 "manufacturer": "Accurex",
 "manufacturer_slug": "accurex",
 "model": "Vari-Flow Air Management System v2.00",
 "model_slug": "vari-flow-v2",
 "aliases": [
  "Vari-Flow",
  "Vari-Flow 2.00",
  "Accurex demand-controlled kitchen ventilation",
  "Auto Scrubber Control Panel",
  "ASCP v2.00"
 ],
 "equipment_type": "Kitchen hood demand-controlled ventilation controls",
 "applies_to": "Accurex Vari-Flow demand-controlled kitchen ventilation systems (hood temperature/optic sensing, exhaust and supply fan VFDs) with a Carel-based controller.",
 "summary": "Vari-Flow is Accurex's demand-controlled kitchen ventilation controller. It modulates exhaust and supply fans from hood temperatures and can talk BACnet MS/TP or BACnet IP through a communication card. The v2.00 points list covers hood control temperatures, fan speeds and status, temperature settings, hood system on/off commands, remote enable, wash and alarm flags.",
 "bacnet_transport": [
  "BACnet MS/TP",
  "BACnet IP"
 ],
 "firmware": "Vari-Flow v2.00",
 "default_device_instance": 77000,
 "access_inferred": false,
 "notes": [
  "The points list states the mapping: Analog and Integer variables are Analog Value objects, Digital variables are Binary Value objects.",
  "The list has objects for up to 10 hood systems, 10 exhaust fans and 4 supply fans; map only the ones the job has.",
  "Access is from the points list's R / R/W column.",
  "The Accurex Auto Scrubber Control Panel (ASCP v2.00, document 481510) prints the same 167 objects; it is covered by this entry.",
  "Vari-Flow v3.00 renumbers and adds objects (63 of the v2.00 objects are not in v3.00); use the list that matches the controller program version."
 ],
 "source": {
  "title": "Vari-Flow Air Management System - Installation, Operation and Maintenance Manual, BMS Points List (v2.00)",
  "doc_number": "481515 Rev. 3",
  "revision_date": "2019-08",
  "url": "https://content.accurex.com/accurex-cms-prod/docs/default-source/ioms/vari-flow_management_system_iom.pdf?sfvrsn=ff6579ed_6"
 },
 "integration": {
  "summary": "Enable the system with BV 102 Remote Enable and switch hood systems with BV 11-20. Read hood control temperatures (AV 11-20), fan speeds (AV 1011 up) and fan status BVs, and watch BV 10 Global Alarm and BV 101 fire status.",
  "minimum_points": [
   {
    "ref": "BV 102",
    "why": "Remote enable of the system (1 = on)",
    "name": "Rem_En"
   },
   {
    "ref": "BV 11",
    "why": "Hood system 1 on/off (1 = on)",
    "name": "Sys1_On_Off"
   },
   {
    "ref": "AV 11",
    "why": "Hood 1 control temperature",
    "name": "H1_Ctemp"
   },
   {
    "ref": "AV 1011",
    "why": "Exhaust fan 1 speed, %",
    "name": "Ef1_Speed"
   },
   {
    "ref": "BV 171",
    "why": "Exhaust fan 1 running",
    "name": "Ef1_Status"
   },
   {
    "ref": "BV 181",
    "why": "Supply fan 1 running",
    "name": "Sf1_Status"
   },
   {
    "ref": "BV 101",
    "why": "Fire system active",
    "name": "Fire_Alm"
   },
   {
    "ref": "BV 10",
    "why": "Any active alarm",
    "name": "GLOBAL_ALARM"
   }
  ],
  "enable": "BV 102 Remote Enable (1 = on) and the per-system On/Off BVs (BV 11-20) let the BMS run the hood systems.",
  "heartbeat": null,
  "remote_sensors": null,
  "setup": [
   "BACnet MS/TP or BACnet IP needs the matching communication card in the controller serial card port, with BACnet Plugin set to YES.",
   "Default device instance is 77000; MS/TP MAC, baud and IP settings are adjusted from the controller display (BACnet IP cards ship in DHCP mode)."
  ],
  "gotchas": [
   "Network settings changed on the display only take effect after a Write on the BACnet Read/Write screen and a power cycle."
  ]
 },
 "points": [
  {
   "type": "AV",
   "instance": 11,
   "name": "H1_Ctemp",
   "description": "Hood 1 Control Temperature",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 12,
   "name": "H2_Ctemp",
   "description": "Hood 2 Control Temperature",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 13,
   "name": "H3_Ctemp",
   "description": "Hood 3 Control Temperature",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 14,
   "name": "H4_Ctemp",
   "description": "Hood 4 Control Temperature",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 15,
   "name": "H5_Ctemp",
   "description": "Hood 5 Control Temperature",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 16,
   "name": "H6_Ctemp",
   "description": "Hood 6 Control Temperature",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 17,
   "name": "H7_Ctemp",
   "description": "Hood 7 Control Temperature",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 18,
   "name": "H8_Ctemp",
   "description": "Hood 8 Control Temperature",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 19,
   "name": "H9_Ctemp",
   "description": "Hood 9 Control Temperature",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 20,
   "name": "H10_Ctemp",
   "description": "Hood 10 Control Temperature",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 51,
   "name": "Ef1_Amps",
   "description": "Exhaust Fan 1 Amps from VFD",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 52,
   "name": "Ef2_Amps",
   "description": "Exhaust Fan 2 Amps from VFD",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 53,
   "name": "Ef3_Amps",
   "description": "Exhaust Fan 3 Amps from VFD",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 54,
   "name": "Ef4_Amps",
   "description": "Exhaust Fan 4 Amps from VFD",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 55,
   "name": "Ef5_Amps",
   "description": "Exhaust Fan 5 Amps from VFD",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 56,
   "name": "Ef6_Amps",
   "description": "Exhaust Fan 6 Amps from VFD",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 57,
   "name": "Ef7_Amps",
   "description": "Exhaust Fan 7 Amps from VFD",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 58,
   "name": "Ef8_Amps",
   "description": "Exhaust Fan 8 Amps from VFD",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 59,
   "name": "Ef9_Amps",
   "description": "Exhaust Fan 9 Amps from VFD",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 60,
   "name": "Ef10_Amps",
   "description": "Exhaust Fan 10 Amps from VFD",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 71,
   "name": "Sf1_Amps",
   "description": "Supply 1 Amps from VFD",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 72,
   "name": "Sf2_Amps",
   "description": "Supply 2 Amps from VFD",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 73,
   "name": "Sf3_Amps",
   "description": "Supply 3 Amps from VFD",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 74,
   "name": "Sf4_Amps",
   "description": "Supply 4 Amps from VFD",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 81,
   "name": "Ef1_kW",
   "description": "Exhaust Fan 1 Power Output",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 82,
   "name": "Ef2_kW",
   "description": "Exhaust Fan 2 Power Output",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 83,
   "name": "Ef3_kW",
   "description": "Exhaust Fan 3 Power Output",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 84,
   "name": "Ef4_kW",
   "description": "Exhaust Fan 4 Power Output",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 85,
   "name": "Ef5_kW",
   "description": "Exhaust Fan 5 Power Output",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 86,
   "name": "Ef6_kW",
   "description": "Exhaust Fan 6 Power Output",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 87,
   "name": "Ef7_kW",
   "description": "Exhaust Fan 7 Power Output",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 88,
   "name": "Ef8_kW",
   "description": "Exhaust Fan 8 Power Output",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 89,
   "name": "Ef9_kW",
   "description": "Exhaust Fan 9 Power Output",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 90,
   "name": "Ef10_kW",
   "description": "Exhaust Fan 10 Power Output",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 101,
   "name": "Sf1_kW",
   "description": "Supply Fan 1 Power Output",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 102,
   "name": "Sf2_kW",
   "description": "Supply Fan 2 Power Output",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 103,
   "name": "Sf3_kW",
   "description": "Supply Fan 3 Power Output",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 104,
   "name": "Sf4_kW",
   "description": "Supply Fan 4 Power Output",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 111,
   "name": "Ef1_FrRe",
   "description": "Exhaust Fan 1 Frequency Reference",
   "units": "Hz",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 112,
   "name": "Ef2_FrRe",
   "description": "Exhaust Fan 2 Frequency Reference",
   "units": "Hz",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 113,
   "name": "Ef3_FrRe",
   "description": "Exhaust Fan 3 Frequency Reference",
   "units": "Hz",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 114,
   "name": "Ef4_FrRe",
   "description": "Exhaust Fan 4 Frequency Reference",
   "units": "Hz",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 115,
   "name": "Ef5_FrRe",
   "description": "Exhaust Fan 5 Frequency Reference",
   "units": "Hz",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 116,
   "name": "Ef6_FrRe",
   "description": "Exhaust Fan 6 Frequency Reference",
   "units": "Hz",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 117,
   "name": "Ef7_FrRe",
   "description": "Exhaust Fan 7 Frequency Reference",
   "units": "Hz",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 118,
   "name": "Ef8_FrRe",
   "description": "Exhaust Fan 8 Frequency Reference",
   "units": "Hz",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 119,
   "name": "Ef9_FrRe",
   "description": "Exhaust Fan 9 Frequency Reference",
   "units": "Hz",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 120,
   "name": "Ef10_FrRe",
   "description": "Exhaust Fan 10 Frequency Reference",
   "units": "Hz",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 131,
   "name": "Sf1_FrRe",
   "description": "Supply Fan 1 Frequency Reference",
   "units": "Hz",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 132,
   "name": "Sf2_FrRe",
   "description": "Supply Fan 2 Frequency Reference",
   "units": "Hz",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 133,
   "name": "Sf3_FrRe",
   "description": "Supply Fan 3 Frequency Reference",
   "units": "Hz",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 134,
   "name": "Sf4_FrRe",
   "description": "Supply Fan 4 Frequency Reference",
   "units": "Hz",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 141,
   "name": "Ef1_LoTemp",
   "description": "Exhaust Fan 1 Low Temperature Setting",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 142,
   "name": "Ef2_LoTemp",
   "description": "Exhaust Fan 2 Low Temperature Setting",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 143,
   "name": "Ef3_LoTemp",
   "description": "Exhaust Fan 3 Low Temperature Setting",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 144,
   "name": "Ef4_LoTemp",
   "description": "Exhaust Fan 4 Low Temperature Setting",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 145,
   "name": "EF5_LoTemp",
   "description": "Exhaust Fan 5 Low Temperature Setting",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 146,
   "name": "EF6_LoTemp",
   "description": "Exhaust Fan 6 Low Temperature Setting",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 147,
   "name": "EF7_LoTemp",
   "description": "Exhaust Fan 7 Low Temperature Setting",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 148,
   "name": "EF8_LoTemp",
   "description": "Exhaust Fan 8 Low Temperature Setting",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 149,
   "name": "EF9_LoTemp",
   "description": "Exhaust Fan 9 Low Temperature Setting",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 150,
   "name": "EF10_LoTemp",
   "description": "Exhaust Fan 10 Low Temperature Setting",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 151,
   "name": "Ef1_HiTemp",
   "description": "Exhaust Fan 1 High Temperature Setting",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 152,
   "name": "Ef2_HiTemp",
   "description": "Exhaust Fan 2 High Temperature Setting",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 153,
   "name": "Ef3_HiTemp",
   "description": "Exhaust Fan 3 High Temperature Setting",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 154,
   "name": "Ef4_HiTemp",
   "description": "Exhaust Fan 4 High Temperature Setting",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 155,
   "name": "Ef5_HiTemp",
   "description": "Exhaust Fan 5 High Temperature Setting",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 156,
   "name": "Ef6_HiTemp",
   "description": "Exhaust Fan 6 High Temperature Setting",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 157,
   "name": "Ef7_HiTemp",
   "description": "Exhaust Fan 7 High Temperature Setting",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 158,
   "name": "Ef8_HiTemp",
   "description": "Exhaust Fan 8 High Temperature Setting",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 159,
   "name": "Ef9_HiTemp",
   "description": "Exhaust Fan 9 High Temperature Setting",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 160,
   "name": "Ef10_HiTemp",
   "description": "Exhaust Fan 10 High Temperature Setting",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 161,
   "name": "Ef1_LoSpeed",
   "description": "Exhaust Fan 1 Low Speed Setting",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 162,
   "name": "Ef2_LoSpeed",
   "description": "Exhaust Fan 2 Low Speed Setting",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 163,
   "name": "Ef3_LoSpeed",
   "description": "Exhaust Fan 3 Low Speed Setting",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 164,
   "name": "Ef4_LoSpeed",
   "description": "Exhaust Fan 4 Low Speed Setting",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 165,
   "name": "Ef5_LoSpeed",
   "description": "Exhaust Fan 5 Low Speed Setting",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 166,
   "name": "Ef6_LoSpeed",
   "description": "Exhaust Fan 6 Low Speed Setting",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 167,
   "name": "Ef7_LoSpeed",
   "description": "Exhaust Fan 7 Low Speed Setting",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 168,
   "name": "Ef8_LoSpeed",
   "description": "Exhaust Fan 8 Low Speed Setting",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 169,
   "name": "Ef9_LoSpeed",
   "description": "Exhaust Fan 9 Low Speed Setting",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 170,
   "name": "Ef10_LoSpeed",
   "description": "Exhaust Fan 10 Low Speed Setting",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 171,
   "name": "Ef1_HiSpeed",
   "description": "Exhaust Fan 1 High Speed Setting",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 172,
   "name": "Ef2_HiSpeed",
   "description": "Exhaust Fan 2 High Speed Setting",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 173,
   "name": "Ef3_HiSpeed",
   "description": "Exhaust Fan 3 High Speed Setting",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 174,
   "name": "Ef4_HiSpeed",
   "description": "Exhaust Fan 4 High Speed Setting",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 175,
   "name": "Ef5_HiSpeed",
   "description": "Exhaust Fan 5 High Speed Setting",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 176,
   "name": "Ef6_HiSpeed",
   "description": "Exhaust Fan 6 High Speed Setting",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 177,
   "name": "Ef7_HiSpeed",
   "description": "Exhaust Fan 7 High Speed Setting",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 178,
   "name": "Ef8_HiSpeed",
   "description": "Exhaust Fan 8 High Speed Setting",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 179,
   "name": "Ef9_HiSpeed",
   "description": "Exhaust Fan 9 High Speed Setting",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 180,
   "name": "Ef10_HiSpeed",
   "description": "Exhaust Fan 10 High Speed Setting",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 181,
   "name": "Sf1_LoSpeed",
   "description": "Supply Fan 1 Low Speed Setting",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 182,
   "name": "Sf2_LoSpeed",
   "description": "Supply Fan 2 Low Speed Setting",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 183,
   "name": "Sf3_LoSpeed",
   "description": "Supply Fan 3 Low Speed Setting",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 184,
   "name": "Sf4_LoSpeed",
   "description": "Supply Fan 4 Low Speed Setting",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 191,
   "name": "Sf1_HiSpeed",
   "description": "Supply Fan 1 High Speed Setting",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 192,
   "name": "Sf2_HiSpeed",
   "description": "Supply Fan 2 High Speed Setting",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 193,
   "name": "Sf3_HiSpeed",
   "description": "Supply Fan 3 High Speed Setting",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 194,
   "name": "Sf4_HiSpeed",
   "description": "Supply Fan 4 High Speed Setting",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1011,
   "name": "Ef1_Speed",
   "description": "Exhaust Fan 1 Speed Percentage",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1012,
   "name": "Ef2_Speed",
   "description": "Exhaust Fan 2 Speed Percentage",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1013,
   "name": "Ef3_Speed",
   "description": "Exhaust Fan 3 Speed Percentage",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1014,
   "name": "Ef4_Speed",
   "description": "Exhaust Fan 4 Speed Percentage",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1015,
   "name": "Ef5_Speed",
   "description": "Exhaust Fan 5 Speed Percentage",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1016,
   "name": "Ef6_Speed",
   "description": "Exhaust Fan 6 Speed Percentage",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1017,
   "name": "Ef7_Speed",
   "description": "Exhaust Fan 7 Speed Percentage",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1018,
   "name": "Ef8_Speed",
   "description": "Exhaust Fan 8 Speed Percentage",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1019,
   "name": "Ef9_Speed",
   "description": "Exhaust Fan 9 Speed Percentage",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1020,
   "name": "Ef10_Speed",
   "description": "Exhaust Fan 10 Speed Percentage",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1031,
   "name": "Sf1_Speed",
   "description": "Supply Fan 1 Speed Percentage",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1032,
   "name": "Sf2_Speed",
   "description": "Supply Fan 2 Speed Percentage",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1033,
   "name": "Sf3_Speed",
   "description": "Supply Fan 3 Speed Percentage",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1034,
   "name": "Sf4_Speed",
   "description": "Supply Fan 4 Speed Percentage",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 10,
   "name": "GLOBAL_ALARM",
   "description": "Global Alarm",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=Alarm"
  },
  {
   "type": "BV",
   "instance": 11,
   "name": "Sys1_On_Off",
   "description": "Hood System 1 On/Off",
   "units": "",
   "access": "W",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 12,
   "name": "Sys2_On_Off",
   "description": "Hood System 2 On/Off",
   "units": "",
   "access": "W",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 13,
   "name": "Sys3_On_Off",
   "description": "Hood System 3 On/Off",
   "units": "",
   "access": "W",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 14,
   "name": "Sys4_On_Off",
   "description": "Hood System 4 On/Off",
   "units": "",
   "access": "W",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 15,
   "name": "Sys5_On_Off",
   "description": "Hood System 5 On/Off",
   "units": "",
   "access": "W",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 16,
   "name": "Sys6_On_Off",
   "description": "Hood System 6 On/Off",
   "units": "",
   "access": "W",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 17,
   "name": "Sys7_On_Off",
   "description": "Hood System 7 On/Off",
   "units": "",
   "access": "W",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 18,
   "name": "Sys8_On_Off",
   "description": "Hood System 8 On/Off",
   "units": "",
   "access": "W",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 19,
   "name": "Sys9_On_Off",
   "description": "Hood System 9 On/Off",
   "units": "",
   "access": "W",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 20,
   "name": "Sys10_On_Off",
   "description": "Hood System 10 On/Off",
   "units": "",
   "access": "W",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 91,
   "name": "T1_Alm",
   "description": "Temp Sensor 1 Failure",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=Alarm"
  },
  {
   "type": "BV",
   "instance": 92,
   "name": "T2_Alm",
   "description": "Temp Sensor 2 Failure",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=Alarm"
  },
  {
   "type": "BV",
   "instance": 93,
   "name": "T3_Alm",
   "description": "Temp Sensor 3 Failure",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=Alarm"
  },
  {
   "type": "BV",
   "instance": 94,
   "name": "T4_Alm",
   "description": "Temp Sensor 4 Failure",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=Alarm"
  },
  {
   "type": "BV",
   "instance": 95,
   "name": "T5_Alm",
   "description": "Temp Sensor 5 Failure",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=Alarm"
  },
  {
   "type": "BV",
   "instance": 96,
   "name": "T6_Alm",
   "description": "Temp Sensor 6 Failure",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=Alarm"
  },
  {
   "type": "BV",
   "instance": 97,
   "name": "T7_Alm",
   "description": "Temp Sensor 7 Failure",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=Alarm"
  },
  {
   "type": "BV",
   "instance": 98,
   "name": "T8_Alm",
   "description": "Temp Sensor 8 Failure",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=Alarm"
  },
  {
   "type": "BV",
   "instance": 99,
   "name": "T9_Alm",
   "description": "Temp Sensor 9 Failure",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=Alarm"
  },
  {
   "type": "BV",
   "instance": 100,
   "name": "T10_Alm",
   "description": "Temp Sensor 10 Failure",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=Alarm"
  },
  {
   "type": "BV",
   "instance": 101,
   "name": "Fire_Alm",
   "description": "Fire System Status",
   "units": "",
   "access": "R",
   "states": "0=Ok, 1=Fire"
  },
  {
   "type": "BV",
   "instance": 102,
   "name": "Rem_En",
   "description": "Remote Enable",
   "units": "",
   "access": "W",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 103,
   "name": "Wash_En",
   "description": "Wash Enable",
   "units": "",
   "access": "W",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 104,
   "name": "Fill_det",
   "description": "Detergent Status",
   "units": "",
   "access": "R",
   "states": "0=Ok, 1=Empty"
  },
  {
   "type": "BV",
   "instance": 105,
   "name": "CWM_status",
   "description": "Cold Water Mist Status",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 106,
   "name": "PCU_filter_1",
   "description": "PCU Filter 1 Status",
   "units": "",
   "access": "R",
   "states": "0=Ok, 1=Clogged"
  },
  {
   "type": "BV",
   "instance": 107,
   "name": "PCU_filter_2",
   "description": "PCU Filter 2 Status",
   "units": "",
   "access": "R",
   "states": "0=Ok, 1=Clogged"
  },
  {
   "type": "BV",
   "instance": 108,
   "name": "PCU_filter_3",
   "description": "PCU Filter 3 Status",
   "units": "",
   "access": "R",
   "states": "0=Ok, 1=Clogged"
  },
  {
   "type": "BV",
   "instance": 131,
   "name": "Sf1_Af_Alm",
   "description": "Airflow Alarm Supply Fan 1",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=Alarm"
  },
  {
   "type": "BV",
   "instance": 132,
   "name": "Sf2_Af_Alm",
   "description": "Airflow Alarm Supply Fan 2",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=Alarm"
  },
  {
   "type": "BV",
   "instance": 133,
   "name": "Sf3_Af_Alm",
   "description": "Airflow Alarm Supply Fan 3",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=Alarm"
  },
  {
   "type": "BV",
   "instance": 134,
   "name": "Sf4_Af_Alm",
   "description": "Airflow Alarm Supply Fan 4",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=Alarm"
  },
  {
   "type": "BV",
   "instance": 141,
   "name": "Sf1_Pres_Alm",
   "description": "Supply Fan 1 Pressure Alarm",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=Alarm"
  },
  {
   "type": "BV",
   "instance": 160,
   "name": "HiTemp_Alm",
   "description": "High Temperature Alarm",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=Alarm"
  },
  {
   "type": "BV",
   "instance": 161,
   "name": "Exh_BO_Alm",
   "description": "Exhaust Starter/VFD Fault",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=Alarm"
  },
  {
   "type": "BV",
   "instance": 162,
   "name": "Sup_BO_Alm",
   "description": "Supply Starter/VFD Fault",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=Alarm"
  },
  {
   "type": "BV",
   "instance": 163,
   "name": "Exh_VBF_Alm",
   "description": "Exhaust VFD By Factory Fault",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=Alarm"
  },
  {
   "type": "BV",
   "instance": 164,
   "name": "Sup_VBF_Alm",
   "description": "Supply VFD By Factory Fault",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=Alarm"
  },
  {
   "type": "BV",
   "instance": 171,
   "name": "Ef1_Status",
   "description": "Exhaust Fan 1 Status",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 172,
   "name": "Ef2_Status",
   "description": "Exhaust Fan 2 Status",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 173,
   "name": "Ef3_Status",
   "description": "Exhaust Fan 3 Status",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 174,
   "name": "Ef4_Status",
   "description": "Exhaust Fan 4 Status",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 175,
   "name": "Ef5_Status",
   "description": "Exhaust Fan 5 Status",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 176,
   "name": "Ef6_Status",
   "description": "Exhaust Fan 6 Status",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 177,
   "name": "Ef7_Status",
   "description": "Exhaust Fan 7 Status",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 178,
   "name": "Ef8_Status",
   "description": "Exhaust Fan 8 Status",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 179,
   "name": "Ef9_Status",
   "description": "Exhaust Fan 9 Status",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 180,
   "name": "Ef10_Status",
   "description": "Exhaust Fan 10 Status",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 181,
   "name": "Sf1_Status",
   "description": "Supply Fan 1 Status",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 182,
   "name": "Sf2_Status",
   "description": "Supply Fan 2 Status",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 183,
   "name": "Sf3_Status",
   "description": "Supply Fan 3 Status",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 184,
   "name": "Sf4_Status",
   "description": "Supply Fan 4 Status",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  }
 ],
 "page": "https://easybacnet.com/bacnet-points-lists/accurex/vari-flow-v2",
 "note": "Provided as-is. Point availability varies by firmware and options; verify against the live device.",
 "disclaimer": "DISCLAIMER: reference only, provided AS IS with no warranty. May contain errors or be out of date. You must verify every point against the manufacturer's current documentation and the live device before use. easybacnet.com accepts no liability for its use and is not affiliated with the manufacturer. Terms: https://easybacnet.com/terms#content"
}