Easy BACnet
  1. Home
  2. BACnet instance calculators
  3. Mitsubishi Electric AE-C400 / EW-C50

BACnet instance calculator · AE-C400 / EW-C50

Mitsubishi Electric AE-C400 / EW-C50 BACnet Instance Calculator

Free browser tool · nothing is uploaded · 5 November 2026

With the BACnet license, the AE-C400 and EW-C50 number objects by class, address and point. Enter an address to get the group, outdoor unit, PI controller, interlocked unit and chiller objects for it.

Short answer

AE-C400 / EW-C50 instances are six digits CC NN PP: an object class (01 group, 41 PI controller, 51 outdoor unit, 61 interlocked unit, 71 chiller system, 91 chiller unit), the address (01-50) and the point. Group 7 Set Temp is AV 10710; outdoor unit 51 (class address 01) COP is AI 510101.

Mitsubishi Electric calculator

Outdoor units: M-NET address minus 50
or a range of address (group, unit or controller) to

The calculator needs JavaScript. The formula and a worked example are below.

Which unit does this instance belong to?

    How the numbers are built

    instance = class x 10000 + address x 100 + point

    PartMeaningRange
    CCObject class: 01 group, 41 PI controller, 51 outdoor unit, 61 interlocked unit, 71 chiller system, 91 chiller unit01-91
    NNAddress of that group or unit (99 = collective)01-50
    PPPoint number01-88

    For outdoor units (class 51) the address is the M-NET outdoor address minus 50, so M-NET address 51 is 01. Group and other addresses come from the controller's initial settings.

    Worked example: address 07

    The first objects for address 07 on the AE-C400 / EW-C50, worked out with the formula above:

    ObjectName (as printed)What it is
    BO 10701On Off SetupStart/stop command for the group
    BI 10702On Off StateGroup run status
    BI 10703Alarm SignalGroup alarm
    MI 10704Error CodeError category for the group
    MO 10705Operational Mode SetupOperating mode command
    MI 10706Operational Mode StateCurrent operating mode
    BI 410703PIcontroller Alarm SignalPI controller alarm
    ACC 410740PIcontroller Electric Energy 1Metered energy, PI controller channel 1
    ACC 410741PIcontroller Electric Energy 2Metered energy, PI controller channel 2
    ACC 410742PIcontroller Electric Energy 3Metered energy, PI controller channel 3
    ACC 410743PIcontroller Electric Energy 4Metered energy, PI controller channel 4
    TL 410784Trend Log PIcontroller Electric Energy 1Trend log of PI controller channel 1
    AI 510701COPOutdoor unit coefficient of performance
    ACC 610739Interlocked Units Apportioned Electric EnergyApportioned energy per interlocked unit
    ACC 610744Interlocked Units Apportionment ParameterApportionment parameter per interlocked unit
    TL 610783Trend Log Interlocked Units Apportioned Electric EnergyTrend log of interlocked unit energy
    TL 610788Trend Log Interlocked Units Apportionment ParameterTrend log of interlocked unit parameter
    BO 710701Chiller On Off SetupChiller start/stop command
    BI 710702Chiller On Off StateChiller run status
    MO 710703Chiller Operational Mode SetupChiller mode command
    MI 710704Chiller Operational Mode StateCurrent chiller mode
    MO 710705Chiller Fan Mode SetupChiller fan mode command
    MI 710706Chiller Fan Mode StateCurrent chiller fan mode
    BI 910711Chiller Unit Alarm SignalAlarm for an individual chiller unit

    Source

    Formula and objects from Centralized Controller AE-C400/EW-C50, BM ADAPTER BACS-AP50 Instruction Book <BACnet function> · WT10808X04 (manufacturer document ↗), re-typed in our points list. Object names are shown as printed.

    Check it against the live device. The calculator applies the formula from the manufacturer’s documentation; the gateway in front of you may expose fewer objects or use other numbers after a firmware change. Easy BACnet scans a network for BACnet IP devices from an Android phone and reads every object on them — a quick way to confirm one unit before you map a whole building.

    Questions

    How do I work out a Mitsubishi Electric instance number?

    AE-C400 / EW-C50 instances are six digits CC NN PP: an object class (01 group, 41 PI controller, 51 outdoor unit, 61 interlocked unit, 71 chiller system, 91 chiller unit), the address (01-50) and the point. Group 7 Set Temp is AV 10710; outdoor unit 51 (class address 01) COP is AI 510101.

    What does the first part of an AE-C400 instance mean?

    It is the object class. 01 is a group, 41 a PI controller, 51 an outdoor unit, 61 an interlocked unit, 71 a chiller system and 91 a chiller unit. 10710 is class 01 (leading zero dropped), address 07, point 10.

    Do I need anything enabled first?

    The BACnet connection license must be registered and the controller must show ONLINE. Apportioned energy objects also need the Charge license.

    Is this Mitsubishi Electric calculator official?

    No. It applies the formula printed in Mitsubishi Electric's own documentation to the points list in our library. Confirm the numbers against a scan of the live device before you map or write anything.

    More instance calculators