active, 29=Winter Ramp Active, 31=Overrides Active
AVmin1Temperature_SetpointOccupied setpoint (space, return or supply per reset mode), default 72°FWrite
AV2Temperature_Heat_Cool_DeadbandOccupied heat/cool deadband, default 4°FWrite
AV3Temperature_Setpoint_UnoccupiedUnoccupied setpoint, default 72.5°FWrite
AV4Temperature_Heat_Cool_Deadband_UnoccupiedUnoccupied deadband, default 15°FWrite
AV16Space_Static_Pressure_SetpointSpace static setpoint, default 0.05inH2OWrite
AV17Supply_Duct_Static_Pressure_SetpointSupply duct static setpoint, default 1.0inH2OWrite
AV18Space_CO2_SetpointSpace CO2 setpoint, default 1000ppmWrite
AV19Outside_Air_Damper_Minimum_Setpoint_OccOccupied minimum OA damper, default 35%Write
AV30Outside_Temp_from_BMSOutside temperature from BMS°FWrite
AV33Space_1_CO2_from_BMSSpace 1 CO2 from BMSppmWrite
AV34Return_CO2_from_BMSReturn CO2 from BMSppmWrite
AV36Space_Static_from_BMSSpace static pressure from BMSinH2OWrite
AV37Space_Temp_from_BMSSpace temperature from BMS°FWrite
AV38SF_Control_Signal_BMSSupply fan speed command (with BV 14)%Write
AV39OAD_Control_Signal_BMSOutside air damper command (with BV 15)%Write
AVmin41Unit_Status_ModeUnit operating mode/state (status mode table)Read
AV42Supply_Temperature_Calculated_SetpointActive supply temperature setpoint°FRead
AV43Cooling_1_Ramp_CapacityCooling ramp 1%Read
AV46Heating_CapacityHeating ramp%Read
AV56OAD_CFM_BMSOutside air damper airflowcfmRead
AV58Chilled_Water_1_Valve_Analog_OutputChilled water valve output%Read
AV59Electric_Heater_1_Analog_OutputElectric heater output%Read
AV60Hot_Water_Valve_1_Analog_OutputHot water valve output%Read
AV61Mod_Gas_Furnace_1_Analog_OutputModulating gas furnace output%Read
AV62Outside_Airflow_MaskOutside airflow percentage%Read
AV63Supply_Fan_Speed_Analog_OutputSupply fan speed output%Read
AV64Modulating_Compressor_Analog_Output_BMSModulating compressor output%Read
AI1Space_Temp_Analog_InputSpace air temperature°FRead
AImin2Supply_Temp_Analog_InputSupply (discharge) air temperature°FRead
AI3Outside_Air_Temp_Analog_InputOutside air temperature°FRead
AI9Space_Static_Pressure_Analog_InputSpace static pressureinH2ORead
AI10Supply_Duct_Static_Pressure_Analog_InputSupply duct static pressureinH2ORead
AI11Space_CO2_1_Analog_InputSpace 1 CO2ppmRead
AI12Return_CO2_Analog_InputReturn CO2ppmRead
Object ID lookup: Accurex Make-Up Air controller point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Make-Up Air (MUA) controller (MUA_01.001) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Accurex Make-Up Air (MUA) controller (MUA_01.001)

How many BACnet points does the Accurex Make-Up Air (MUA) controller (MUA_01.001) have?

This list has 58 BACnet objects: 7 analog inputs, 27 analog values, 2 binary inputs, 13 binary values, 9 integer values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Accurex Make-Up Air (MUA) controller (MUA_01.001) BACnet points are writable?

28 of the 58 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Accurex Make-Up Air (MUA) controller (MUA_01.001) BACnet documentation?

The source is BACnet Integration Guide for Makeup Air Systems (485941 (MUA_01.001)), revision 10/2022, published free by Accurex at https://content.accurex.com/accurex-cms-prod/docs/default-source/brochures/485941-bacnet-integration-guide-mua_01.001.pdf.

What are the minimum BACnet points to integrate the Accurex Make-Up Air (MUA) controller (MUA_01.001)?

Start with BV 2 System_Enable (Unit enable (1 = enabled)); BV 3 BMS_Occupancy_Command (Occupancy: 0 = occupied, 1 = unoccupied); AV 1 Temperature_Setpoint (Occupied temperature setpoint, °F); BV 1 BMS_Watchdog (Watchdog; write 1 regularly when BMS commands); BV 4 Reset_All_Alarms (Resets alarms); AV 41 Unit_Status_Mode (Unit mode number (status mode table)); AI 2 Supply_Temp_Analog_Input (Supply air temperature, °F); BI 2 Supply_Fan_1_Status_Digital_Input (Supply fan running); BV 19 Global_Alarm (Any active alarm); IV 9 LatestAlm (Latest alarm code; 0 = none).

How do I enable BMS control of the Accurex Make-Up Air (MUA) controller (MUA_01.001)?

BV 2 System_Enable enables or disables the unit, and BV 3 BMS_Occupancy_Command sets occupancy (default occupancy mode expects the BMS command; schedule, digital input or fixed modes can be chosen at the controller).

Does the Accurex Make-Up Air (MUA) controller (MUA_01.001) need a BACnet heartbeat or have a communication timeout?

BV 1 BMS_Watchdog must be written True regularly whenever the BMS commands the fan, damper or sensor values. If it stays False longer than the timeout (default 15 min, adjustable), an alarm is raised (alarm 19) and the controller goes back to local control and sensors. With Enable Relinquish Default on, commandable points are cleared 5 minutes after the watchdog drops.

Can the BMS supply sensor values to the Accurex Make-Up Air (MUA) controller (MUA_01.001)?

Set the source BV to BMS (BV 6, 9, 10, 12, 13) and write the value to AV 30 outside temperature, AV 33 space CO2, AV 34 return CO2, AV 36 space static or AV 37 space temperature. Keep the watchdog alive or the controller falls back to its local sensor.

How do I check these points on the real Make-Up Air (MUA) controller (MUA_01.001)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Accurex BACnet points lists

Source: BACnet Integration Guide for Makeup Air Systems · 485941 (MUA_01.001) · rev. 10/2022. Object names, instances and units are reproduced as published; descriptions are our own.