BACnet instance calculator · Procon BAC-IP/50

Mitsubishi Electric Procon BAC-IP/50 BACnet Instance Calculator

Free browser tool · nothing is uploaded · 5 November 2026

The Procon BAC-IP/50 gives every unit on its G-50 a block of objects numbered 1, the 3-digit unit address and the point number.

Short answer

Procon BAC-IP/50 unit objects are 1 UUU PP: a leading 1, the unit address (001-050) and the point number. Unit 017's setpoint command (point 09) is AO 101709. Outdoor (OC/BC) error codes use the same pattern with addresses 051-100 and point 22.

Mitsubishi Electric calculator

1-50
51-100
or a range of unit address to

The calculator needs JavaScript. The formula and a worked example are below.

Which unit does this instance belong to?

    How the numbers are built

    instance = 100000 + unit address x 100 + point

    PartMeaningRange
    1Fixed first digit1
    UUUUnit address (OC/BC addresses 051-100 for point 22)001-100
    PPPoint number01-27

    Unit addresses are the M-NET addresses of the units on the G-50. Only the master unit of each group accepts commands. System objects (100023-100027) are fixed.

    Worked example: unit address 017

    The first objects for unit address 017 on the BAC-IP/50, worked out with the formula above:

    ObjectName (as printed)What it is
    BO 101701nnn_ON_wOn/Off setup
    BI 101702nnn_ON_rOn/Off state
    AI 101703nnn_ECodeUnit error code, 4 digits (8000 = no error)
    MO 101704nnn_MD_wOperation mode setup
    MI 101705nnn_MD_rOperation mode state
    MO 101706nnn_FS_wFan speed setup
    AI 105122nnn_ECodeOC/BC (outdoor) error code, 8000 = no error

    Source

    Formula and objects from Procon BAC-IP/50 Installation and User Guide · rev. 2009-07-20 (manufacturer document ↗), re-typed in our points list. Object names are shown as printed.

    Check it against the live device. The calculator applies the formula from the manufacturer’s documentation; the gateway in front of you may expose fewer objects or use other numbers after a firmware change. Easy BACnet scans a network for BACnet IP devices from an Android phone and reads every object on them — a quick way to confirm one unit before you map a whole building.

    Questions

    How do I work out a Mitsubishi Electric instance number?

    Procon BAC-IP/50 unit objects are 1 UUU PP: a leading 1, the unit address (001-050) and the point number. Unit 017's setpoint command (point 09) is AO 101709. Outdoor (OC/BC) error codes use the same pattern with addresses 051-100 and point 22.

    Why do my commands to a unit do nothing?

    Only the group's master unit accepts commands on the BAC-IP/50; writes to slave unit addresses have no effect.

    Is this Mitsubishi Electric calculator official?

    No. It applies the formula printed in Mitsubishi Electric's own documentation to the points list in our library. Confirm the numbers against a scan of the live device before you map or write anything.