Easy BACnet
  1. Home
  2. BACnet instance calculators
  3. Fujitsu UTY-VBGX VRF gateway

BACnet instance calculator · UTY-VBGX VRF gateway

Fujitsu BACnet Instance Calculator (UTY-VBGX VRF)

Free browser tool · nothing is uploaded · 5 November 2026

Fujitsu's UTY-VBGX gateway puts the refrigerant system and unit address inside every instance number. Enter the addresses and get the full object list for that unit, or paste an instance to see which unit it belongs to.

Short answer

On a Fujitsu UTY-VBGX every indoor unit object is a 6-digit number TT rr uu: a 2-digit point code (10-17), the refrigerant system address (00-99) and the indoor unit address (00-63). Outdoor unit objects use point codes 30-33 with the outdoor unit address (0-3) at the end. So the setpoint command for refrigerant system 2, indoor unit 5 is AO 100205.

Fujitsu calculator

0-99
0-63
0-3
or a range of indoor unit address to

The calculator needs JavaScript. The formula and a worked example are below.

Which unit does this instance belong to?

    How the numbers are built

    instance = point code x 10000 + refrigerant system x 100 + unit address

    PartMeaningRange
    TTPoint code: which object of the unit (10-17 indoor, 30-33 outdoor)10-17, 30-33
    rrRefrigerant system address00-99
    uuIndoor unit address (outdoor unit address for OU objects)00-63 (OU 0-3)

    The addresses are the ones the Fujitsu configuration tool shows for each unit after it scans the VRF network. Gateway-wide and batch objects (all units at once) sit at fixed low instances 0-2.

    Worked example: refrigerant system 02, indoor unit 05

    The first objects for refrigerant system 02, indoor unit 05 on the UTY-VBGX, worked out with the formula above:

    ObjectName (as printed)What it is
    AI 100205IU_rr_uu_SetTemp_StatusCurrent setpoint
    AI 110205IU_rr_uu_SpaceTemp_StatusRoom temperature
    AI 120205IU_rr_uu_AutoTempLoLim_StatusAuto mode setpoint low limit
    AI 130205IU_rr_uu_AutoTempHiLim_StatusAuto mode setpoint high limit
    AI 140205IU_rr_uu_CoolTempLoLim_StatusCool mode setpoint low limit
    AI 150205IU_rr_uu_CoolTempHiLim_StatusCool mode setpoint high limit
    BI 300200OU_rr_uu_Error_StatusOutdoor unit fault
    BI 310200OU_rr_uu_ForcedOff_StatusForced-off status
    BO 310200OU_rr_uu_ForcedOff_SettingForced-off command
    MI 300200OU_rr_uu_ErrorCode_StatusOutdoor unit error code (1-255)
    MI 310200OU_rr_uu_CapacitySave_StatusCapacity saving level
    MI 320200OU_rr_uu_LowNoiseOp_StatusLow noise operation status

    Source

    Formula and objects from BACnet Gateway for VRF System UTY-VBGX Instruction Manual (PICS & User Manual) · rev. r1.3.2 (2017) (manufacturer document ↗), re-typed in our points list. Object names are shown as printed.

    Check it against the live device. The calculator applies the formula from the manufacturer’s documentation; the gateway in front of you may expose fewer objects or use other numbers after a firmware change. Easy BACnet scans a network for BACnet IP devices from an Android phone and reads every object on them — a quick way to confirm one unit before you map a whole building.

    Questions

    How do I work out a Fujitsu instance number?

    On a Fujitsu UTY-VBGX every indoor unit object is a 6-digit number TT rr uu: a 2-digit point code (10-17), the refrigerant system address (00-99) and the indoor unit address (00-63). Outdoor unit objects use point codes 30-33 with the outdoor unit address (0-3) at the end. So the setpoint command for refrigerant system 2, indoor unit 5 is AO 100205.

    Why does my Fujitsu indoor unit setpoint read AO 100101?

    100101 is point code 10 (setpoint), refrigerant system 01, indoor unit 01. Every other indoor unit uses the same point codes with its own system and unit address in the last four digits.

    What is the device instance of the UTY-VBGX?

    It is set in the Fujitsu configuration tool. The object table shows 144000 and the configuration section says 144; give each gateway its own value. The calculator only changes the object instances.

    Is this Fujitsu calculator official?

    No. It applies the formula printed in Fujitsu's own documentation to the points list in our library. Confirm the numbers against a scan of the live device before you map or write anything.

    More instance calculators