DOAS unit controller (dedicated outdoor air system) · BACnet points list

Accurex DOAS microprocessor controller (DOAS_08.000) BACnet points list

Updated 4 November 2026

Short answer

Accurex DOAS units use a c.pCO-family controller that offers BACnet IP or BACnet MS/TP once the BACnet license is installed. The points list is fixed for every configuration, so some points do not apply to a given unit. The BMS enables the unit, commands occupancy and setpoints, and can take over fans, damper and sensor inputs while it keeps writing a watchdog.

This page lists 93 BACnet objects for the Accurex DOAS microprocessor controller (DOAS_08.000) — 48 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Accurex’s own free documentation, linked below.

Manufacturer
Accurex
Model
DOAS microprocessor controller (DOAS_08.000)
Equipment
DOAS unit controller (dedicated outdoor air system)
Equipment type
Rooftop units, AHUs & DOAS
BACnet objects
93 (48 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
DOAS_08.000 Rev 2
Also known as
Accurex DOAS, Accurex dedicated outdoor air system, DOAS_08.000, 485940, Accurex c.pCO DOAS
Source document
BACnet Integration Guide for Dedicated Outdoor Air Systems · 485940 (DOAS_08.000 Rev 2) · rev. 01/2023
Download CSV 93 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Accurex’s current documentation and the live device before use. Not official Accurex information. Terms of use.

BMS integration notes: Accurex DOAS microprocessor controller (DOAS_08.000)

Integration in brief

With the BACnet license installed, set the BACnet IP or MS/TP settings in the controller's Network Settings menu. Write BV 2 to enable the unit and BV 3 for occupancy; setpoints such as AV 1 can be adjusted. To command fans, damper or sensor values, set the matching BMS-source BV and write BV 1 watchdog repeatedly.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 2System_EnableUnit enable (1 = enabled)Write
BV 3BMS_Occupancy_CommandOccupancy: 0 = occupied, 1 = unoccupiedWrite
AV 1Temperature_SetpointOccupied temperature setpoint, °FWrite
BV 1BMS_WatchdogWatchdog; write 1 regularly when BMS commandsWrite
BV 4Reset_All_AlarmsResets alarmsWrite
AV 40Unit_Status_ModeUnit mode number (status mode table)Read
AI 2Supply_Temp_Analog_InputSupply air temperature, °FRead
BI 2Supply_Fan_1_Status_Digital_InputSupply fan runningRead
BV 23Global_AlarmAny active alarmRead
IV 5LatestAlmLatest alarm code; 0 = noneRead

Enable & remote start

BV 2 System_Enable enables or disables the unit, and BV 3 BMS_Occupancy_Command sets occupancy (the default occupancy mode expects the BMS command; a schedule, digital input or fixed mode can be chosen at the controller instead).

Heartbeat & communication loss

BV 1 BMS_Watchdog must be written True regularly whenever the BMS commands fans, damper or sensor values. If it stays False longer than the timeout (default 15 min, adjustable), alarm 79 is raised and the controller goes back to local control and sensors. With Enable Relinquish Default on, commandable points are cleared to relinquish defaults 5 minutes after the watchdog drops.

Sensors & values from the BMS

Set the source BV to BMS (BV 7-16) and write the value to the matching AV 26-35 (outside/return RH and temperature, space/return CO2, space RH, static and temperature). The watchdog must be kept alive or the controller falls back to the local sensor.

Network setup

Watch out for

Accurex DOAS microprocessor controller (DOAS_08.000) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

93 of 93 shown
Type
Other
Access
Show
Accurex DOAS microprocessor controller (DOAS_08.000) BACnet Points List
DescriptionStates
BVmin1BMS_WatchdogBMS watchdog; write 1 regularlyWriteActive/Inactive
BVmin2System_EnableMaster system enable/disableWriteEnabled/Disabled
BVmin3BMS_Occupancy_CommandBuilding occupancy commandWriteUnoccupied/Occupied
BVmin4Reset_All_AlarmsAlarm reset commandWriteReset/Normal
BV7Outside_RH_Source_BMSUse outside RH from BMS (AV 26)WriteBMS/Local
BV8Outside_Temp_Source_BMSUse outside temp from BMS (AV 27)WriteBMS/Local
BV9Return_RH_Source_BMSUse return RH from BMS (AV 28)WriteBMS/Local
BV10Return_Temp_Source_BMSUse return temp from BMS (AV 29)WriteBMS/Local
BV11Space_1_CO2_Source_BMSUse space 1 CO2 from BMS (AV 30)WriteBMS/Local
BV12Space_2_CO2_Source_BMSUse space 2 CO2 from BMS (AV 31)WriteBMS/Local
BV13Return_CO2_Source_BMSUse return CO2 from BMS (AV 32)WriteBMS/Local
BV14Space_RH_Source_BMSUse space RH from BMS (AV 33)WriteBMS/Local
BV15Space_Static_Source_BMSUse space static from BMS (AV 34)WriteBMS/Local
BV16Space_Temp_Source_BMSUse space temp from BMS (AV 35)WriteBMS/Local
BV17SF_Control_Source_BMSBMS controls supply fan speed (AV 36)WriteBMS/Local
BV18EF_Control_Source_BMSBMS controls exhaust fan speed (AV 37)WriteBMS/Local
BV19OAD_Control_Source_BMSBMS controls outside air damper (AV 38)WriteBMS/Local
BVmin23Global_AlarmAny alarm activeReadAlarm/Normal
BV24BMS_Watchdog_ActiveWatchdog statusReadActive/Inactive
BI1Exhaust_Fan_1_Status_Digital_InputExhaust fan 1 statusReadActive/Inactive
BImin2Supply_Fan_1_Status_Digital_InputSupply fan 1 statusReadActive/Inactive
IV1Temperature_Reset_ModeOccupied supply temperature reset modeWrite1=No Reset, 2=Space Reset, 3=Return Reset, 4=Outside Reset
IV2Temperature_Reset_Mode_UnoccupiedUnoccupied reset modeWrite1=No Reset, 2=Space Reset, 3=Return Reset, 4=Outside Reset
IVmin5LatestAlmMost recent active alarm code (alarm table), 0 = noneRead
IV6Device_Enable_DO_WordBit-packed outputs wordReadBit 0=Compressor 1 Start, 1=Compressor 2 Start, 2=Compressor 3 Start, 3=Compressor 4 Start, 8=Condenser Fan Ramp 1 Stage 1 Start, 9=Condenser Fan Ramp 1 Stage 2 Start, 10=Condenser Fan Ramp 1 Stage 3 Start, 12=Condenser Fan Ramp 2 Stage 1 Start, 13=Condenser Fan Ramp 2 Stage 2 Start, 14=Condenser Fan Ramp 2 Stage 3 Start, 16=Furnace 1 Start, 17=Furnace 2 Start, 20=Supply Fan Start, 21=Exhaust Fan Start
IV7Ref_Ckt_PressTemp_Alarm_WordBit-packed refrigeration circuit alarm wordReadBit 0=Circuit A Discharge Pressure Sensor Alarm, 1=Circuit A Discharge Temp Sensor Alarm, 2=Circuit A Suction Pressure Sensor Alarm, 3=Circuit A Suction Temp Sensor Alarm, 4=Circuit B Discharge Pressure Sensor Alarm, 5=Circuit B Discharge Temp Sensor Alarm, 6=Circuit B Suction Pressure Sensor Alarm, 7=Circuit B Suction Temp Sensor Alarm, 8=Circuit A High-Pressure Switch Alarm, 9=Circuit A Low-Pressure Switch Alarm, 10=Circuit B High-Pressure Switch Alarm, 11=Circuit B Low-Pressure Switch Alarm, 12=Circuit A High Sat Discharge Temp Alarm, 13=Circuit B High Sat Discharge Temp Alarm
IV8Device_Offline_WordBit-packed device offline wordReadBit 0=Space T-Stat 1 Offline, 1=Space T-Stat 2 Offline, 2=Space T-Stat 3 Offline, 3=Space T-Stat 4 Offline, 4=VFD Offline Supply Fan, 8=Expansion Board 1 Alarm, 9=Expansion Board 2 Alarm, 10=Expansion Board 3 Alarm, 11=Expansion Board 4 Alarm, 27=Master Unit Offline Alarm, 28=Slave Unit 1 Offline Alarm, 29=Slave Unit 2 Offline Alarm, 30=Slave Unit 3 Offline Alarm, 31=Slave Unit 4 Offline Alarm
IV9Device_Alarm_WordBit-packed sensor/device alarm wordReadBit 0=Cold Coil Temperature Sensor Alarm, 2=Mixed Temperature Sensor Alarm, 3=Supply Duct Static Pressure Sensor Alarm, 4=Supply Fan AFMS Alarm, 5=Supply Air Temp Sensor Alarm, 6=Exhaust Fan AFMS Alarm, 7=Exhaust Temperature Sensor Alarm, 8=Outside Air Temp Sensor Alarm, 9=Outside RH Sensor Alarm, 10=OAD AMD Alarm, 11=GreenTrol OAD AFMS Alarm, 12=Return CO2 Sensor Alarm, 13=Return Duct Static Pressure Sensor Alarm, 14=Return Temperature Sensor Alarm, 15=Return RH Sensor Alarm, 16=Space CO2 Sensor Alarm, 17=Space RH Sensor Alarm, 18=Space Static Pressure Sensor Alarm, 19=Space Temperature Sensor Alarm, 20=IG Furnace Alarm, 22=Inverter Scroll 1 Alarm, 24=EVD Valve A Alarm, 26=SF VFD Alarm
IV10System_WordBit-packed system status/alarm wordReadBit 0=Heat Wheel Enable, 1=Preheat Enable, 2=Reversing Valve (Cooling (0)/Heating(1)), 6=Supply Temp Low Limit Alarm, 7=Supply Temp High Limit Alarm, 8=Supply High Duct Static Alarm, 9=Supply Fan 1 Alarm, 10=Exhaust Fan 1 Alarm, 11=Drain Pan Alarm, 12=Freeze Stat Alarm, 13=Filter Alarm, 14=Space High Static Alarm, 15=Return Low Static Alarm, 16=Shutdown Input Alarm, 17=Energy Recovery Wheel High Diff Pressure, 18=Energy Recovery Wheel Rotation Alarm, 20=Heat Pump Heating Lock Out Alarm, 21=Permanent Memory - Too Many Writes, 22=BMS Offline Alarm, 28=Heat-Cool Only - Dehumidification Request Active, 29=Heat-Cool Only - Heating Request Active, 30=Heat-Cool Only - Coil Setpoint Alarm Active, 31=Heat-Cool Only - Supply Setpoint Alarm Active
IV11Unit_Status_WordBit-packed unit status wordReadBit 0=Off/Standby, 1=Unoccupied Start, 2=Occupied Start, 3=Opening Dampers, 4=Dampers Open, 5=Fan Start Delay, 6=Exhaust Fan On, 7=Supply Fan On, 8=System On, 9=Soft Shutdown, 10=System Disabled, 11=Remote Off, 12=System Shutdown Alarm, 13=Supply Fan Only, 14=Exhaust Fan Only, 15=Purge Mode (Supply and Exhaust Only), 16=Case Heat Active, 17=Fans Only, 18=Economizing, 19=Energy Recovery Active, 20=Cooling, 21=Heating, 22=Dehumidifying, 23=Hot Gas Reheat Active, 24=HGRH Purging, 25=Dehum w/Heat, 26=Energy Recovery Defrost Active, 27=Heat Pump Defrost Active, 28=Morning Warm Up/Cool Down Active, 29=Winter Ramp Active, 31=Overrides Active
AVmin1Temperature_SetpointOccupied setpoint (space, return or supply per reset mode), default 72°FWrite
AV2Temperature_Heat_Cool_DeadbandOccupied heat/cool deadband, default 4°FWrite
AV3Temperature_Setpoint_UnoccupiedUnoccupied setpoint, default 70°FWrite
AV4Temperature_Heat_Cool_Deadband_UnoccupiedUnoccupied deadband, default 20°FWrite
AV5Cooling_Coil_Setpoint_MinCooling coil leaving air setpoint, default 50°FWrite
AV6Cooling_Coil_Setpoint_MaxMax coil leaving setpoint for coil reset, default 55°FWrite
AV7Dehumidification_SetpointSpace/return dehumidification setpoint, default 55%RHWrite
AV11Unoccupied_Dehumidification_SetpointUnoccupied dehumidification setpoint, default 60%RHWrite
AV14Supply_Fan_CFM_SetpointSupply fan airflow setpointcfmWrite
AV15Exhaust_Fan_CFM_SetpointExhaust fan airflow setpointcfmWrite
AV16OAD_CFM_SetpointOutside air damper airflow setpointcfmWrite
AV21Return_Duct_Static_Pressure_SetpointReturn duct static setpoint, default -2.0inH2OWrite
AV22Space_Static_Pressure_SetpointSpace static setpoint, default 0.05inH2OWrite
AV23Supply_Duct_Static_Pressure_SetpointSupply duct static setpoint, default 1.0inH2OWrite
AV24Space_CO2_SetpointSpace CO2 setpoint, default 1000ppmWrite
AV25Outside_Air_Damper_Minimum_Setpoint_OccOccupied minimum OA damper, default 35%Write
AV26Outside_RH_from_BMSOutside RH from BMS%RHWrite
AV27Outside_Temp_from_BMSOutside temperature from BMS°FWrite
AV28Return_RH_from_BMSReturn RH from BMS%RHWrite
AV29Return_Temp_from_BMSReturn temperature from BMS°FWrite
AV30Space_1_CO2_from_BMSSpace 1 CO2 from BMSppmWrite
AV31Space_2_CO2_from_BMSSpace 2 CO2 from BMSppmWrite
AV32Return_CO2_from_BMSReturn CO2 from BMSppmWrite
AV33Space_RH_from_BMSSpace RH from BMS%RHWrite
AV34Space_Static_from_BMSSpace static pressure from BMSinH2OWrite
AV35Space_Temp_from_BMSSpace temperature from BMS°FWrite
AV36SF_Control_Signal_BMSSupply fan speed command (with BV 17)%Write
AV37EF_Control_Signal_BMSExhaust fan speed command (with BV 18)%Write
AV38OAD_Control_Signal_BMSOutside air damper command (with BV 19)%Write
AVmin40Unit_Status_ModeUnit operating mode/state (status mode table)Read
AV41Supply_Temperature_Calculated_SetpointActive supply temperature setpoint°FRead
AV42Cooling_1_Ramp_CapacityCooling ramp 1%Read
AV50HP_Ramp_CapacityHeat pump heating ramp%Read
AV51Heating_CapacityHeating ramp%Read
AV53Hot_Gas_Reheat_RampHot gas reheat ramp%Read
AV64Total_Exhaust_Fan_CFM_BMSTotal exhaust fan airflowcfmRead
AV65Total_Supply_Fan_CFM_BMSTotal supply fan airflowcfmRead
AV66OAD_CFM_BMSOutside air damper airflowcfmRead
AV68Chilled_Water_1_Valve_Analog_OutputChilled water valve output%Read
AV70Electric_Heater_1_Analog_OutputElectric heater output%Read
AV72Energy_Recovery_Analog_OutputEnergy recovery output%Read
AV73Exhaust_Fan_Speed_Analog_OutputExhaust fan speed output%Read
AV74Hot_Water_Valve_1_Analog_OutputHot water valve output%Read
AV76Mod_Gas_Furnace_1_Analog_OutputModulating gas furnace output%Read
AV78Outside_Air_Damper_Analog_OutputOutside air damper output%Read
AV79Supply_Fan_Speed_Analog_OutputSupply fan speed output%Read
AV80Modulating_Compressor_Analog_Output_BMSModulating compressor output%Read
AV90Coil_Temperature_Calculated_SetpointCalculated coil leaving setpoint°FRead
AI1Space_Temp_Analog_InputSpace air temperature°FRead
AImin2Supply_Temp_Analog_InputSupply (discharge) air temperature°FRead
AI3Outside_Air_Temp_Analog_InputOutside air temperature°FRead
AI4Mixed_Temp_Analog_InputMixed air temperature°FRead
AI5Cold_Coil_1_Temp_Analog_InputCooling coil 1 leaving air temperature°FRead
AI7Return_Temp_Analog_InputReturn air temperature°FRead
AI8Exhaust_Temp_Analog_InputExhaust air temperature°FRead
AI9Space_RH_Analog_InputSpace relative humidity%RHRead
AI10Outside_RH_Analog_InputOutside relative humidity%RHRead
AI11Return_RH_Analog_InputReturn relative humidity%RHRead
AI12Return_Duct_Static_Pressure_Analog_InputReturn duct static pressureinH2ORead
AI13Space_Static_Pressure_Analog_InputSpace static pressureinH2ORead
AI14Supply_Duct_Static_Pressure_Analog_InputSupply duct static pressureinH2ORead
AI15Space_CO2_1_Analog_InputSpace 1 CO2ppmRead
AI17Return_CO2_Analog_InputReturn CO2ppmRead
Object ID lookup: Accurex DOAS microprocessor controller point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the DOAS microprocessor controller (DOAS_08.000) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Accurex DOAS microprocessor controller (DOAS_08.000)

How many BACnet points does the Accurex DOAS microprocessor controller (DOAS_08.000) have?

This list has 93 BACnet objects: 15 analog inputs, 48 analog values, 2 binary inputs, 19 binary values, 9 integer values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Accurex DOAS microprocessor controller (DOAS_08.000) BACnet points are writable?

48 of the 93 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Accurex DOAS microprocessor controller (DOAS_08.000) BACnet documentation?

The source is BACnet Integration Guide for Dedicated Outdoor Air Systems (485940 (DOAS_08.000 Rev 2)), revision 01/2023, published free by Accurex at https://content.accurex.com/accurex-cms-prod/docs/default-source/ioms/485940-bacnet-integration-guide-doas_08.000.pdf.

What are the minimum BACnet points to integrate the Accurex DOAS microprocessor controller (DOAS_08.000)?

Start with BV 2 System_Enable (Unit enable (1 = enabled)); BV 3 BMS_Occupancy_Command (Occupancy: 0 = occupied, 1 = unoccupied); AV 1 Temperature_Setpoint (Occupied temperature setpoint, °F); BV 1 BMS_Watchdog (Watchdog; write 1 regularly when BMS commands); BV 4 Reset_All_Alarms (Resets alarms); AV 40 Unit_Status_Mode (Unit mode number (status mode table)); AI 2 Supply_Temp_Analog_Input (Supply air temperature, °F); BI 2 Supply_Fan_1_Status_Digital_Input (Supply fan running); BV 23 Global_Alarm (Any active alarm); IV 5 LatestAlm (Latest alarm code; 0 = none).

How do I enable BMS control of the Accurex DOAS microprocessor controller (DOAS_08.000)?

BV 2 System_Enable enables or disables the unit, and BV 3 BMS_Occupancy_Command sets occupancy (the default occupancy mode expects the BMS command; a schedule, digital input or fixed mode can be chosen at the controller instead).

Does the Accurex DOAS microprocessor controller (DOAS_08.000) need a BACnet heartbeat or have a communication timeout?

BV 1 BMS_Watchdog must be written True regularly whenever the BMS commands fans, damper or sensor values. If it stays False longer than the timeout (default 15 min, adjustable), alarm 79 is raised and the controller goes back to local control and sensors. With Enable Relinquish Default on, commandable points are cleared to relinquish defaults 5 minutes after the watchdog drops.

Can the BMS supply sensor values to the Accurex DOAS microprocessor controller (DOAS_08.000)?

Set the source BV to BMS (BV 7-16) and write the value to the matching AV 26-35 (outside/return RH and temperature, space/return CO2, space RH, static and temperature). The watchdog must be kept alive or the controller falls back to the local sensor.

How do I check these points on the real DOAS microprocessor controller (DOAS_08.000)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Accurex BACnet points lists

Source: BACnet Integration Guide for Dedicated Outdoor Air Systems · 485940 (DOAS_08.000 Rev 2) · rev. 01/2023. Object names, instances and units are reproduced as published; descriptions are our own.