VRF BACnet gateway (per indoor unit) · BACnet points list

Sinclair SDV5 VRF BACnet Gateway GW-BAC BACnet points list

Updated 4 November 2026

Short answer

The GW-BAC connects up to four XYE buses (64 indoor and 32 outdoor units per bus, 256 indoor units in total) to BACnet IP. Every indoor unit appears as its own BACnet device with the same small object set: on/off, mode, fan speed, setpoints, locks, room temperature and error code. This file lists that per-indoor-unit object set. Outdoor units appear as separate devices with their own read-only object list.

This page lists 15 BACnet objects for the Sinclair SDV5 VRF BACnet Gateway GW-BAC — 12 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Sinclair’s own free documentation, linked below.

Manufacturer
Sinclair
Model
SDV5 VRF BACnet Gateway GW-BAC
Equipment
VRF BACnet gateway (per indoor unit)
Equipment type
VRF & split air conditioners
BACnet objects
15 (12 writable)
Transport
BACnet IP
Firmware
Not stated
Default device instance
Network number x 10000 + port x 1000 + indoor unit address
Also known as
GW-BAC, SDV5 BACnet gateway, Sinclair VRF BACnet gateway
Source document
GW-BAC Commercial Air Conditioners SDV5 (user manual)

Instance calculator. This list prints one unit; the other units follow a formula. Sinclair SDV5 VRF BACnet gateway GW-BAC instance calculator →

Download CSV 15 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Sinclair’s current documentation and the live device before use. Not official Sinclair information. Terms of use.

BMS integration notes: Sinclair SDV5 VRF BACnet Gateway GW-BAC

Integration in brief

Give the gateway an IP address and a unique BACnet network number (2-254) on its web page, restart it, then discover one BACnet device per indoor unit. Map on/off, mode, fan speed and setpoint for each unit, and read room temperature, alarm and error code. All indoor unit devices share the same object instances.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 1On/Off SettingUnit on/off (1 = on)Write
MV 1Mode Setting1 Off, 2 Fan, 3 Cool, 4 Heat, 5 Auto, 6 DryWrite
AV 1Temperature SettingRoom setpoint, 17-30 °CWrite
MV 2Fan Speed SettingFan speed 1-7, 8 = autoWrite
AI 1Room TemperatureRoom temperature, °CRead
BI 2Alarm IndicationIndoor unit error (1 = error)Read
AI 7Malfunction CodeActive error code number, 0 = noneRead

Enable & remote start

No enable point. Each indoor unit is controllable once the gateway sees it on its XYE bus.

Network setup

Watch out for

Sinclair SDV5 VRF BACnet Gateway GW-BAC BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

15 of 15 shown
Type
Multi-state
Access
Show
Sinclair SDV5 VRF BACnet Gateway GW-BAC BACnet Points List
DescriptionStates
AImin1Room TemperatureRoom temperature at the indoor unit°CRead
AImin7Malfunction CodeError code number (0 = no error)Read
BImin2Alarm IndicationIndoor unit error statusRead0=No error, 1=Error
BVmin1On/Off SettingIndoor unit on/offWrite0=Off, 1=On
BV4Remote Control Lock SettingLock the remote controlWrite0=Unlock, 1=Lock
BV5Controller Lock SettingLock the wired controllerWrite0=Unlock, 1=Lock
MVmin1Mode SettingOperating modeWrite1=Off, 2=Fan, 3=Cool, 4=Heat, 5=Auto, 6=Dry
MVmin2Fan Speed SettingFan speed; 9 shows fan off (read only)Write1-7=Fan speed 1-7, 8=Auto, 9=Fan off (status only)
MV3Mode Limit SettingLock out cooling or heating modeWrite1=Unlocked, 2=Cooling mode locked, 3=Heating mode locked
MV5Fan Lock/Unlock SettingLock the fan at one speedWrite1-7=Lock at speed 1-7, 8=Unlock
AVmin1Temperature SettingRoom setpoint, 17-30 °C°CWrite
AV2Dual Point (Cooling) SettingCooling setpoint in Auto mode°CWrite
AV3Dual Point (Heating) SettingHeating setpoint in Auto mode°CWrite
AV4Cooling Temperature Limit SettingLowest allowed cooling setpoint; 0 = unlocked°CWrite
AV5Heating Temperature Limit SettingHighest allowed heating setpoint; 0 = unlocked°CWrite
Object ID lookup: Sinclair SDV5 VRF BACnet Gateway GW-BAC point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the SDV5 VRF BACnet Gateway GW-BAC and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Sinclair SDV5 VRF BACnet Gateway GW-BAC

How many BACnet points does the Sinclair SDV5 VRF BACnet Gateway GW-BAC have?

This list has 15 BACnet objects: 2 analog inputs, 5 analog values, 1 binary input, 3 binary values, 4 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Sinclair SDV5 VRF BACnet Gateway GW-BAC BACnet points are writable?

12 of the 15 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Sinclair SDV5 VRF BACnet Gateway GW-BAC BACnet documentation?

The source is GW-BAC Commercial Air Conditioners SDV5 (user manual), published free by Sinclair at https://sinclair-solutions.com/files/user-manual-en/sdv5/sinclair-um-gw-bac-en.pdf.

What are the minimum BACnet points to integrate the Sinclair SDV5 VRF BACnet Gateway GW-BAC?

Start with BV 1 On/Off Setting (Unit on/off (1 = on)); MV 1 Mode Setting (1 Off, 2 Fan, 3 Cool, 4 Heat, 5 Auto, 6 Dry); AV 1 Temperature Setting (Room setpoint, 17-30 °C); MV 2 Fan Speed Setting (Fan speed 1-7, 8 = auto); AI 1 Room Temperature (Room temperature, °C); BI 2 Alarm Indication (Indoor unit error (1 = error)); AI 7 Malfunction Code (Active error code number, 0 = none).

How do I enable BMS control of the Sinclair SDV5 VRF BACnet Gateway GW-BAC?

No enable point. Each indoor unit is controllable once the gateway sees it on its XYE bus.

How do I check these points on the real SDV5 VRF BACnet Gateway GW-BAC?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Sinclair BACnet points lists

Source: GW-BAC Commercial Air Conditioners SDV5 (user manual). Object names, instances and units are reproduced as published; descriptions are our own.