VRF BACnet IP gateway · BACnet points list

Fujitsu UTY-VBGX BACnet Gateway for VRF BACnet points list

Updated 28 October 2026

Short answer

The UTY-VBGX connects a Fujitsu Airstage VRF network to BACnet IP and creates a fixed set of objects for every indoor and outdoor unit it finds, plus gateway-wide batch commands. Object names and instances are built from the refrigerant system and unit addresses, so the instance number tells you which unit a point belongs to. Device name, instance and port are set with the Fujitsu configuration tool.

This page lists 55 BACnet objects for the Fujitsu UTY-VBGX BACnet Gateway for VRF — 25 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Fujitsu’s own free documentation, linked below.

Manufacturer
Fujitsu
Model
UTY-VBGX BACnet Gateway for VRF
Equipment
VRF BACnet IP gateway
Equipment type
VRF & split air conditioners
BACnet objects
55 (25 writable)
Transport
BACnet IP
Firmware
Not stated
Default device instance
144000
Also known as
UTY-VBGX, UTYVBGX, BACnet Gateway for VRF System, Fujitsu General BACnet gateway
Source document
BACnet Gateway for VRF System UTY-VBGX Instruction Manual (PICS & User Manual) · rev. r1.3.2 (2017)
Download CSV 55 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Fujitsu UTY-VBGX BACnet Gateway for VRF

Integration in brief

Set the gateway IP, device instance and LON unit address with the Fujitsu configuration tool, scan the VRF network for units, and download the configuration. Each indoor unit then appears as a block of IU_rr_uu objects; map on/off, mode, setpoint, room temp and the error status first.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BO 100101IU_rr_uu_Operation_SettingStart/stop the indoor unitCommand
MO 100101IU_rr_uu_OperationMode_SettingCommand the operating modeCommand
AO 100101IU_rr_uu_SetTemp_SettingSetpoint commandCommand
MO 110101IU_rr_uu_FanSpeed_SettingFan speed commandCommand
BI 110101IU_rr_uu_Operation_StatusConfirm run statusRead
MI 100101IU_rr_uu_OperationMode_StatusRead back the modeRead
AI 110101IU_rr_uu_SpaceTemp_StatusRoom temperatureRead
BI 100101IU_rr_uu_Exists_StatusShows whether the unit is presentRead
BI 150101IU_rr_uu_Error_StatusIndoor unit faultRead
MI 150101IU_rr_uu_ErrorCode_StatusError code (1-255) when a fault is activeRead

Enable & remote start

No enable point is described. Remote controller prohibition is a 65-state multistate (IU_rr_uu_RC_Prohibit_Setting, or Batch_RC_Prohibition_Setting for all units) whose states combine filter reset, start, start/stop, mode, setpoint and timer lockouts, plus All. Outdoor units have a ForcedOff setting.

Network setup

Watch out for

Fujitsu UTY-VBGX BACnet Gateway for VRF BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

55 of 55 shown
Type
Other
Access
Show
Fujitsu UTY-VBGX BACnet Gateway for VRF BACnet Points List
DescriptionStates
DEV144000UTY-VBGXGateway device objectRead
BI0Gateway_ES_StatusEnergy saving statusReadInactive=Not used, Active=Energy Saving
BI1Gateway_Error_StatusGateway error statusReadInactive=Normal, Active=Abnormal
BO0Gateway_ES_SettingEnergy saving commandCommandInactive=Not Used, Active=Energy Saving
MI0Gateway_ErrorCode_StatusGateway error codeRead1=No Error, 2=Hardware Error, 3=No Configuration Present
AO0Batch_SetTemp_SettingSetpoint for all indoor units°C (or °F per configuration)Command
BO1Batch_Operation_SettingOn/off for all indoor unitsCommandInactive=Off, Active=On
MO0Batch_OperationMode_SettingMode for all indoor unitsCommand1=Cool, 2=Heat, 3=Fan, 4=Dry, 5=Auto
MO1Batch_FanSpeed_SettingFan speed for all indoor unitsCommand1=Low, 2=High, 3=Med, 4=Auto, 5=Quiet, 6=Med-Low, 7=Med-High
MO2Batch_RC_Prohibition_SettingRemote controller prohibition for all units (65 states)CommandSee RC Prohibition table in manual (65 states)
AI100101IU_rr_uu_SetTemp_StatusCurrent setpoint°C (or °F per configuration)Read
AImin110101IU_rr_uu_SpaceTemp_StatusRoom temperature°C (or °F per configuration)Read
AI120101IU_rr_uu_AutoTempLoLim_StatusAuto mode setpoint low limit°C (or °F per configuration)Read
AI130101IU_rr_uu_AutoTempHiLim_StatusAuto mode setpoint high limit°C (or °F per configuration)Read
AI140101IU_rr_uu_CoolTempLoLim_StatusCool mode setpoint low limit°C (or °F per configuration)Read
AI150101IU_rr_uu_CoolTempHiLim_StatusCool mode setpoint high limit°C (or °F per configuration)Read
AI160101IU_rr_uu_HeatTempLoLim_StatusHeat mode setpoint low limit°C (or °F per configuration)Read
AI170101IU_rr_uu_HeatTempHiLim_StatusHeat mode setpoint high limit°C (or °F per configuration)Read
AOmin100101IU_rr_uu_SetTemp_SettingSetpoint command°C (or °F per configuration)Command
AO110101IU_rr_uu_AutoTempLoLim_SettingSet auto mode low limit°C (or °F per configuration)Command
AO120101IU_rr_uu_AutoTempHiLim_SettingSet auto mode high limit°C (or °F per configuration)Command
AO130101IU_rr_uu_CoolTempLoLim_SettingSet cool mode low limit°C (or °F per configuration)Command
AO140101IU_rr_uu_CoolTempHiLim_SettingSet cool mode high limit°C (or °F per configuration)Command
AO150101IU_rr_uu_HeatTempLoLim_SettingSet heat mode low limit°C (or °F per configuration)Command
AO160101IU_rr_uu_HeatTempHiLim_SettingSet heat mode high limit°C (or °F per configuration)Command
BImin100101IU_rr_uu_Exists_StatusIndoor unit present on the networkReadInactive=Not Exists, Active=Exists
BImin110101IU_rr_uu_Operation_StatusRun statusReadInactive=Off, Active=On
BI120101IU_rr_uu_ThermostatOFF_StatusThermostat-off statusReadInactive=Reset, Active=Set
BI130101IU_rr_uu_FilterSign_StatusFilter signReadInactive=Unsigned, Active=Signed
BI140101IU_rr_uu_Emergency_StatusEmergency stop statusReadInactive=Normal, Active=Stop
BImin150101IU_rr_uu_Error_StatusIndoor unit faultReadInactive=Normal, Active=Fault
BI160101IU_rr_uu_TempLimValid_StatusSetpoint limits enabledReadInactive=Invalid, Active=Valid
BOmin100101IU_rr_uu_Operation_SettingOn/off commandCommandInactive=Off, Active=On
BO110101IU_rr_uu_ThermostatOFF_SettingThermostat-off commandCommandInactive=Reset, Active=Set
BO120101IU_rr_uu_Reset_Filter_SettingFilter sign resetCommandInactive=Reset, Active=Not Reset
BO130101IU_rr_uu_TempLimValid_SettingEnable setpoint limitsCommandInactive=Invalid, Active=Valid
MImin100101IU_rr_uu_OperationMode_StatusCurrent modeRead1=Cool, 2=Heat, 3=Fan, 4=Dry, 5=Auto
MI110101IU_rr_uu_FanSpeed_StatusCurrent fan speedRead1=Low, 2=High, 3=Med, 4=Auto, 5=Quiet, 6=Med-Low, 7=Med-High
MI120101IU_rr_uu_AirFlowDirVT_StatusVertical louver positionRead1=1, 2=2, 3=3, 4=4, 5=Swing
MI130101IU_rr_uu_AirFlowDirHZ_StatusHorizontal louver positionRead1=1, 2=2, 3=3, 4=4, 5=5, 6=Swing
MI140101IU_rr_uu_RC_Prohibit_StatusRemote controller prohibition status (65 states)ReadSee RC Prohibition table in manual (65 states)
MImin150101IU_rr_uu_ErrorCode_StatusIndoor unit error code (1-255)ReadSee error content table in manual
MOmin100101IU_rr_uu_OperationMode_SettingMode commandCommand1=Cool, 2=Heat, 3=Fan, 4=Dry, 5=Auto
MOmin110101IU_rr_uu_FanSpeed_SettingFan speed commandCommand1=Low, 2=High, 3=Med, 4=Auto, 5=Quiet, 6=Med-Low, 7=Med-High
MO120101IU_rr_uu_AirFlowDirVT_SettingVertical louver commandCommand1=1, 2=2, 3=3, 4=4, 5=Swing
MO130101IU_rr_uu_AirFlowDirHZ_SettingHorizontal louver commandCommand1=1, 2=2, 3=3, 4=4, 5=5, 6=Swing
MO140101IU_rr_uu_RC_Prohibit_SettingRemote controller prohibition commandCommandSee RC Prohibition table in manual (65 states)
BI300101OU_rr_uu_Error_StatusOutdoor unit faultReadInactive=Normal, Active=Fault
BI310101OU_rr_uu_ForcedOff_StatusForced-off statusReadInactive=Reset, Active=Set
BO310101OU_rr_uu_ForcedOff_SettingForced-off commandCommandInactive=Reset, Active=Set
MI300101OU_rr_uu_ErrorCode_StatusOutdoor unit error code (1-255)ReadSee error content table in manual
MI310101OU_rr_uu_CapacitySave_StatusCapacity saving levelRead1=Not set, 2=100%, 3=90%, 4=80%, 5=70%, 6=60%, 7=50%, 8=40%
MI320101OU_rr_uu_LowNoiseOp_StatusLow noise operation statusRead1=Not Set, 2=-/-/E, 3=-/A/-, 4=-/A/E, 5=1/-/-, 6=1/-/E, 7=1/A/-, 8=1/A/E, 9=2/-/-, 10=2/-/E, 11=2/A/-, 12=2/A/E, 13=3/-/-, 14=3/-/E, 15=3/A/-, 16=3/A/E
MO300101OU_rr_uu_LowNoiseOp_SettingLow noise operation commandCommand1=Stop, 2=Level1-Quiet, 3=Level1-Ability, 4=Level2-Quiet, 5=Level2-Ability, 6=Level3-Quiet, 7=Level3-Ability
MO310101OU_rr_uu_CapacitySave_SettingCapacity saving commandCommand1=Not set, 2=100%, 3=90%, 4=80%, 5=70%, 6=60%, 7=50%, 8=40%

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the UTY-VBGX BACnet Gateway for VRF and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Fujitsu UTY-VBGX BACnet Gateway for VRF

How many BACnet points does the Fujitsu UTY-VBGX BACnet Gateway for VRF have?

This list has 55 BACnet objects: 8 analog inputs, 8 analog outputs, 11 binary inputs, 7 binary outputs, 1 device, 10 multi-state inputs, 10 multi-state outputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Fujitsu UTY-VBGX BACnet Gateway for VRF BACnet points are writable?

25 of the 55 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Fujitsu UTY-VBGX BACnet Gateway for VRF BACnet documentation?

The source is BACnet Gateway for VRF System UTY-VBGX Instruction Manual (PICS & User Manual), revision r1.3.2 (2017), published free by Fujitsu at https://www.bacnetinternational.net/catalog/manu/fujitsu%20general%20limited/UTY-VBGX%20PICS%20&%20User%20Manual%20eng%20r1.3.2.pdf.

What are the minimum BACnet points to integrate the Fujitsu UTY-VBGX BACnet Gateway for VRF?

Start with BO 100101 IU_rr_uu_Operation_Setting (Start/stop the indoor unit); MO 100101 IU_rr_uu_OperationMode_Setting (Command the operating mode); AO 100101 IU_rr_uu_SetTemp_Setting (Setpoint command); MO 110101 IU_rr_uu_FanSpeed_Setting (Fan speed command); BI 110101 IU_rr_uu_Operation_Status (Confirm run status); MI 100101 IU_rr_uu_OperationMode_Status (Read back the mode); AI 110101 IU_rr_uu_SpaceTemp_Status (Room temperature); BI 100101 IU_rr_uu_Exists_Status (Shows whether the unit is present); BI 150101 IU_rr_uu_Error_Status (Indoor unit fault); MI 150101 IU_rr_uu_ErrorCode_Status (Error code (1-255) when a fault is active).

How do I enable BMS control of the Fujitsu UTY-VBGX BACnet Gateway for VRF?

No enable point is described. Remote controller prohibition is a 65-state multistate (IU_rr_uu_RC_Prohibit_Setting, or Batch_RC_Prohibition_Setting for all units) whose states combine filter reset, start, start/stop, mode, setpoint and timer lockouts, plus All. Outdoor units have a ForcedOff setting.

How do I check these points on the real UTY-VBGX BACnet Gateway for VRF?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

Source: BACnet Gateway for VRF System UTY-VBGX Instruction Manual (PICS & User Manual) · rev. r1.3.2 (2017). Object names, instances and units are reproduced as published; descriptions are our own.