BACnet instance calculator · SDV5 VRF BACnet gateway GW-BAC
Sinclair SDV5 GW-BAC BACnet Device ID Calculator
Free browser tool · nothing is uploaded · 5 November 2026
The Sinclair GW-BAC makes every SDV5 indoor and outdoor unit its own BACnet device. Its device instance comes from the gateway's network number, the RS-485 port and the unit address.
Indoor unit device instance = network number x 10000 + port x 1000 + indoor address; outdoor units add 100 to the address. Network 2, port 1, indoor unit 7 is 21007; outdoor unit 3 on the same port is 21103. Every indoor unit device has the same object instances.
Sinclair calculator
The calculator needs JavaScript. The formula and a worked example are below.
Which unit is this device?
How the numbers are built
device = network x 10000 + port x 1000 + address (outdoor + 100)
| Part | Meaning | Range |
|---|---|---|
| network | BACnet network number set on the gateway's web page | 2-254 |
| port | RS-485 port (0 = the one next to the Ethernet jack) | 0-3 |
| address | Indoor unit address (outdoor: 100 + outdoor address) | 0-63 (OU 0-31) |
Set a BACnet network number of 2-254 that nothing else uses on the gateway's web page, then restart it. Ports are numbered 0-3, port 0 being the one next to the Ethernet jack.
Worked example: network 2, port 1, indoor unit 7
The first objects for network 2, port 1, indoor unit 7 on the GW-BAC, worked out with the formula above:
| Unit type | Device instance | For |
|---|---|---|
| Indoor unit device | 21007 | BACnet network number 2, RS-485 port 1, Indoor unit address 7 |
| Outdoor unit device | 21103 | BACnet network number 2, RS-485 port 1, Outdoor unit address 3 |
Source
Formula and objects from GW-BAC Commercial Air Conditioners SDV5 (user manual) (manufacturer document ↗), re-typed in our points list. Object names are shown as printed.
Check it against the live device. The calculator applies the formula from the manufacturer’s documentation; the gateway in front of you may expose fewer objects or use other numbers after a firmware change. Easy BACnet scans a network for BACnet IP devices from an Android phone and reads every object on them — a quick way to confirm one unit before you map a whole building.
Questions
How do I work out a Sinclair instance number?
Indoor unit device instance = network number x 10000 + port x 1000 + indoor address; outdoor units add 100 to the address. Network 2, port 1, indoor unit 7 is 21007; outdoor unit 3 on the same port is 21103. Every indoor unit device has the same object instances.
Is the Sinclair GW-BAC the same as the Systemair gateway?
They use the same device instance formula. The Systemair SYS GW IMS BAC(A) list also covers outdoor units and HTHM modules; it has its own calculator.
Is this Sinclair calculator official?
No. It applies the formula printed in Sinclair's own documentation to the points list in our library. Confirm the numbers against a scan of the live device before you map or write anything.
More instance calculators
- Fujitsu UTY-VBGX VRF gatewayFujitsu's UTY-VBGX gateway puts the refrigerant system and unit address inside every instance number.
instance = point code x 10000 + refrigerant system x 100 + unit address - Mitsubishi Electric BAC-HD150 BM AdapterThe BAC-HD150 BM Adapter numbers every CITY MULTI group's objects as M-NET number, group number and point number.
instance = M-NET number x 10000 + group x 100 + point - Mitsubishi Electric AE-C400 / EW-C50With the BACnet license, the AE-C400 and EW-C50 number objects by class, address and point.
instance = class x 10000 + address x 100 + point - Mitsubishi Electric PAC-YG31CDA (G-50A)The legacy PAC-YG31CDA BACnet interface serves up to ten G-50A controllers and numbers each group's objects by G-50A number, group and point.
instance = G-50A number x 10000 + group x 100 + point - Mitsubishi Electric Procon BAC-IP/50The Procon BAC-IP/50 gives every unit on its G-50 a block of objects numbered 1, the 3-digit unit address and the point number.
instance = 100000 + unit address x 100 + point - Daikin DMS502B71 VRV BACnet interfaceThe Daikin DMS502B71 BACnet interface gives every VRV indoor unit group the same 35-member object template.
instance = unit number x 256 + member number - Toshiba BMS-IFBN1281U BN interfaceToshiba Carrier's BN interface gives every indoor unit the same block of objects, numbered from the unit's central control address and a fixed function code.
instance = central control address x 256 + function code - Gree GMS GW BACnet converterGree's GMS GW 1 and GMS GW 12 converters number every split unit's objects from its line and remote control address.
instance = class x 1048576 + (line - 1) x 131072 + address x 256 + object